Electronics Ei600 Series Battery Powered Smoke and Heat Alarms
Instruction Manual
Instructions
Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your Alarm. The leaflet should be regarded as part of the product. If you are just installing the unit, the leaflet must be given to the householder. The leaflet is to be given to any subsequent user.
9V Replaceable Battery
Model| Alarm Type| Hardwired Interconnect| RF Capability Supplied| Optional RF
Module Model No.
Ei605| Optical| No| No| None
Ei605C| Optical| Yes| Yes| Ei605MRF
Ei605CRF| Optical| Yes| Yes| Ei605MRF
Ei603C| Heat| Yes| Yes| Ei605MRF
Ei603CRF| Heat| Yes| Yes| Ei605MRF
10 Year Lithium Battery Built-in
Model| Alarm Type| Hardwired Interconnect| RF Capability Supplied| Optional RF
Module Model No.
Ei605TY| Optical| No| RF Capability Supplied| Optional RF Module Model No.
Ei605TYC| Optical| Yes| No| None
Ei605TYW| Optical| No| Yes| Ei605MTYRF
Ei603TYC| Optical| Yes| Yes| Ei605MTYRF
Ei605TYCRF| Heat| Yes| Yes| Ei605MTYRF Ei600MRF
Ei605TYWRF| Optical| Yes| Yes| Ei605MTYRF
Ei603TYCRF| Optical| No| Yes| Ei605MTYRF
Ei603TYCRF| Heat| Yes| Yes| Ei605MTYRF Ei600MRF
Ei603| Heat| Yes| Yes| Ei605MRF
Ei603RF| Heat| Yes| Yes| Ei605MRF
Note: Certain Alarms may be supplied (on request) with the appropriate RF module fitted
Quick Start Guide
LOCATE CORRECT SITING POINT FIX BASEPLATE TO
CEILING
ALARM SHOULD BE CEILING MOUNTED AT LEAST 300MM FROM WALLS & OBSTRUCTIONS,
IDEALLY CENTRALLY IN ROOM/AREA
CONNECT BATTERY SNAPS IR YRRERYNIY
CONNECT THE BATTERY TO THE BATTERY SNAPS TO POWER THE UNIT
PLACE ALARM & TWIST ON TO BASE
PLACE ALARM & TWIST ON TO BASE
ON 10 YEAR LITHIUM BATTERY ALARM MODELS TWISTING THE UNIT ON TO THE BASE
AUTOMATICALLY CONNECTS THE BATTERY
TEST ALARM
PRESS THE TEST BUTTON
TEST ALARM AT LEAST WEEKLY
Location & Positioning
Introduction
Congratulations on purchasing an Ei600 Series Alarm. You can easily install
these alarms throughout the property on escape routes, on each storey, in
corridors & in closed rooms to give warning of fire.
The Heat Alarms can be installed in kitchens and other areas where Smoke
Alarms are unsuitable.
Models Ei605C/Ei603C/Ei605TYC & Ei603TYC can be interconnected with hard
wiring to give the loudest alarm sound level throughout the house.
All models (except Ei605 & Ei0STY) can be interconnected using the RadioLINK
plug-in modules (These modules must be purchased separately when they are not
supplied with the Alarm (see Table 1).
Note: Certain alarms may be supplied (on request) with the appropriate RF
module fitted.
SMOKE ALARMS – Ei605 Series
Sufficient smoke must enter your Smoke Alarm before it will respond. Your
Smoke Alarm needs to be within 7.5 metres of the fire to respond quickly.
Smoke Alarms also need to be in positions where they can be heard throughout
the property, so they can wake you and your family in time for everyone to
escape. A single Smoke Alarm will give some protection if it is properly
installed, but most homes will require two or more (preferably interconnected)
to ensure that a reliable early warning is given. For recommended protection
you should put individual Smoke Alarms in all rooms (apart from kitchen and
bathroom) where fire is most likely to break out.
Your first Smoke Alarm should be located between the sleeping area and the most likely sources of fire (living room, kitchen for example), but it should not be more than 7.5 metres from the door to any room where a fire may start and block your escape from the house.
HEAT ALARMS – Ei603 Series
The Heat Alarm gives a fire warning when the temperature at the Alarm reaches
58°C. It is ideal for kitchens, garages, boiler houses and other areas where
there are normally high levels of fumes, smoke or dust i.e. places where Smoke
Alarms cannot be installed without the risk of excessive nuisance alarms. A
Heat Alarm should only be used in rooms adjoining escape routes, in
conjunction with Smoke Alarms on the escape routes.
All Heat Alarms must be interconnected to the Smoke Alarms to ensure that the early warning will be heard, particularly by somebody sleeping. A properly designed early warning fire system ensures the alarm is given before the escape routes become blocked with smoke. Therefore there must be Smoke Alarms along the escape routes as Heat Alarms would not give sufficient warning. However, a fire in a closed room (e.g. kitchen) adjoining the escape route, can eventually cause the corridor to become smoke-logged due to smoke leaking out from around the door before adequate warming can be given by detectors in the corridor. (Smoke leaking out from a room is often cool and slow moving so it can take a long time to rise to the ceiling, and travel to a detector which could be some distance away). A Heat Alarm in the closed room will give early warning of fire in that room and help overcome this problem.
Multi-Storey Dwellings
If your home has more than one floor, at least one Alarm should be fitted on
each level (see Figure 1). Preferably the units should be interconnected (if
feature is present on unit) so as to give sufficient warning throughout the
property. RadioLINK plug-in modules are ideal in this situation as the units
will then interconnect using Radio Frequency (RF) signals – so no wiring is
required Figure 1 illustrates where Heat Alarms and Smoke Alarms should be
located in a typical two storey house. Note the spacings in “Protection
Levels” which ensure the early detection of fire and that the waming wil be
heard.
Locate Heat Alarms in rooms adjoining escape routes – itches, garages, boiler
houses etc. where Smoke Alarms are unsuitable. Install within 5.3m of
potential sources of fire.
Single Storey Dwelling
If the premises is one storey you should put your first Smoke Alarm in a
corridor or hallway between the sleeping and living areas. Place it as near to
the living area as possible, but make sure that it can be heard loudly enough
in the bedroom to wake someone. See Figure 2 for placement example.
In houses with more than one sleeping area, Smoke Alarms should be placed
between each sleeping area and the living area and it is recommended that Heat
Alarms should be placed in the kitchen & garage.
Recommended Protection
Fire authorities recommend you put individual Smoke Alarms in or near all
rooms where fire is most likely to break out (apart from the locations to
avoid e.g bathrooms – see Section 3). The living room is the most likely place
for a fire to
For minimum protection
- Smoke Alarm on each storey &
- in each sleeping area =
- every 7.5 metres of hallways and rooms
- within 3 metres of all bedroom doors
- all units interconnected (where feature is present)
**For recommended protection
**
- in addition 1o the above): &
- Smoke Alarms in every room (except K kitchens and bathrooms)
- Heat Alarms located in kitchens, = garages etc. within 5.3m of potential fire sources
start at night, followed by the kitchen (where a Heat Alarm is recommended) and then the dining room. Consideration should be given to installing Smoke Alarms in any bedrooms where fires might occur, for instance, where there is an electrical appliance such as an electric blanket or heater, or where the occupant is a smoker. In addition, consideration should be also given to installing Smoke Alarms in any rooms where the occupant is unable to respond very well to a fire starting in that room, such as an elderly or sick person or a very young child.
Checking Alarms Can Be Heard
With the Alarms sounding in their intended locations check that the alarm can
be heard in each bedroom with the door closed, above the sound of any TV/audio
systems. The TV/audio systems should be set to a reasonably loud conversation
level. If you cannot hear the alarm over the sound of the TV/audio system, the
chances are it would not wake you. Interconnecting the Alarms using either a
hard-wired interconnection (where the feature is present) or RadioLINK plug-in
modules will help to ensure that the alarm will be heard throughout the
property.
Positioning
Ceiling Mounting
Hot smoke rises and spreads out, so a central ceiling position is the
recommended location. The air is “dead” and does not move in corners,
therefore Smoke & Heat Alarms must be mounted away from comers. Keep at least
0.3m from walls and comers (see Figure 3). Additionally, mount the unit at
least 0.3m from any light fitting or decorative object which might prevent
smoke or heat entering the Smoke/ Heat Alarm.
We do not recommend wall mounting these Smoke/Heat Alarms.
On a Sloping Ceiling
With a sloping or peaked ceiling install a Smoke Alarm within 600mm of the
peak or a Heat Alarm within 150mm of the peak (measured vertically). If this
height is less than 600mm for Smoke Alarms or 150mm for Heat Alarms the
ceiling is regarded as being flat (see Figure 4).
Locations to avoid DON’T place Smoke Alarms in any of the following areas:
- Bathrooms, kitchens, shower rooms, garages or other rooms where the smoke alarm may be triggered by steam, condensation, normal smoke or fumes. Keep at least 6 metres away from sources of normal smoke/fumes.
- Locate away from very dusty or dirty areas as dust build-up in the chamber can impair performance. It can also block the insect screen mesh and prevent smoke from entering the smoke detector chamber.
- Do not locate in insect infested areas. Small insects getting into the smoke detector chamber can cause intermittent alarms.
DON’T place Heat Alarms in any of the following areas:
- Bathrooms, shower rooms or other rooms where the unit may be triggered by steam or condensation.
DON’T place Smoke or Heat Alarms in any of the following areas:
-
Places where the normal temperature can exceed 40°C or be below -10°C (e.g. attics, furnace rooms, directly above ovens or kettles etc.) as the heat/steam could cause nuisance alarms.
-
Near a decorative object, door, light fitting, window moulding etc., that may prevent smoke or heat from entering the Alarm
-
Surfaces that are normally warmer or colder than the rest of the room (e.g. attic hatches). Temperature differences might stop smoke or heat from reaching the unit.
-
Next to or directly above heaters or air conditioning vents, windows, wall vents etc.
that can change the direction of airflow. -
In very high or awkward areas (e.g. over stairwells) where it may be difficult to reach the alarm (for testing, hushing or battery replacement).
-
Locate the unit at least 1m from dimmer controlled lights and wiring as some dimmers can cause interference.
-
Locate unit at least 1.5m and route wiring at least 1m away from fluorescent light fittings as electrical “noise” and/or flickering may affect the unit.
Installation
Installation Procedure
-
Select a location complying with the advice in Section 2.
-
Remove the mounting plate from the Smoke/Heat Alarm by twisting it in an anti-clockwise direction (see Figure 5).
-
Place the mounting plate on the ceiling exactly where you want to mount the Alarm. With a pencil, mark the location of the two screw holes.
-
If interconnecting Alarms using hard-wired connections, run suitable twin core cabling to the marked locations of each Alarm. Make the connections to the Alarm (see Section 4).
-
Taking care to avoid any electrical wiring in the ceiling, drill holes using a 5.0mm drill bit through the centre of the marked locations. Push the plastic screw anchors provided into the drilled holes. Screw the mounting plate to the ceiling. If using RadioLINK Smoke/Heat Alarms then they should be mounted with antennas in the same orientation (i.e. essentially parallel). This means picking a part of the building, say the front wall of the building and then installing all mounting plates in the same orientation with respect to this (see figure 6).
ROTATE UNIT ANIT-GLOCKWISE
UNIT WILL NOT TWIST OFF IT MAY BE TAMPERPROOFED SEE FIGURE 8c -
Connect the battery to the battery snaps as shown in the Quick Start Guide (for 9V Replaceable Battery models only).
mounting plates n the same. direction -
Carefully line up the unit on the base, gentle press home & twist on. (This connects the batteries in the 10 Year Lithium Battery models). Install all the other Alarms similarly.
-
Press the Test button on each alarm to ensure that the Alarm works (see Figure 7a for Smoke Alarm & 7b for Heat Alarm).
-
For hard-wired interconnected Alarms, hold down the Test button on each Alarm in turn and check that all other interconnected Alarms. sound.
-
If using RadioLINK interconnection, see booklet ‘RF Modules for Battery Powered Smoke & Heat Alarms.
Install all the other Alarms similarly.
Smoke Alarm
Heat Alarm
Tamperproofing the Alarms
Tamperproofing the Alarms The Alarm can be made tamperproof to prevent unauthorised removal of the Alarm.
Break off the small pillar on the base as shown in figure 8a. To remove the
Alarm from the ceiling it is now necessary to use a small screwdriver, to
release the catch (push catch towards the ceiling) and then twist off the
alarm (see figure 8b). If necessary it is possible to further secure the Alarm
by using a No.2 or No.4 (2 to 3mm diameter – not supplied) self tapping screw
6 to 8mm long (see figure 8d), to firmly lock the Alarm and its mounting plate
together (see figure 8c). WARNING! To prevent injury, this apparatus must be
securely attached to the ceiling in accordance with the installation
instructions. Attach the Alarm to the mounting plate.
How to Tamperproof
PUSH UP CATCH & TWIST ALARM ANTI-CLOCKWISE TO REMOVE
How to Remove
Line up the screw (not supplied) on the “U” shaped recessed area shown in figure 8c and screw firmly home. To remove the Alarm from the ceiling, remove the screw first, and then twist off anti-clockwise.
Interconnection – Hard Wired
A combined maximum of 12 Smoke Alarms and/or Heat Alarms may be wired together
such that when one unit senses fire all other units sound a warning – (see
Table 1 for the alarms with hardwired interconnect option). This helps ensure
the alarm will be heard throughout the property. Do not connect to any other
device as it may damage the unit or affect performance.
OPENING IN MOUNTING PLATE
A maximum of 250 metres of two core, 0.5mm² to 0.75mm², stranded signal cable
can be used, (maximum resistance between detectors 50 ohm). The Alarms are
interconnected by wiring all the terminals marked 1 together, and all the
terminals marked 2 together (see in Figure 9a). Note: Draughts from wiring
openings, conduit, or mounting boxes/holes, may blow smoke away from the
sensing chamber, making it insensitive. It is essential that all such ceiling
openings be closed with silicone sealant or similar.
- Run the two core cable to the Alarm locations.
- Bring the cable through the opening in the mounting plate (before screwing it to the ceiling) see figure 9b.
- If you are bringing the wiring along the surface, break out the two notches (see figure 10a).
- Using a small screwdriver, lift off the terminal block by raising it vertically (see figure 10b).
- Screw the two cable cores into the terminal block (see figure 10b). Then carefully press the terminal block back on to the two pins in the base.
- Twist the Alarm clockwise on to the mounting plate.
USE SCREWDRIVER TO GENTLY LIFT OUT THE TERMINAL BLOCK
SCREW CABLES INTO TERMINAL BLOCK
Install and connect all the other Alarms similarly.
Now test the first Alarm by pressing and holding the Test button (this may take up to 5 seconds). The red indicator light will flash about once a second on the first Alarm and all other Alarms should sound. Check all the other Alarms similarly. Note: These Alarms should be interconnected only within the confines of a single family living unit. If they are connected between different residences there may be excessive nuisance alarms. Everybody may not be aware that they are being tested or that it is a nuisance alarm caused by cooking etc.
Testing, Maintenance & Power Supply Monitoring
Your Alarm is a life saving device and should be checked periodically. Regularly check that the red light on the Alarm flashes approx once a minute to show the units are powered. Replace the Alarm if the flashing stops. 5.1 Manually Testing your Alarms
- Press and hold the Test Button until the Alarm sounds and the red light flashes (see Figure 7a & 7b). The Alarm will stop sounding shortly after the button is released.
- If the Alarms are interconnected using hard-wired connections, check that all interconnected Alarms sound.
- If they are interconnected using RadioLINK modules, hold down the Test button until the blue light on the cover of the Alarm illuminates. Check that all other Alarms sound.
- Release the Test button. The Alarm and all connected Alarms should stop sounding.
- Repeat this procedure for all other Alarms in the system.
WARNING: Do not test with flame. This can set fire to the Alarm and damage the house. We do not recommend testing with smoke or heat as the results can be misleading unless special apparatus is used. When you press the Test button it simulates the effect of smoke in a Smoke Alarm and heat in a Heat Alarm which they could experience in a real fire. So, there is no need to test either Alarms with smoke or heat.
Test/Hush Button to Control Nuisance Alarms
The Smoke Alarms have a combined Test/Hush button to help you control
nuisance/false alarms. If, when the Alarm sounds, there is no sign of smoke or
noise to indicate that there is a fire, it should be assumed that it is due to
an actual fire and the dwelling should be evacuated immediately. Check the
house carefully in case there is a small fire smouldering somewhere. Check
whether there is some source of smoke or fumes, for example cooking fumes
being drawn past the Alarm by an extractor. If there are frequent
nuisance/false alarms it may be necessary to re-locate the Smoke Alarm away
from the source of the fumes.
If you installed Alarms with RadioLINK modules and did not House Code them, you may be receiving alarm signals from a neighbouring system. This can be easy rectified by “House Coding” your Alarms see booklet ‘RF Modules for Battery Powered Smoke & Heat Alarms.
- To cancel a false alarm from a Smoke Alarm (which has its red light flashing rapidly), press the Test/Hush button (the Smoke Alarm will automatically switch to a reduced sensitivity condition). The Smoke Alarms will be silenced for a period of approximately 10 minutes. The red light on the cover of the Smoke Alarm will flash every 10 seconds (instead of 40 seconds) to indicate that the unit has been silenced.
- The Smoke Alarm will reset to normal sensitivity at the end of the silenced period (10 minutes). If additional silenced time is required, simply push the Test/ Hush button again.
- If kitchen usage/layout is such that there are an unacceptable level of nuisance alarms, re-locate the Smoke Alarm further away where it will be less affected by cooking fumes etc. We recommend the use of a Heat Alarm in the Kitchen area to avoid such nuisance alarms.
Power Supply Monitoring
What to do when an Alarm is beeping:
- A Smoke Alarm is beeping about every 40 seconds with the red light flashing at the same time:
- If it is a 9V Replaceable Battery model then replace the battery.
- If it is a 10 Year Lithium Battery model this indicates that the Lithium Battery is partially depleted and the Smoke Alarm needs to be replaced. (check the “replace by” date marked on the side of the Alarm).
- A Heat Alarm is beeping about every 40 seconds. – If it is a 9V Replaceable Battery model then replace the battery. – If it is a 10 Year Lithium Battery model this indicates that the Lithium Battery is partially depleted and the Smoke Alarm needs to be replaced. (check the “replace by” date marked on the side of the Alarm).
Battery Replacement – (9V Replaceable Battery models only) A fresh
Alkaline Battery should last for over a year. When the battery power is low
and replacement is necessary, the Smoke Alarm will “beep” and the red light
will flash at the same time about every 40 seconds for at least 30 days. The
Heat Alarm will also beep once per minute, but the red light will not flash at
the same time when the battery is low. The battery must then be replaced.
Also, replace the battery if the Alarm does not sound when the Test Button is
pressed. For maximum reliability, replace the battery at least once a year.
When you replace the battery you must press the Test button to check that the
Alarm is functioning correctly. Only replace the battery with the following
alkaline battery: Duracell MN1604.
All Models: Prolonged exposure to low or high temperatures or high
humidity may reduce battery life. Prolonged periods of alarm will also reduce
battery life.
Cleaning your Alarm Clean your Alarm regularly. Use a soft bristle brush
or the brush attachment of your vacuum cleaner to remove dust and cobwebs from
the side slots where the smoke/ heat enters. To clean the cover, wipe with a
damp cloth and dry thoroughly.
WARNING: Do not paint your Alarm.
Other than the maintenance and cleaning described in this leaflet, no other
customer servicing of this product is required. Repairs, when needed, must be
performed by the manufacturer.
Smoke Alarm Automatic Self-Test
The smoke chamber in the Smoke Alarms automatically tests itself every 40
seconds. If the chamber is degraded it will beep without the red light
flashing at the same time. If this happens clean the unit. If the beeping
persists and the beep does not coincide with a red light flash, return the
unit for service (see Section 9 – Getting your Smoke Alarm Serviced).
Dust & Insect Contamination
All Smoke Alarms and particularly the optical (photoelectric) type are prone
to
dust and insect ingress which can cause false alarms. (Heat Alarms are not as
susceptible to dust and contamination as Smoke Alarms, but it is prudent to
clean them periodically).
The latest design, materials and manufacturing techniques have been used in
the construction of Ei Electronics Alarms to minimise the effects of
contamination. However it is impossible to completely eliminate the effect of
dust and insect contamination, and therefore, to prolong the life of the Alarm
you must ensure that it is kept clean so that excess dust does not build up.
Any insects or cobwebs in the vicinity of the Smoke Alarm should be promptly
removed.
In certain circumstances even with regular cleaning, contamination can build
up in the smoke sensing chamber causing the alarm to sound. Contamination is
beyond our control, it is totally unpredictable and is considered normal wear
and tear. For this reason, contamination is not covered by the guarantee and a
charge is made for all such servicing work.
End of life
The entire Alarm must be replaced if:-
(i) All Models:
- The unities installed for over 10 years (check the “replace by” date marked on the side of the unit).
(ii) All 10 Year Lithium Battery models only
- The Smoke Alarm is giving a short beep about every 40 seconds and the red light flashes at the same time for longer than 1 hour. The Heat Alarm is giving a short beep about every 40 seconds for longer than 1 hour.
- The Alarm fails to sound the horn loudly when the test button is pressed.
Before the Alarm is safely discarded, remove from the mounting plate. With the
9V
Replaceable Battery models disconnect the battery.
Do not put the Alarm into a fire.
The Alarm should be disposed in a safe and environmentally sound manner at
your local recycle centre. Contact your local authority for further advise.
Fire Safety Advice
When using household protective devices, basic safety precautions should always be followed, including those listed below .
- Please read all instructions.
- Rehearse emergency escape plans so everyone at home knows what to do in case the alarm sounds.
- Use the Alarm Test Button to familiarise your family with the Alarm sound and to practice fire drills regularly with all family members. Draw up a floor plan that will show each member at least 2 escape routes from each room in the house. Children tend to hide when they don’t know what to do. Teach children how to escape, open windows, and use roll up fire ladders and stools without adult help. Make sure they know what to do if the alarm goes off.
- Constant exposure to high or freezing temperatures, high humidity or a high level of nuisance alarms may reduce the life of the battery.
- Nuisance alarms can be quickly silenced by fanning vigorously with a newspaper or similar to remove the smoke or press the test / hush button.
- Do not attempt to remove, recharge or burn the battery, as it may explode. If it is necessary to remove the battery for separate disposal, handle carefully to avoid possible eye damage or skin irritation if battery has leaked or corroded.
- To maintain sensitivity to smoke/heat, do not paint or cover the Alarm in any manner; do not permit any accumulation of cobwebs, dust or grease.
- If Alarm has been damaged in any way or does not function properly, do not attempt a repair. Return the Alarm (see Section 9).
- This appliance is intended ONLY for premises having a residential type environment.
WARNING! This is not a portable product. To prevent injury, it must be
securely mounted following the instructions in this instruction manual.
Smoke/Heat Alarms are not a substitute for insurance. The supplier or
manufacturer is not your insurer.
Fire Safety Hints
Store petrol and other flammable materials in proper containers.
Discard oily or flammable rags.
Always use a metal fireplace screen and have chimneys cleaned regularly.
Replace worn or damaged sockets, switches, home wiring and cracked or frayed
electrical cords and plugs.
Do not overload electrical circuits.
Keep matches away from children.
Never smoke in bed. In rooms where you do smoke, always check under cushions
for smouldering cigarettes and ashes.Service central heating systems
regularly.
Be sure all electrical appliances and tools have a recognised approval label.
This device cannot protect all persons at all times. It may not protect against the three most common causes of fatal fires:
- Smoking in bed.
- Leaving children at home alone.
- Cleaning with flammable liquids, such as petrol.
Further information can be obtained from the Fire Brigade.
Planning Your Escape Route For When The Alarms Sound
-
Check room doors for heat or smoke. Do not open a hot door. Use an alternate escape route. Close doors behind you as you leave.
-
If smoke is heavy, crawl out, staying close to floor. Take short breaths, if possible, through a wet cloth or hold your breath. More people die from smoke inhalation than from flames.
-
Get out as fast as you can. Do not stop for packing. Have a prearranged meeting place outside for all family members. Check everybody is there.
-
Call the Fire Brigade from a neighbour’s house or mobile phone. Remember to give your name and address.
-
NEVER re-enter a burning house.
Alarm Limitations
Limitations of Smoke/Heat Alarms
Smoke/Heat Alarms have significantly helped to reduce the number of fire
fatalities in countries where they are widely installed. However independent
authorities have stated that they may be ineffective in some circumstances.
There are a number of reasons for this:
- Smoke/Heat Alarms will not work if the batteries are depleted or if they are not connected. Test regularly and replace the entire Alarm when it fails to operate.
- Smoke/Heat Alarms will not detect fire if sufficient smoke or heat does not reach the Alarm. Smoke/Heat may be prevented from reaching the Alarm if the fire is too far away, for example, f the fire is on another floor, behind a closed door, in a chimney, in awall cavity, o if the prevailing air draughts carry the smoke o heat away. Installing
Smoke/Heat Alarms on both sides of closed doors and installing more than one Alarm as recommended in this leaflet very significantly improve the probability of early detection.
- The Smoke/Heat Alarm may not be heard.
- RadioLINK may not work due to interference or due to the signal being blocked by furniture, renovations etc.
- A Smoke/Heat Alarm may not wake a person who has taken drugs or alcohol
- The Alarms may not detect every type of fire to give sufficient early warning. They are particularly ineffective with: fires caused by smoking in bed, escaping gas, violent explosions, poor storage of flammable rags and/or liquids, (for example petrol, paint, spirts etc), overloaded electrical circuits, arson, children playing with matches.
- Smoke/Heat Alarms don’t last indefinitely. We recommend replacement after 10 years as a precaution.
RadioLINK Accessories
Ei605MRF RadioLINK Interconnect module for the 9V Replaceable Battery
models. It plugs into the rear of the Alarm. This ensures that when one
Alarm senses fire, all units sound to give an alarm through-out the house –
(see Table 1).
Ei605MTYRF RadioLINK Interconnect module for the 10 Year Lithium
Battery models. It plugs into the rear of the Alarm. This ensures that
when one Alarm senses fire, all units sound to give an alarm through-out the
house – (see Table 1).
EI600MRF RadioLINK* Interconnect module for the Ei603TYC only. It plugs into the rear of the Alarm. This ensures that when one Alarm senses fire, all units sound to give an alarm through-out the house – (see Table 1).
Getting Your Alarm Serviced
If your Alarm fails to work after you have read the sections on “Installation”, “Testing and Maintenance” and “Troubleshooting”, then contact Customer Assistance at the nearest address given at the end of this leaflet. If it needs to be returned for repair or replacement put it in a padded box with the battery disconnected (9V Replaceable Battery models only). The 10 Year Lithium Battery models must be removed from the mounting plate. Send it to “Customer Assistance” at the nearest address given on the Alarm o in this leaflet. State the nature of the fault, where the Alarm was purchased and the date of purchase.
Five Year Guarantee
Ei Electronics guarantees this Alarm (excluding the battery in the 9V Replaceable Battery models) for five years from date of purchase against any defects that are due to faulty materials or workmanship. This guarantee only applies to normal conditions of use and service, and does not include damage resulting from accident, neglect, misuse, unauthorised dismantling, or contamination howsoever caused. This guarantee excludes incidental and consequential damage. If this Alarm should become defective within the guarantee period, it must be returned to Ei Electronics, with proof of purchase, carefully packaged, with the problem clearly stated (see Section 9). We shall at our discretion repair or replace the faulty unit.
Do not interfere with the Alarm or attempt to tamper with it. This wil invalidate the guarantee, but more importantly may expose the user to shock or fire hazards.
This guarantee is in addition to your statutory rights as a consumer.
Troubleshooting
Alarms sound for no apparent reason
- House Code your Alarms – see booklet ‘RF Modules for Battery Powered Smoke & Heat Alarms’. If the Alarms are in the default factory settings, neighbouring units may cause them to alarm.
- Check for fumes, steam, etc. from the kitchen or bathroom. Paint and other fumes can cause nuisance alarms.
- Check for any sign of contamination such as cobwebs or dust. Clean the alarm as described in Section 5 if necessary.
- Press the TestHush button on the Smoke Alarm causing the Alarm (this can be identified as the Alarm with the red light flashing rapidly) this will silence the Smoke Alarm for 10 minutes (and also silence all other interconnected Alarms in the system).
- Smoke & Heat Alarms, with RadioLINK modules, sound for 2 seconds every 4 hours – this indicates that there is a depleted battery somewhere in the system – check all Alarms as outlined in section 5 “Power Supply Monitoring”.
The Alarm fails to sound when the Test button is pressed
- Check the age of the unit – see the “replace by” label on side of unit.
- Check the battery snaps are firmly connected on the 9V Replaceable Battery models.
On the 10 Year Lithium Battery models ensure the unit is twisted fully home on the mounting plate, as this connects the battery.
The crossed out wheelie bin symbol that s on your product indicates the this product and s batteries should ot be disposed of via the normal household waste stream. Proper disposal will prevent possible harm [0 the environment or to human health. When disposing of this product please separate i from other wasio streams (o ensure tha t can be recycled n an environmentally sound manner. For more deals on collection and proper I disposal, please contact your local government office or the etalor wharf you purchased this product.
0359
Ei Electronics, Shannon, Co. Clare, Ireland19DoP
No.19-0003
EN14604:2005 + AC:2008Smoke Alarm Devices: Ei605, Ei605C, Ei605TYC, Ei605TYW,
Ei605CRF, Ei605TYCRF, Ei605TYWRF
Fire Safety
Nominal activation conditions/ sensitivity, response delay (response time) and
performance under fire condition| Pass| Vibration resistance| Pass
Operational reliability| Pass| Humidity resistance| Pass
Tolerance to voltage supply| Pass| Corrosion resistance| Pass
Tolerance to voltage supply| Pass| Corrosion resistance| Pass
Response delay and temperature resistance| Pass| Electrical stability| Pass
Heat Alarm Devices:
Ei603C, Ei603TYC, Ei603, Ei603RF
The Declaration of Performance No. 19-0003 may be consulted at ww.eielectronics.com/compliance
Contact Us
Aico Ltd. Mile End Business Park, Maesbury Rd, Oswestry, Shropshire SY10
8NR, U.K.
Telephone: 01691 664100 www.aico.co.uk
Ei Electronics. Shannon, Co Clare, Ireland.
Tel: 061 471277 www.eielectronics.com