Quick Start
-
Put the unit in a dry, clean place.
-
Plug the unit into a power outlet.
-
Plug in the loads.
Never plug in a laser printer or plotter. This kind of loads can draw more power than the unit can provide. -
Press the On/Off button for 1 second. The green LED on the front panel turns on. If it doesn’t, do troubleshooting as outlined in this manual.
-
One at a time, turn on the loads. If the buzzer is continuously on, the unit is overloaded. Turn off unnecessary loads.
-
To turn the unit off, press the On/Off button for more than 3 seconds.
Safety Instructions
Do not expose this unit to water.
This unit contains sealed lead-acid batteries:
- Servicing should be done by people qualified in the care of high-energy power supplies.
- Use insulated tools.
- Remove rings, watches, or other metal objects before opening the unit.
- Do not open the battery. Its contents are toxic.
- Do not short the battery terminals. This may cause a fire or explosion.
- Do not put the battery in a fire to dispose of it. It may explode.
Save This Manual
It contains important installation and operating instructions. Keep it in a
safe place.
The Alpha Tetrex UPS
The Alpha Tetrex Uninterruptible Power Supply (UPS) is a microprocessor- controlled line interactive unit designed for indoor use. It has automatic frequency sensing to match the output frequency with the input’s. If the output is overloaded, the unit automatically shuts down to protect the loads. The drawings below are for illustrative purposes only. See your unit for the exact type, number and location of the connectors and controls used.
Using the On/Off Button
- AC start with green mode on: When the unit is connected to line power, press this button for 1 second to turn on the unit.
- Green mode: When green mode is on and the line becomes unqualified and less than 20 watts of power is drawn by the loads, the unit automatically turns off. When the line is requalified, the unit automatically turns on.
- AC start with green mode off: When the unit is connected to line power, press this button until the beeping stops. The unit is turned on and green mode is disabled.
- DC start with green mode on: This starts the unit when line power is absent or unqualified. Press this button for up to three seconds. Backup battery power is provided to the loads.
- DC start with green mode off: This starts the unit when line power is absent or unqualified. Press this button until the unit starts beeping. Backup battery power is provided to the loads and green mode is disabled.
- Shut off: Press the on/off button for more than 3 seconds.
- Self test: When the unit is connected to line power, press the on/off button.
- Buzzer off: Except for the low battery and overload alarms, turn off the buzzer by pressing the on/off button for 1 second.
Alarms and Troubleshooting
This unit has several audible alarms. To turn off the alarm, press the power button.
- Slow Alarm (1 beep every 2 seconds): Most alarms except for low battery and overload. See the troubleshooting table.
- Low Battery Alarm (1 beep every 1/2 second): The unit is operating on battery power and the battery is almost discharged. This alarm cannot be shut off.
- Overload (continuous beeping): The unit is overloaded and it automatically turns itself off. Disconnect unnecessary loads and restart the unit. This alarm cannot be shut off.
Symptom | Troubleshooting Table Causes | Action |
---|---|---|
Unit does not turn on, the LED is not on. | The | |
power switch is not pushed. | Push it for more than 1 second | |
Battery voltage less than 20 VDC. | Plug the unit into the line for at least 6 |
hours to recharge the battery then restart.
Load less than 20W when unit is in battery mode.| This is normal. The unit’s
“green mode” is active.
PCB failure.| Contact Alpha Technologies.
Unit is always in battery mode.| Power cord loose.|
Plug it in.
AC fuse blown or breaker tripped.| Replace the fuse or reset the breaker.
PCB failure.| Contact Alpha Technologies.
Backup time less than predicted| Battery is not
charged.| Plug the unit into the line for at least 6 hours to recharge the
battery then restart.
PCB failure.| Contact Alpha Technologies.
The buzzer is continuously beeping| The unit is overloaded.|
Turn off some of the loads.
For emergency technical support 7 days a week / 24 hours a day call:
USA: 1-800-863-3364
CANADA: 1-800-667-8743
For technical support or for other information, contact Alpha’s customer service department at:
United States: 360-647-2360
Canada: 604-430-1476
United Kingdom: +44-1279-422110
Germany: +49-9122-79889-0
Middle East: +357-253-75675
Australia: +61-2-9722-3320
Communications
The Alphamon software and the unit’s RS-232 port let you remotely monitor and
control the unit. The software is supported by DOS, Windows
3.1/95/98/2000/ME/XP/NT, Novell Netware, and Linux. Contact Alpha Technologies
for more information.
The software lets you:
- Turn off the unit.
- Set up an alarm when line power is unqualified.
- Shut off power to the loads before the battery is drained.
Cable kits to connect your unit to a computer are available from Alpha Technologies. Installation instructions are in the “read me” file in the software.
Specifications
Specifications subject to change without notice.
WARRANTY
LIMITED 24-MONTH WARRANTY AC PRODUCTS
Alpha Technologies warrants its equipment to be free of manufacturing defects in material and workmanship for 24 months from the date of manufacture. The liability of Alpha Technologies under this warranty is solely limited to repairing, replacing, or issuing credit for such equipment (at the discretion of Alpha Technologies), provided that:
- Alpha Technologies’ Customer Service Department is promptly notified, by facsimile or telephone, that a failure or defect has occurred.
- Alpha Technologies’ Customer Service Department issues a Return Materials Authorization (RMA) number, and designates the service location. The RMA must be marked on the outside of the shipping container.
- Purchaser is responsible for all inbound shipping and handling charges (COD and freight collect will not be accepted without prior approval from Alpha Technologies); Alpha Technologies will pay outbound surface shipping charges for return of repaired equipment.
- A satisfactory examination of the returned unit by Alpha Technologies’ Service personnel shall disclose that defects have not been caused by misuse, neglect, improper installation, repair, alteration, or accident, or failure to follow instructions furnished by Alpha Technologies. If Alpha Technologies’ Service personnel determine that the unit has been damaged due to one of these causes, or if the unit is free of defects, a handling or repair fee may be assessed before returning the unit.
CONCERNING BATTERIES, PERIPHERAL DEVICES, ATTACHMENTS OR APPARATUS NOT MANUFACTURED BY ALPHA TECHNOLOGIES, ALPHA WILL ASSIGN TO THE PURCHASER ITS RIGHTS UNDER THE ORIGINAL MANUFACTURER’S WARRANTY OF SUCH BATTERIES, PERIPHERAL DEVICES, ATTACHMENTS OR APPARATUS, BUT OFFERS NO ADDITIONAL WARRANTIES IN CONNECTION THEREWITH.
THIS LIMITED 24-MONTH WARRANTY IS INSTEAD OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE.
IN NO CASE SHALL ALPHA TECHNOLOGIES BE LIABLE FOR ANY INCIDENTAL, SPECIAL OR
CONSEQUENTIAL DAMAGES WHATSOEVER, INCLUDING WITHOUT LIMITATION ANY CLAIM FOR
LOST PROFITS OR REVENUES, EVEN IF ALPHA TECHNOLOGIES HAS BEEN ADVISED OF THE
POSSIBILITY OF SUCH, FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED.
Any action for breach of this limited 24-month warranty must be brought within 24 months from date of manufacture. This limited 24-month warranty does not extend to any unit that has been repaired or altered by any party other than Alpha Technologies or its Authorized Service Center. Alpha Technologies reserves the right to discontinue particular models and to make modifications in design and/or function at any time, without notice and without incurring obligations to modify previously purchased units.
Alpha Technologies
3767 Alpha Way
Bellingham, WA, USA 98226
Tel: 360-647-2360
Fax: 360-671-4936
Alpha Technologies Ltd.
4084 McConnell Court
Burnaby, BC, Canada V5A 3N7
Tel: 604-430-1476
Fax: 604-430-8908
Alpha Technologies
Cartel Business Estate
Edinburgh Way
Harlow, Essex CM20 2TT, UK
Tel: +44-1279-422110
Fax: +44-1279-423355
Alpha Technologies GmbH
Hansastrasse 8
D-91126 Schwabach, Germany
Tel: +49-9122-79889-0
Fax: +49-9122-79889-21
MTI Technologies
P.O. Box 56468
Limassol, Cyprus 3307
Tel: +357-253-75675
Fax: +357-253-59595
Alpha Technologies
Units R5-R7, Regents Park Estate
Cnr Park Rd. and Prince’s Rd East
Regents Park, NSW 2143, Australia
Tel: +61-2-9722-3320
Fax: +61-2-9722-3321
Alpha sales and service offices located throughout the world
© 2004 Alpha Technologies
http://www.alpha.com
References