CHLORIDE Edge Glo Exit Instruction Manual
- June 17, 2024
- CHLORIDE
Table of Contents
CHLORIDE Edge Glo Exit
Specifications
- Model: WGLO EDGE-GLO EXIT
- Manufacturer: Signify North America Corporation
- Address: 200 Franklin Square Drive, Somerset, NJ 08873, USA
- Phone: 855-486-2216
- Website: www.chloride-lighting.com
- Year: July 2018
- 12NC: 443580497581
Product Usage Instructions
Mounting Instructions
-
Remove Edge-Glo Exit fixture and hardware from the box. Inspect contents for any damage.
-
Using the housing as a template, cut the required opening in the mounting surface.
-
Remove the two screws to detach the electronics chassis.
-
Attach the housing to the structure behind the mounting surface.
-
Connect AC wiring – Green wire to ground, White wire to Common,
Black wire to 120VAC or Blue wire to 277VAC. -
Reattach electronics chassis to housing using the two screws removed earlier.
-
Remove two wing nuts from the front of the electronics chassis.
-
Secure panel assembly to housing assembly using the two wing nuts removed earlier.
-
Route wires from housing through the plastic bushing found in the back of the panel assembly.
-
Connect the two pin harness to the light bar.
FAQ (Frequently Asked Questions)
-
Q: Can this product be used outdoors?
A: No, this equipment should not be used outdoors as per safety instructions provided by the manufacturer. -
Q: What should I do if battery acid comes in contact with skin or eyes?
A: If acid is spilled on skin or eyes, flush with fresh water and contact a physician immediately. -
Q: How can I maintain warranty for equipment with batteries?
-
A: Equipment with batteries must be installed or placed on charge within the prescribed period after shipment to maintain warranty.
WGLO EDGE-GLO EXIT
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
- This sign shall be installed only where there is adequate color contrast between the sign legend and the interior wall finish behind the sign to provide for sufficient visibility.
- All servicing should be performed by qualified personnel only.
- Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than intended use.
- Do not use outdoors.
- Do not let supply cords touch hot surfaces.
- Do not mount near gas or electric heaters.
INSTALLATION AND OPERATING INSTRUCTIONS
Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or eyes, flush acid with fresh water and contact a physician immediately.
SAVE THESE INSTRUCTIONS
WARNING – Shut off AC power to branch circuits to which units will be
connected. All wiring should be per N.E.C. Articles 501-4(b) and local codes.
To maintain warranty, equipment with batteries must be installed or placed on
charge within prescribed period after shipment.
GENERAL INSTRUCTIONS
Mounting Instructions
Figure 1 provides an overall view of the fixture and shows all of the critical
dimensions. Refer to this illustration as you mount the fixture.
- Remove Edge-Glo Exit fixture and hardware from the box. Inspect contents to ensure that no damage occurred during shipment.
- Using the housing as a template, cut the required opening in the mounting surface.
- Remove the two screws shown so that the electronics chassis can be removed.
- Remove one 7/8” knockout for AC service entry. Attach AC conduit using ½” conduit bushing.
- Attach housing to structure behind mounting surface.
- Connect AC wiring at this time. Connect Green wire to ground and White wire to Common. Connect Black wire to 120VAC or Blue wire to 277VAC (cap off unused wire to prevent shorting).
- Reattach electronics chassis to housing using the two screws removed in step 3.
- Remove the two wing nuts from the front of the electronics chassis.
- Remove two screws that secure front panel of lens assembly and set them aside.
- Secure panel assembly to housing assembly using the two wing nuts removed earlier. Route wires from housing thru the plastic bushing found in the back of the panel assembly.
- Connect the two pin harness to the light bar. If a self-powered battery backup unit is being installed, remove the two knockouts from the front panel of the lens assembly. Secure the switch and LED indicators from the housing assembly to the sheet metal bracket found inside the panel assembly.
- Reattach the front cover to the panel assembly.
- Energize the AC circuit and ensure that the fixture lights. If the unit has the self-powered battery backup option, push the test switch and ensure that the fixture remains lit.
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ
08873, USA Phone: 855-486-2216
www.chloride-lighting.com
- Signify Canada Ltd./Signify Canada Ltée. 281 Hillmount Road,
- Markham ON, Canada L6C 2S3 Phone: 800-668-9008
- July 2018
- 12NC: 443580497581
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>