KeepRite XC35CX Quiet Line Condensing Unit Instruction Manual
- June 17, 2024
- KeepRite
Table of Contents
APPLICATION BULLETIN
KPB-4006-02-1
CS-322
Rev. 1 August 2023
XC35CX Quiet Line Condensing Unit
National Refrigeration and Air Conditioning Canada Corp.
159 Roy Blvd., P.O. Box 2020, Brantford, ON, Canada N3T 5Y6
KQ-QUIETLINE – XC35CX (RTC) REAL TIME CLOCK
New XC35CX control
Beginning August 2023, KeepRite will begin to manufacture all models in the
Quiet Line Condensing unit product line with an updated XC35CX Dixell control.
The updated control includes the functionality of a programmable (RTC) Real
Time Clock. The RTC eliminates the need for a conventional mechanical time
clock for air and electric defrost applications. This bulletin serves to
highlight the wiring and programming changes required to activate the RTC
feature on Non ESP+ applications.
Part#1111400 Firmware: V6-MT or V6-LT
Medium/High-Temperature Units (Timed Air Defrost)
Medium and High-Temperature units are now equipped with a control relay “R1
Defrost Timer Relay”. This relay requires field wiring to the common terminal
on the room thermostat. This will de-energize the liquid line solenoid coil,
close the solenoid valve, and pump down the system to perform the air defrost
cycle.
Figure:1 Wiring Diagram: S2Q1W6/KA151XC
Low-Temperature Units (Timed Electric Defrost)
Low-temperature units are now equipped with a control relay “R1 Defrost Timer
Relay”. This relay requires field wiring to the common terminal on the room
thermostat and the evaporator fan motors or fan contactor coil, depending on
the evaporator(s) used. This will de-energize the fans and liquid line
solenoid coil, close the solenoid valve, and pump down the system to perform
the electric defrost cycle. An additional control relay “R2 Defrost
Termination Relay” requires wiring to the “X” terminal on the evaporator
terminal board. When energized, the relay coil will close a set of normally
open (N.O) contacts wired to terminals 22 & 23 on the XC35CX control and
terminate defrost.
Figure 2:Wiring Diagram: T3Q1W6/LPE152-XC
XC35CX Control Programming
All Quiet line Condensing units with the updated XC35CX control will not have
timed defrost capabilities enabled. All defrost settings will remain dormant
unless specifically enabled. To enable the RTC functionality the following
will need to be manually entered. ”Hur” Setting for local time and Date, “Pdt”
Pump down duration time. Time allowed for pump down when a defrost cycle is
initiated, default Time (2 minutes), “otd” Off Time Defrost Duration Default
(40 Minutes).
Defrost Cycle Start time “df1-8 ” and “nu” Setpoints will need to be
programmed to enable the Defrost clock functionality (Up to 8 Defrost Cycles
available).
Figure:3 Real Time Clock and Defrost Functions (Programming Menu)
Fig:1 Wiring Diagram: S2Q1W6/KA151XC Fig 2:Wiring Diagram:
T3Q1W6/LPE152-X Fig:3 Real Time Clock and Defrost Functions
(Programming Menu)
REAL TIME CLOCK AND DEFROST FUNCTIONS
(Controlling parameters: Configuration Setpoint, alarms and defrost schedule)
Parameter | Description | Low | Medium | Prog. Level |
---|---|---|---|---|
Std | Set point for Pump-down | 7 | 27 | Pr2 |
HYd | Hysteresis for Pump-down | 14 | 20 | Pr2 |
Pdt | Pump down duration | 2 | Pr1 | |
otd | Off time defrost duration | 40 | Pr1 | |
oA2 | Digital output AUX2 configuration (Relay 5A) | PdU | Pr2 | |
i2F | Digital input 2 function | PdE | Pr2 | |
i2P | Digital input 2 polarity | CL | Pr2 | |
dF1 | 1st Defrost Cycle starting time | nu | Pr1 | |
dF2 | 2nd Defrost Cycle starting time | nu | Pr1 | |
dF3 | 3rd Defrost Cycle starting time | nu | Pr1 | |
dF4 | 4th Defrost Cycle starting time | nu | Pr1 | |
dF5 | 5th Defrost Cycle starting time | nu | Pr1 | |
dF6 | 6th Defrost Cycle starting time | nu | Pr1 | |
dF7 | 7th Defrost Cycle starting time | nu | Pr1 | |
dF8 | 8th Defrost Cycle starting time | nu | Pr1 |
Refer to https://docs.k-rp.com/1110230.pdf for additional Programming
instructions.
1. Additional Resources
KeepRite Refrigeration website: Commercial Refrigeration Systems & Solutions |
KeepRite Refrigeration (k-rp.com)
KeepRite Refrigeration equipment website: TQZ – Outdoor Air Cooled Quiet
Scroll Condensing Units – Trenton refrigeration (trp.com)
APPROVED FOR FOR PUBLIC DISTRIBUTION