Schneider Electric GEX3940200-01 Multifix Apparatus Boxes Instruction Manual

January 23, 2024
Schneider Electric

GEX3940200-01 Multifix Apparatus Boxes

Product Information

The Multifix apparatus boxes are designed for use in EI30 and
EI60 fire walls. They are suitable for installations in both wood
and steel beam constructions. The boxes are made to accommodate
standard plaster boards with thicknesses of 13 mm. The minimum beam
size required for installation is 70 mm.

Product Usage Instructions

Box Placement for EI60 and EI30 Fire Wall

When installing the Multifix apparatus boxes in a fire wall,
follow the guidelines below:

  • For EI60 fire walls:

    • Use 2×13 mm standard plaster board.

    • Place the boxes at equal distances between wood/steel
      beams.

    • Ensure a minimum distance of 70 mm between the boxes and the
      beams.

  • For EI30 fire walls:

    • Use 1×13 mm standard plaster board.

    • Place the boxes at equal distances between wood/steel
      beams.

    • Ensure a minimum distance of 70 mm between the boxes and the
      beams.

Box Installation Height

The Multifix apparatus boxes can be installed at various heights
within the fire wall. The following height ranges are
acceptable:

  • For EI60 fire walls:
    • Minimum height: 150 mm
    • Maximum height: 1100 mm
  • For EI30 fire walls:
    • Minimum height: 150 mm
    • Maximum height: 1100 mm

Box Placement and Wall Construction for EI60 Fire Wall

For EI60 fire walls, the following example demonstrates the
placement of the Multifix apparatus boxes:

  • Use 2×13 mm standard plaster board.

  • Place the boxes at equal distances between wood/steel
    beams.

  • Ensure a minimum distance of 70 mm between the boxes and the
    beams.

Box Placement and Wall Construction for EI30 Fire Wall

For EI30 fire walls, the following example demonstrates the
placement of the Multifix apparatus boxes:

  • Use 1×13 mm standard plaster board.

  • Place the boxes at equal distances between wood/steel
    beams.

  • Ensure a minimum distance of 70 mm between the boxes and the
    beams.

Specifications

  • Manufacturer: Schneider-Electric Industries SAS
  • Model: Multifix apparatus boxes
  • Approval: RISEFR 050-0211

FAQ

Q: What type of plaster board should be used with the Multifix

apparatus boxes?

A: The Multifix apparatus boxes are compatible with standard
plaster boards with a thickness of 13 mm.

Q: What is the minimum beam size required for

installation?

A: The minimum beam size required for installation is 70 mm.

Q: How should the boxes be secured to the vertical beam

structure?

A: The boxes can be secured to the vertical beam structure using
beam fixings, screws, or nails. Alternatively, they can be
installed in additional horizontal beams using similar means.

Q: What is the recommended distance between the box centers

when installing on opposite sides of the wall?

A: When installing on opposite sides of the wall, a minimum
distance of 200 mm between the box centers is recommended.

Q: Should the fire-classified walls be insulated?

A: Usually, fire-classified walls are fully insulated. If the
walls are not insulated, a chamber of 300 mm should be created in
each direction and filled with mineral wool. Always use stone for
insulation.

Multifix apparatus boxes
Example of Box placement and Wall construction For EI60 fire wall

2×13 mm standard plaster board

Wood / Steel Beam

Wood / Steel Beam

Wood / Steel Beam

min 70 mm
Stone wool density min 28kg/m³

X

Max. Ø 74 mm

X

X

X = Equal Distance

Example of Box placement and Wall construction For EI30 fire wall

1×13 mm standard plaster board

Wood / Steel Beam

Wood / Steel Beam

Wood / Steel Beam

Stone wool density min 28kg/m³

min 70 mm

X

Max. Ø 74 mm

X

X

X = Equal Distance

GEX3940200-01 June-2023

Schneider-Electric Industries SAS, 35 Rue Joseph Monier, 92500 Rueil Malmaison, France www.se.com/contact

1/2

Multifix apparatus boxes

Box placement for EI60 and EI30 fire wall
Min. 300mm

Applicable installations and combinations related to fire class

150 mm

Min. 200mm

Box installation
height
El 60
El 30

Min. 150 mm

Max. 1100 mm

Max. 1100 mm

Max. 1100 mm

Max. 200 mm

1100 mm 200 mm

Box facing opposite side

en Instruction for Multifix standard apparatus boxes in sv Anvisning för Multifix väggdosor i brandklassade

fire-classified walls EI30 and EI60

väggar EI30 och EI60

Specific requirements on installation in fire-classified walls to maintain

Speciella krav för installation i brandklassade väggar för att bibehålla

the level of protection against spread of fire. Information is related to

skydd mot spridning av brand. Anvisningen gäller enkeldosor, 1½

single boxes, 1½ module and double boxes.

modul och dubbeldosor.

EI30 classified walls with minimum of 1×12,5 mm standard type of

EI30 klassade väggar med minst 1×12,5 mm standard gipsskiva och

plaster board and and EI60 classified walls with minimum of

EI60 klassade väggar med minst 2×12,5 mm standard gipsskiva.

2×12,5 mm standard type of plaster board. Both types with minimum

Båda med minst 70 mm regel i trä eller stål.

beam size of 70 mm. Beams in steel or wood are accepted.

Typgodkännande RISEFR 050-0211.

Approval RISEFR 050-0211.

Dosorna infästes på horisontella eller vertikala reglar med

Boxes have to be secured to the vertical beam structure with beam

regelfästen, skruvar eller spik.

fixings, screws or nails, alternatively in additional horizontal beams

Tabellen ovan visar vilka kombinationer och montagehöjder ovan golv

with similar means.

som är tillåtna.

In the table you find out possible combinations and acceptable

Vid montering av dosor på bägge sidor av väggen måste avstånd

heights for the installation from the floor level.

mellan respektive centrum vara minst 200 mm.

Regarding installation in opposite sides of the wall, allow minimum

Vanligtvis är brandklassade väggar fullisolerade. Om väggarna inte är

200 mm distance between the box centers.

isolerade skapas ett isolerat fack runt dem, 300 mm åt vardera håll

Usually fire-classified walls are fully insulated. If the walls are not

med stenull. Använd alltid stenull med densitet på minst 28 kg/m³.

insulated you have to create a chamber of 300 mm each direction

and fill with mineral wool. Concerning insulation, always use stone

wool with minimum density of 28 kg/m³.

no Veiledning for Multifix veggbokser i EI30 og EI60 brannklassifiserte vegger
For å hindre spredning av brann, stilles det krav til installasjon i brannklassifiserte vegger. Informasjonen gjelder enkel boks, 1½ modul og dobbel boks. EI30 klassifiserte vegger med minimum 1×12,5 standard gipsplate og EI60 klassifiserte vegger med minimum 2×12,5 standard gipsplate. Begge med minimum 70 mm tre- eller stålstender. Godkjenning RISEFR 050-0211. Boksene monteres på stående eller liggende stender med tilhørende stenderfeste, skruer eller spiker. I tabellene over finner du maks. monteringshøyde ved forskjellige bokskombinasjoner. Ved montering av bokser på begge sider av veggen, må senteravstanden mellom boksene være minimum 200 mm. Brannklassifiserte vegger er vanligvis fullisolerte. I tilfelle veggene mangler isolasjon, er det nødvendig å lage et kammer på 300 mm i hver retning og isolere med steinull. Vedrørende isolasjonstype, bruk alltid steinull med tetthet 28 kg/m³.

fi Ohjeet Multifix KR palorasioille-EI30 ja EI60 luokitelluissa seinissä
Erityiset vaatimukset asentamisesta paloluokiteltuihin seiniin suojaustason ylläpitämiseksi palon leviämistä vastaan. Tieto liittyy palokojerasioiden, 1.5- palokojerasioiden ja kaksoispalokojerasioiden asennukseen. EI30 luokitellut seinät vähintään 1×12,5 mm kipsilevyllä ja EI60-luokitellut seinät vähintään 2×12,5 mm kipsilevyllä. Molemmissa tyypeissä rangan vähimmäissyvyys 70 mm. Palkit jotka on valmistettu teräksestä tai puusta hyväksytään. Hyväksyntä RISEFR 050-0211. Palorasiat on kiinnitettävä pystysuoraan palkkirakenteeseen rankatuen avulla tai naulaamalla/ruuvaamalla. Taulukosta löydät mahdolliset yhdistelmät ja hyväksyttävät asennuskorkeudet lattiatasosta. Asenna seinän vastakkaisille puolille vähintään 200 mm etäisyys rasioiden keskipisteiden välillä. Yleensä paloluokitellut seinät ovat täysin eristettyjä. Jos seinät eivät ole eristettynä on luotava 300 mm:n tila kumpaankin suuntaan ja täytettävä villalla. Käytä eristykseen aina kivivillaa, jonka vähimmäistiheys on 28 kg/m³.

GEX3940200-01 June-2023

Schneider-Electric Industries SAS, 35 Rue Joseph Monier, 92500 Rueil Malmaison, France www.se.com/contact

2/2

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals