Ei Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm Instruction Manual
- June 17, 2024
- Ei Electronics
Table of Contents
Ei3024 / 3016 / 3014
Alarms
Instruction Manual
Mains Powered
EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm
Read and retain carefully for as long as the product is being used. It
contains vital information on the operation and installation of your Alarm.
The leaflet should be regarded as part of the product.
If you are just installing the unit, the leaflet MUST be given to the
householder. The leaflet is to be given to any subsequent user.
Introduction
The Ei3024 is a Multi-Sensor Fire Alarm with heat enhanced optical smoke
sensor and automatic dust compensation, delivering a faster response to a
wider range of fires. It detects both smoke and heat from a fire and is ideal
for hallway, landing, living room and bedroom areas.
The Ei3016 is an Optical Smoke Alarm, with a proven optical sensor and
automatic dust compensation delivering a fast response to smouldering fires.
It is ideal for hallway, landing and living room areas.
The Ei3014 is a Heat Alarm with a Class A1 heat detection sensor. It can only
to be used as part of a fire detection system, i.e. interconnected with Ei
Electronics mains powered Multi-Sensor Fire or Smoke Alarms. It is ideal for
kitchens, garages, boiler houses and other areas where there are normally high
levels of fumes, smoke or dust i.e. places where Smoke Alarms cannot be
installed without the risk of excessive nuisance alarms.
Up to 12 Alarms can be interconnected so that if one senses fire, all Alarms
sound. It can be a hardwired interconnection, a wireless interconnection or a
mixture of both (for the wireless option an Ei3000MRF SmartLINK module needs
to be added to each Alarm – sold separately).
The Ei3000 series is supplied with a mounting plate that allows very quick and
simple installation of the Alarm. The mains and battery power is automatically
connected as the Alarm slides onto the mounting plate. Each Alarm comes with
built-in rechargeable backup batteries to power the Alarm in the event of a
mains failure.
AudioLINK
The Ei3000 series Alarms are AudioLINK enabled. This feature allows the user
to download information from the Alarm through the use of a mobile App. For
more information on using this feature, please refer to the relevant section
on www.eielectronics.com or
www.aico.co.uk.
1.1 Overview
Ei3024 Multi-Sensor Fire Alarm
![Ei Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm
- Fire Alarm](https://manuals.plus/wp-content/uploads/2024/02/Ei-Electronics- EI3024-Multi-Sensor-Fire-Alarm-Optical-Smoke-Alarm-Heat-Alarm-Fire-Alarm.png)
Ei3016 Optical Alarm | Ei3014 Heat Alarm |
---|
![Ei Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm
- Optical Alarm](https://manuals.plus/wp-content/uploads/2024/02/Ei- Electronics-EI3024-Multi-Sensor-Fire-Alarm-Optical-Smoke-Alarm-Heat-Alarm- Optical-Alarm.png)|
1.2 Technical Specifications
Optical Sensor | Optical (Ei3024 and Ei3016) |
---|---|
Heat Sensor | Thermistor Class A1 Detection (Ei3014 and Ei3024) |
Power Supply | 100-250V AC, 50Hz, 0.25W |
Battery Backup | Built-in 10-year rechargeable Vanadium Pentoxide Lithium |
cells. Fully
charged, the battery will provide up to 6 months (without module
fitted) or 3 months (with module fitted) back-up without mains power
Alarm Sounder| Piezoelectric Horn
Alarm Sound Level| 85dB(A) at 3 meters (min)
Memory Feature| Indicates that the Alarm has previously detected fire
Self Test| Sensors, batteries and electronics are automatically tested
periodically
Test/Hush Button| Checks sensors, electronics, interconnection and sounder.
If the unit is in alarm when pressed, it silences the alarm for 10min
Visual indicators| Green LED – Power supply
Yellow LED – Fault, EOL
Red LED – Memory or alarm (if coincides with horn sounding)
AudioLINK| Enabled
Operational Life| 10 years
Interconnection| Up to 12 units can be interconnected via a hardwired or
wireless system (using optional Ei3000MRF SmartLINK module)
Fixings| Supplied with Easi-fit anti-tamper mounting plate with integral
terminal block and wiring cover, includes screws and wall plugs
Operating Temperature| Normal: 0°C to +40°C (Storage: 0°C to +40°C) *
Humidity Range| 15% to 95% RH (non-condensing)
Plastic Material| UL94V-0 flame retardant rated
Dimensions| Ei3016:
Package – 155mm x 155mm x 70mm
Product: – Ø150mm x 63mm
Package – 155mm x 155mm x 65mm
Weight| 350g (including packaging)
Warranty| 5 year (limited)
Approvals| KM522831
KM83678
EN14604:2005+AC 2008
BS5446-2:2003
- Temperature and Humidity conditions are for normal operation and storage. Units will function outside these ranges as required by the specific product Standards. Extended exposure to conditions outside these ranges can reduce product life. For advice on prolonged operation outside these ranges consult the manufacturer.
Installation
2.1 Important Safety Instructions
Mains operated Alarms should be installed and interconnected by a
qualified electrician in accordance with the local appropriate Regulations for
Electrical Installations. Failure to install this Alarm correctly may expose
the user to shock or fire hazards and damage the product.
The Alarm is designed to be permanently mounted, using its own built-in
terminal block to connect it to the mains. The mounting plate can be screwed
directly to the ceiling. Alternatively, it can be screwed to a standard
junction box (BS 4662 single gang accessory box) . It requires a typical
current of 3mA. The Alarm must not be exposed to dripping or splashing. There
are important markings on the underside of the Alarm.
Alternative Energy Sources – (Wind, Solar, UPS etc.)
This product is designed to be connected to a Pure or True Sine Wave 230V AC
supply. If connecting to a power source that utilises an inverter, e.g. PV
solar panel, the Total Harmonic Distortion (THD) must be less than 5% . If in
doubt please check with the manufacturer of the inverter. This also applies to
battery powered UPS (Uninterruptible Power Supply) inverters.
Light Dimmer Circuits – The Alarms must not be powered from a light
dimmer circuit.
Do not install Alarms in new or renovated buildings until all work is
completed.
The Alarm must not be connected when the house wiring insulation is
being checked with high voltages. i.e. Do not use a high voltage insulation
tester on the Alarm.
The Alarm must be continuously powered 24 hours a day so it is important
that it is not on a circuit that can be turned off by a switch.
(UK) BS 5839-6: 2013 gives the following recommendations regarding the
mains supply to be used in a Grade D system. The power supply for the Alarms
should be derived from the public electricity supply to the dwelling. The
mains supply to the Alarms should take the form of either: (a) an independent
circuit at the dwelling’s main distribution board, in which case no other
electrical equipment should be connected to this circuit (other than a
dedicated monitoring device installed to indicate failure of the mains supply
to the Alarms); or (b) a separately electrically protected, regularly used
local lighting circuit. Alarms should be connected on a single final circuit,
unless the means of interconnection is by radio signals (e.g. RadioLINK) .
(See BS 5839-6: 2013 for further information)
(IRE) Please refer to ET101: 2008: National Rules for Electrical
Installations
2.2 Where to locate the Alarm
The advice here follows the guidance in British Standard BS 5839-Part 6:2013
and IS 3218:2013 in general (for further information refer to the relevant
standards).
The main reason for fitting Smoke/Heat/Multi-Sensor Alarms in dwellings is to
ensure that when there is a fire, sufficient early warning is given so that
everybody can escape safely. This means that the fire Alarms should ideally be
located near all potential sources of fires and that the alarm should be heard
throughout the house – particularly in the bedrooms.
It is also important that nuisance/false alarms are minimised to ensure the
Alarms are not disabled or ignored.
A single Smoke Alarm will give some protection if it is properly installed,
but most homes will require two or more to ensure that a reliable early
warning is given. For recommended protection you should put individual Smoke
Alarms in all rooms where fire is most likely to break out (apart from the
kitchen and bathroom).
BS 5839-Part 6:2013 and IS 3218:2013 give guidance on:
– how many Alarms to install
– what type of Alarm to use
– where to position Alarms
The above points will depend on the type of dwelling to be protected and the
level of fire risk.
Fire Risk Assessment
The ‘Grade’ and ‘Category’ of system that should be installed depends on the
fire risk. It is therefore recommended that a Fire Risk Assessment is
undertaken. The Risk Assessment would be based on a combination of
probabilities:
– fire occurring
– injury or death to occupant
– system operating correctly with a fire
– early detection and warning to occupants in the event of a fire.
The greater the risks, the more comprehensive and reliable systems needs to
be.
LD (Life protection in Dwellings) Systems define the level of fire protection
required for households, depending on the fire risk and regulations. Ei
Electronics recommends that an LD1 system be installed for optimum protection.
Please see following pages for detailed information.
UK Requirements (BS 5839-6:2013)
LD 1 OPTIMUM PROTECTION
for dwellings where occupants may be at high risk (e.g. elderly)
Optimum Protection LD1: As LD2, but in addition Smoke or Heat Alarms should be
located in all rooms and other areas of the dwelling.
(apart from toilets or bathroom)
Interconnect all Alarms
LD 2 BASIC PROTECTION
for new or materially altered dwellings or existing dwellings with poor
structural fire precautions
Basic Protection LD2: Smoke or Heat Alarms in all rooms or areas that present
a high fire risk to occupants. (apart from toilets or bathroom)
Interconnect all Alarms
LD 3 MINIMUM PROTECTION
Minimum Protection LD3: Alarms in all hallways, stairways and circulation
areas that form part of the escape routes from the dwelling.
Multi-Sensor or Smoke Alarms located:
- on each storey
- every 7.5 m of hallways and escape routes
- within 3m of all bedroom doors (apart from toilets & bathrooms )
Heat Alarms located in:
- each Kitchen (Heat Alarms must be within 5.3m of potential fire sources)
Multi-Sensor or Heat Alarms located in:
- each Living room (i.e. most frequently used daytime room)
![Ei Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm
- Multi Story](https://manuals.plus/wp-content/uploads/2024/02/Ei-Electronics-
EI3024-Multi-Sensor-Fire-Alarm-Optical-Smoke-Alarm-Heat-Alarm-Multi-Story.png)
Multi Storey Dwelling LD1| Multi Storey Dwelling LD2
---|---
Multi-Sensor Fire Alarm| Optical Smoke Alarm| Heat Alarm| do not fit Alarm
---|---|---|---
ROI Requirements (IS 3218:2013)
LD1 OPTIMUM PROTECTION
for dwellings where occupants may be at high risk (e.g. elderly)
Optimum Protection LD1: As LD2, but also including attics / lofts / other
spaces in which a fire might start (apart from toilets or bathroom).
Interconnect all Alarms
LD2 BASIC PROTECTION
for new or materially altered dwellings or existing dwellings with poor
structural fire precautions
Basic Protection LD2: all circulation areas that form part of an escaper route
within the dwelling, and all high fire risk areas / rooms e.g. kitchen, living
rooms, garages and all bedrooms (apart from toilets or bathroom).
Interconnect all Alarms
Multi-Sensor or Smoke Alarms located:
- on each storey
- every 7.5 m of hallways and escape routes
- within 3m of all bedroom doors
(apart from toilets & bathrooms )
Heat Alarms located in:
- each Kitchen
(Heat Alarms must be within 5.3m of potential fire sources)
Multi-Sensor or Heat Alarms located in:
- each Living room (i.e. most frequently used daytime room)
![Ei Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm
- OPTIMUM PROTECTION](https://manuals.plus/wp-content/uploads/2024/02/Ei-
Electronics-EI3024-Multi-Sensor-Fire-Alarm-Optical-Smoke-Alarm-Heat-Alarm-
OPTIMUM-PROTECTION.png) Multi Storey Dwelling LD1| Multi Storey Dwelling LD2
---|---
Multi-Sensor Fire Alarm| Optical Smoke Alarm| Heat Alarm| do not fit Alarm
---|---|---|---
2.3 Which Alarm in what room?
Location| Ei3024 Mutil-Sensor Fire Alarm| E i3016 Optical Smoke Alarm| E i3014
Heat Alarm (i)
---|---|---|---
Hall, Corridors, Escape routes| |
|
Kitchens / Garages| | | (iii)
Living Rooms| | | (ii)
Bedrooms| | |
Shower / Bathrooms| | |
(i) A Heat Alarm should only be used in a room adjoining an escape route, in
conjunction with Multi-Sensor Fire Alarms or Smoke Alarms on the escape
routes. All the Alarms should be interconnected to ensure the early warning
will be heard.
(ii) Some Fire authorities (concerned with the slow response of Heat Alarms)
advise that Multi-Sensor Fire Alarms or Smoke Alarms should be fitted in
living rooms. This is acceptable according to BS 5839-6 provided there are
clearly not going to be problems with nuisance alarms. Fit Heat Alarms only if
nuisance alarms are very likely and it is acceptable that a warning will only
be given by the Heat Alarm when there is a very significant flaming fire in
the room. If the door(s) and windows are not closed to contain the fire and
heat, it is extremely unlikely that the Heat Alarm would respond before a
Multi-Sensor Fire Alarm or Smoke Alarm sited outside in the corridor.
(iii) In enclosed kitchens with doors closed.
Improved Audibility
The effectiveness of a Category LD2 (UK) system can be significantly enhanced
if an additional Alarm (interconnected) is installed in the master bedroom.
This will help ensure that a responsible person will quickly be alerted to a
fire and can arrange for an orderly evacuation of children and other
vulnerable occupants.
Grade D System
The mains powered Ei3024 Multi Sensor Fire Alarm, Ei3016 Smoke Alarm and
Ei3014 Heat Alarm with rechargeable battery back-up, covered by these
instructions are suitable for the requirements for a Grade D System.
A Grade D system is needed for:
– new or materially altered dwellings up to three-storeys, with no floor over
200m² in area.
– Existing dwellings with poor structural fire precautions, up to three
storeys, with no floor over 200m² in area.
– Houses in Multiple Occupation (HMOs) of one or two-storeys, with no floor
over 200m² in area.
– Individual dwellings units of two or more rooms in HMOs.
Check that a Grade D system is adequate for the dwelling into which the system
is being installed.
2.4 Where in the room?
The locations must comply with applicable building regulations Ceiling Mounting
Hot smoke rises and spreads out, so a central ceiling position is the
preferred location. The air is “dead” and does not move in corners, therefore
Alarms must be mounted away from corners. Fit the Alarm:
– At least 300mm away from walls (see Figure 1).
– At least 300mm from any light fitting or decorative object which might
obstruct smoke / heat entering the Alarm. Wall Mounting (Ei3016 only)
If ceiling mounting is impractical, only the Ei3016 Optical Smoke Alarm may be
mounted on a wall, provided that:
a) the top of the detection element is between 150mm and 300mm below the
ceiling (see Figure 2);
b) the bottom of the detection element is above the level of any door
openings;
Wall mounting should only be considered where close spaced beams or similar
obstructions may preclude ceiling mounting. It is considered to be the
responsibility of the installer/client to determine if the presence of
asbestos in the ceiling material would make ceiling mounting ‘impractical’.
![Ei Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm
- Sloping Ceiling](https://manuals.plus/wp-content/uploads/2024/02/Ei-
Electronics-EI3024-Multi-Sensor-Fire-Alarm-Optical-Smoke-Alarm-Heat-Alarm-
Sloping-Ceiling.png)Sloping Ceiling
With a sloping or peaked ceiling install a Smoke or Multi-Sensor Fire Alarm within 600mm of the peak (measured vertically) and a Heat Alarm within 150mm. If the height of the peak is less than 600mm in the case of Smoke or Multi- Sensor Fire Alarms or 150mm in the case of Heat Alarms, it is regarded as being flat. (see Figure 3).
2.5 Locations to avoid
DON’T place Smoke, Heat or Multi-Sensor Fire Alarms in any of the following
areas:
-
Bathrooms, shower rooms or other rooms where the Alarm may be triggered by steam, condensation.
-
Places where the normal temperature can exceed 40°C or be below 4°C (e.g. furnace rooms, directly above ovens or kettles etc.) as the heat/steam could cause nuisance alarms.
-
Near a decorative object, door, light fitting, window moulding etc., that may prevent heat or smoke from entering the Alarm.
-
Surfaces that are normally warmer or colder than the rest of the room (e.g. attic hatches) .
Temperature differences might stop heat or smoke from reaching the Alarm. -
Next to or directly above heaters or air conditioning vents, windows, wall vents etc. where air draughts can change the direction of airflow and cause rapid temperature fluctuations.
-
In very high or awkward areas (e.g. over stairwells) where it may be difficult to reach the Alarm (for testing, hushing etc.).
-
Locate away from very dusty or dirty areas as dust build-up on the optical smoke sensor can impair performance. It can block the insect screen mesh and prevent smoke from entering the sensor. Dust build up can also increase the response time of the heat sensor.
-
Locate the Alarm at least 1m from dimmer controlled lights and wiring as some dimmers can cause interference.
-
Locate the Alarm at least 1.5m and route wiring at least 1m away from fluorescent light fittings as electrical “noise” and/or flickering may affect the Alarm. Do not wire into the same circuit as fluorescent lights or dimmers.
-
Do not locate in insect infested areas. Small insects getting into the optical smoke sensor can cause intermittent false alarms. Insects and contamination on the heat sensor can increase its response time.
-
Do not locate in a damp or humid area.
Do not locate Heat Alarms directly above a sink or cooker – Keep at least 1 m horizontal distance between these items and the Alarm.
2.6 Mounting and wiring
-
Select a location complying with the advice in previous sections.
-
Disconnect the AC mains supply from the circuit that is going to be used.
-
Lift off the wiring cover as shown in Figure 4.
The wiring must be connected to the terminal block on the mounting plate as follows:
L: Live – connect to the house wires coloured brown or marked L.
N: Neutral – connect to the house wires coloured blue or marked N.
IC: Inter connect – see figures 5 and 6 and further information in Section 2.7.
Note: Wiring must be installed in compliance with local regulations.
Warning: Mixing (or leaving unattached) the Live and Neutral connections when interconnecting Alarms may damage all the Alarms – ensure that the same colour wires are used throughout the premises for Live, Neutral and Interconnect wires.
We strongly recommend that you check for the following before connecting the Alarm:
• check for Live and Neutral using a two probe tester.
• check for Live using a neon tester.
• check that the Interconnect wire is NOT connected to Live, Neutral or Earth. Do not use an Earth wire for the Interconnect line.
Note: The Alarm does not need to be earthed. However the terminal marked **** is provided for the convenience of the installer so that any copper Earth wire or cable coloured green and yellow, can be safely terminated.
To interconnect Alarms connect all the IC terminals together as shown in Figure 9 (see Interconnecting Alarms section). -
If the mains wires are recessed, bring the wires through the rear hole in the mounting plate as shown in Figure 5.
If the mains wires are being brought along the surface:
(a) position the mounting plate so the cable trunking is as shown in Figure 5.
(b) the mounting plate has a removable section, take it out to interface directly with 25mm trunking as shown in Figure 6.
If interfacing to 16mm trunking carefully cut around the marked section, leaving the top intact and replace the section. (If you are not using surface wiring, the removable section must be left in place for electrical safety reasons).
There are two other positions which are also suitable for the surface wiring to enter (and exit) the Alarm, one next to the removable section and another directly opposite. -
Carefully align the mounting plate and screw into place. Connect the wires to the terminal block.
With recessed wiring, ensure the rear gasket seals around the edge of the hole in the ceiling or wall.
This is to prevent air draughts affecting the smoke/heat entering the Alarm. If the hole is too large or the Alarm does not seal it, it should be sealed with silicone rubber or equivalent. -
Replace the wiring cover and carefully line up the Alarm on the base and slide on (see Figure 7).
-
Connect the mains power to the Alarm circuit. Check the green light on the front of the Alarm is on.
-
Press and hold the test/hush button for 10 seconds (see Figure 8) . The horn will sound. Check that any interconnected Alarms also sound within this period. The test button sounds the local horn and on release this horn stops immediately, and all the interconnected Alarms can then be heard in the distance as they will continue to sound for a further 3 seconds.
-
Attach the ’fuse board label’ provided on or near the distribution board and write in date installed and the number of Alarms on the circuit.
-
Ensure the Alarm operates correctly – see TESTING and MAINTAINING YOUR ALARM section.
2.7 Interconnecting Alarms
With interconnected Alarms, when one device detects Fire all detectors will
alarm. All horns will sound but only Alarms detecting the emergency event will
be flashing their red LED alarm indicator.
Heat Alarms should always be interconnected to Smoke or Multi-Sensor Fire
Alarms to ensure early warning.
Note: A maximum of 12 Fire / Smoke / Heat / CO Alarms and accessory
devices can be interconnected in an Ei Electronics Alarm system. (Any Ei3000
series Alarm can also be interconnected to an Ei2110e, Ei160e and Ei140RC
Series).
If you wish to connect more than 12 alarms, contact your local helpline.
WARNING: Do not connect these Alarms to any other type of Ei Alarm (apart
from those listed above) or to any other model produced by another
manufacturer. Doing so may damage the Alarms and could result in a shock or
fire hazard.
Systems using more than 3 or 4 Alarms must be very carefully planned to ensure
nuisance alarms are not excessive. e.g. from cooking fumes or steam. The
following is suggested:
- In an RF system an Ei Electronics Control Switch (Ei450) should be incorporated and be readily accessible to all occupants so that the source of an alarm can be quickly identified. This is especially important when both Fire and CO Alarms are used in the same system as the occupant will need to open all windows and doors if it is a CO incident but do the opposite to slow down a fire.
- All Alarms must be cleaned and maintained regularly.
- A qualified person must be on call to quickly remove any nuisance Alarms (i.e. Alarm with red LED alarm indicator flashing rapidly) which are causing all the other Alarms to sound.
Make electrical connections as shown in Figure 9.Wiring must be installed in compliance with local regulations.
In the UK and Ireland it is recommended that the following coloured cores are
used (for example with triple flat 6243YH cable).
230V supply : Brown
Neutral : sleeved blue at terminations
Interconnect : Black
In the other countries consult the local regulations as they maybe different
from the UK regulations.
The interconnect wire (minimum 0.75mm² cable) must be treated as if it was
Live. It should be insulated and sheathed.
A maximum of 250 metres of wire can be used (maximum resistance between
detectors 50 Ohms).
Alarms should be interconnected only within the confines of a single family
living unit. If they are connected between different units, there may be
excessive nuisance alarms.
Everybody may not be aware that they are being tested or that it is a nuisance
alarm caused by cooking etc.
The Alarm can also be RF interconnected to other RF Alarms and devices by
installing an Ei3000MRF SmartLINK Module. See the User manual for the
Ei3000MRF for further details on RF interconnection.
It is also equipped to work in a hybrid system (combination of hard-wired and
RF interconnected Alarms and devices).
Please note in a hybrid system containing CO / Heat / Fire / Smoke Alarms
we recommend using an Ei3000 series Alarm as the hybrid link to the RF section
of the system.
Ensure the Alarms operate correctly – see TESTING YOUR ALARM in the user
section.
2.8 Removing the Alarm
Disconnect mains before removal
-
Locate removal slot
Locate the arrow on the front face of the Alarm The slot is located directly above the arrow -
Insert screwdriver
Insert a flat-bladed screwdriver horizontally about 10mm into the centre of the removal slot -
Slide Alarm off base
With the screwdriver still inserted, push the lower half of the Alarm away from the screwdriver, it the direction of the arrows on the cover -
Remove Alarm
Hold the lower half of the Alarm and remove from the baseplate by lowering the Alarm towards the floor
Testing
3.1 Testing and maintaining your Alarm
Frequent testing of all your Alarms is a requirement to ensure they are
functioning correctly.
Guidelines and best practices for testing are as follows:
- After the system is installed.
- Once monthly thereafter.
- After prolonged absence from the dwelling (e.g. after holiday period) .
- After repair or servicing of any of the systems elements or household electrical works.
Inspecting and Testing proceedure
-
Check power
Check that there is a constant green light on the cover -
Test
Press the test button for 10 seconds.
The Alarm will sound loudly
(i) Check that the green LED power indicator is on continuously.
(ii) Check also that there are no faults i.e. NO green, yellow or red LED
flashing (if this is the case please see indicator summary table)
(iii) Press the test button for up to 10 seconds and ensure that the Alarm
sounds. This tests the sensor, electronics and sounder are working. The Alarm
will stop when the button is released. Pressing the test button simulates the
effect of smoke and/or heat and therefore is the best way to ensure the Alarm
is operating correctly. (Refer to indicator summary table if you see Red or
Yellow LED flashes) .
(iv) Interconnected Alarms only – Test the first unit by pressing the test
button for 10 seconds.
All the Alarms should sound within 10 seconds of the first horn sounding.
After releasing the test button, the local horn will stop sounding immediately
and the interconnected Alarms will be heard sounding in the distance for a
further 3-4 seconds. This feature gives an audible verification that the
interconnection is OK. Check all the other Alarms in the same way.
(v) Check the functioning of the mains battery back-up directly after
installation and then at least yearly as follows:
– Turn off the mains power at the distribution board and check that the green
indicator light is now flashing (1 flash every 48 seconds) to indicate the
Alarm is on backup battery power.
– Press the Test/Hush button for up to 10 seconds and ensure the horn sounds
loudly.
– Monitor the Alarm over a 3 minute period for any fault chirps and or yellow
LED fault indicator flashes (Refer to “Fault Modes” table on what to do if
this occurs)
– Turn the mains supply at the distribution board back on.
Switching off Mains for long periods
If the premises are regularly being left without mains power for long periods
the Alarms should be removed from their mounting plates and the Ei3000MRF
modules (if fitted) should be removed to prevent the batteries becoming fully
depleted. (This is sometimes done with holiday homes which are only occupied
in the summer).
The Ei3000MRF modules (if required) must be re-fitted to the Alarms and the
Alarms must be re-attached to the mounting plates when the premises are re-
occupied. Ensure to match the original RF module back to the same Alarm head.
(Long term storage (over 1 year) can damage the batteries such that they will
not recharge when the units are re-connected to the mains supply).
WARNING: DO NOT TEST WITH FLAME
This can set fire to the Alarm and damage the house. We also do not recommend
testing with heat as the results can be misleading unless special apparatus is
used.
3.2 Cleaning your Alarm
Clean your Alarm regularly. In dusty areas it may be necessary to clean the
Alarm more frequently.
- Vacuum
![Ei Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm
-
Vacuum](https://manuals.plus/wp-content/uploads/2024/02/Ei-Electronics- EI3024-Multi-Sensor-Fire-Alarm-Optical-Smoke-Alarm-Heat-Alarm- Vacuum.png)Vacuum around the side vents to clean
- Wipe
Clean the Alarm with a clean damp cloth and dry thoroughly
- Wipe
Use the narrow nozzle attachment of your vacuum cleaner to remove dust, insects and cobwebs from the sides and cover slots where the airflow enters. Clean the outside cover by occasionally wiping with a clean damp cloth then dry thoroughly with a lint free cloth. Do not use any cleaning agents, bleaches, detergents or polishes, including those in aerosol cans.
WARNING: Do not paint your Alarm.
Other than the cleaning described above, no other customer servicing of this
product is required.
Servicing or repairs, when needed, must be performed by the manufacturer.
All Alarms are prone to dust and insect ingress, which can cause false alarms
or failure to alarm.
In certain circumstances, even with regular cleaning, contamination can build
up in the smoke sensing chamber causing the Alarm to sound or fail.
Contamination is beyond our control, it is totally unpredictable and is
considered normal wear and tear. For this reason, contamination is not covered
by the guarantee.
What to do in case of alarm
(i) . Check room doors for heat or smoke. Do not open a hot door.
Use an alternate escape route. Close all doors behind you as you leave. (ii) . If smoke is heavy, crawl out, staying close to floor.
Take short breaths, if possible, through a wet cloth or hold your breath. More
people die from smoke inhalation than from flames.(iii). Get out as fast as you can. Do not stop for packing. Have a
prearranged meeting place outside for all family members. Check everybody is
there. (iv). Call the Fire Brigade immediately on a mobile phone or
from a neighbour‘s house. Make sure to call the Brigade for all fires no
matter how small – fires can suddenly spread. Also call the Brigade even if
the alarm is automatically transmitted to a remote manned centre – the link
may have failed. (v). NEVER re-enter a burning
house.
Troubleshooting and Indicator summary tables
Your Alarm does not sound when you press the Test button| • Check the Alarm is
secured correctly on the mounting plate.
• Wait 15 seconds after connecting the power before button testing.
• Hold button down firmly for at least 10 seconds.
• If the horn does not sound, then your Alarm must be returned for repair or
replacement – see GETTING YOUR ALARM SERVICED section
---|---
Your Alarm sounds for no apparent reason| • If, when the Alarm sounds, there
is no sign of smoke, heat or noise to indicate that there is a fire, you
should get your family into a safe place, before you start investigating.
Check the house carefully in case there is a small fire smouldering somewhere.
Check for smoke, fumes, steam, very hot air etc.
• Locate the Alarm that sounds and has flashing red LED.
• If you have thoroughly investigated and are sure that it is just a nuisance
alarm, simply press the Test/Hush button briefly to silence the Alarm for 10
minutes. This will also silence any interconnected Alarms for the same
period. When the Alarm is in ‘Hush’ mode the red LED will continue to flash
while it detects the presence of smoke or heat.
The Alarm will reset to normal functionality at the end of the 10 minute.
If additional silenced time is required, simply push the Test/Hush Button
again.
• If you experience frequent nuisance/false alarms, it may be necessary to re-
locate the Alarm away from the source of the fumes or if it continues to sound
without smoke or heat being present and cleaning the Alarm does not solve the
problem, it needs to be replaced
Interconnected Alarms do not all sound| • Hold test button for at least 10
seconds to ensure that the signal is transmitted to all the interconnected
Alarms.
• If this is not the case and you have a hardwired interconnection, we
recommend you consult a qualified electrician.
• If the Alarm is fitted with an RF module for wireless interconnection, check
that all Alarms in the RadioLINK system are powered and are house-coded
correctly. (see the Ei3000MRF SmartLINK module manual)
Pressing the Test/Hush button does not silence the Alarm| Always make sure
that you are pressing the Test/Hush button on the Alarm that sounds with the
red LED flashing.
Your Alarm chirps/beeps/flashes| In standby mode, the Alarm does not sound,
beep, chirp or flash. The only light on is the green power LED.
The Alarm automatically monitors the battery, sensor and electronics
periodically to ensure that all are satisfactory. If a fault has been found,
the Alarm alerts the occupier to this via short chirps from its sounder and
its yellow LED fault indicator flashes every 48 seconds. The Alarm will also
indicate any faults when the test button is pressed.
See indicator summary table on the next pages
Normal mode
Mode| Action| Green LED (power)| Yellow LED
(fault)| Red LED (alarm)| Sound
Power up| Slide onto mounting plate|
x 1
|
x 1
|
x 1
|
—
Standby|
—
| |
—
|
—
|
—
Testing (monthly)| Press and hold test button| |
—
|
—
|
In alarm mode
Detecting fire|
—
| |
—
| |
Activated via interconnect|
—
| |
—
|
—
|
Pressing Silence Button on Alarm detecting fire|
—
| |
—
| |
x 10mins
- With the test button held the green LED will flicker/pulse every second
= LED on solid = LED flashing
Memory mode
Status
|
Action
|
Red LED (alarm)
| Sound
0-24h
|
—
|
x2
every 48 sec
|
—
24h +
| Press and hold test button|
x2
every 8 sec
|
To erase the memory
| Keep test button pressed for >20s| |
Sounds until test button is released
The Alarm memory is an important feature where even if the house is unoccupied
during an alarm condition it warns the homeowner that the Alarm has previously
detected Fire and been in alarm.
The memory feature also helps identify the unit which has previously triggered
an entire alarm system, which can also be very helpful after the entire alarm
system has gone into alarm and then stopped, for no obvious reason. Once the
source alarm has been identified, appropriate action can be taken e.g. in the
case of a fire alarm event in memory, investigate the cause of nuisance /
false alarms by ensuring kitchen or bathroom doors are kept closed to prevent
very hot air or steam from cookers / showers reaching the heat sensor on the
Alarm, locate the Alarm further away from the source of steam or condensation,
replace the Alarm if it is thought to be defective or remove the unit in the
short term.
The memory feature has two operation modes:
– memory indication for 24 hour period after alarm.
– memory recall on demand
24-hour memory indicators: For 24 hours after alarming, the red LED will
flash twice every 48 seconds (approx)
Memory recall on demand: To review the memory status at any time, press
and hold the test button, the red LED will flash twice to convey the alarm
event in memory, if any.
Reset Memory: Hold down the test button for at least 20 seconds. Cover
the horn with a cloth to muffle the alarm during this time.
Clearing of the memory is indicated by a 1-second-long flash of the red LED.
Please note that the alarm memory will also be reset if the Alarm is removed
from its mounting plate.
Fault modes and Memory indicator
What you hear / see
| What it means| What to do
Green LED 1
(power)| Yellow LED 2
(fault)| Red LED (alarm)| Chirps
x1
every 48 sec|
__
|
__
|
__
| AC mains off| Reconnect AC mains power
__
|
x1
every 48 sec
|
__
| | AC mains off Low battery backup| Reconnect AC mains
power
|
x1
every 48 sec
| __|
| Low battery backup| Replace Alarm
|
x2
every 48 sec
|
__
|
x2
| Sensor fault| Replace Alarm
|
x3
every 48 sec
|
__
|
x3
|
End of Life
| Replace Alarm
|
x4
every 8 sec
|
__
|
x4
| Max Dust Compensation has been reached| see Maximum Dust
Compensation section
|
Flashes as per fault type
|
__
|
__
| Fault chirps have been silenced. Rate of the yellow LED flashing
indicates fault type| If required chirping can be silenced again by
pressing Silence button
|
__
|
when pressing Test button
|
__
| There has been an alarm in your absence| Check Alarm memory section
1 ON when AC mains power is switched on, flashes every 48s when on backup
battery, OFF when both AC mains and backup battery are off.
2 If you are unsure of the amount of flashes of the Yellow LED you can at
any time while a fault condition exists, press the Test button. The relevant
number of flashes will then be 8s apart.
Note: Fault chirps can be silenced by pressing the Test/Hush button.
The Alarm can communicate its status and history through various Led flashes
and chirps/beeps.
However, a more comprehensive report of all such events is available through
the AudioLINK download via the App.
Low Battery Backup Fault
If the battery backup supply is depleted, the sounder will give one short
chirp with one yellow LED fault indicator flash every 48 seconds. In this case
check that the green LED power indicator is on continuously. If it is off, or
flashing every 48 seconds, the Alarm is not receiving 230V AC mains power and
is being powered by the battery backup. The chirp every 48 seconds indicates
that the battery is depleted. The battery is not replaceable. Check fuses,
circuit breakers and wiring to determine the cause of the interruption to the
mains power. If in doubt, contact a qualified electrician. Once mains power is
reinstated, the chirps should cease within 2 hours as the battery charges up.
Fully charged, the battery will provide up to 4 months back-up without mains
power. If the chirping persists for over 2 hours with the green light on,
there may be some other problem with the Alarm. The Alarm must be returned for
repair or replacement – see GETTING YOUR ALARM SERVICED section.
Sensor Fault
The Alarm regularly checks the optical smoke sensor and/or thermistor heat
sensor for correct operation. If the Alarm has found a fault with the sensor,
it will give 2 short chirps with 2 yellow LED flashes every 48 seconds. In
this case, the Alarm must be returned for repair or replacement – see GETTING
YOUR ALARM SERVICED section
End of Life
Once the Alarm passes its 10th year of installation, it will give 3 short
chirps with 3 yellow LED flashes every 48 seconds to indicate it has reached
its end of useful life.
The entire Alarm must be replaced (Also check the replace by date on the label
on the side of the Alarm). Disconnect the mains first and replace the Alarm –
see ‚Removing the Alarm‘ section.
Maximum Dust Compensation (Ei3016 and Ei3024 only)
The Alarm monitors the dust contamination build-up in the optical smoke
chamber and then compensates for it, reducing the possibility of false alarms.
If however, the Alarm gives 4 short chirps with 4 yellow LED flashes when the
test button is pressed, it indicates that the Alarm has reached the maximum
dust compensation. When this occurs, the Alarm will continue to operate as
normal, but there is an increased risk of false alarms caused by dust
contamination.
If contamination has occurred quickly (e.g. due to dust from carpets being
replaced) and the Alarms are sounding, the dust compensation may take some
hours to operate. In this situation, remove the Alarm from the ceiling, leave
it disconnected for 5 minutes, then reinstall the unit (the air must be clean
i.e., dust and smoke free). The dust compensation will now operate quickly,
within 60 seconds.
Temporarily Silencing the Fault chirps
If the test / hush button is pressed on an Alarm that is giving fault chirps
and yellow LED fault indicator flashes, the Alarm will be silenced (Fault Hush
mode) for a period of 12 hours. However, the Alarm will sound / function as
normal within that period should it detect Fire (except if the fault detected
is a sensor fault) . The yellow LED fault indicator will continue to flash as
before to indicate the fault is still present. This is a useful feature should
the fault occur at night as it keeps the disturbance at a time when people in
the building are trying to sleep to a minimum. The fault chirps would return
12 hours later, which perhaps may be a more suitable time to address the fault
issue with the Alarm. In case of low backup battery voltage and end of life
fault chirps, this can be repeated as required. A sensor fault condition can
only be hushed once.
Important safeguards
Limitations of Fire Alarms
Multi-Sensor Fire / Smoke / Heat Alarms can significantly help to reduce the
risk of fire fatalities.
However independent authorities have stated that these systems may be
ineffective in some fire situations. There are a number of reasons for this:
- The Alarms will not work if the mains power supply is off or disconnected and the backup battery is depleted. Test regularly to ensure the power supply is functioning as required.
- The Alarms will not detect fire if sufficient heat/smoke does not reach the Alarms. Heat/smoke may be prevented from reaching the Alarm if the fire is too far away, for example, if the fire is on another floor, behind a closed door, in a chimney, in a wall cavity, or if the prevailing air drafts carry the heat/smoke away. Installing Heat Alarms and Smoke Alarms on both sides of closed doors and throughout the house or premises as recommended in this leaflet will very significantly improve the probability of early detection.
- The Alarms may not be heard. An Alarm may not wake a person who has taken drugs or alcohol.
- The Alarms may not detect every type of fire to give sufficient early warning.
- The Alarms don’t last indefinitely. The manufacturer recommends regular monthly testing and replacement after, at most, 10 years, as a precaution.
When a fire system is installed, basic safety precautions should always be followed, including those listed below:
- Please read all instructions.
- Use the Testing of the Alarm as a means to familiarise your family with the alarm sound and to practice fire drills regularly with all family members. Rehearse emergency escape plans so everyone at home knows what to do in case the Alarm sounds. Further information can be obtained from your local fire prevention officer.
- To maintain sensitivity to Fire, do not paint or cover the Alarm in any manner and; do not allow cobwebs, dust or grease to accumulate.
- If the Alarm has been damaged in any way or does not function properly, do not attempt a repair.
Return the Alarm – see Section 7 – ‘SERVICE AND GUARANTEE‘ section.
- This appliance is only intended for premises having a residential type environment.
- Fire Alarms are not a substitute for insurance. The supplier or manufacturer is not your insurer.
- Do not dispose of your Alarm in a fire.
Service and Guarantee
7.1 Getting your Alarm serviced
If, within the guarantee period, your Alarm fails to work after you have
carefully read all the instructions, checked the unit has been installed
correctly, and is receiving AC power, then contact us.
If you are advised to return your Alarm, please ensure that the Alarm is
placed in a padded box, not attached to the mounting plate (as the Alarm can
give beeps or alarm if the Test/Hush button is pressed during shipping), with
the proof of purchase and a note stating the nature of the fault.
7.2 Guarantee
Ei Electronics guarantees this Alarm for five years from the date of purchase
against any defects that are due to faulty materials or workmanship. If this
Alarm should become defective within the guarantee period, we shall at our
discretion repair or replace the faulty unit.
This guarantee only applies to normal conditions of use and service, and does
not include damage resulting from accident, neglect, misuse, unauthorised
dismantling, or contamination howsoever caused. This guarantee excludes
incidental and consequential damage.
This guarantee does not apply to any product that has been modified in any way
by a third party or has been fitted with a third party element.
Do not interfere with the Alarm or attempt to tamper with it. This will
invalidate the guarantee but more importantly may expose the user to shock or
fire hazards.
This guarantee is in addition to your statutory rights as a consumer.
The crossed out wheelie bin symbol that is on your product indicates that this
product should not be disposed of via the normal household waste stream.
Proper disposal will prevent possible harm to the environment or to human
health. When disposing of this product please separate it from other waste
streams to ensure that it can be recycled in an environmentally sound manner.
For more details on collection and proper disposal, please contact your local
government office or the retailer where you purchased this product.
0086
Ei Electronics, Shannon, Co. Clare, Ireland
18
DoP No.18-0001
EN14604:2005 + AC:2008
Smoke Alarm Devices: Ei3016, Ei3024
Fire Safety
Nominal activation conditions/ sensitivity, response delay (response time) and
performance under fire condition| Pass| Vibration resistance| Pass
---|---|---|---
Operational reliability| Pass| Humidity resistance| Pass
To lerance to voltage supply| Pass| Corrosion resistance| Pass
Response delay and temperature resistance| Pass| Electrical stability| Pass
**** Heat Alarm Devices:
Ei3014, Ei3024
The Declaration of Performance No. 17-0001 may be consulted at
www.eielectronics.com/compliance
KM522831
KM83678
EN14604:2005+AC 2008
BS5446-2:2003
Aico Ltd. Mile End Business Park, Maesbury Rd, Oswestry, Shropshire SY10
8NN, U.K.
Tel: 01691 664100
www.aico.co.uk
Ei Electronics. Shannon, Co Clare, Ireland.
Tel:+353 (0)61 471277
www.eielectronics.com
© Ei Electronics 2018
P/N B18660 Rev0
Documents / Resources
| Ei
Electronics EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat
Alarm
[pdf] Instruction Manual
EI3024 Multi Sensor Fire Alarm Optical Smoke Alarm Heat Alarm, EI3024, Multi
Sensor Fire Alarm Optical Smoke Alarm Heat Alarm, Alarm Optical Smoke Alarm
Heat Alarm, Smoke Alarm Heat Alarm, Alarm Heat Alarm, Heat Alarm
---|---
References
- Aico | The European Market Leader in Home Life Safety
- Company - EI Electronics
- Manual-Hub.com – Free PDF manuals!