TempZone 2024 Floor Heating Ruler Cable Instruction Manual
- June 16, 2024
- TempZone
Table of Contents
TempZone 2024 Floor Heating Ruler Cable
Product Information and Specifications
Product Specifications and Details
Radiant floor heating systems are uniquely designed for use as primary or
supplemental heat sources in residential or light commercial applications for
use under tile, stone, hardwood, engineered hardwood, carpet (verify
installation is in compliance with local electrical code), and laminate
flooring.
The TempZone™ Floor Heating Cable is composed of a twin-conductor cable and a
cold lead of 15 feet for connection to a power source. The heating cable
delivers 3.7 watts/linear foot. Wattage per square foot depends on the
installation.
The TempZone™ heating cable consists of a copper alloy resistance-heating
element insulated with a high temperature
Fluoropolymer having high dielectric strength and the ability to withstand
high temperatures to ensure safety.
The cores are surrounded by an aluminium foil screening with a copper drain
wire, which provides additional mechanical strength and a ground path. A foil
shield surrounds the copper ground to virtually eliminate EMF. An outer high
temperature PVC jacket strengthens the cable and protects against corrosion.
Selection of TempZone™ Floor Heating Cable
The TempZone™ Floor Heating Cable is available in either 120V or 240V and a
range of lengths to meet the requirements of each installation. To determine
the appropriate product for your installation, refer to the “Installation and
Spacing Recommendations” chart below.
WarmlyYours TempZone™ Floor Heating Cable can be installed at 3- or 4-inch
intervals to meet the needs of any installation. To determine which spacing
works best for your installation, consider the following:
Installation and Spacing Recommendations
3-inch Spacing | 4-inch Spacing | |
---|---|---|
Wattage (depends on cable length) | 15 watts/sq. ft. | 11 watts/sq. ft. |
Heating Type | Primary or supplemental | Supplemental |
Subfloor Type | Concrete and wood | Wood (and other non-concrete surfaces) |
Flooring Type | Tile, stone, laminate, carpet * | Hardwood, engineered wood, |
laminate, carpet*
Wet Areas| Bathrooms, showers| N/A
Climate| Colder and warmer climates| Warmer climates
Recommended uses| Older homes where insulation may not be optimal| New homes
with optimal insulation values
Coverage| 120V: up to 108 sq. ft. 240V: up to 216 sq. ft.| 120V: up to 143.9
sq. ft. 240V: up to 287.9 sq. ft.
* Note : Cable must be embedded in a 3/8 inch layer of self-leveling underlayment.
Before You Begin
General Precautions Before Installation of the TempZone™ Floor Heating Cable
-
TempZone™ Floor Heating Cable must NOT touch, cross over, or overlap itself at any point.
This could cause the cable to overheat. Use TempZone™ Cable Fixing Strips to avoid bunching or crossover of the cable. -
Do NOT cut the TempZone™ Floor Heating Cable. Altering the cable length may result in overheating and damage to the cable. Ensure that you order the correct cable length for your installation.
-
Take precautions to avoid damage to the TempZone™ cable during installation. Do not drop sharp objects or carelessly step on the cable. Do not bang the trowel on the heating cable while applying mortar.
-
If you are replacing a floor with an existing floor heating system, completely remove old mats and/or cable before installing new the TempZone™ Floor Heating Cable.
-
TempZone™ floor heating cables should be separated from other heat sources. Per the National Electric Code, section 424.39, heating elements of cables must be separated at least 200 mm (8 in) from the edge of outlet boxes and junction boxes that are to be used for mounting surface luminaires. A clearance of not less than 50 mm (2 in) shall be provided from recessed luminaires and their trims, ventilation openings and other such openings in room surfaces. No heating cable shall be covered by any surface-mounted equipment.
-
Do not install TempZone™ Floor Heating Cable when the ambient temperature is below 50˚F (10˚C).
-
If using a thermal insulation underlayment between the self-leveling underlayment-encased cable and the final floor covering (verify installation is in compliance with local electrical code), use a product with a typical R-value of 0.027 or less. The floor covering materials used with this product must not exceed a thermal insulation R-value of 1.
-
WarmlyYours recommends using CeraZorb® underlayment when installing cable over a concrete floor or slab to allow a greater percentage of heat generated to transfer to the flooring surface.
-
The bending radius of the TempZone™ Floor Heating Cable during installation should not be less than 25 mm (1 in).
-
The cold lead is 15 feet long. WarmlyYours recommends allowing 12 inches of cold lead wire to extend from the thermostat box to facilitate easier thermostat connection. Any excess cold lead may be trimmed. Please follow all national and local electric codes.
-
Center the floor thermostat sensor between two adjacent runs of TempZone™ Floor Heating Cable. Do not locate floor thermostat sensor closer than 1 inch to the cable or allow it to overlap any other cable.
-
Carpet and laminate manufacturers may recommend a maximum limit for the temperature setting on the thermostat of 86ºF (30ºC).
-
Do not install the TempZone™ Floor Heating Cable under permanent fixtures (e.g. cabinets, bathtubs), in closets or in walls
-
Allow for a sufficient drying or curing period of the subfloor and finished floor covering before and after installing the TempZone™ Floor Heating Cable. Do NOT operate floor heat until the thinset or self-leveling underlayment (SLU) has completely cured.
-
Please note the thickness of the factory splice and cold lead and plan accordingly. The subfloor may need to be chiseled or routed to allow placement of the splice and endcap
-
When using self-leveling underlayment (SLU), WarmlyYours recommends priming the floor before attaching the Cable Fixing Strips and securing the cable. Doing so will ensure that the primer covers the subfloor completely. Whenever using SLU, ALWAYS follow the installation recommendations set forth by the SLU’s manufacturer. It is very important to adhere the heating cable securely to the subfloor, otherwise the heating cable may float to the top of the SLU.
Important Electrical Precautions Before Installation
IMPORTANT : Where required, all electrical connections should be performed by a licensed, certified electrician in accordance with local and national electrical code requirements.
- TempZone™ Floor Heating Cable has an earth-grounding braid (metal sheath). The earth-grounding braid should be properly grounded. The core wires should be connected to the main power supply.
- Verify that cable voltage matches the voltage of circuit.
- Check the ohms resistance of the TempZone™ Floor Heating Cable before, during, and after installation. Resistance value should match the value given on the label attached to the cable. A tolerance of -5/+10% at 20ºC (68ºF) is allowed.
- Local electrical codes may require the low-voltage sensor wire to be installed in conduit. If this is required, do not install the low-voltage sensor lead in the conduit containing the cold leads. Provide a separate conduit for the low-voltage sensor wire.
- WarmlyYours strongly recommends connecting the Circuit Check™ device to warn of accidental damage to the TempZone™ Floor Heating Cable or lead wires during installation.
- TempZone™ Floor Heating Cable should be connected to a Listed Class–A Ground Fault Circuit Interrupter (GFCI). If using one of our programmable or nonprogrammable Listed thermostats that include a built-in GFCI, then a separate Class–A GFCI is not required.
- If the GFCI is tripped during normal operation and cannot be reset, there may be a fault in the cable. Do NOT attempt to re-energize the TempZone™ Floor Heating Cable. Do NOT bypass the GFCI under any circumstances. Contact a qualified electrician or WarmlyYours for assistance.
- Indicate which branch circuits or circuit breakers supply the power to the floor heating cable in a convenient location (e.g. taped to the circuit breaker box) for reference by the electrical inspector or homeowner. Retain the UL labels for each TempZone™ Floor Heating Cable. Leave one UL label attached to the floor heating cable.
- Use only Listed conduit, fittings, and other components.
- TempZone™ Floor Heating Cable shall not extend beyond the room or area in which it originates.
- The TempZone™ Floor Heating Cable should only be installed by qualified personnel who are familiar with the construction and operation of the TempZone™ Floor Heating Cable and the risks involved.
- The installation of the TempZone™ Floor Heating Cable shall be in accordance with all manufacturer’s instructions and local and national codes.
- In Canada, the installation shall be made according to the provisions of section 62 of the Canadian Electrical Code, Part 1.
- When used in wet locations, Installation shall be in accordance with the National Electric Code, NFPA-70 and CAN/CSAC22.1, Canadian Electric code, Part 1 (CEC) and that final acceptance is to be made in the field by the Authority Having Jurisdiction (AHJ).The UL Listing for this product covers use in wet locations for US and CANADA. Wet location installation in United States shall be in accordance with the National Electric Code, NFPA 70 and any other applicable jurisdictional code and final acceptance is to be made by the Authority Having Jurisdiction (AHJ).
WARNING : Risk of electric shock and fire. Damage to supply conductor insulation may occur if conductors are routed less than 2 in. (51 mm) from this heating product. Refer to installation instructions for recommended means of routing supply conductors.
Planning the Installation
Selection of Floor Covering material
The floor covering materials used with this product must not exceed a thermal insulation R-value of 1.
**Examples of Common R-values for Floor Covering Materials***
Floor Covering Material | Thickness (inches) | R-value |
---|---|---|
Carpet | 3/8 | 1.0 |
Tile (ceramic, mosaic) | 1/4 | 0.15 |
Laminate | 3/8 | 0.675 |
Plywood | ½ | 0.63 |
Natural stone (granite, limestone, marble, sandstone) | 1 | 0.38 to 0.114 |
Wood | 3/4 | 0.80 maximum |
*These values are provided for general reference purposes only. Consult the floor covering manufacturer for product-specific information.
Thermal Insulation
The insulation levels of the floor will affect both the performance and
operating costs of the TempZone™ floor heating system. Thermal insulation
reflects the heat upwards into the floor tile instead of allowing heat to
penetrate into the subfloor, keeping the floor warmer for a longer time.
When the cable is installed on a concrete slab, we recommend adding a layer of
insulation to the slab prior to installing the TempZone™ Floor Heating Cable.
Adding insulation on top of the concrete slab and beneath any floor heating
system will allow a greater percentage of heat generated to transfer to the
flooring surface. WarmlyYours recommends using 5 mm thick CeraZorb® synthetic
cork underlayment.
Calculation of Length of Cable Required
To determine the appropriate cable length for the installation, measure the area to be heated and calculate the area in square feet. Do not include the area covered by fixed objects, such as appliances, bathtubs, cabinets, etc. Refer to the “Installation and Spacing Recommendations” chart in section 1.2 to determine the recommended watt density per square foot for the type of installation.
Calculation of On-Center Spacing (OC)
In order to fit the TempZone™ Floor Heating Cable properly in the designated
space, it is necessary to determine the spacing between the cables. This is
called on-center spacing or OC.
Combine cable lengths if more than one is needed for the installation. Once
the OC spacing has been calculated and the correct length of cable for the
area to be heated is obtained, installation of the floor heating cable can
begin. The formula assumes that 3-inch spacing will be used between the
heating cable and walls or fixed objects, and full OC spacing between cable
runs. To make cable placement easier, make a measuring template out of
cardboard in the width of the OC spacing less the thickness of the cable.
Place the template along to the cable run just completed to determine where
the next run of cable should be positioned.
IMPORTANT : To avoid overheating, OC spacing should not be less than 3 inches and area loading should not exceed 15 watts/square foot.
IMPORTANT : Do not order more cable than necessary as cable cannot be shortened.
Wattage Yields
| Watts Per Square Foot
---|---
Watts/linear ft| 3.7
Watts/ft2 at 3”| 14.8
Watts/ft2 at 3.5”| 12.7
Watts/ft2 at 3.75”| 11.84
Watts/ft2 at 4”| 11.1
Watts/ft2 at 4.75”| 9.3
Watts/ft2 at 5”| 8.9
Electrical Considerations
Floor Sensors and Temperature Control
Floor Sensor (not required for all systems)
Systems using an Spiration Series control may require a low-voltage floor
sensor. Carpet or laminate flooring manufacturers may require the use of a
low-voltage sensor with their floor covering. Check with the manufacturer for
specific recommendations.
This sensor is embedded in the floor and monitors the floor temperature. Check
the ohms reading of the sensor wire before and after installation to make sure
it has not changed. Most sensor wires have an ohms reading of 8,000 to 20,000
Ω, and your ohmmeter must have a 20 kΩ setting for this measurement. The floor
sensor should be centered in between two resistance wires, leaving
approximately 1.5 inches on either side and extending about 6 inches into the
heated area. Avoid placing the sensor in an area affected by a draft, a
radiator or other heat source, or the sun.
A second, backup sensor may be installed and can be purchased separately.
The sensor cable should be routed to the thermostat and installed on the wall
at a suitable operating height.
Do not allow any other cable to overlap the sensor cable. When heating
laminate and carpeted floors (U.S. only), the maximum temperature setting
limit on thermostat should not exceed the flooring manufacturer’s
recommendations.
Route TempZone™ Floor Heating Cable lead wires to a junction box or to the thermostat. Never connect the floor heating cable to other cables. The thermostat and the cable lead wires must be connected in parallel- -not in series.
Type of Wire | Color |
---|---|
120 V | Yellow and Black |
240 V | Red and Black |
Floor Sensor | Black |
Electrical Requirements for the System
Where required, all electrical work for the floor heating cable installation must be done by a qualified, licensed electrician in accordance with local building and electrical codes and the National Electrical Code (NEC), especially Article 424, Part IX of the NEC, ANSI/NFPA 70 and Section 62 of the Canadian Electrical Code (CEC), Part I, as well as any other applicable statutory requirements.
WarmlyYours recommends the following controls and accessories for the TempZone™ Floor Heating Cable:
- Spiration Series controls feature a Listed Class-A GFCI and a floor sensor to regulate the actual temperature of the floor
- Non-GFCI circuit breaker
In most installations, a Class-A GFCI is required by national and local codes
for protection against ground leakage currents. A Class-A GFCI is included
with the Spiration Series controls. If not using a WarmlyYours thermostat, a
Class-A GFCI thermostat or circuit breaker may be needed.
The TempZone™ Floor Heating Cable should be connected to a non-GFCI circuit
breaker for complete disconnection on all poles with minimum 0.12 inch
disconnection distance.
The thermostat should be installed in a single-gang box, flush with the wall
at a height of approximately 5 feet or eye level for easy access and
operation. The floor sensor cable and the TempZone™ Floor Heating Cable cold
leads shall be routed to the thermostat in separate UL Listed conduits if
conduit is required by local and national electric codes.
If the floor heating cable load exceeds the 15-amp thermostat power rating,
consult WarmlyYours for information on alternative solutions using master
thermostats and power modules.
Wiring Diagram
Note : All electrical work must be done by a qualified, licensed electrician in accordance with local building and electrical codes, and the National Electrical Code (NEC), especially Article 424, Part IX of the NEC, ANSI/NFPA 70 and Section 62 of the Canadian Electrical Code (CEC), Part I, as well as any other applicable statutory requirements.
Example of typical wiring diagram for 120V or 240V installations is given in Figure 1. Refer to the instructions that came with your specific thermostat.
Figure 1. Wiring Diagram for 120V or 240V WarmlyYours TempZone™ Floor Heating Cable Installation
Installation and Operation
Recommended Equipment and Items for Installation
The following equipment and items are recommended for installation of the WarmlyYours TempZone™ Floor Heating Cable :
- Ohmmeter (or multimeter)
- Circuit Check™
- Hot glue gun (if using hot glue to secure the Cable Fixing Strips)
- Industrial-grade hot glue (if using hot glue to secure the Cable Fixing Strips)
- Chisel or router to create a groove for the splice in the subfloor
- Hammer
- Screwdriver
- Protective wall plate
- Duct tape or high temperature tape
- Staples, nails, adhesive or 1⁄2 inch screws to attach the Cable Fixing Strips to the subfloor
- Class-A Ground Fault Circuit Interrupter (if not using a WarmlyYours thermostat)
- Single-gang electrical box for each thermostat or power module
- Listed electrical conduit (to be provided by installer)
- Permanent marker
- Tape measure
- Utility scissors
Pre-Installation Preparation
-
Document the plan. Follow a SmartPlan™ obtained from WarmlyYours or prepare a floor plan of the area to be heated. Using a floor plan, with the TempZone™ Floor Heating Cable layout marked, makes it easy to trace the heating cable routing for troubleshooting if necessary.
-
Select the appropriate TempZone™ Floor Heating Cable, ensuring it is the correct length and voltage.
-
Identify a suitable location for installing the thermostat and low-voltage sensor if used.
-
Mark the layout of the floor heating cable on the floor plan. Taking photographs of the area may also be helpful.
-
Inspect the TempZone™ Floor Heating Cable visually and ensure that it is not damaged. Check voltage, wattage, and resistance values on the label.
-
Proper surface preparation of floor is extremely important. Make absolutely sure that there are no objects on the floor that might damage the TempZone™ Floor Heating Cable. Sweep the floor to ensure it is completely clear of debris, including nails, sharp metallic objects, wood, construction debris, and damaged or defective cables.
-
If applicable, install CeraZorb® on the concrete subfloor. Follow the manufacturer’s instructions when installing the CeraZorb® insulating underlayment.
-
Check resistance of TempZone™ Floor Heating Cable with an ohmmeter upon removing it from the package. The resistance value of the heating cable should match the value on the label attached to the cable with a tolerance of -5/+10% allowed at 20º C (68º F). Record the resistance value on the warranty card in section 10.
IMPORTANT :The electrical resistance of the cable must be checked before you begin and monitored throughout the installation process to ensure there has been no damage causing shorts or breaks. WarmlyYours recommends at least three readings be taken: -
Before starting installation
-
After securing the cable in place on the subfloor
-
After installing the flooring surface on top of the cable
-
Using an ohmmeter, check the insulation resistance of the cable between the core wires and to the ground wire. It should always read infinity.
-
Use a Circuit Check™ device during cable installation. These devices will provide an audible alarm if the wire is damaged or cut during installation. A continuity checker is not acceptable for these tests
IMPORTANT : Beware of Using a Continuity Checker!
For cables that have over 200 Ω resistance, some continuity checkers do not send enough current to get completely through the wire and emit the noise or light that affirms proper continuity. Please use a digital ohmmeter.
Three (3) ohm readings should be taken for each WarmlyYours TempZone™ Floor Heating Cable at each stage of the installation and recorded in the table on the warranty card in section 10.
Refer to Figure 2 for instructions about how to attach the ohmmeter to take each type of reading. -
Core to Core: This is the reading between the two inner conductors on the lead wires.
-
Core to Ground, Yellow / Red Lead: This is the reading between the inner core and the outer ground sheath on the lead wire. This reading should be infinity.
-
Core to Ground, Black Lead: This is the reading between the inner core and the outer ground sheath on the lead wire at the finish point of the cable. This reading should be infinity.
Figure 2. Attachment points for ohm readings
-
Core to Core
-
Core to Ground Wire
-
Core to Ground Wire
Circuit Check™ Instructions
-
Install TempZone™ Floor Heating Cable
Install the floor heating cable in accordance with the design layout and instructions provided by WarmlyYours. -
Test the Circuit Check™
Before connecting any wires, install the batteries in the device and turn it on and off to test the alarm. After
confirming that the alarm is in good working order, connect the wires as follows:- Connect black inner conductor core wire to the black terminal
- Connect second inner conductor core wire to the red terminal
There are two ways of doing the next step:
- Split the ground sheath in two. Connect one half of the ground sheath to the green terminal, turn on the Circuit Check™, and touch the other half of the ground sheath to one of the inner conductor wires.
- Install the entire ground into the green terminal. Turn on unit and use a paper clip as a bridge between the ground wire and either one of the inner conductors. Either method should activate the alarm. If the Circuit Check™ does not pass all these tests, please call WarmlyYours 24/7 Installation Support at 800-875-5285 for assistance.
-
Activate the Circuit Check™ and Proceed to Install Flooring
-
If the Circuit Check™ Alarm Sounds, Stop!
If the alarm sounds, there is a short in the circuit or break in the system. Refer to the troubleshooting guide in section 8 of this installation manual or call 24/7 Installation Support at 800-875-5285. WarmlyYours can ship a splice kit to repair the short. Alternatively, the wire may be repaired by an electrician. Please see the wire repair documents “Instructions for Twin Conductor TempZone™ Repair” at www.warmlyyours.com/publications/TZ-TWIN- REPAIR-30027-B/download and “TempZone™ Cut & Turn Twin Conductor Solder Method Wire Repair” at www.warmlyyours.com/publications/TZ-TWIN-SOLDER- REPAIR-30028-A/download or call us 24/7 at 800-875-5285.
Figure 5. How to connect the Circuit Check™ for installation
Installation of TempZone™ Floor Heating Cable
Install TempZone™ Cable Fixing Strips
Install Cable Fixing Strips in a direction perpendicular to the direction the
cable will run. Cable Fixing Strips should be installed at least 3 inches from
the wall perimeter to yield proper cable coverage calculations.
WarmlyYours recommends securing the cable to the floor every 20 inches using
tape or hot glue to keep the cable in position until the self-leveling
underlayment is applied. When working around cabinets or vanities, install the
Cable Fixing Strips at a distance that will allow the cable to be installed
1-1/2 inches away from the cabinet or vanity base.
Each row of Cable Fixing Strips should be positioned at the appropriate intervals to ensure the desired OC spacing (3 or 4 inches) for the installation.
Secure the Cable Fixing Strips to the floor. There are several acceptable methods for doing so.
For plywood, cement board, or similar surfaces:
- Secure Cable Fixing Strip with galvanized nails or screws.
For concrete or similar surfaces:
- Concrete nails are recommended for best results.
- Double-sided tape, hot glue, or a strong spray adhesive may be used if the floor is thoroughly cleaned and the Cable Fixing Strips are cleaned to remove any oils.
- If spray adhesive is used, be sure to carefully follow all of the manufacturer’s instructions. WarmlyYours recommends applying the spray adhesive to both the back of the Cable Fixing Strip and the floor.
Figure 6. Securing the Cable Fixing Strips
Install the TempZone™ Floor Heating Cable
-
Begin installing the heating cable from the thermostat or junction box. Follow the pattern marked on the floor plan (if supplied). Please note the thickness of the factory splice and cold lead and plan accordingly.
-
Unwind the cable from the spool. Secure it using the TempZone™ Cable Fixing Strips. Avoid bunching the cable or crossing over other parts of the cable.
-
The TempZone™ Floor Heating Cable should be installed in a uniformly-spaced serpentine pattern. Refer to either “Product Selection Guide–120V” or “Product Selection Guide–240V” in section 9 for spacing information.
-
Take note of the cable’s halfway point marking indicated on the cable. This mark should match the halfway point indicated on the custom SmartPlan™ supplied with the order (optional).
-
Route the power leads from the floor to the thermostat box. If using multiple heating cables, route the power leads from the floor to a junction box or thermostat box in the wall.
NOTE : Leads should be protected at the point they leave the floor. Rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, electrical metallic tubing, or other means approved by local electrical codes should be used. -
For installations including a thermostat, the low-voltage floor sensor should be placed in between the loops created by the cable and held in place with a small amount of thinset or hot glue. See Figure 7.
Figure 7. Placement of the floor temperature sensor
The sensor wire cannot cross any heating cable or lead wire. It must extend at
least 6 inches into the heated area. The sensor and its wire should be covered
directly with thinset or self-leveling underlayment.
The cold lead wires should be placed above the subfloor, along the side of the
heated area at least 2 inches from the heating wire. Secure the cold lead
wires with a suitable tape or hot glue before the thinset or self leveling
underlayment is applied over the cables.
- Use an ohmmeter check the continuity, insulation resistance, and resistance values again after the cable has been installed. Compare these post-installation values with pre-installation values to ensure they are consistent. Record post-installation values on the warranty card in section 10. Attach Circuit Check™ to cold leads at this time.
- Apply thinset or self-leveling compound over the heating cable and subfloor. Acrylic, latex, or polymer modified thinset cement may be used. Ensure that the material you select is compatible with the flooring material. Contact the adhesive manufacturer for more information and curing times.
Ensure that there are no air gaps during application of thinset or self- leveling underlayment (SLU). Make sure the heating cable, factory splices, and low-voltage thermostat sensor (if used) are completely embedded in the thinset or SLU. If SLU is used, be sure to use any primer required by the manufacturer.
A single- or double-layer method may be used over any subfloor (plywood, cement slab, concrete backer board, or mud bed). These methods are suitable for any stone or tile floor covering. For carpet (U.S. only), vinyl or laminate floor coverings, WarmlyYours recommends covering the floor heating system with 3/8 inch of self-leveling underlayment (total depth, whether the single- or double-layer application method is used) to create a smooth surface for installing these types of flooring. Follow the instructions appropriate to the type of floor covering to be used.
CAUTION : Careless use of the trowel can damage the heating cable. Never drop or bang a trowel directly on the cable.
Instructions for Installation in Wet Locations
-
Installation shall be in accordance with the National Electrical Code, NFPA-70 and CAN/CSA- C22.1, Canadian Electrical code (CEC), Part 1 and that final acceptance is to be made in the field by the Authority Having Jurisdiction (AHJ).
-
WarmlyYours recommends using a separate heating cable for shower areas. Installations shall be in accordance with the National Electric Code, NFPA 70 and any other applicable jurisdictional codes and final acceptance is to be made by the Authority Having Jurisdiction (AHJ).
-
If insulation board is being used over a slab, use suitable glue or cement-based adhesive, or thinset mortar to adhere it to the slab. If installing in a wet location, ensure the slope of the mortar bed is maintained so that it directs water to the drainpipe.
-
Make sure the power lead factory splice (the connection between the power lead and the heating cable) and the cable end seal, are located outside the shower area and at least 1ft. away from shower openings and other similar areas normally exposed to water. Make sure the control is located at least 4 ft. away from shower openings such that it cannot be exposed to water or touched by a person in the shower area.
-
Weave the cable back and forth across the area at the desired spacing. Maintain slight tension on the cable to ensure it does not pull loose. If desired, use hot glue at intervals to help ensure it stays secure. NEVER space the cables less than 3” apart.
-
Mark where the factory splice will be placed. Cut the matting or membrane and insert splice. It may be necessary to secure the splice to the floor with hot glue, adhesive or thinset.
-
Embed the heating cable between studs, at a spacing of 3 studs. Closer spacing may result in overheating and damage to building structures. A wider spacing may not provide sufficient power to warm the floor.
-
Continue to lay out the cable until the cable end cap is reached. Mark final location of end cap. Cut the matting or membrane and insert the end cap. It may be necessary to secure the end cap to the floor with hot glue, adhesive or thinset.
-
Always remember to install the thermostat sensor (if applicable) 6” into an open loop of the heating wire.
Instructions for Installation Under Tile and Stone Flooring
Option 1: Single-layer method for tile and stone
Apply a layer of 3/8 inch latex-modified thinset cement or self-leveling
underlayment (SLU) over the heating cable. Lay the tile or stone directly into
that layer of thinset cement.
OR
Option 2: Double-layer method for tile and stone
Embed the heating cable in a skim coat of latex-modified thinset or self-
leveling underlayment, completely covering the heating element and the sensor
wire. Apply a second layer of thinset and lay tiles as usual. The recommended
depth for both layers of thinset or SLU is 3/8 inch.
The single-layer method is used most by experienced installers in small
applications with easy access.
WarmlyYours does NOT recommend the single-layer method for installing mosaics
or tiles of different sizes or if you have not installed an electric radiant
heating system under tile or stone before.
Waiting Period: Regardless of method used, installation of floor heating cable
under tile or stone requires 2 to 28 days for the latex-modified thinset or
self-leveling underlayment to cure. Follow manufacturer recommendations for
cure times applicable to your installation.
IMPORTANT : Do NOT turn on the WarmlyYours TempZone™ Floor Heating Cable
system until after the thinset or self-leveling underlayment (SLU) has fully
cured. Doing so will result in damage to the system and cause the thinset or
SLU to become brittle. Failure of the thinset or SLU may cause damage to the
embedded cable. This type of damage is not covered by the WarmlyYours
warranty.
Instructions for Installation Under Carpet, Vinyl, or Laminated Flooring
Before applying SLU, ensure that the cable is firmly secured to the subfloor to prevent it from floating to the top of the self-leveling underlayment. Attach the Circuit Check™ at this time. Cover cable with 3/8 inch layer of self-leveling underlayment.
Testing
Testing the Cable
IMPORTANT : Do NOT supply the system with electric current to test.
All testing should be done with a digital ohmmeter. Supplying the system with a 120V or 240V electric current before the installation is complete is not needed to test the system.
Take the Ohm Readings
The electrical resistance of the WarmlyYours TempZone™ Floor Heating Cable must be checked before you start and monitored throughout the installation process to ensure there has been no damage causing shorts or breaks.
We recommend at least three readings be taken:
- Before starting installation
- After securing the cable in place on the subfloor
- After installing the flooring surface on top of the cable
Use an ohmmeter to measure the resistance.
Record the Ohm Readings
The value on the UL label should be within -5/+10% variance at 20ºC (68ºF) of
the original measurement indicated on the label. The electrician should
carefully mark the initial ohm reading taken onto the warranty card in section
10. Should the initial ohm reading be outside the -5/+10% variance, refer to
section 8, Troubleshooting, or call WarmlyYours Technical Support at
800-875-5285.
The specified resistance value and other important information can be found on
the WarmlyYours TempZone™ Floor Heating Cable product label. Figure 8 depicts
a sample product label. The information provided in the figure is for
illustration purposes only. Refer to label included with the cable for actual
values.
Figure 8. Sample product label
Go by the Numbers
The resistance should be measured from the inner core of the yellow (120V) or
red (240V) lead wire at one end to the inner core of the black lead wire at
the other end. Make sure that the probe of the ohmmeter does not touch the
tinned sheath wire at either end. Do not hold the wires onto the probes with
your fingers.
Even your body’s electrical resistance can affect the reading if you touch the
meter poles. A digital meter is easier to use and strongly recommended. Verify
that the batteries of the ohmmeter are good. Set your ohmmeter to measure
resistance in the range of 0 to 200 Ω.
For cables that have over 200 Ω resistance, it may be necessary to set the
ohmmeter to the next higher range of measurement to get an accurate ohm
reading.
Three (3) ohm readings should be taken for each WarmlyYours TempZone™
Floor Heating Cable at each stage of the installation and recorded in the
table on the warranty card in section 10. Refer to Figure 9 for instructions
about how to attach the ohmmeter to take each type of reading.
- Core to Core: This is the reading between the two inner conductors on the lead wires.
- Core to Sheath, Yellow / Red Lead: This is the reading between the inner core and the outer ground sheath on the lead wire. This reading should be infinity.
- Core to Sheath, Black Lead: This is the reading between the inner core and the outer ground sheath on the lead wire at the finish point of the cable. This reading should be infinity.
The ground wire may differ from the images above.
The ground wire may be represented as a additional wire with a stripe.
The testing procedure is still performed the same way
Figure 9. Attachment points for ohm readings
Operating Tips
Operating Tips
- When first energized, the TempZone™ Floor Heating Cables may take approximately 1 to 3 hours or more to fully warm your floor. Heating results will vary depending on climate and building materials.
- Energy consumption will vary depending on user preferences. To reduce energy consumption, set the thermostat to a lower temperature setting or operate for a shorter duration.
- Energy consumption can be minimized by turning the system off when floor heat is not required. However, additional time will be needed for the floor to warm up when the system is turned on again.
- WarmlyYours recommends and offers thermostats with a setback option. This option reduces warm-up time by setting the system to operate at a lower floor temperature, instead of completely turning it off, during the setback period(s).
- Avoid placing thick mats, rugs, mattresses, and broad-based or box-bottomed furniture on the heated floor, especially where the floor temperature sensor is located. These objects restrict the transfer of heat away from the cables and trap heat. This causes the floor beneath the object to become warmer than other areas in the room. Trapped heat may also cause discoloration or damage to some floor covering materials.
- Avoid using mats with rubber or vinyl backing, as the heat may cause them to decompose and stain the floor covering.
- When heating a hardwood floor, the flooring manufacturer may require that the floor be kept at a steady temperature, without a setback. Please consult the flooring manufacturer for any requirements to radiant heating.
Troubleshooting
Identify the Problem
If the system is not functioning properly, refer to the “Quick Reference Troubleshooting Guide” to determine the cause of the problem.
Quick Reference Troubleshooting Guide
Ohm Reading | What It Indicates | What to Do Next |
---|---|---|
Zero | Open circuit or short | Obtain ShortStop fault finder* from WarmlyYours |
to check distance to break.
Lower than the acceptable range, but some continuity is present| Ohmmeter
batteries may be low| Replace batteries and take ohm readings again.
Multiple electrical shorts| Obtain ShortStop fault finder from WarmlyYours.
Take a reading between each core wire and ground to determine the location of
the short.
Within range (-5/+10%) of specified value on UL label| No break| Check for an
electrical short.
Higher than acceptable range| Possible short| Obtain ShortStop fault finder
from WarmlyYours. Take a reading between each core wire and ground to
determine the location of the short.
Infinity| Ohmmeter may be set to incorrect scale| Set ohmmeter to correct
scale and test again. (Correct scale settings:
0 to 200 Ω for cable;
0 to 20,000 Ω for sensor wire)
Possible short| Obtain ShortStop fault finder* from WarmlyYours. Take a
reading between each core wire and ground to determine the location of the
short.
Possible break| Contact WarmlyYours for assistance.
*Note : A floor plan with the layout of the installation is required to determine the location of the short. For installations without a plan, please contact WarmlyYours technical support at 800-875-5285.
Troubleshooting
Locating a Fault in the TempZone™ Floor Heating Cable
Use a Circuit Check™ device during cable installation. These devices will provide an audible alarm if the wire is damaged or cut during installation. A continuity checker is not acceptable for these tests.
Beware of Using a Continuity Checker!
With cables that have over 200 Ω resistance, some continuity checkers do not
send enough current to get completely through the wire and emit the noise or
light that affirms proper continuity. For this reason, we always recommend
using a digital ohmmeter for any product testing or troubleshooting.
After the installation, if necessary, the position of a break can be found
with the WarmlyYours Troubleshooting Kit. A time domain reflectometer
(ShortStop) will not be able to find a break without an installation plan.
Repair kits and guidance are available from WarmlyYours 24/7 Technical Support
at 800-875-5285, or go to
www.WarmlyYours.com/support for
additional information.
Electrical Fault Finding
If the system is not functioning properly, turn off the system and have a licensed, certified electrician perform the following:
- Complete all steps of the installation process.
- Verify that all wiring connections, including grounding of the system, are correct.
- Check the sensor wire for proper ohm reading.
- Ensure all wires have been connected, including grounding of the system, in accordance with the wiring diagrams.
- Verify that the breaker supplying power to the WarmlyYours thermostat is a non-GFCI circuit breaker ( Note : If using a thermostat not provided by WarmlyYours, a GFCI-circuit breaker may be required).
- Make sure multiple cables have been wired in parallel and not in series.
- Confirm that the thermostat is receiving the correct voltage and outputting the same voltage when calling for heat.
- Using a well-calibrated, digital ohmmeter with good batteries, check the ohm resistance level of each heating cable. Refer to sections 5.2.10 and 5.3 for instructions about how to attach the ohmmeter.
Verify that these values are within -5%/+10% at 20ºC (68ºF) of the resistance value listed on the product label. If the measured values exceed the acceptable range, refer to the “Quick Reference Troubleshooting Guide” in section 8.1. If the measured value is not within range of the original reading, the cable may have been damaged in some way during installation.
If all of the above items have been completed and the system is still not operating correctly, then determine if there is a break or a short under the floor.
Checking for Breaks or Shorts
To check for a break, measure the ohm resistance of each cable. When taking an ohm reading, ensure that you do the following:
- Do not touch either of the probe ends with any part of your body. If the probe end is in contact with the body, the meter will measure the internal resistance of your body, not the cable.
- Set ohmmeter to the proper scale (0 to 200 Ω for heating cable or 0 to 20,000 Ω for the sensor wire).
The ohm resistance readings should be within -5/+10% at 20ºC (68ºF) of the nominal resistance indicated by the factory on the UL label. Refer to the “Quick Reference Troubleshooting Guide” in section 8.1. to determine what the ohm readings indicate.
Additional Information for Identifying Electrical Shorts
In some rare occasions during installation, a high pressure point on the cable
can occur and cause a break in the insulation between the core conductor and
the metal sheath. This opening in the insulation layer can create an
electrical short, even though the ohm reading from one line conductor to the
other line conductor is normal and does not indicate a circuit break. In these
rare circumstances, a continuity test will show no continuity (a reading of
infinity) between the line conductor and the ground wire and/ or between the
other line core conductor and the ground. A mega ohm meter can be used to test
the wire insulation in these cases.
There should be no continuity (indicated by a resistance reading of infinity,
not zero) between each line conductor and ground. If the ohmmeter reveals
continuity between both the line conductor and ground, there is a short in the
circuit.
Checking for Breaks or Shorts Using an Underground Fault Detector
There are two ways to locate breaks or electrical shorts with underground fault detectors:
- A break or short can most easily be found with a high potential (hipot) insulation tester, a high-voltage generating device that generates a ground or heat at the break point. The hipot can be used with infrared cameras to scan the floor and detect the exact location of the break. Contact WarmlyYours for more information about renting our troubleshooting kit.
- A break or short can sometimes be found with a time domain reflectometer (ShortStop fault finder), which measures the distance of the wire between the tester and the short point. A floor plan with the layout of the installation is required to determine the location of the short.
Warranty Information
Please complete and return the warranty card
Thank you for purchasing your new WarmlyYours TempZone™ Floor Heating Cable. To register your system, go online to www.warmlyyours.com/floor-heating/twin- cable/warranty, or simply complete, detach and mail this warranty card within 30 days of date of purchase to: WarmlyYours, 590 Telser Rd., Lake Zurich, IL 60047. For your convenience, you may also fax this card to 800-408-1100. WarmlyYours recommends that you make a copy for your records.
Terms and Conditions
WarmlyYours, Inc. warrants the WarmlyYours TempZone™ Floor Heating Cable
electric floor warming system (“the Product”) to be free from defects in
materials and workmanship for twenty five (25) years from the date of sale,
provided that the Product is installed in accordance with the WarmlyYours
product installation manual, any special written or oral design or
installation guidelines provided by WarmlyYours for the specific project that
the Product is intended, the provisions of the National Electrical Code (NEC),
or Canadian Electrical Code (CEC) and all applicable local building and
electrical codes.
If the Product is determined to be defective in materials and workmanship, and
has not been damaged as a result of misuse, misapplication or improper
installation, WarmlyYours will, at the customer’s discretion, either refund
the original cost of the Product or reimburse the cost for any labor and
materials required to perform the repair or replacement of the Product.
Controls sold under the WarmlyYours name are warranted for specific coverage
periods. Please see http://www.warmlyyours.com/warranty for the length of
warranty coverage for each control. Should the control be defective or
malfunction, return the control to WarmlyYours and it will be repaired or
replaced (at WarmlyYours’ discretion). The warranty does not cover removal or
reinstallation costs. See entire warranty in packaging.
WarmlyYours Inc. assumes no responsibility under this warranty for any damage to the Product prior to or during installation by anyone, including, but not limited to tradespeople or visitors to the job site, or damage caused as a result of post-installation work. Call our toll free number, 800-875-5285, if you have any questions about installation. The Limited Warranty is null and void if the Product owner or his representative attempts to repair the Product without receiving authorization. Upon notification of an actual or possible problem, WarmlyYours will issue an Authorization to Proceed under the terms of the Limited Warranty.
Warranty Subject to the Following Conditions:
- The warranty of the warming system must be registered by completing and returning the attached “System Warranty Registration Card” to WarmlyYours, Inc. within thirty (30) days of date of purchase. Please keep your invoice, as proof of date of purchase will be required in the event of a claim.
- The heating cable must be installed flat under tile, stone, resilient flooring or laminate wood in a latex-modified thinset or a Portland-based cement.
- The warming system must be electrically grounded and protected by a GFCI (Ground Fault Circuit Interrupter).
- The installation must comply with all national and local electrical and building codes, including the National Electrical Code (NEC), the Canadian Electrical Code (CEC), Part I, and Authority Having Jurisdiction (AHJ), as well as any other applicable statutory requirements.
- The manufacturer hereby reserves the right to inspect the installation site at any reasonable time.
- The warranty is not automatically transferred with change of ownership, but the manufacturer may, on application, transfer the warranty for the period remaining. This transfer is solely at the discretion of the manufacturer.
- The warming system should be used strictly in accordance with the following:
- The voltage of the circuit should match the voltage of the warming system, and the size of the circuit should be such that the warming system does not occupy more than 80% of the circuit capacity.
- Should you feel no warmth on the floor within 60 minutes, verify that there is power to the control or thermostat. Contact WarmlyYours after verifying that there is power through the load wires. Under no circumstances should you or anyone else tamper with or attempt to repair the warming system – this will render the warranty null and void.
- Switch the warming system on and off as you would any conventional electric heater, although timers or thermostats may be used if preferred.
- Use reasonable care in the operation of the warming system. Do not drop heavy articles on the flooring or pierce the flooring with sharp objects.
- All restrictions and warnings detailed in the installation manual must be strictly followed.
WARMLYYOURS, INC. DISCLAIMS ANY WARRANTY NOT PROVIDED HEREIN, INCLUDING ANY
IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A
PARTICULAR PURPOSE.
WARMLYYOURS FURTHER DISCLAIMS ANY RESPONSIBILITY FOR SPECIAL, INDIRECT,
SECONDARY, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE
OF THIS PRODUCT, INCLUDING INCONVENIENCE OR LOSS OF USE. THERE ARE NO
WARRANTIES WHICH EXTEND BEYOND THE FACE OF THIS DOCUMENT. NO AGENT OR
REPRESENTATIVE OF WARMLYYOURS HAS ANY AUTHORITY TO EXTEND OR MODIFY THIS
WARRANTY UNLESS SUCH EXTENSION OR MODIFICATION IS MADE IN WRITING BY A
CORPORATE OFFICER. WarmlyYours makes no claim as to the amount of floor/room
temperature rise, the time to reach a given floor/room temperature or final
floor/room temperature is due to the innumerable variations in building
construction and environmental conditions.
RETURN POLICY
Product will be accepted for return if it is in resalable condition. The
product must be in exactly the same condition as when we shipped it to you.
Customer Support
Free Design Service • 24/7 Installation Support • No Nonsense™ Warranty • 800-875-5285 • www.WarmlyYours.com