Replacing GWR Sensor Electronics
Instruction Sheet for Smart Line Transmitters:
SLG700 Level Transmitters
Document No: 34-SL-33-02
Effective Date: 2/21/2017
Supersedes: 12/1/2016
Please take appropriate steps to avoid ESD damage when handling transmitter
electronics assemblies.
All local electrical codes, and relevant service and repair regulations must
be observed.
When installed as explosion-proof or flame-proof in a hazardous location, keep
covers tight while the transmitter is energized. Disconnect power to the
transmitter in the non-hazardous area prior to removing end caps for service.
When installed as nonamended or non-sparking equipment in a hazardous
location, disconnect power to the transmitter in the non-hazardous area, or
determine that the location is nonhazardous before disconnecting or connecting
the transmitter wires.
Tools required
Use this tool | For this item |
---|---|
AF 2.0 mm Allen key | M4 set screw for Separating Sensor Electronics Housing |
from Process Connector and Communications Housing
AF 1.5 mm Allen key| M3 set screw for end cap removal
Parker Super O-ring Lubricant or equivalent| Transmitter re-assembly
Step – 1: Determine transmitter Firmware version of the Sensor and
Communications Modules (refer to the SLG700 Transmitter User’s Manual
34-SL-25-11). See table below.
Table 1: Sensor firmware version and ability to upgrade a transmitter
. Sensor Firmware Version | Notes: |
---|---|
1.000000/1.000100 | COMM PCBA and ADVANCED DISPLAY must be replaced or have |
firmware upgraded.
TERM PCBA must be replaced if the version number in the date code is not ‘C’.
An example of a correct date code label shown on the bottom of the terminal
PCBA assembly, as shown in Figure 1.
1.010000, 1.020000 and later versions| Sensor electronics is replaceable
Step – 2: Remove power from transmitter.
Step – 3: If a new terminal assembly is also being installed follow
instructions 34-ST-33-64. The relevant part numbers are listed in Table 2
Table 2: Terminal assembly versions.
GWR Level Terminator Module w/Lightning Protection Kit for HART Modules|
50095191-502
---|---
GWR Level Terminator Module w/Lightning Protection Kit for FF Modules|
50095191-510
GWR Level Terminator Module w/o Lightning Protection Kit for HART Modules,|
50095191-501
GWR Level Terminator Module w/o Lightning Protection Kit for FF Modules|
50095191-509
Step – 4: If a new Communications Module is also being installed follow
instructions #34-ST-33-69.
Step – 5: Separate the sensor housing from the process connector by first
loosening the 4 mm setscrews (3) and gently separating the sensor electronics
housing. Do not discard setscrews or o-rings.
Step – 6: Loosen the end cap locking screw and unscrew the end cap on the Sensor Electronics side of the Transmitter Communications Housing
Step – 7: If equipped with a Display Module, carefully depress the two
tabs on the sides of the Display Module, and pull it off. Ensure the interface
connector (8-pin header) is not lost. Do not discard the Display Module, or
connector.
Step – 8: Loosen the two retaining screws, and carefully pull the
Communication Module from
the Sensor Electronics compartment (do not discard the retaining set screws).
Step – 9: Carefully remove the sensor cable from the “P2” connector on
the Communication Module at the bottom of the Communication Module.
Step – 10: Carefully unscrew the Sensor Electronics Housing from the
Communications Housing.
Step – 11: Carefully transfer orange o-ring from old sensor electronics
housing to new housing. Clean off o-ring and apply o-ring lubricant before re-
installing.
Step – 12: Thread the ribbon cable of new Sensor Electronics Housing into
Communications Housing.
Step – 13 : Screw Sensor Electronics Housing into Communications Housing
taking care not to damage the ribbon cable. The ribbon cable connector must be
rotated with the sensor housing to ensure that it does not twist more than ½
turn during the process. Extreme care must be taken to avoid pinching the
cable during rotation.
Screw only as far as indicated in Figure 4.
There should be 2.5 mm clearance between the Communications housing and the
top fin of the Sensor electronics housing. The o-ring should not be visible.
Over-tightening will irreparably damage the ribbon cable.
WARNING: Do not tightly screw the Sensor Housing into the Electronics
Housing.
The connection should be to the point where the o-ring is not visible.
Ensure the O-ring is not pinched
Step-14: Tighten set screw as shown in Figure 4. The set-screw should not
protrude from the Communications electronics housing. Protrusion indicates
that the sensor housing is screwed an incorrect amount into the communications
housing.
Step – 15: Carefully align and connect the sensor ribbon cable to the
connector “J4” at the bottom of the Communication Module. Pin 1 must be
aligned with contact 1 of the ribbon cable indicated by the colored edge wire.
Note: Sensor ribbon cable wire aligns with pin 1 of J4 as shown. The
Communication Module is then rotated 180 degrees to seat in Communications
Housing.
Step – 16: Carefully, insert the Communication Module into the
Communication Electronics Housing. Ensure that the sensor ribbon cable is not
pinched.
Step – 17: Tighten the two Communications Module retaining screws.
Step – 18: If a new Communications Module is being used, duplicate the
jumper settings on the original module.
Step – 19: If applicable, re-install the Display Module as follows:
– Orient the display as desired.
– Install the Interface Connector in the Display Module such that it will mate
with the socket for the display in the Communication Module.
– Carefully line up the display, and snap it into place. Verify that the two
tabs on the sides of the display latch.
Orient the Display for proper viewing through the end cap window.
You can rotate the meter mounting orientation in 90° increments.
Step – 20 : Apply o-ring lubricant to the end cap o-ring before
installing the end cap. Reinstall the end cap and tighten the end cap locking
screw.
Step – 21: Ensure the small RF connector is seated firmly in place, on
the bottom of the sensor electronics housing. See Figure 6 Step – 22: If necessary, replace the O-ring at
the top of the process connector. Apply o-ring lubricant and carefully replace
the sensor electronics housing without pinching the O-ring. Tighten the set
screws.
Step – 23: Turn ON transmitter power.
Step – 24: Comm and Sensor Model Number reconciliation
- If the COMM Firmware version is 1.020000 the transmitter should power up and operate with no further configuration required. However, if the sensor electronics housing has been used in another transmitter, a further configuration step is necessary. See the Appendix for detailed instructions.
- If the COMM Firmware version is 1.010000, the model number information will not be visible. This does not affect the operation of the transmitter.
Step – 25: If upgrading transmitter from sensor firmware version 1.000×00, the transmitter configuration will need to be set. However, if a new COMM module was ordered at the same time as the sensor electronics a basic configuration will be already in place. See manuals:
Publication # | Publication Title |
---|---|
34-SL-25-11 | SLG 700 Smart Line Guided Wave Radar User’s Manual |
34-SL-25-06 | SLG 700 Smart Line Level Transmitter Guided Wave Radar HART© |
Option User’s Manual
34-SL-25-07| SLG 700 Smart Line Level Transmitter Guided Wave Radar FOUNDATION
Fieldbus Option Manual
Note: The transmitter stores it’s configuration on the COMM PCBA. Therefore you do not need to transfer the configuration.
Hazardous Locations
Warning – : When installed as explosion-proof or flame-proof in a
hazardous location, keep covers tight while the transmitter is energized.
Disconnect power to the transmitter in the nonhazardous area prior to removing
end caps for service. When installed as non-incentive or nonspeaking
equipment, disconnect power to the transmitter in the non-hazardous area, or
determine that the location is non-hazardous before disconnecting or
connecting the transmitter wires.
Product Approvals – : All replacement sensor electronic modules are built
according to the same quality and regulatory processes as the original
transmitter parts and complete transmitter. Deviating from this instruction
sheet, or using other replacement parts, may invalidate the product approvals
marked on the transmitter nameplate.
Hi-Pot (Dielectric Strength) Test – : The replacement sensor electronic
modules are hi-pot tested at the factory prior to shipment, using a voltage of
850V for 1 second. If applicable standards for the installation still require
a hi-pot test after device repair, the voltage shall not exceed 600Vac or
850Vdc between loop terminals and case. The hi-pot test will fail with
lightning protection terminal assemblies installed. The hi-pot test must only
be performed with a non-lightning protected terminal assembly installed in the
transmitter during the test.
The Hi-Pot test may be performed on the transmitter electronics, before re-
installing on the process connector.
Appendix: Reconciling Model Numbers
If a spare sensor electronics housing has been used in a transmitter, it will
likely have a model number which does not match the model number stored in the
COMM electronics. This will cause an error.
Using three-button interface and display:
The error can be identified by selecting
Monitor
-
Non-critical errors
o The error will appear as Model Number Mismatch
To clear this error, select
Monitor -
Model Number
The Sensor Model Number and the Communication Model number can be displayed.
To clear the error, a Matching Source will have to be selected. In most cases
this will be the COMM module; however, in some cases Sensor module can be
selected. The Do Match must be selected to clear the fault.
Refer to the User’s manual for instructions on using the three-button
interface.
Using the DTM:
The error can be identified from the Monitor, Device Status & Alarms screen.
The error is identified as Model Number Mismatch (see Figure 7)
To clear this error, Navigate to the Advanced Configuration, Services tab and select Reconcile Model Numbers. In most cases, it will be appropriate to select Use Comm Module Model Number to clear the error. After selection, the transmitter will restart.
Sales and Service
For application assistance, current specifications, pricing, or name of the
nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC
Honeywell Process Solutions,
Phone: + 800 12026455 or
+44 (0) 1202645583
(TAC) hfs-tacsupport@honeywell.com|
EMEA
Honeywell Process Solutions,
Phone: + 800 12026455 or
+44 (0) 1202645583
Email: (Sales)
FP-Sales-Apps@Honeywell.com
or
(TAC)
hfs-tac-support@honeywell.com|
AMERICAS
Honeywell Process Solutions,
Phone: (TAC) 800-423-9883
or 215-641-3610
(Sales) 1-800-343-0228
Email: (Sales)
FP-Sales-Apps@Honeywell.com
or
(TAC)
hfs-tac-support@honeywell.com
---|---|---
Australia
Honeywell Limited
Phone: +(61) 7-3846 1255
FAX: +(61) 7-3840 6481
Toll Free 1300-36-39-36
Toll Free Fax:
1300-36-04-70| China – PRC – Shanghai
Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826
---|---
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033| South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
For more information
To learn more about Smart Line Transmitters,
visit www.process.honeywell.com
Or contact your Honeywell Account Manager
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, USA, TX 77042
Honeywell Control Systems Ltd
Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jung Road
Shanghai, China 20061
www.process.honeywell.com
34-SL-33-02 Rev.2
February 2017