Schneider Electric GEX3940200-01 Multifix Apparatus Boxes Instruction Manual
- January 23, 2024
- Schneider Electric
Table of Contents
- GEX3940200-01 Multifix Apparatus Boxes
- Product Information
- Product Usage Instructions
- Box Placement for EI60 and EI30 Fire Wall
- Box Installation Height
- Box Placement and Wall Construction for EI60 Fire Wall
- Box Placement and Wall Construction for EI30 Fire Wall
- Q: What type of plaster board should be used with the Multifix
- Q: What is the minimum beam size required for
- Q: How should the boxes be secured to the vertical beam
- Q: What is the recommended distance between the box centers
- Q: Should the fire-classified walls be insulated?
GEX3940200-01 Multifix Apparatus Boxes
Product Information
The Multifix apparatus boxes are designed for use in EI30 and
EI60 fire walls. They are suitable for installations in both wood
and steel beam constructions. The boxes are made to accommodate
standard plaster boards with thicknesses of 13 mm. The minimum beam
size required for installation is 70 mm.
Product Usage Instructions
Box Placement for EI60 and EI30 Fire Wall
When installing the Multifix apparatus boxes in a fire wall,
follow the guidelines below:
-
For EI60 fire walls:
-
Use 2×13 mm standard plaster board.
-
Place the boxes at equal distances between wood/steel
beams. -
Ensure a minimum distance of 70 mm between the boxes and the
beams.
-
-
For EI30 fire walls:
-
Use 1×13 mm standard plaster board.
-
Place the boxes at equal distances between wood/steel
beams. -
Ensure a minimum distance of 70 mm between the boxes and the
beams.
-
Box Installation Height
The Multifix apparatus boxes can be installed at various heights
within the fire wall. The following height ranges are
acceptable:
- For EI60 fire walls:
- Minimum height: 150 mm
- Maximum height: 1100 mm
- For EI30 fire walls:
- Minimum height: 150 mm
- Maximum height: 1100 mm
Box Placement and Wall Construction for EI60 Fire Wall
For EI60 fire walls, the following example demonstrates the
placement of the Multifix apparatus boxes:
-
Use 2×13 mm standard plaster board.
-
Place the boxes at equal distances between wood/steel
beams. -
Ensure a minimum distance of 70 mm between the boxes and the
beams.
Box Placement and Wall Construction for EI30 Fire Wall
For EI30 fire walls, the following example demonstrates the
placement of the Multifix apparatus boxes:
-
Use 1×13 mm standard plaster board.
-
Place the boxes at equal distances between wood/steel
beams. -
Ensure a minimum distance of 70 mm between the boxes and the
beams.
Specifications
- Manufacturer: Schneider-Electric Industries SAS
- Model: Multifix apparatus boxes
- Approval: RISEFR 050-0211
FAQ
Q: What type of plaster board should be used with the Multifix
apparatus boxes?
A: The Multifix apparatus boxes are compatible with standard
plaster boards with a thickness of 13 mm.
Q: What is the minimum beam size required for
installation?
A: The minimum beam size required for installation is 70 mm.
Q: How should the boxes be secured to the vertical beam
structure?
A: The boxes can be secured to the vertical beam structure using
beam fixings, screws, or nails. Alternatively, they can be
installed in additional horizontal beams using similar means.
Q: What is the recommended distance between the box centers
when installing on opposite sides of the wall?
A: When installing on opposite sides of the wall, a minimum
distance of 200 mm between the box centers is recommended.
Q: Should the fire-classified walls be insulated?
A: Usually, fire-classified walls are fully insulated. If the
walls are not insulated, a chamber of 300 mm should be created in
each direction and filled with mineral wool. Always use stone for
insulation.
Multifix apparatus boxes
Example of Box placement and Wall construction For EI60 fire wall
2×13 mm standard plaster board
Wood / Steel Beam
Wood / Steel Beam
Wood / Steel Beam
min 70 mm
Stone wool density min 28kg/m³
X
Max. Ø 74 mm
X
X
X = Equal Distance
Example of Box placement and Wall construction For EI30 fire wall
1×13 mm standard plaster board
Wood / Steel Beam
Wood / Steel Beam
Wood / Steel Beam
Stone wool density min 28kg/m³
min 70 mm
X
Max. Ø 74 mm
X
X
X = Equal Distance
GEX3940200-01 June-2023
Schneider-Electric Industries SAS, 35 Rue Joseph Monier, 92500 Rueil Malmaison, France www.se.com/contact
1/2
Multifix apparatus boxes
Box placement for EI60 and EI30 fire wall
Min. 300mm
Applicable installations and combinations related to fire class
150 mm
Min. 200mm
Box installation
height
El 60
El 30
Min. 150 mm
Max. 1100 mm
Max. 1100 mm
Max. 1100 mm
Max. 200 mm
1100 mm 200 mm
Box facing opposite side
en Instruction for Multifix standard apparatus boxes in sv Anvisning för Multifix väggdosor i brandklassade
fire-classified walls EI30 and EI60
väggar EI30 och EI60
Specific requirements on installation in fire-classified walls to maintain
Speciella krav för installation i brandklassade väggar för att bibehålla
the level of protection against spread of fire. Information is related to
skydd mot spridning av brand. Anvisningen gäller enkeldosor, 1½
single boxes, 1½ module and double boxes.
modul och dubbeldosor.
EI30 classified walls with minimum of 1×12,5 mm standard type of
EI30 klassade väggar med minst 1×12,5 mm standard gipsskiva och
plaster board and and EI60 classified walls with minimum of
EI60 klassade väggar med minst 2×12,5 mm standard gipsskiva.
2×12,5 mm standard type of plaster board. Both types with minimum
Båda med minst 70 mm regel i trä eller stål.
beam size of 70 mm. Beams in steel or wood are accepted.
Typgodkännande RISEFR 050-0211.
Approval RISEFR 050-0211.
Dosorna infästes på horisontella eller vertikala reglar med
Boxes have to be secured to the vertical beam structure with beam
regelfästen, skruvar eller spik.
fixings, screws or nails, alternatively in additional horizontal beams
Tabellen ovan visar vilka kombinationer och montagehöjder ovan golv
with similar means.
som är tillåtna.
In the table you find out possible combinations and acceptable
Vid montering av dosor på bägge sidor av väggen måste avstånd
heights for the installation from the floor level.
mellan respektive centrum vara minst 200 mm.
Regarding installation in opposite sides of the wall, allow minimum
Vanligtvis är brandklassade väggar fullisolerade. Om väggarna inte är
200 mm distance between the box centers.
isolerade skapas ett isolerat fack runt dem, 300 mm åt vardera håll
Usually fire-classified walls are fully insulated. If the walls are not
med stenull. Använd alltid stenull med densitet på minst 28 kg/m³.
insulated you have to create a chamber of 300 mm each direction
and fill with mineral wool. Concerning insulation, always use stone
wool with minimum density of 28 kg/m³.
no Veiledning for Multifix veggbokser i EI30 og EI60 brannklassifiserte vegger
For å hindre spredning av brann, stilles det krav til installasjon i
brannklassifiserte vegger. Informasjonen gjelder enkel boks, 1½ modul og
dobbel boks. EI30 klassifiserte vegger med minimum 1×12,5 standard gipsplate
og EI60 klassifiserte vegger med minimum 2×12,5 standard gipsplate. Begge med
minimum 70 mm tre- eller stålstender. Godkjenning RISEFR 050-0211. Boksene
monteres på stående eller liggende stender med tilhørende stenderfeste, skruer
eller spiker. I tabellene over finner du maks. monteringshøyde ved
forskjellige bokskombinasjoner. Ved montering av bokser på begge sider av
veggen, må senteravstanden mellom boksene være minimum 200 mm.
Brannklassifiserte vegger er vanligvis fullisolerte. I tilfelle veggene
mangler isolasjon, er det nødvendig å lage et kammer på 300 mm i hver retning
og isolere med steinull. Vedrørende isolasjonstype, bruk alltid steinull med
tetthet 28 kg/m³.
fi Ohjeet Multifix KR palorasioille-EI30 ja EI60 luokitelluissa seinissä
Erityiset vaatimukset asentamisesta paloluokiteltuihin seiniin suojaustason
ylläpitämiseksi palon leviämistä vastaan. Tieto liittyy palokojerasioiden,
1.5- palokojerasioiden ja kaksoispalokojerasioiden asennukseen. EI30
luokitellut seinät vähintään 1×12,5 mm kipsilevyllä ja EI60-luokitellut seinät
vähintään 2×12,5 mm kipsilevyllä. Molemmissa tyypeissä rangan vähimmäissyvyys
70 mm. Palkit jotka on valmistettu teräksestä tai puusta hyväksytään.
Hyväksyntä RISEFR 050-0211. Palorasiat on kiinnitettävä pystysuoraan
palkkirakenteeseen rankatuen avulla tai naulaamalla/ruuvaamalla. Taulukosta
löydät mahdolliset yhdistelmät ja hyväksyttävät asennuskorkeudet
lattiatasosta. Asenna seinän vastakkaisille puolille vähintään 200 mm etäisyys
rasioiden keskipisteiden välillä. Yleensä paloluokitellut seinät ovat täysin
eristettyjä. Jos seinät eivät ole eristettynä on luotava 300 mm:n tila
kumpaankin suuntaan ja täytettävä villalla. Käytä eristykseen aina kivivillaa,
jonka vähimmäistiheys on 28 kg/m³.
GEX3940200-01 June-2023
Schneider-Electric Industries SAS, 35 Rue Joseph Monier, 92500 Rueil Malmaison, France www.se.com/contact
2/2