KQ-QUIETLINE – XC35CX (RTC) REAL TIME CLOCK

New XC35CX control
Beginning August 2023, KeepRite will begin to manufacture all models in the Quiet Line Condensing unit product line with an updated XC35CX Dixell control. The updated control includes the functionality of a programmable (RTC) Real Time Clock. The RTC eliminates the need for a conventional mechanical time clock for air and electric defrost applications. This bulletin serves to highlight the wiring and programming changes required to activate the RTC feature on Non ESP+ applications.
Part#1111400 Firmware: V6-MT or V6-LT

Medium/High-Temperature Units (Timed Air Defrost)

Medium and High-Temperature units are now equipped with a control relay “R1 Defrost Timer Relay”. This relay requires field wiring to the common terminal on the room thermostat. This will de-energize the liquid line solenoid coil, close the solenoid valve, and pump down the system to perform the air defrost cycle.
Figure:1 Wiring Diagram: S2Q1W6/KA151XC

Low-Temperature Units (Timed Electric Defrost)

Low-temperature units are now equipped with a control relay “R1 Defrost Timer Relay”. This relay requires field wiring to the common terminal on the room thermostat and the evaporator fan motors or fan contactor coil, depending on the evaporator(s) used. This will de-energize the fans and liquid line solenoid coil, close the solenoid valve, and pump down the system to perform the electric defrost cycle. An additional control relay “R2 Defrost Termination Relay” requires wiring to the “X” terminal on the evaporator terminal board. When energized, the relay coil will close a set of normally open (N.O) contacts wired to terminals 22 & 23 on the XC35CX control and terminate defrost.
Figure 2:Wiring Diagram: T3Q1W6/LPE152-XC

XC35CX Control Programming

All Quiet line Condensing units with the updated XC35CX control will not have timed defrost capabilities enabled. All defrost settings will remain dormant unless specifically enabled. To enable the RTC functionality the following will need to be manually entered. ”Hur” Setting for local time and Date, “Pdt” Pump down duration time. Time allowed for pump down when a defrost cycle is initiated, default Time (2 minutes), “otd” Off Time Defrost Duration Default (40 Minutes).
Defrost Cycle Start time “df1-8 ” and “nu” Setpoints will need to be programmed to enable the Defrost clock functionality (Up to 8 Defrost Cycles available).
Figure:3 Real Time Clock and Defrost Functions (Programming Menu)

Fig:1 Wiring Diagram: S2Q1W6/KA151XC  KeepRite XC35CX Quiet Line Condensing
Unit - Diagram 1 Fig 2:Wiring Diagram: T3Q1W6/LPE152-X KeepRite XC35CX Quiet Line Condensing Unit - Diagram
2Fig:3 Real Time Clock and Defrost Functions (Programming Menu)
REAL TIME CLOCK AND DEFROST FUNCTIONS
(Controlling parameters: Configuration Setpoint, alarms and defrost schedule)

Parameter Description Low Medium Prog. Level
Std Set point for Pump-down 7 27 Pr2
HYd Hysteresis for Pump-down 14 20 Pr2
Pdt Pump down duration 2 Pr1
otd Off time defrost duration 40 Pr1
oA2 Digital output AUX2 configuration (Relay 5A) PdU Pr2
i2F Digital input 2 function PdE Pr2
i2P Digital input 2 polarity CL Pr2
dF1 1st Defrost Cycle starting time nu Pr1
dF2 2nd Defrost Cycle starting time nu Pr1
dF3 3rd Defrost Cycle starting time nu Pr1
dF4 4th Defrost Cycle starting time nu Pr1
dF5 5th Defrost Cycle starting time nu Pr1
dF6 6th Defrost Cycle starting time nu Pr1
dF7 7th Defrost Cycle starting time nu Pr1
dF8 8th Defrost Cycle starting time nu Pr1

Refer to https://docs.k-rp.com/1110230.pdf for additional Programming instructions.
1. Additional Resources
KeepRite Refrigeration website: Commercial Refrigeration Systems & Solutions | KeepRite Refrigeration (k-rp.com)
KeepRite Refrigeration equipment website: TQZ – Outdoor Air Cooled Quiet Scroll Condensing Units – Trenton refrigeration (trp.com)
APPROVED FOR FOR PUBLIC DISTRIBUTION

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals