nortronic SR-2303AC-4CH-DIN 4 Channels DALI Phase Dimmer Instruction Manual
- June 4, 2024
- nortronic
Table of Contents
SR-2303AC-4CH-DIN 4 Channels DALI Phase Dimmer
Instruction Manual
Important: Read All Instructions Prior to Installation
Function introduction
Product Data
Output Voltage| Max. Load Current| Max. Load Power| DALI
Consumption| Size(LxWxH)
---|---|---|---|---
4x(100-240)VAC| 4×1.8A| 4x400W @ 230V
4x200W @ 110V| < 2mA| 145.4x90x66.4mm
Compatible Load Types
Load Symbol| Load Type| Maximum Load| Remarks
| Dimmable LED lamps| 1200W @ 110V, 1400W @ 230V
2150W @ 110V, 2300W @ 230V
3125W @ 110V, 3250W @ 230V
4100W @ 110V, 4200W @ 230V| Due to the variety of LED lamp designs, the
maximum number of LED lamps per channel is further dependent on the power
factor result when connected to a dimmer.
| Dimmable LED drivers| 1200W @ 110V, 1400W @ 230V
2150W @ 110V, 2300W @ 230V
3125W @ 110V, 3250W @ 230V
4100W @ 110V, 4200W @ 230V| Maximum permitted number
of drivers per channel is 200W/400W divided by driver nameplate power rating.
| Incandescent lighting,
Halogen 240V lamps| 1400W @ 110V, 1800W @ 230V
2300W @ 110V, 2600W @ 230V
3250W @ 110V, 3500W @ 230V
4200W @ 110V, 4400W @ 230V|
| Low voltage halogen
lighting with electronic
transformers| 1200W @ 110V, 1400W @ 230V
2150W @ 110V, 2300W @ 230V
3125W @ 110V, 3250W @ 230V
4100W @ 110V, 4200W @ 230V|
- In compliance with IEC 62386-101:2014, IEC 62386-102:2014, IEC 62386-207 Ed2.
- Built-in DALI-2 interface, DALI DT6 device
- Match all DALI systems in the market
- Safe and reliable full isolation design
- DALI phase dimmer, trailing edge dimming
- Supports resistive loads and capacitive loads
- DALI signal input, and DALI address can be set with buttons and displayed on the digital display
- DALI address quantity can be set as 1/2/3/4 to control 4 channels load simultaneously or separately
- 4 channels AC100-240V output
- To dim and switch single-color dimmable LED lamps, dimmable LED driver, and traditional incandescent and halogen lights
- Din rail installation, is easy and fast
- Waterproof grade: IP20
Safety & Warnings
- DO NOT install with power applied to the device.
- DO NOT expose the device to moisture.
Operation
Set DALI Address Manually Via Buttons
- Press and hold down any of the two buttons until the numeric digital display flashes, then release the buttons.
- Click any of the two buttons once to select a digit, and click again to change the digit until the desired DALI address appears. Click the first button to set the “tens” position and the second button to set the “units” position. The address can be set from 00~63.
- Then press and hold down any of the 2 buttons until the numeric digital display stops flashing to confirm the setting.
Note: DALI address can be manually assigned from 00-63-FF, by factory defaults, no DALI address is assigned for the driver, and the display shows . Setting the DALI address will reset the dimmer to factory defaults.
DALI Address Assigned by DALI Masters.
DALI address can also be assigned by the DALI Master controller automatically,
please refer to user manuals of compatible DALI Masters for specific
operations.
Note: The digital display will show AU when the DALI master is assigning
addresses.
Set DALI Address Quantity.
- Press and hold down both of the two buttons until the numeric digital display flashes, then release the button.
- Click the first button to select “1A”, “2A”, “3A” or “4A” which means 1/2/3/4 DALI addresses.
- Then press and hold down any of the 2 buttons until the numeric digital display stops flashing to confirm the setting.
For example, when we set the DALI address to 00:
When selecting 1A, all 4 channels load will be the same address 00 and
controlled simultaneously.
When selecting 2A, channels L1&L3 will be same address 00, channel 2&4 will be
same address 01.
When selecting 3A, channels L1&L4 will be addressed 00, channel L2 will be
addressed 01, and channel L3 will be addressed 02.
When selecting 4A, channel L1 will be addressed 00, channel L2 will be
addressed 01, channel L3 will be addressed 02, and channel L4 will be
addressed 03.
Note: The channels with the same address will be controlled simultaneously,
and the channels with different addresses will be controlled separately.
Reverse-phase control (trailing edge)
Set the minimum dimming brightness point.
The factory dimming range is 1%~100%, but the 1% can be re-set as below:
Operate the DALI master to dim a load of L1 to a brightness you want, then
press and hold down the Min. set button until the light flashes, which means
the minimum point is set at this brightness now. You can not dim lower than
this brightness point. The minimum point will be covered by repeating that.
How to reset it to factory defaults: dim up the Load of L1 to 100%, then press
and hold Min. set button until a load of L1 flashes.
Note:
- The dimming range of this dimmer is 1%-100%, but some load types may flicker when dimmed to 1%, thus a minimum brightness shall be set higher than 1% to avoid flickering during the dimming process.
- Whatever the DALI address quantity is set as 1A, 2A, 3A, or 4A, the minimum brightness shall be set or reset only by adjusting the Load L1 output brightness and pressing Min. set button. Once the minimum brightness is set, all 4 channels’ load can not be dimmed below this value.
Wiring Diagram
-
With DALI bus
This phase dimmer adopts trailing edge dimming (reverse phase control), the dimming range is 1%~100%, please make sure the connected loads support reverse phase control. Please refer to the user manual of the load or consult the supplier of the load. -
With AC Push
Product Dimension
Read User Manual Online (PDF format)