Carrier FB4 Residential Fan Coil Units Instructions
- June 16, 2024
- Carrier
Table of Contents
Carrier FB4 Residential Fan Coil Units
Product Information
Specifications
- Model: FB4, FE4, FF1E, FFM, FH4, FJ4, FV4, FX4, FZ4, PF4, FMA
- Type: Residential Fan Coil Units
Introduction
- The FB4, FE4, FF1E, FFM, FH4, FJ4, FV4, FX4, FZ4, PF4, FMA Residential Fan Coil Units are designed to provide efficient cooling and heating in residential buildings.
- This product manual provides detailed instructions for the service and maintenance of the units.
Safety Considerations
It is important to follow all safety codes and guidelines when installing or servicing the fan coil units.
The following safety precautions should be taken:
- Wear safety glasses, protective clothing, and work gloves.
- Have a fire extinguisher available.
- Read and follow all warnings or cautions included in the literature and attached to the unit.
- Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
- In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
- Recognize the safety-alert symbol and be alert to the potential for personal injury.
Fan Coil Description and Troubleshooting
- The FB4C, FJ4, FX4D, PF4, FF1E, and FZ (odd sizes) fan coil units are equipped with a fan motor and relays for efficient operation.
- The manual provides troubleshooting guidelines for identifying and resolving any issues that may arise with the fan coil units.
Fan Motor
- The fan motor is responsible for circulating air through the unit. If the fan motor is not functioning properly, it can affect the overall performance of the unit.
- Refer to the manual for instructions on inspecting and maintaining the fan motor.
Relays
- Relays are used to control the operation of various components in the fan coil unit. If a relay fails, it can result in improper functioning of the unit.
- The manual provides guidance on troubleshooting and replacing relays when necessary.
Care and Maintenance
The following components require regular care and maintenance:
- Filter Assembly: Clean or replace the filters regularly to ensure proper airflow and prevent dust buildup.
- Cooling Coil, Drain Pan, and Condensate Drain: Inspect and clean these components to prevent clogs and ensure efficient cooling.
- Blower Motor and Wheel: Regularly inspect and lubricate the blower motor and wheel to maintain optimal performance.
FF1E, FFMA, FMA
The following components require regular care and maintenance:
- Air Filter: Clean or replace the air filter regularly to maintain good indoor air quality.
- Cooling Coil, Drain Pan, and Condensate Drain: Inspect and clean these components to prevent clogs and ensure efficient cooling.
- Blower Motor and Wheel: Regularly inspect and lubricate the blower motor and wheel to maintain optimal performance.
Thermostatic Expansion Valves (TXV)
- The fan coil units are equipped with thermostatic expansion valves (TXV) to control the flow of refrigerant. The manual provides information on troubleshooting and maintaining the TXV.
Problems Affecting TXV
- The manual addresses common problems that can affect the performance of the TXV, such as clogs or leaks. It guides how to identify and resolve these issues.
Aluminum Coil Unit TXV’s
- If the fan coil unit has an aluminum coil, specific instructions are provided for maintaining and troubleshooting the TXV associated with it.
Piston Body Cleaning and Replacement
- The manual provides instructions on how to clean or replace the piston body, which is an important component of the refrigerant flow-control system.
Liquid Tube Strainer
- The liquid tube strainer helps filter out debris that may be present in the refrigerant.
- The manual guides cleaning and maintaining the liquid tube strainer.
Aluminum Coil Repair
- If the aluminum coil of the fan coil unit requires repair, the manual provides instructions on how to address common issues and perform necessary repairs.
Pre-Installation
- Before installing the fan coil unit, it is important to follow the pre-installation guidelines provided in the manual.
- These guidelines ensure a proper and safe installation process.
FAQ
Q: How often should I clean or replace the air filter?
- A: The air filter should be cleaned or replaced every 1-3 months, depending on the level of dust and pollutants in the environment.
Q: What should I do if the fan motor is not working?
- A: If the fan motor is not working, first check for any loose connections or tripped breakers.
- If the issue persists, consult the troubleshooting section of the manual or contact a professional technician for assistance.
Q: How often should I inspect and clean the cooling coil and drain pan?
- A: It is recommended to inspect and clean the cooling coil and drain pan at least once a year or as needed.
- Regular maintenance helps prevent clogs and ensures efficient cooling.
Q: Can I replace the relays myself?
- A: If you have experience and knowledge in electrical systems, you may be able to replace relays yourself.
- However, it is recommended to consult the manual and follow all safety precautions.
- If you are unsure, it is best to contact a professional technician.
SAFETY CONSIDERATIONS
-
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions that may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70. -
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
-
Recognize safety information. This is the safety alert symbol. When you see this symbol on the unit and in instruction manuals, be alert to the potential for personal injury.
-
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death.
-
WARNING signifies hazards that could result in personal injury or death.
-
CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage.
-
NOTE is used to highlight suggestions that will result in enhanced installation, reliability, or operation.
WARNING
UNIT OPERATION AND SAFETY HAZARD
- Failure to follow this warning could result in personal injury or death. Puron® (R-410A) systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410 equipment.
Ensure service equipment is rated for R-410.
PERSONAL INJURY AND PROPERTY DAMAGE HAZARD
- Failure to follow this warning could result in property damage, personal injury, or death.
- For continued performance, reliability, and safety, the only approved accessories and replacement parts are those specified by the equipment manufacturer. The use of non-manufacturer-approved parts and accessories could invalidate the equipment’s limited warranty and result in fire risk, equipment malfunction, and failure. Please review the manufacturer’s instructions and replacement part catalogs available from your equipment supplier.
INTRODUCTION
- The “F” and “PF” series fan coil units are designed for flexibility in a variety of applications that meet upflow, horizontal, or downflow requirements. Units are available in 1-1/2 through 5-ton nominal cooling capacities.
- Factory-authorized, field-installed electric heater packages are available in 3 through 30 kilowatts.
- FMA4X and FMA4P Fan Coils are designed with application flexibility in mind and are suitable for closet and flush mount installations. Units are available with field-installed electric heat with circuit breaker. Units are used indoors as the fan coil for split-system heat pumps or air conditioners. The FMA4P uses a refrigerant piston metering device and a 3-speed PSC Motor. FMA4X uses a TXV and a 5-speed multi-tap ECM Motor for efficiency. Units are available in 18,000 through 36,000 Btuh nominal cooling capacities.
- NOTE: Nuisance sweating may occur if the unit is installed in a humid location with low airflow.
- Units are designed for upflow applications only. Local codes may linit this free-air-return type unit to installation in single-level applications.
ELECTRICAL OPERATION HAZARD
- Failure to follow this warning could result in personal injury or death. Before installing or servicing the unit, always turn off all power to the unit.
- There may be more than one disconnect switch.
- Turn off the accessory heater power if applicable. Lock out and tag the switch with a suitable warning label.
Fan Coil Description and Troubleshooting FY5, FH4, PF4 (even sizes) and FF1E (even sizes), Fan Motor
- The motor is a two or three-speed direct drive. High-speed lead is black, low-speed lead is red, and common lead is yellow. Be sure the proper blower speed has been selected.
- The motor is turned on through two different routes. The first occurs when the thermostat calls for the fan in cooling, heat pump, or fan-only mode. A 24VAC signal is sent to the relay, causing the relay to close its normally open contacts, turning the fan on.
- The second occurs when there is a call for electric heat. A 24VAC signal is sent to the heater sequencer/relay, causing it to close, directing 230V through the normally closed contact of the fan relay, turning the fan on. The fan remains on until the sequencer/relay opens.
- If the motor does run, test the motor for an open winding or a winding shorted to the motor case. If either is present, replace the motor.
Electric Heater Service
- Service can be completed with a heater in place. Shut off power before servicing.
Limit Switch
- Refer to the (Electric Heater Function and Troubleshooting on p23) section of this manual.
Sequencer
- Refer to the (Electric Heater Function and Troubleshooting on p23) section of this manual.
Transformer
- A 40-VA transformer supplies 24V power for the control circuit. Check for 208/230V on the primary side of the transformer. If present, check for 24V on the secondary side.
- NOTE: The Transformer is fused. Do not short circuit.
Fan Relay
- The relay coil is 24V. Check for proper control voltage. Replace the relay if faulty.
Cleaning or Replacing Refrigerant Flow-Control Device
- Refer to Fig. 26 and instructions given in (Piston Body Cleaning and Replacement on 27).
- The refrigerant flow-control device is protected by a wire mesh strainer. It is located inside the 3/8-in. liquid tube at the field braze joint next to the flow-control device. Access to the strainer is through the field braze joint.
Sequence of Operation
Condensing Unit
- COOLING—When the thermostat calls for cooling, the circuit between R and G is complete and single-pole single-throw relay FR is energized. The normally open contacts close causing the blower to operate.
- The circuit between R and Y is also complete. This completed circuit causes the contactor in the outdoor unit to close which starts the compressor and outdoor fan.
- HEATING—When the thermostat calls for heating and the FAN switch is set on AUTO, the circuit between R and W is complete. The heater sequence SEQ is energized which closes the contacts of the relay. There will be a time delay.
- This completed circuit energizes all heating elements HTR and blower motor.
Heat Pump
- COOLING—On a call for cooling, the thermostat makes circuits R-O, R-Y, and R-G. Circuit R-O energizes the reversing valve, switching it to the cooling position. Circuit R-Y energizes the contactor starting the outdoor fan motor and compressor.
- Circuit R-G energizes the indoor unit blower relay starting the indoor blower motor.
- When the thermostat is satisfied, its contacts open de-energizing the contact reversing valve and blower relay. This stops the compressor and fan motors.
- HEATING—On a call for heating, the thermostat makes circuits R-Y and R-G. Circuit R-Y energizes the contactor starting the outdoor fan motor and compressor. Circuit R-G energizes the indoor blower relay starting the blower motor.
- Should the temperature continue to fall, an R-W circuit is made through the second-stage room thermostat bulb. Circuit R-W energizes a sequencer bringing on supplemental electric heat.
- When the thermostat is satisfied, its contacts open de-energizing the contactor and sequencer. All heaters and motors should stop.
CES013003-00, 01 (HK61EA002, HK61EA006) Control Boards
- This section of the service manual describes the CESO130003-00 and -01 PCB by examining the functional operation of the PCB components.
Printed Circuit Board (PCB) Component
Layout of the actual PCB is depicted in Fig. 1 and Fig. 2.
- The low-voltage stripped leads are used to connect the 24V side of the transformer to the indoor thermostat and outdoor section.
- A 5A fuse is used to protect the low-voltage transformer secondary.
- The fan relay is controlled by the thermostat and turns the fan on and off.
- A plug is used as the connection for PCB power and electric heaters. Note the PINs on the plug.
- A time-delay relay circuit keeps the fan motor running for approximately 90 seconds after G is de-energized. The time delay can be defeated by cutting jumper JW1 on the CES0130003-01, HK61EA002, and HK61EA006.
Unit Functions
Transformer
- Proper Wiring of Transformer Primary or High Side Yellow wire from Molex plug is wired to C terminal on transformer and black wire from PCB relay (normally-open) terminal is wired to 208V or 230V terminal on transformer. Units are factory wired at 230V terminal.
- Proper Wiring of Transformer Secondary or 24V Side Red wire of the transformer is wired to the terminal on the PCB and the brown wire of the transformer is wired to the C terminal on the PCB.
NOTE: The terminal on the PCB is used to protect the transformer. The terminal is connected through the fuse to the R terminal on the PCB.
Indoor Fan
- Wiring
- The indoor fan motor yellow lead is wired to the C terminal on the transformer.
- The red, blue, or black speed lead is wired to the SPT terminal on the fan relay part of the PCB. Units are factory-wired on medium speed (blue lead connected).
- NOTE: Unused fan speed leads must be capped or taped off to prevent direct short to the cabinet surface.
- Functional Control
- a. Thermostat and Relay Control
- When the thermostat calls for the fan in cooling, heat pump, heating, or fan-only mode, a 24VAC signal is sent to the relay. This causes the relay to close its normally open contacts, turning on the fan.
- When the thermostat no longer calls for the fan, the signal sent to the relay is turned off and the relay opens causing the fan to turn off after a 90-second fan-off delay.
- b. Sequencer/Electric Heat Relay Interlock
- The fan will also operate whenever there is a call for electric heat, even if the fan relay is not energized. This happens because the fan is interlocked with the first stage of electric heat through the normally closed contact of the fan relay.
NOTE: The fan interlock is only connected to first-stage electric heat (W2). W3 and E do not contain an interlock with a fan. See outdoor thermostat installation instructions when electric heat staging is desired.
Electric Heat
When the thermostat calls for electric heat, a 24VAC signal is sent to the sequencer/heat relay through W2, causing the first stage to turn on. W3 and E also receive signals if wired in with W2. If W3 and E are not wired to W2, the sequencers/heat relays can be controlled individually to stage additional electric heat. The sequence control is described in the following section:
- W2
- When the thermostat sends a signal to W2, a 24VAC signal is applied across sequencer/relay No. 1, causing it to close. When sequencer/relay No. 1 closes, the first stage of electric heat is energized. In straight electric heat, the fan is also energized through the normally closed contacts of the fan relay. In cooling, heat pump, or manual fan mode, the fan will already be running since the fan relay would have been energized. When the thermostat stops calling for electric heat, the 24VAC signal to sequencer/relay No. 1 turns off and Bsequencer opens after a delay of 60 to 90 seconds. Heaters equipped with relays will be de-energized immediately. When the sequencer/relay opens, the first stage of heat turns off along with a fan, providing the thermostat is not calling for the fan.
- W3
- When a signal is sent to W3, a 24VAC signal to sequencer/relay No. 2 causes it to close, with the second stage of electric heat turning on. The 24VAC signal applied to sequencer/relay No. 1 causes the fan to operate. Timing is such that sequencer/relay No. 1 will turn on before sequencer/relay No. 2. When the signal to W3 is turned off, sequencer/relay No. 2 opens. If W2 is also satisfied, the first stage of electric heat and fan will also turn off, providing the thermostat is not calling for the fan.
- E
- When the thermostat sends a signal to E, a 24VAC signal is sent to sequencer/relay No. 3. The 24VAC signal applied to sequencer/relay No. 3 turns on the third stage of electric heat. The 24VAC signal applied to sequencer/relay No. 1 turns on the first stage of electric heat and fan. When the thermostat stops calling for electric heat, the signal to sequencers/relays 1, 2, and 3 are turned off, and sequencers/relays open. This causes electric heat to turn off with the fan, providing the thermostat is not calling for the fan.
- NOTE: Electric heaters are factory-wired with all stages tied together. If independent staging is desired, consult outdoor thermostat installation instructions, or corporate thermostat instructions.
Troubleshooting the Printed Circuit Board (CES013000-00, 01 / HK61EA002 / HK61EA006)
- Use wiring schematics shown in Fig. 1, and Fig. 2 as a guide in troubleshooting PCB unless otherwise noted.
- If the Fan Will Not Turn On from the Thermostat
- IF THERE IS NO HIGH VOLTAGE TO TRANSFORMER:
- Check the plug/receptacle connection. This supplies power from heaters to the PCB Fan Relay. Be sure the plug is connected properly.
- Check sequencer/relay No. 1 and plug wiring. Yellow wire should be connected to Pin No. 9 of the plug and to the limit switch. The black wire should be connected to Pin No. 7 of the plug and to sequencer/relay No. 1.
- Check field power leads L1 and L2. If these are not receiving power, the system cannot function.
- IF TRANSFORMER HAS HIGH VOLTAGE APPLIED TO IT:
- Check low-voltage transformer leads R (red) and C (brown). Be sure they are wired to the correct locations.
- Check the output voltage of the transformer secondary side R (red) and C (brown). Be sure the transformer output is between 18VAC and 30VAC. If the transformer output is incorrect and the transformer is receiving the correct input voltage (208V or 230V), then the transformer needs to be replaced with the recommended transformer. If no problem exists with the transformer secondary, proceed to items 3 and 4.
- Check the low-voltage fuse shown in Fig. 1 or Fig. 2. If a fuse is blown, replace it with an identical 5A fuse. The transformer cannot supply power to the board with the fuse blown or loose. If a fuse blows when a unit has power applied to it, the system most likely has one of the following problems:
- Check all 24V wiring for an electrical short.
- The maximum load on transformer is 40VA. If the load on a transformer is excessive, the low-voltage 5A fuse will blow to protect the transformer. If the load exceeds the VA rating of the transformer, a larger VA-rated transformer needs to be installed. Check sequencers/relays for excessive current draw.
- Check the wiring of heaters. If a heater is miswired, a fuse may blow. If a heater is miswired, correct the miswiring by comparing it to the heater wiring label.
- Check connections on the primary side of the transformer. If they are not connected properly, the transformer secondary cannot supply the 24V signal to energize the fan relay. If a transformer is receiving the correct primary voltage but is not putting out the correct secondary voltage, the transformer needs to be replaced.
- If the Electric Heat Stages do not Turn On the Fan Will Turn On
IF THERE IS NO HIGH VOLTAGE TO TRANSFORMER:
- Check the plug connection between the heaters and the board. This supplies power to the transformer and fan. Be sure the plug is connected properly.
- Check sequencer/relay No. 1 and plug wiring. The yellow wire should be connected to Pin No. 9 of the plug and the limit switch. The black wire should be connected to Pin No. 7 of the plug and to sequencer/relay No. 1.
- Check incoming high-voltage power leads. If these are not receiving power, the system cannot function.
IF TRANSFORMER HAS VOLTAGE APPLIED TO IT:
- Check low-voltage transformer leads R (red) and C (brown). Make sure they are wired to the correct location. The unit will not function without proper connections.
- Check the output voltage of the transformer secondary side R (red) and C (brown). If the transformer output is low (less than 18VAC), refer to items 3 and 4 of the previous “IF
TRANSFORMER HAS HIGH VOLTAGE APPLIED TO IT” section.
IF TRACES ARE OVERHEATED ON THE BACK OF THE PCB:
- Usually, whenever a trace is blown on a PCB, it means either there has been a high-voltage short or high voltage has been applied to a low-voltage circuit. This can be prevented by making sure the PCB is wired correctly before the PCB has power applied to it.
If the Transformer Fuse Keeps Blowing:
- When a low-voltage fuse blows, it means the transformer would have blown if a fuse had not been in the circuit to protect it. The fuse usually blows when there is a high current draw on the transformer, high voltage applied to a low-voltage circuit, or a direct secondary short.
- When there is a high current draw on the transformer, it is most likely because the transformer has been shorted or the system is trying to draw more VA than the transformer rating allows. When a fuse blows because of high voltage, the system has mixed high- and low-voltage signals.
- Check the wiring of sequencers/relays as shown in Fig. 1 and Fig. 2. Be sure the transformer is not shorting out because thermostat wires are miswired.
- Check the wiring of relays as shown in Fig. 1 and Fig. 2. Be sure low-voltage and high-voltage wiring is correct.
- Check the VA draw on the transformer. If the VA draw is more than the VA rating of the transformer, the fuse will blow. If this is the case, replace the transformer with one that has a higher VA rating and meets system specifications.
If Fan Runs Continuously:
- If the PCB has no low-voltage power, check the blue and black fan leads. These may be switched at sequencer/relay.
- If the PCB has low-voltage power, check the fan relay to see if it is opening and closing. It may be stuck in the normally closed position due to debris in the relay.
Transformer Failure:
- Check 208V and 230V transformer connections. They may be miswired.
FB4C, FJ4, FX4D, PF4, FF1E, and FZ (odd sizes)
Fan Motor
- The multi-speed ECM motor used with this product contains two parts: the control module and the motor winding section. Do not assume the motor or module is defective if it does not start. Go through the steps described below before replacing the control module or the entire motor. The control module is available as a replacement part.
- It is normal for the motor to rock back and forth on startup. Do not replace the motor if this is the only problem identified.
If the motor is not running:
- Check for proper high voltage and ground at the L, G, and N connections at the motor. Correct any voltage issue before proceeding to the next step.
- The motor is communicated through 24VAC signals to the 1, 2, 3, 4, 5, and C (common) terminals. Not all taps are programmed, if low voltage is applied to a non-programmed terminal, the motor will not operate, which is normal.
- Verify the part number of the motor matches the correct replacement motor part number for the unit model number.
- Initiate a demand from the thermostat and check the voltage between C (common) and terminal 1- 5. If voltage is present and the motor isn’t operating, then the motor/control module is failed.
- Before installing the replacement control module, the motor section condition needs to be verified.
- Check to see if the blower wheel spins freely.
- To check for short to ground, use an ohmmeter to measure the resistance from any one of the motor connector pins to the aluminum end plate of the motor.
- This resistance should be greater than 100,000 ohms.
- Check the motor phase-to-phase resistance between each of the leads in the three-pin motor connector. The lead-to-lead resistance across any two leads should be less than 20 ohms. Each lead-to-lead resistance should be the same within ± 10 percent.
- If any motor fails any of the three tests, do not install a new control module. The new control can fail if placed on a defective motor.
- The prior fan coil models with multi-speed ECM blower motors used a printed circuit board, similar to the PSC models. The current fan coils do not use the printed circuit board and rely on the motor control programming to provide the off-delay timing.
- Another design aspect of the control board was to provide a resistor in the “G” circuit in case a power-stealing thermostat was used. This resistor is not part of the wiring harness, as shown on the wiring diagram. The resistor is a 2W, 1500-ohm resistor.
- If the resistor has failed to open, a likely cause is due to the power-stealing thermostat. Connecting C (common) may resolve the issue. Having an open resistor should not affect the operation of the motor.
Fan Speed Selection
- The fan speed selection is done at the motor connector. Units with or without electric heaters require a minimum CFM. Refer to the unit wiring label to ensure that the fan speed selected is not lower than the minimum fan speed indicated.
- To change motor speeds disconnect the BLUE fan lead from motor connector terminal No. 2 (factory default position) and move to desired speed-tap; 1, 2, 3, or 5.
- Speed-taps 1, 2, and 3 have a 90-second blower-off time delay pre-programmed into the motor. Speed-tap 4 is used for electric heat only (with 0 second blower time delay) and the WHITE wire should remain on tap 4.
- Speed-tap 5 is used for high static applications but has a 0-second blower time delay pre-programmed into the motor. See
- Airflow Performance tables for actual CFM. Also, see Fig. 4 for the motor speed selection location.
- NOTE: In low static applications, a lower motor speed tap should be used to reduce the possibility of water being blown off the coil.
Constant Air Flow
- Unlike fan coils using induction motors where static pressure affects airflow, these fan coils are constant airflow units. The blower delivers the requested airflow regardless of static pressure. Consult fan coil Product Data for static pressure limits. The ECM2.3/5.0 is pre-programmed and contains airflow tables for all modes of operation. Blower characteristics (requested airflow, torque, and speed) are known from laboratory testing
- If any two characteristics are known, the third is defined.
- The requested airflow is known from the Easy Select board configuration and thermostat signals. Torque is known because it is directly related to stator current, which is measured by motor control. Speed is measured by counting back EMF pulses from stator windings. This information is entered into an expression that calculates torque from speed and airflow numbers. If the calculation does not match stored blower characteristics, torque is adjusted until an agreement is reached. This calculation and adjustment is performed every 0.8 seconds while the motor is in operation.
- There is no direct measure of static pressure, but the unit does react to a change in static to maintain constant airflow. A change in pressure will result in a change in stator speed and torque. The motor will begin to adjust on the next sampling, calculate the new desired speed and torque, and adjust as necessary.
Integrated Controls and Motor ECM2.3/5.0
- An ECM2.3/5.0 is fed high-voltage AC power through the 5-pin connector (Fig. 6 or Fig. 5). The AC power is then internally rectified to DC by a diode module. After rectification, the DC signal is electronically communicated and fed in sequential order to three stator windings. The frequency of these commutation pulses determines motor speed. The rotor is permanently magnetized.
- An ECM2.3/5.0 is powered with high voltage at all times. The motor will not run with high voltage alone. Low voltage must be applied to the control plug to run the motor.
ECM2.3/5.0 Control Power
- The ECM2.3/5.0 control power is supplied from the R circuit through printed circuit runs to motor control Connector-Pin 8, through the motor control harness to the motor. The C side of the low-voltage control power circuit is connected by a printed circuit that runs to motor Connector pins 9, 10, and 11, then through the motor control harness to the motor.
Low-Voltage Circuit Fusing and Reference
- The low-voltage circuit is fused by a board-mounted 5A automotive-type fuse placed in series with transformer SEC2 and R circuit.
- The C circuit of the transformer is referenced to the chassis ground through a printed circuit run at SEC1 connected to metal standoff marked.
- NOTE: The PCB must be mounted with two screws and motor ground lead secured to the blower housing or erratic motor operation can result.
- Transformer, Motor, and Electric Heater Power Connection
- Transformer high voltage supplied from electric heater package or high voltage leads through 12-pin heater connector plug/recp2. The ECM2.3/5.0 power connections are made at the transformer’s primary terminals.
- The transformer secondary connections are made at SEC1 and SEC2 connectors.
PCB Layout and Description (FV4)
- NOTE: The layout of the actual PCB is depicted in Fig. 7.
- The Easy Select Board is the interface between the ECM motor and other system components. The board offers choices of electric heater size, outdoor unit size and type, comfort or efficiency settings, on and off delay profiles, and continuous fan speed.
- The installer should select the correct size of components that are being installed in each installation.
- If no selections are made, the factory default settings are for the largest heater, largest outdoor unit, AC system type, nominal airflow adjustment, and 0/90 time delay.
- NOTE: The outdoor unit model should have an AHRI rating with the variable speed fan coil. Some outdoor unit models will not work properly with this fan coil.
- Power for the system is supplied from a 230VAC, 60-Hz line. Class 2 voltage (24VAC nom.), used for thermostat connections, is derived from a transformer located near PCB.
- The 24VAC secondary circuit includes a 5A automotive-type fuse in the SEC2 circuit.
- Connection to the heater panel is made through a 12-pin connector PL-1.
- Connections to the thermostat are made at screw terminals. Twenty-one pin terminals comprise field select taps for the motor.
- Fuse Data: 5A automotive-type ATC/ATO (tan)
- 32V
- 200 percent current opening time of five seconds maximum
Electrical Connections
- Twenty-one 0.110-in pin terminals are used to provide programming selections for operating modes of ECM2.3/5.0. The selection modes are listed below.
- For additional information, refer to the Easy Select Configuration Taps section.
- AUX Heat Range—(Violet Wire)
- AC/HP Size—(Blue Wire) Type—(Orange Wire)
- AC/HP CFM Adjust—(Black Wire)
- AC/HP Time Delay—(Grey Wire)
- Continuous Fan—(Yellow Wire)
- Sequence of Operation (FV4)
Continuous Fan Mode
- The thermostat closes circuit R to G. The unit delivers the airflow selected for fan-only operation.
Cooling Mode—Single-Speed or Two-Speed High
- The thermostat closes circuits R to G, R to Y/Y2, and R to O (heat pump only). A circuit R to Y1 is required for two-speed high operation.
- Airflow delivered the airflow selected by AC/HP SIZE selection and CFM ADJUST selection.
Cooling Mode—Two-Speed Low
- The thermostat closes R to G and R to Y1 and R to O (heat pump only). The unit delivers two-speed low airflow for AC/HP SIZE and CFM ADJUST selected.
- Cooling + Dehumidify Mode (Thermostat or Comfort Zone II-B and Single-Speed Outdoor Unit Installed) J1 jumper must be pulled from Easy Select Board. Control closes R to G, R to Y/Y2, and R to O (heat pump only) and opens R to DH.
- Dehumidification is active when 24VAC is removed from the DH terminal.
- The unit delivers 20 percent less airflow.
SuperDehumidify Mode
(Thermidisat or Comfort Zone II-B indoor control, Single-Speed Outdoor Unit)
- This mode is only activated by the indoor control when COOL to DEHUMIDIFY and SUPERDEHUMIDIFY are configured at the control and there is a call for dehumidification without a call for cooling.
- The control closes R to Y/Y2, R to O (heat pump only), and opens R to DH and R to G. This signals the fan coil to run at minimum airflow for maximum humidity removal.
- The control will cycle the equipment 10 minutes on and 10 minutes off until satisfied.
Heat Pump Heating Mode — Single-Speed or Two-Speed High
- The thermostat closes R to Y/Y2 and R to G. A circuit R to Y1 is required for two-speed high operation. The unit delivers airflow selected by AC/HP SIZE selection and CFM ADJUST selection.
- The selected delay profile is active in this mode.
Heat Pump Heating Mode — 2-Speed Low
- The thermostat closes R to G and R to Y1. The unit delivers two-speed low airflow for AC/HP SIZE and CFM ADJUST selected. The selected delay profile is active in this mode.
- Non-Staged Auxiliary with Heat Pump Heating Mode Thermostat should already have closed R to G, R to Y2 for heat pump heating operation.
- With the J2 jumper in place, energizing either W1 or W2 will produce the W2 airflow. This is the greater of heat pump heating and auxiliary heat airflow plus an additional 15 percent. The elected delay profile is not active in this mode.
Staged Auxiliary Heat with Heat Pump Heating Mode
- The auxiliary heat can be staged by removing the J2 jumper that ties the W1 and W2 terminals together.
- Staging can be done by using outdoor Bthermostats or by using the Intelligent Heat Staging option where the indoor control can be configured for three-stage electric heat.
- The unit will automatically adjust airflow when the different stages of heat are energized. The airflow delivered will depend on the heat pump size selected and the electric heat size selected.
- The greater of the two airflows will be delivered. The selected delay profile is not active in this mode.
Electric Heat without Heat Pump
- The thermostat closes R to W and the thermostat should be set up to energize G with W. This is due to the Super Comfort Heat programming in the motor.
- Energizing W without G will result in 25% lower airflow delivery.
- The selected delay profile is not active in this mode.
Super Comfort Heat Mode
- This is a special heating mode only available on FV4 fan coils combined with a Thermidistat Control or Comfort Zone II-B. When this option is selected, the indoor control will monitor the outdoor temperature. The control will drop the G signal to the fan coil when the outdoor temperature is between 10° and 40° F. This triggers the motor to slow to approximately 213 CFM per ton. The heaters will stage as needed during this mode and the motor will adjust airflow as required. Below 10° F, the W1 control output will automatically energize on a call for heat. The ECM2.3/5.0 power connections are made at the transformer’s primary terminals. The transformer secondary connections are made at SEC1 and SEC2 connectors.
Easy Select Configuration Taps
- The Easy Select taps are used by the installer to configure the system. The ECM2.3/5.0 uses selected taps to modify its operation to a pre-programmed table of airflows. Airflows are based on system size and mode of operation and those airflows are modified in response to other inputs such as the need for de-humidification (Fig. 7).
- The FV4 Fan Coils must be configured to operate properly with the system components with which it is installed. To successfully configure a basic system (see information printed on the circuit board located next to select pins), move the six select wires to pins that match the components used, along with homeowner preferences.
Auxiliary Heat Range
- The installer must select the auxiliary heat airflow approved for application with a kW-size heater installed. Each select pin is marked with a range of heaters for which airflow (also marked) is approved. For increased comfort select the narrowest kW range matching the heater size, for example, 0-10 for a 10-kW heater. This airflow must be greater than the minimum CFM for electric heater application with the size system installed for safe and continuous operation.
- Note that airflow marked is the airflow that will be supplied in emergency heat mode and heating mode on air conditioners when electric heat is the primary heating source. To ensure safe heater operation in heat-pump heating mode, when electric heaters are energized, the ECM2.3/5.0 will run the higher heat pump airflow and electric heater airflow. The factory default selection is the largest heater range approved (Fig. 7).
AC/HP Size
- The factory default setting for air conditioner or heat pump size is the largest unit meant for application with the model of the fan coil purchased.
- The installer needs to select the air conditioner or heat pump size to ensure that the airflow delivered falls within the proper range for the size of the unit installed in all operational modes (Fig. 7).
- Unpack the unit and move to the final location. Remove the carton taking care not to damage the unit. Inspect equipment for damage before installation. File a claim with the shipping company if the shipment is damaged or incomplete.
- Locate the unit rating plate which contains proper installation information.
- Check the rating plate to be sure the unit matches job specifications.
System Type
- The type of system must be selected.
- AC—air conditioner (approx. 350 CFM/ton)
- HP-COMFORT—provides lower airflow than air conditioner selection (approximately 315 CFM/ton) in heating mode. In cooling mode supplies 350 CFM/ton.
- HP-EFF—provides the same airflow for heat pump heating and cooling modes (approximately 350 CFM/ton).
- The factory setting is AC (Fig. 7).
AC/HP CFM Adjust
- Select low, nominal, or high airflow. The factory selection is NOM. The adjusted selections HI/LO will regulate airflow supplied for cooling and heat pump heating modes only, +15 percent and -10 percent respectively.
- The adjust selection options are provided to adjust airflow supplied to meet individual installation needs for such things as noise, comfort, and humidity removal (Fig. 7).
ON/OFF Delay
- NOTE: ON/OFF Delay is active only in cooling and heat pump-only heating modes. In auxiliary heat mode or emergency heat mode, the ON delay is 0 seconds and the OFF delay is fixed and cannot be overridden.
- Select the desired time delay profile. Four motor-operation delay profiles are provided to customize and enhance system operation (Fig. 7).
The selection options are:
- The standard 90-second OFF delay (factory setting 0/90).
- No delay option is used for servicing units or when a thermostat is utilized to perform delay functions (0/0).
- A 30–seconds ON / 90–second OFF delay profile is used when it is desirable to allow system coils time to heat up/cool down before airflow.
- This profile will minimize cold blows in heat pump operation and could enhance system efficiency (30/90).
- ENH, enhanced selection provides a 30–second ON / 150–seconds at 70 percent airflow and no OFF delay.
Continuous Fan
Select the desired continuous-fan profile LO, MED, or HI. Airflow is provided to customize and enhance the continuous fan functions (Fig. 7).
The possible selections are:
- LO – provides 50 percent of Y/Y2 Cool airflow.
- MED – provides 65 percent of Y/Y2 Cool airflow (71 percent on the 006 model).
- HI – provides 100 percent of Y/Y2 Cool airflow. The factory setting is LO.
- NOTE: If applied to a two-speed unit, do not select continuous fan as HI since low-speed cooling will also run at HIGH airflow and insufficient dehumidification may result.
Easy Select Board Jumpers
- J1 – This jumper must be pulled to activate dehumidification mode. The jumper connects R to DH. With the jumper in, the DH terminal is always energized. With the jumper pulled, the DH terminal is de-energized. A control such as the Thermidistat must be used to supply the 24V signal when there is no call for dehumidification and turn off the 24V when there is a call for dehumidification.
- J2 – This jumper activates heat staging. The jumper connects the W1 and W2 terminals. If either is energized, W2 airflow is delivered.
- With the jumper pulled, there are separate airflows for W1 and W2.
Airflow Delivery
- These units deliver airflow depending on the system size selections and operating mode. The thermostat energizes a combination of terminals on the Easy Select Board which tells the motor what CFM to deliver. The following are typical operating modes and the terminals that should be energized on the Easy Select Board.
- NOTE: The DH terminal on the Easy Select Board is for dehumidification. It is de-energized on a call for dehumidification.
Variable Speed Motor Logic Sequence:
- The ECM motors in these fan coils are programmed to deliver a variety of airflows. The motor goes through:
- COOLING – The nominal cooling airflow for these fan coils is 350 CFM per ton. Selecting the HI adjust tap increases the airflow to 400 CFM per ton. The LO tap decreases airflow to 315 CFM per ton. The low adjustment is only active during normal cooling mode. Removing the signal from the DH terminal reduces the airflow to 80 percent of the cooling airflow. Removing the G signal for Superdehumidify reduces the airflow to 50 percent of cooling.
- HEATING – The base heat pump only heating airflow is determined by the SYSTEM TYPE selection on the Easy Select Board. If HP-EFFICIENCY is selected, the airflow is the same as Cooling. IF HP-COMFORT is selected, the airflow is 315 CFM per ton.
- The airflow will adjust if necessary when auxiliary heating is required. When both the Y/Y2 and W1 or W2 terminals are energized, the motor will run the higher of the heat pump or electric heat airflows. During Super Comfort Heat mode, the indoor control removes the G signal from the board. This slows the motor to 75 percent of the heat pump airflow. If the CFM adjust is set to LO, it will deliver 67.5 percent of heat pump airflow during Super Comfort Heat mode.
Troubleshooting
If Traces Are Overheated on the Back of PCB:
- Usually, whenever there is a trace broken on the PCB, it means either there has been a high-voltage short or high voltage has been applied to a low-voltage circuit.
- This can be prevented by making sure the PCB is wired correctly before the fan coil has power applied to it.
If the PCB Fuse Keeps Blowing:
- When the low-voltage fuse blows, it means the transformer would have blown if the fuse had not been in a circuit to protect it.
- The fuse usually blows when there is a high current drawn on a transformer, high voltage applied to a low-voltage circuit, or a direct secondary short.
- When there is a high current drawn on a transformer, it is most likely because the transformer has been shorted or the system is trying to draw more VAC than the transformer rating allows.
- When the fuse blows because of high voltage, the system has mixed high and low-voltage signals.
- Check the transformer and thermostat wiring (Fig. 7). Be sure the transformer is not shorting out because the thermostat wires are miswired.
- Check the wiring of relays (Fig. 7). Be sure low-voltage and high-voltage wiring are connected to proper sequencers.
- Check the VA draw on the transformer. If the VA draw is more than the VA rating of the transformer, the fuse will blow. If this is the case, replace the transformer with one that has a higher VA rating.
Troubleshooting Common Problems Airflow Too Low:
- Y1 instead of Y/Y2 on single-speed air conditioner or heat pump application. Y1 input is only for two-speed applications. Using this terminal will deliver about 60 percent of full cooling airflow.
- Wrong Easy Select Board selection. Selecting an outdoor unit or electric heater smaller than installed will result in low airflow for the application.
- G is not energized with a call for cooling or heating. This triggers Super
- Comfort Heat or SuperDehumidify mode which delivers 50 percent of cooling airflow.
- J1 jumper pulled with no thermostat or de-humidist installed. The J1 jumper ties the DH terminal to R and is installed at the factory.
- When pulled, a Thermidistat or dehumidistat supplies a 24V signal to DH when there is no call for dehumidification (reverse logic).
- When there is no signal on DH, the motor reduces airflow to 80 percent for better dehumidification.
Airflow Too High:
- Wrong Easy Select Board selection. The fan coil is factory set for the largest outdoor unit and largest electric heater. Select sizes that are installed.
- Continuous fan set too high for two-speed applications. Set to MED or LO.
Motor Will Not Stop:
- Allow time for off delay to time out. In units built before serial number 0101A, any W call will have a two-minute off delay independent of delay selection.
- This is programmed into the motor and cannot be overridden.
- In units built after 0101A, the off delay on any W call is one minute and cannot be overridden.
- Some power-stealing thermostats could bleed enough voltage to cause the motor to run slowly when there is no heating or cooling call.
- Disconnect the thermostat wires and wait two minutes to see if a motor stops. If it stops, replace the thermostat, or install a resistor per thermostat installation instructions.
Motor Will Not Start:
- See the following section, “Troubleshooting ECM2.3/5.0 Motor and Controls.”
Troubleshooting ECM2.3/5.0 Motor and Controls
CAUTION ELECTRICAL OPERATIONS HAZARD
- Failure to follow this caution may result in equipment damage or improper operation.
- High voltage is always present in the motor. Disconnect power to the unit before removing or replacing connectors or servicing the motor. Wait at least five minutes after disconnecting the power before opening the motor.
- The ECM/ICM motor used with this product contains two parts: the control module and the motor winding section. Do not assume the motor or module is defective if it does not start.
- Go through the steps described below before replacing the control module, Easy Select Board, or entire motor. The control module is available as a replacement part.
If Motor Turns Slowly:
- It is normal operation to run noticeably slower if the G terminal is not energized in cooling or heat pump heating modes.
- Attach blower access panel. The motor may appear to run slowly if the access panel is removed.
- If the Motor Does Not Run
Turn the power off, wait five minutes, and check the following:
- With power turned off, check the 5A fuse on the Easy Select Board.
- Check all plugs and receptacles for any deformation or corrosion that could cause bad connections. Be sure the plugs are fully seated.
- CAUTION ELECTRICAL OPERATION HAZARD
- Failure to follow this caution may result in equipment damage or improper operation.
- DO NOT remove or apply a 5-pin plug on a motor with power on. Arcing could occur, which can damage the control module
Turn the power back on and check the following:
- Check for 24VAC on SEC1 and SEC2. If no voltage is present, check the transformer.
- Verify that approximately 230VAC is present at the motor.
- Verify low voltage control signals to the motor according to the procedure below.
Use the following procedure to check low-voltage signals:
- The ECM motor in these fan coils receives low-voltage signals from the Easy Select Board through the wiring harness assembly. The combination of pins energized at the motor determines the speed the motor will run. The procedure below isolates the fan coil from all external devices such as a thermostat, condensing unit, humidifier, or electronic air cleaner. There is also a specific troubleshooting example to demonstrate the process. Table 7 provides information needed to verify that the correct voltages are present at the motor and the Easy Select Board.
THERMOSTAT:
- Remove all thermostat and accessory wires from the Easy Select Board.
- On Easy Select Board, jumper screw terminals (1 at a time): R-G, R-Y/Y2, R-Y1, R-W1, R-W2. If the motor runs in all cases, check thermostat outputs.
- Thermostat wires may be broken, or the thermostat may be miswired, configured incorrectly, or defective.
- If the motor does not run, or runs in some cases, but not others, continue this procedure to check the wiring harness and circuit board.
WIRING HARNESS:
- Remove the 16-pin plug from the motor.
- Check for appropriate voltages on the 16-pin connector with screw terminals jumpered (Table 2).
- If signals check correctly, and the motor does not run, inspect the wiring harness for loose pins or damaged plastic that could cause poor connections.
- If connections are good, either the control module or motor is defective.
- If proper signals are not present, check the circuit board using the procedure below:
PIN PLUG (PL-1) ON EASY SELECT BOARD:
- Completely disconnect the wire harness from the Easy Select Board.
- Jumper the screw terminals one at a time; R-G, R-Y/Y2, R-Y1, R-W1, R-W2 and check for appropriate voltages on the Easy Select Board pins. If proper signals are not present, replace the Easy Select Board. If proper signals are present at the pins and not at the 16-pin connector to the motor, the wiring harness is defective.
TROUBLESHOOTING EXAMPLE:
- The motor is not running on a call for heat pump heating after jumpering the Easy Select Board screw terminals as described in Thermostat section above.
- With all thermostat wires removed from Easy Select Board, place a jumper wire between R and Y/Y2 low-voltage screw terminals on the Easy Select Board.
- Check Table 4 for PIN on the 16-pin connector associated with the Y/Y2 signal. The correct pin is No. 14. The far-right column of the table shows that (-)12VDC should be present between Pin No. 14 and Pin No. 1 (common) on the 16-pin connector.
- Set meter to read DC voltage. Place meter leads between Pins No. 1 (common) and No. 14 and checks for (-)12VDC. If the signal is present, the problem is in the module or motor. If the signal is not present, the problem is either in the wiring harness or Easy Select Board.
- These steps can be repeated for other modes of operation.
To check the Easy Select Board:
- Leave jumper wire in place between R and Y/Y2.
- Check Table 4 under the “Volt Meter on Easy Select Board Plug” column and row for Pin No. 14 on the motor plug to see the PIN on the Easy Select Board that should have voltage. The correct pin is No.
- The column on the far right will show the voltage that should be present between Pin No. 2 and Pin No. 9 (common).
- Place meter leads between Pins No. 2 and No. 9 on the Easy Select Board and check for (-)12VDC.
- If voltage is present, the wiring harness is bad. If not, the Easy Select Board is bad.
Verify Motor Winding Section:
Before proceeding with module replacement, check the following to ensure the
motor winding section is functional. With the control module removed and
unplugged from the winding section:
- The resistance between any two motor leads should be similar.
- The resistance between any motor lead and the unpainted motor end plate should be greater than 100,000 ohms.
- If motor winding fails one of these tests, it is defective and must be replaced.
Accessories
- AUXILIARY TERMINALS—The AUX and HUM terminals on the Easy Select Board are tied directly to the G terminal, and provide a 24VAC signal whenever the G terminal is energized (Fig. 8). During In super dehumidify mode, the G signal is not present and the auxiliary terminals are not energized. If the installation includes the use of this operating mode, do not use these terminals to control accessories. See the Electronic Air Cleaner and Humidifier sections for further information.
- ELECTRONIC AIR CLEANER CONNECTIONS —The AUX1 and AUX2 terminals are not always energized during blower operation, as described above. When using an electronic air cleaner with the FV4 fan coil, use an Airflow Sensor. The airflow sensor turns on the electronic air cleaner when the fan coil blower is operating.
- HUMIDIFIER / HUMIDISTAT CONNECTIONS—Easy Select Board terminals HUM1 and HUM2 are provided for direct connection to the low-voltage control of a humidifier through a standard humidistat. These terminals are energized with 24VAC when a G thermostat signal is present. Alternately, the 24VAC signal may be sourced from the W and C terminal block connections when electric heaters are used as the primary heating sources. When using a Thermidistat™ Control, Zone Perfect Plus, or Comfort Zone II, the 24VAC signal may be sourced directly from the Thermidistat HUM terminal.
FV4 Dehumidify Mode
- NOTE: Humidistat must open on humidity rise.
- Latent capacities for systems using the FK4, FV4, and 40FK fan coils are better than average systems. If increased latent capacity is an application requirement, the field wiring terminal block provides connection terminals for the use of a standard humidistat.
- The FK4, FV4, and 40FK fan coils will detect the humidistat contacts opening on increasing humidity and reduce its airflow to approximately 80 percent of nominal cooling mode airflow. This reduction will increase the system’s latent capacity until the humidity falls to a level that causes the humidistat to close its contacts. When the contacts close, airflow will return to 100 percent of the selected cooling airflow. To activate this mode, remove jumper J1 and wire in a standard humidistat. Carefully consult product airflow data for cooling and dehumidification modes.
Table 4 – FV4 Motor Control Test Values (With 16-pin connector at motor unplugged)
FE4
- The model FE4A fan coil is designed to be installed with a communicating user interface. The FE4A fan coil will provide airflow at a rate commanded by the User Interface.
- The nominal airflow/ton rate is 350 CFM/ton. The User Interface will modify the commanded airflow under certain operating modes. Refer to the User Interface literature for further system control details.
- This fan coil will not respond to commands from a common thermostat except under certain emergencies explained in this document.
Electronically Commutated Motor ECM 3.0
- An ECM 3.0 is fed high-voltage AC power through the 5-pin connector.
- The AC power is then internally rectified to DC by a diode module.
- After rectification, the DC signal is electronically communicated and fed in sequential order to 3 stator windings.
- The frequency of these communication pulses determines motor speed. The rotor is permanently magnetized.
ECM 3.0 Control Power
- The ECM 3.0 control power is supplied from the R circuit through printed circuit runs to motor control connector Plug 1, Pin 1, and through the motor control harness to the motor.
- The C side of the low-voltage control power circuit is connected by a printed circuit that runs to motor connector Plug 1, Pin 2 then through the motor control harness to the motor.
- A digital signal is sent from Plug 1, Pins 3, and 4 to communicate with the motor including all airflow requirements.
Low-Voltage Circuit Fusing and Reference
- The low-voltage circuit is fused by a board-mounted 5A automotive-type fuse placed in series with transformer SEC2 and R circuit.
- The C circuit of the transformer is referenced to the chassis ground through a printed circuit run at SEC1 connected to the metal standoff.
- NOTE: The PCB must be mounted with two screws and motor ground lead secured to the blower housing or erratic motor operation can result.
- Transformer, Motor, and Electric Heater Power Connection
- Transformer high voltage supplied from electric heater package or high voltage leads through 12-pin heater connector plug/recp2.
- The ECM 3.0 power connections are made at the transformer’s primary terminals. The transformer secondary connections are made at SEC1 and SEC2 connectors.
Troubleshooting (FE4)
- NOTE: Always check high and low voltage supply to the fan coil components. Check the integrity of the plug receptacle connections and fan coil wiring harness before assuming a component failure.
LED Description
- LEDs built into the fan coil control provide the installer or service person information concerning the operation and/or fault condition of the fan coil control and ECM motor.
- This information is also available in the system
- User Interface in text with basic troubleshooting instructions. Careful use of the information displayed will reduce the need for extensive manual troubleshooting.
- The amber LED located at the bottom center of the control adjacent to the motor harness plug is the Motor Status LED, and it is labeled MOTOR.
- A second amber LED, located in the upper right center of control adjacent to System Communications connector (A, B, C, D) is the System Status LED, and it is labeled STATUS.
- The green LED labeled COMM is also located adjacent to the System Communications connector, below the STATUS LED, and is used as an indicator of system communications status. Status
- Codes will be displayed on the STATUS LED using the following protocol
- The number of short flashes indicates the first digit of the code.
- The number of long flashes indicates the second digit of the code.
- A short flash is 0.25 seconds on. A long flash is one second on.
- The time between flashes is 0.25 seconds.
- The time between the last short flash and the first long flash is 1 second.
- The LED will be off for 2.5 seconds before repeating the code.
Fan Coil Control Start-Up and System Communications
Troubleshooting
- On power up, the green COMM LED will be turned off until successful system communications are established (this should happen within 10 seconds).
- Once communications with the User Interface are successful, COMM LED will be lit and held on.
- At the same time, the amber STATUS LED will be lit and held continuously on until a request for operating mode is received.
- The STATUS LED will be on any time the fan coil is in idle mode.
- If, at any time, communications are not successful for a period exceeding two minutes, fan coil control will only allow emergency heating or cooling operation using a common thermostat, a non-communicating outdoor unit, and the R, C, Y, O, W outdoor unit terminal strip connections and will display Status Code 16, System Communication Fault, on amber STATUS LED.
- No further fan coil troubleshooting information will be available at User Interface until communications are re-established.
If COMM LED does not light within the proper time and the status code is not displayed:
- Check the system transformer’s high and low voltage to be sure the system is powered.
- Check the fuse on the fan coil control to be sure it is not blown. If the fuse is open, check the system wiring before replacing it to be sure a short does not cause a failure of the replacement fuse.
- If COMM LED does not light within the proper period and the status code is displayed:
- Check system wiring to be sure User Interface is powered and connections are made from A to A, B to B, etc. and wiring is not shorted.
- Mis-wiring or shorting of the ABCD communications wiring will not allow successful communications.
- NOTE: Shorting or Mis-wiring low voltage system wiring will not cause damage to the fan coil control or User Interface but may cause the low voltage fuse to open.
ECM Motor Troubleshooting
- The ECM motor used in this product consists of two parts: the control module and the motor winding section.
- Do not assume the motor or module is defective if it does not start. Use the designed-in LED information aids and follow the troubleshooting steps described below before replacing the motor control module or the entire motor.
- The motor control module is available as a replacement part.
Verify Motor Winding Section
- WARNING ELECTRICAL SHOCK HAZARD
- Failure to follow this warning could result in personal injury or death or possible equipment damage.
- After disconnecting power from the ECM motor, wait at least five minutes before removing the control section. Internal capacitors require time to discharge.
- Minor injuries from electrical shock may result from early contact with live metal parts.
Before proceeding to replace a motor control module:
- Check the motor winding section to be sure it is functional.
- Remove the motor control module section and unplug the winding plug.
- The motor shaft should turn freely, resistance between any two motor leads should be similar, and resistance between any motor lead and unpainted motor end should exceed 100,000 ohms.
- Failing any of these tests, the entire ECM motor must be replaced.
- Passing all of the tests, the motor control module alone can be replaced.
Motor Turns Slowly
- Low static pressure loading of the blower while the access panel is removed will cause the blower to run slowly. Particularly at low airflow requests. This is normal, do not assume a fault exists.
- Recheck airflow and system static pressure using User Interface service screens with access panels in place.
- NOTE: Blower motor faults will not cause a lockout of the blower operation. Fan coil control will attempt to run the blower motor as long as the User Interface maintains a demand for airflow.
- Fan coil control will not operate electric heaters while a fault condition exists. The fan coil control communicates with the motor at least once every five seconds, even when the motor is idle.
- If, during operation, the fan coil control does not communicate with the motor for more than 25 seconds, the motor will shut itself down and wait for communications to be re-established.
Using Motor LED in Troubleshooting
- The MOTOR LED is connected to the blower motor communication line and works with the fan coil control microprocessor and the STATUS LED to provide fan coil operation and troubleshooting information.
- When the motor is commanded to operate, the MOTOR LED will be turned on and will flash each time instructions are sent to the motor.
- When the motor is commanded to stop, the MOTOR LED will be turned off.
- If the MOTOR LED is lit, flashing and the motor is running, or if the MOTOR LED is off and the motor is stopped, the operation is normal and no motor fault exists. If the MOTOR LED is lit, flashing and the motor does not run, or if the MOTOR LED is off and the motor is running, check the STATUS LED for the Status Code. Refer to the troubleshooting instructions for the indicated Status Code in Section E, Fan Coil Troubleshooting.
Fan Coil Troubleshooting
- Fan coil faults indicated by flashing codes on the amber system STATUS LED can be resolved using the troubleshooting information provided below.
- Codes are listed in order of priority, from highest to lowest. Though multiple faults can exist at any time, only the highest priority code will be displayed on the STATUS LED. Clearing the indicated fault when multiple faults exist will cause the next highest priority Status Code to be flashed. All existing faults, as well as a fault history, can be viewed at User Interface.
STATUS CODE 45, CONTROL BOARD TEST FAULT:
- The fan coil control has failed internal start-up tests and must be replaced.
- No other service procedure will be correct.
STATUS CODE 37, HEATER OUTPUT SENSED “ON” WHEN NOT ENERGIZED:
- Fan coil control is provided with circuitry to detect the presence of a 24VAC signal on the Electric Heater stage 1 and stage 2 outputs.
- If fan coil control detects a 24VAC signal on either heater stage output and it is not supplying a signal, Status Code 37 will be displayed on the STATUS LED. Fan coil control will turn off output and command the blower motor to supply an airflow determined to be safe for the current operation mode with electric heaters energized.
To find the fault:
- Stop all system operations at the User Interface and check heater stage 24VAC outputs.
- Disconnect the electric heater at plug/receptacle 2 and check the heater wiring for faults. See Status Code 36 for more information.
STATUS CODE 44, MOTOR COMMUNICATION FAULT:
- The MOTOR LED is connected to the blower motor communication line and works with the fan coil control microprocessor and STATUS LED to provide fan coil operation and troubleshooting information.
- When a motor is commanded to operate, the MOTOR LED will be turned on and will flash each time instructions are sent to the motor.
- When the motor is commanded to stop, the MOTOR LED will be turned off. The MOTOR LED will not flash to indicate communications when it is turned off.
- Fan coil control is constantly communicating with the motor, even when the motor and MOTOR LED are off. If the motor does not acknowledge receipt of communications, the control will display Status Code 44 on
- STATUS LED and continue to try to communicate with the motor. If the motor acknowledges communication, the status code will be cleared.
If the MOTOR LED is lit and flashing and the motor does not run:
- Check the STATUS LED. If the STATUS LED is indicating a Status 44 code, check the motor wiring harness for proper connection to the control and motor receptacles.
- Check the motor wiring harness to be sure all wiring complies with the wiring diagram description, makes a complete circuit from connector to connector, and is not shorted.
- Check 12VDC low-voltage supply to motor at Pins 1 (+) and 2 (-) of motor header connection to fan coil control.
- If all checks are normal, the fan coil control is good and the control module on the motor may need replacement. Check the motor and Motor Control Module following the instructions in (ECM Motor Troubleshooting on 14).
- Shorted or miswiring of the low-voltage motor harness wiring will not cause damage to the fan coil control or motor control module.
- If the MOTOR LED is off, the STATUS LED is indicating a Status Code 44 and the motor is running:
- Disconnect the motor harness at the fan coil control. If the motor continues to run, the fan coil control is good and the control module on the motor may need replacement
STATUS CODE 25, INVALID MOTOR / MODEL SELECTION:
On initial start-up, the fan coil control shall poll the motor for its size
data and check the fan coil size data stored in the fan coil control memory.
- If the motor size is incorrect for fan coil size or fan coil size data is invalid, Status Code 25 will be displayed on the STATUS LED.
- If model size data is missing (as is the case when a replacement fan coil control is installed), the system User Interface will prompt the installer to enter the correct model size from a list of valid sizes.
- If the motor size is incorrect for the model size, the motor must be replaced with the proper size motor. Fan coil control will not respond to operation requests until this fault condition is resolved.
STATUS CODE 27, INVALID OUTDOOR UNIT SIZE:
- On initial power-up, fan coil control will write into memory outdoor unit size as provided by User Interface in a fully communicating system.
- If the outdoor unit size is invalid, Status Code 27 will be displayed on the STATUS LED.
- User Interface will prompt the installer to choose a size from a list of valid sizes for application with a fan coil.
- Check communications wiring to be sure the User Interface has established communications with the outdoor unit or select the proper size from the valid size list provided by the User Interface.
- Check the motor and motor control module following the instructions in (ECM Motor Troubleshooting on).
STATUS CODE 26, INVALID HEATER SIZE:
- On initial power-up, fan coil control will write into memory the electric heater size as read from the heater if the heater is provided with an Identifier Resistor (IDR). The heater size must be valid for a combination of indoor and outdoor components installed. Fan coil control will read the IDR value connected to Pins 5 and 8 of the heater harness connector. If no resistor is found, the system User Interface will prompt the installer to verify that no heater is installed.
- Verifying that this is correct will establish that the fan coil is operating without an electric heater accessory. Upon choosing a negative option, the installer will be prompted to select the heater size installed from a list of valid heater sizes for the fan coil and outdoor unit size installed.
- If the heater ID resistor value read is invalid, Status Code 26 will be displayed on the STATUS LED.
- If the heater installed is equipped with a resistor connected to Pins 5 and 8 of heater harness connector and Status Code 26 is displayed on STATUS LED:
- Check wiring harness connections to be sure connections are secure.
- If symptoms persist, disconnect the wiring harness at the fan coil control heater header and check for a resistance value greater than 5000 ohms.
- Check for proper wiring of resistor assembly.
- Make sure the heater size installed is an approved size for outdoor units and fan coil sizes installed.
- NOTE: Fan coil control will not operate the electric heater until this Status Code is resolved.
- If the heater size is set through the User Interface, the heater will be operated as a single-stage heater.
- If staging is desired, the IDR value must be read by the fan coil control.
Table 5 – FE4 Self-identifying Resistor Values
STATUS CODE 36, HEATER OUTPUT NOT SENSED WHEN ENERGIZED:
- Fan coil control is provided with circuitry to detect the presence of a 24VAC signal on the Electric Heater stage 1 and stage 2 outputs.
- If fan coil control energizes either heater stage and does not detect the 24VAC signal on output, Status Code 36 will be displayed on the
- STATUS LED Fan coil control will continue to energize heater output(s) and adjust blower operation to a safe airflow level for energized electric heat stage(s).
- To find the fault, check for 24VAC on heater stage outputs. The fan coil control or sensing circuit may be bad.
- NOTE: It may be useful as an electric heater troubleshooting procedure to disconnect the system communications to force Status Code 16 enabling emergency heat mode. It is difficult to know which heater output is energized or not energized in normal operation. When the fan coil is operated in emergency heat mode using electric heaters, both outputs are energized and de-energized together. Terminal strip inputs to control can then be connected from R to W to turn on both electric heat outputs.
- Heater output sensing circuits can then be checked to resolve Status Code 36 or 37 problems.
STATUS CODE 41, BLOWER MOTOR FAULT
If MOTOR LED is lit and flashing and the motor does not run:
- Check STATUS LED. If the STATUS LED is indicating Status Code 41, motor control has detected that the motor will not come up to speed within 30 seconds of being commanded to run or that the motor has been slowed to below 250 rpm for more than 10 seconds after coming up to speed. The motor wiring harness and fan coil control are operating properly, do not replace them.
- Check to be sure that the blower wheel is not rubbing the housing.
- Check the motor to be sure that the motor shaft is not seized (the motor control module must be removed and electronics disconnected from windings to perform this check properly).
- Check the motor windings section following instructions in (ECM Motor Troubleshooting on).
If all these checks are normal, the motor control module may need replacement.
STATUS CODE 16, SYSTEM COMMUNICATION FAULT:
- If, at any time, system communications are not successful for a period exceeding two minutes, the fan coil control will only allow emergency heating or cooling operation using a common thermostat, a non-communicating outdoor unit, and the R, C, Y, O,W outdoor unit terminal strip connections and will display Status Code 16 on the amber
STATUS LED. See (Emergency Heating and Cooling Modes on p1).
- No further fan coil troubleshooting information will be available at the User Interface until communications are reestablished.
- Check system wiring to be sure the User Interface is powered and connections are made A to A, B to B, etc. and wiring is not shorted.
- Mis-wiring or shorting of the ABCD communications wiring will not allow successful communications. Correcting wiring faults will clear the code and reestablish communications.
- Shorting or miswiring the low-voltage system wiring will not cause damage to the fan coil control or the User Interface but may cause the low-voltage fuse to open.
STATUS CODE 46, BROWNOUT CONDITION:
- If the secondary voltage of the transformer falls below 15VAC for a period exceeding four seconds, Status Code 46 will be displayed on STATUS LED.
- If the system includes a non-communicating outdoor air conditioner or heat pump, the User Interface will command the fan coil to turn off the Y output-controlling compressor.
- When the secondary voltage rises above 17VAC for more than four seconds, the brownout condition is cleared and normal system operation will resume subject to any minimum compressor off delay function which may be in effect. Brownout does not affect blower or electric heater operation.
STATUS CODE 53, OUTDOOR AIR TEMPERATURE SENSOR FAULT:
- If an OAT sensor is found at power-up, input is constantly checked to be within a valid temperature range. If the sensor is found to be open or shorted at any time after initial validation, Status Code 53 will be displayed at amber STATUS LED.
- Check for faults in the wiring connecting the sensor to OAT terminals. Using an Ohmmeter, check the resistance of the thermistor for a short or open condition.
- If the thermistor is shorted or open, replace it to return the system to normal operation. If the fault is in the wiring connections, correcting the fault will clear the code and return the system to normal operation.
- NOTE: If the fault condition is an open thermistor or a wiring problem that appears to be an open thermistor and the power to the fan coil control is cycled off, the fault code will be cleared on the next power-up but the fault will remain and the system operation will not be as expected. This is because on power-up, the fan coil control cannot discern the difference between an open sensor or if a sensor is not installed.
Emergency Heating and Cooling Modes
- Fan coil control can provide emergency heating or cooling using a common heat/cool thermostat if there are no system communications, the fault is in the User Interface and no replacement is immediately available.
- To activate these modes, the thermostat and outdoor unit must be wired as a common heating/cooling system to fan coil control RYWC terminals. Fan coil control must be powered and display Status Code 16, System Communication Fault.
- NOTE: These emergency modes do not provide the level of comfort and efficiency expected by the consumer and should only be activated when
- User Interface cannot be replaced immediately.
FE4A FAN COIL SEQUENCE OF OPERATION
- The FE4A fan coil is designed for installation with a communicating
- User Interface. This fan coil will not respond to commands provided by a common thermostat except under certain emergencies described in the Start-Up and Troubleshooting sub-section.
- The User Interface uses temperature; humidity and other data supplied from indoor and outdoor system components to control heating or cooling systems for optimum comfort.
FE4A ADVANCED TROUBLESHOOTING:
Troubleshooting the FE Fan Coil Circuit Board:
- Production Unit circuit board Fan Coil part number HK38EA011
- RCD Replacement circuit board HK38EA012
- Older circuit board part numbers HK38EA006 and HK38EA009 Primary test that should be performed:
Motor Line Voltage Check
- Turn off power (240V).
- Remove Plug 3 from the ECM motor
- Turn on power.
- Check Plug 3, terminals 4 and 5, to ensure there are 240V.
- Turn off the power.
- Reconnect Plug 3 to the motor.
The following troubleshooting techniques will assist in determining the correct component to replace when the Fan Coil Board (HK38AE011) presents a Fault Code 44 or 41:
- Disconnect power from the unit (240V).
- Disconnect the ABCD connector from the board.
- Disconnect Plug 1 from the board (HK38AE011) (Fig. 13).
- Turn on power (240V).
- After reestablishing power, you should receive Fault Code 44, and the motor LED should be off.
- Place a jumper across the R and G terminals on the low-voltage terminal block
- Fault Code 44 should still be flashing.
- The Motor LED should be flashing, indicating the board can transmit a signal to the motor.
- If the Motor LED is not flashing, check to ensure that 24V is present across R and C on the low-voltage terminal block and that there is a good connection with the R and G jumper.
- If 24V is present and the jumper/connections are good,
- Replace the board. Check Board
- If Fault Code 44 and the Motor LED are both flashing, place a DC voltmeter across terminals PL1-1 Red (+) to PL1-2 Green (-) (Fig. 13).
- Across terminal PL1-1 and PL1-2, a 12VDC should be present. If 12VDC is not present, replace the circuit board (HK38AE011).
- If Fault Code 44 is flashing and the Motor LED is flashing, place a DC voltmeter across terminal PL1-3 (+) and PL1-2 (-).
- Across terminal PL1-3 (+) and PL1-2 (-), the DC volt meter should display 5VDC. The voltage should be very stable and should not fluctuate more than 0.02VDC. If the voltage fluctuates, get a different voltmeter before proceeding to the following steps.
- Reconnect Plug 1 to the circuit board (HK38AE011) and connect the DC voltmeter across terminals PL1-3 Yellow (+) and PL1-2 Green (-).
- Does the voltage appear to fluctuate more than in step 15? Typical voltmeters will show a fluctuation of 0.2VDC to 1VDC. The amount of fluctuation is not important. You could see even more fluctuation depending on the voltmeter used.
- Check the blower motor serial output signal. The blinking LED on the control board represents the serial output signal. You can measure the signal with a DC voltmeter by removing Plug 1 from the circuit board (HK38AE011) and connecting the DC voltmeter across PL1-4 (+) and PL1-2 (-). The voltage should be near 0VDC but it will fluctuate briefly several times per second. If you have an analog voltmeter, the needle briefly will go high several times per second. If you have a digital voltmeter with a bar graph, it will show a large change in magnitude on the bar graph several times per second. If you have a plain, digital voltmeter, it will show a brief fluctuation in voltage, and the magnitude may vary depending on the voltmeter used.
WARNING ELECTRICAL SHOCK HAZARD
- Failure to follow this warning could result in personal injury or death.
- Disconnect all power to the unit before servicing the field wires or removing the control package.
- The disconnect (when used) on the access panel does not disconnect power to the line side of the disconnect but does allow safe service to all other parts of the unit.
The minimum maintenance requirements for this equipment are as follows:
-
Inspect and clean or replace air filters each month or as required.
-
Inspect the cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary. An inspection port is provided on all A-coil delta plates. Remove the plastic plug to inspect.
Replace the plug after inspection. -
Inspect the blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
-
Inspect electrical connections for tightness and controls for proper operation each heating and cooling season. Service as necessary
CAUTION CUT HAZARD
- Failure to follow this caution may result in personal injury.
- Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts
Filter Assembly
- To clean or replace the air filter, push plastic connectors toward the center of the unit and remove the filter access panel outward. Push the filter up and back into the unit. Then slide the filter out.
- Clean the filter by using cold water and mild detergent. Rinse and allow the filter to dry. No oiling or coating of the filter is required.
- New filters are available from your local distributor. Place the filter in the slot with cross-mesh binding up or facing the cooling coil and replace the filter access panel.
Cooling Coil, Drain Pan, and Condensate Drain
- The cooling coil is easily cleaned when it is dry. Inspect the coil and clean (if necessary) before each cooling season. To check or clean the cooling coil, remove the coil access panel. If the coil is coated with dirt or lint, vacuum it with a soft brush attachment.
- Be careful not to bend coil fins. If the coil is coated with oil or grease, clean it with a mild detergent and water solution. Rinse the coil thoroughly with clear water. Be careful not to splash water on insulation.
FFM and FMA
WARNING ELECTRICAL OPERATION HAZARD
- Failure to follow this warning could result in personal injury or death.
- Before installing or servicing the system, always turn off the main power to the system. There may be more than one disconnect switch. Turn off the accessory heater power if applicable. Lock out and tag the switch with a suitable warning label.
Fan Motor
- The FFMANP(018,024,030,036) and FMA4P motor is a three-speed PSC direct drive. High-speed lead is black, medium-speed lead is red, low-speed lead is blue, and common lead is purple. The FFMANP(019,025,031,037) and FMA4X motor is a five-speed ECM direct drive. The cooling speed tap is selected by connecting the green wire to the desired motor tap number indicated on the motor plug. For the electric heat fan speed selection connect the white wire to the desired motor tap number indicated on the motor plug. Be sure proper blower speed has been selected.
- The blower motor in this unit has blower-off delays. The blower-off delay is 30–90 seconds and will keep the motor running after a heating or cooling call ends.
- The motor is turned on through two different routes. The first occurs when the thermostat calls for the fan in cooling, heat pump, or fan-only mode. A 24VAC signal is sent to the relay, causing the relay to close its normally open contacts, turning the fan on.
- The second occurs when there is a call for electric heat. A 24VAC signal is sent to the heater sequencer/relay, causing it to close, directing 230V through the normally closed contact of the fan relay, and turning the fan on. The fan remains on until the sequencer/relay/PCB opens.
- If the motor does run, test the motor for an open winding or a winding shorted to the motor case. If either is present, replace the motor.
Time Delay
-
FFMANP(019,025,031,037) and FMA4X have a time delay built into the motor logic. FFMANP(018,024,030,036) and FMA4P units with date codes before 1715V have sequencers. FFMANP(018,024,030,036) and FMA4P units with date codes 1715V or later have a time delay printed circuit board.
-
The Time Delay Printed Circuit Board (PCB) is a logic-controlled time delay activated by the low-voltage control signal (G) from the thermostat. The PCB includes a normally open relay that closes to energize the blower motor when the G terminal is energized. Then when the G terminal is de-energized the relay energizing the blower motor remains closed for 90–100 seconds before opening.
NOTE: Aluminum coil models with PSC motors can be wired to different OFF time delays. See installation instructions for the wiring diagram. -
NOTE: The following sequence of operation is based on units installed with a PSC motor and Time Delay Printed Circuit Board (PCB). For units with an ECM motor, the off-delay is programmed into the motor.
-
Follow Table 6 below, ECM Motor Speed Taps & the corresponding blower OFF delays for each speed tap.
Continuous Fan
- The thermostat closes R to G. G energizes and completes a circuit to the indoor blower motor. When G is de-energized, there is a 90-second blower off-delay.
Cooling Mode
- The thermostat energizes R to G, R to Y, and R to O (heat pump only). G energizes and completes the indoor blower motor.
- Y energizes the outdoor unit (O is energized for the heat pump). When a cooling call is satisfied, G is de-energized, and there is a 90-second blower off-delay.
Heat Pump Heating Mode
- The thermostat energizes R to G and R to Y. G energizes and completes the circuit to the indoor blower motor.
- When a heating call is satisfied, G is de-energized, and there is a 90-second blower off-delay.
Heat Pump Heating with Auxiliary Electric Heat
- The thermostat energizes R to G, R to Y, and R to W1. G energizes and completes a circuit to the indoor blower motor.
- W1 energizes electric heat relay(s) which completes the circuit to heater element(s). When W1 is de-energized, electric heat relay(s) open, turning off heater elements.
- When G is de-energized there is a 90-second blower off-delay.
Electric Heat or Emergency Heat Mode
- The thermostat closes R to W1. W1 energizes electric heat relay(s) which completes a circuit to heater element(s).
- The blower motor is energized through normally closed contacts on the fan relay.
- When W1 is de-energized, electric heat relay(s) opens, and there is no blower off-delay. (units with ECM motor will have a blower off-delay based on motor speed tap selection).
Comments:
- The THR and THC are connected to the transformer output.
- When the G has a signal, the FAN will supply 24VAC power to control the fan relay.
- When the G signal is gone, the FAN will stop 24 VAC output after 90 seconds.
- CN3 and CN7 are dummy connection terminals.
Electric Heater Service
- Service can be completed with a heater in place. Shut off power before servicing.
Limit Switch
- Refer to (Electric Heater Function and Troubleshooting on p23). Sequencer
- Early EHK2 heater kits included sequencers instead of relays. Refer to (Electric Heater Function and Troubleshooting on p23).
Transformer
- A 40VA transformer supplies 24V power for the control circuit. Check for 208/230V on the primary side of the transformer. If present, check for 24V on the secondary side.
- NOTE: The Transformer is fused. Do not short circuit.
Fan Relay
- Later EHK2 heater kits included relays instead of sequencers. The relay coil is 24V. Check for proper control voltage. Replace the relay if faulty.
- Cleaning or Replacing Refrigerant Flow-Control Device
FFM AND FMA4P
- The FFM and FMA4P piston can be removed and cleaned if believed to be plugged. This unit’s piston is unique and replacements are available from RCD.
- The filter drier should be located on the liquid line at the indoor unit to prevent particulates from plugging the piston.
FFM and FMA4X
- The FFM and FMA4X fan coils use an R-410A TXV. The TXVs are preset at the factory and do not need adjustment for reliable operation.
- Reference the outdoor unit instructions to properly charge the unit to the correct subcooling. For optimal performance, adjust the TXV so that 6º F of superheat is measured at the outdoor unit’s vapor service valve when the indoor return air is 80º F DB/67º F WB and outdoor ambient is 82º F DB. To increase superheat turn the TXV adjustment stem clockwise no more than one rotation at a time. After an adjustment is made, wait until the superheat temperature has been stable for 15 minutes before making further adjustments.
Sequence of Operation
Condensing Unit
-
COOLING—When the thermostat calls for cooling, the circuit between R and G is complete and single-pole single-throw relay FR is energized.
-
The normally open contacts close causing the blower to operate.
-
The circuit between R and Y is also complete. This completed circuit causes the contactor in the outdoor unit to close which starts the compressor and outdoor fan. When the thermostat is satisfied, its contacts open the de-energizing contactor and blower relay. This stops the compressor and outdoor fan motor. The indoor fan motor will stop after 90-100 seconds on the FFMANP(018,024,030,036) and FMA4P, and 30 or 90 seconds on the FFMANP(019,025,031,037) and FMA4X.
-
HEATING—When the thermostat calls for heating and the FAN switch is set on
-
AUTO, the circuit between R and W is complete. The heater sequence SEQ is energized which closes the contacts of the relay.
-
There will be a time delay.
This completed circuit energizes all heating elements HTR and blower motor. When the thermostat is satisfied, its contacts open the de-energizing heat relay. -
This de-energizes the sequencer. All heaters should stop. The indoor fan motor will stop after 90-100 seconds on the FFMANP(018,024,030,036) and FMA4P, and 30 or 90 seconds on the FFMANP(019,025,031,037) and FMA4X.
Heat Pump
- COOLING—On a call for cooling, the thermostat makes circuits R-O, R-Y, and R-G. Circuit R-O energizes the reversing valve, switching it to the cooling position. Circuit R-Y energizes the contactor starting the outdoor fan motor and compressor. Circuit R-G energizes the indoor unit blower relay starting the indoor blower motor.
- When the thermostat is satisfied, its contacts open de-energizing the contactor reversing valve and blower relay. This stops the compressor and outdoor fan motor. The indoor fan motor will stop after 90-100 seconds on the
- FFMANP(018,024,030,036) and FMA4P, and 30 or 90 seconds on the FFMANP(019,025,031,037) and FMA4X.
- HEATING—On a call for heating, the thermostat makes circuits R-Y and R-G. Circuit R-Y energizes the contactor starting the outdoor fan motor and compressor. Circuit R-G energizes the indoor blower relay starting the blower motor.
- Should the temperature continue to fall, an R-W circuit is made through the second-stage room thermostat bulb. Circuit R-W energizes a sequencer bringing on supplemental electric heat.
- When the thermostat is satisfied, its contacts open de-energizing the contactor and sequencer. All heaters should stop. The indoor fan motor will stop after 90-100 seconds on the FFMANP(018,024,030,036) and FMA4P, and 30 or 90 seconds on the FFMANP(019,025,031,037) and FMA4X.
Electric Heater Function and Troubleshooting FB4, FE4, FF1E, FH4, FJ4, FV4, FX4, FZ and PF4
- IMPORTANT: 2023 model fan coils (FJ4) are designed to use KFFEH electric heaters, and are not compatible with KFCEH heaters.
- This section describes KFC, and KFD series electric heaters in exclusion of Smart Heat by examining the functional operation of these heaters.
- Description of Electric Heater Components
Limit Switch
- The limit switch is a temperature sensitive control whose function is to prevent system from overheating in abnormal conditions.
- The temperature settings often vary from heater to heater due to variations in airflow patterns and element radiant heat conditions.
- The devices are sized to remain on-line under heat pump conditions (115° air off coil) and minimum CFM, but trip to prevent outlet air conditions above 200° F or excessive component or duct temperatures.
- The device itself consists of a bimetallic disc, which when overheated ”snaps through” to open a normally closed high-voltage, high-current switch.
- When system temperatures cool sufficiently, the switch will automatically reset to its closed position. Normal failure mode for this switch is open.
- If a limit switch has been determined to be defective, NEVER BYPASS
- THE LIMIT SWITCH. When replacing limit switch, ensure that it is replaced with a limit switch of identical opening temperature and closing differential.
- Limit switches are typically color coded to identify their range.
KFC and KFD Electric Heat Relay
- KFC and KFD electric heater packages have relays controlling the heater elements instead of sequencers. A small rectifier PCB is mounted to each relay which converts the incoming 24VAC control signal to DC.
- In addition to the rectifier circuit, the second and third stage relays contain a time-on delay circuit of five seconds for second stage, and eight seconds for third stage.
- When the control signal is removed from the relays, all relays will open with no time-off delay.
Troubleshooting KFC and KFD Series Electric Heaters
- Discolored Wire Insulation at Terminal
- Check quick-connect terminal at discoloration. Connection may be loose, creating a high resistance through connection point.
Fuse Failure
- Check for shorted wire. Replace wire. Never try to fix wire using electrical tape.
- Check shorted element. If element is shorted, replace heater. No Heat
- Check fuse for failure. If fuse has failed, refer to (Fuse Failure on p23).
- Check for faulty transformer. Check output voltage of transformer secondary side R (red) and C (brown). Make sure output is between 18VAC and 30VAC. If output voltage is low and input voltage tests normal, replace transformer.
- Check for miswired heater plug harness.
- Check limit switch or sequencer failure. These switches should have failed in open position. If output voltage is zero volts, replace switch.
- Check heater relay and PCB (KFC and KFD heaters only). Control voltage input to PCB should be 24VAC. Output to relay should be 18VDC minimum. If input is present but no output, replace PCB. If output is present, replace relay.
Heater Will Not Turn Off
- Check low-voltage wiring for miswire
- Check for shorted elements to ground.
- Replace sequencer/relays. They may be stuck closed.
Nuisance Trips
- Check for low airflow due to dirty filters, blocked registers, or undersized duct.
- Check blower motor and wheel for proper operation. Excessive current draw of motor will cause internal overload to trip.
- The fan speed may be low.
FFM and FMA
- This section describes EHK2 series electric heaters by examining functional operation of this heater.
- Service can be completed with heater in place. Shut off power before servicing.
Description of Electric Heater Components Limit Switch
- The limit switch is a temperature sensitive control that’s function is to prevent system from overheating in abnormal conditions. The temperature settings often vary from heater to heater due to variations in airflow patterns and element radiant heat conditions.
- The devices are sized to remain on-line under heat pump conditions (115° F air off coil) and minimum CFM, but trip to prevent outlet air conditions above 200° F or excessive component or duct temperatures.
- The device itself consists of a bimetallic disc, which when overheated “snaps through” to open a normally closed high-voltage, high-current switch. When system temperatures cool sufficiently, the switch will automatically reset to its closed position.
- Normal failure mode for this switch is open.
- If a limit switch has been determined to be defective, NEVER BYPASS THE LIMIT SWITCH. When replacing limit switch, ensure that it is replaced with a limit switch of identical opening temperature and closing differential.
- Limits switches are typically color-coded to identify their range.
Sequencer
- Early production EHK2 heaters have sequences controlling the heater elements. The sequencer is essentially a thermally-activated time-delay relay normally activated by low-voltage control signals from thermostat.
- The typical sequencer is a 1- or 2-pole normally open device which energizes within 30 to 70 seconds after application of control signal and de-energizes 60 to 90 seconds after control signal is removed.
- In simplistic terms, the sequencers which we use are nothing more than normally open limit switches which sit on top of a small resistive heater.
- When voltage is applied to this heater, a positive temperature coefficient resistor (PTC), heat is supplied to a bimetallic disc which “snaps through” and closes switch.
- The time required for PTC to heat to a sufficient point controls ON timing of device. The time required for disc to cool down when power is removed controls OFF time of device.
- The PTC can be varied to provide varied timing.
- Typically a short ON equates to a long OFF.
- Because this is a thermally-activated device, ambient conditions affect the ON/OFF cycle. Higher ambient temperature means shorter ON times and longer OFF times.
- Application of these devices is such that the first switch ON not only turns on first heater element, but also ensures that indoor fan is energized, because first ON is last OFF.
- This ensures fan remains ON until the last heater de-energizes. The Time Delay
- Printed Circuit Board (PCB) is a logic controlled time delay activated by low-voltage control signal (G) from thermostat.
- The PCB includes a normally open relay which closes to energize the blower motor when the G terminal is energized.
- Then when the G terminal is de-energized the relay energizing the blower motor remains closed for 90 – 100 seconds before opening.
Relays
- Later production EHK2 heaters have relays controlling the heater elements instead of sequencers. A small rectifier PCB is mounted to each relay which converts the incoming 24VAC control signal to DC.
- In addition to the rectifier circuit, the second and third stage relays contain a time-on delay circuit of five seconds for second stage, and eight seconds for third stage.
- When the control signal is removed from the relays, all relays will open with no time-off delay.
Care and Maintenance
FB4, FE4, FH4, FJ4, FV4, FX4, FZ4 and PF4
- To continue high performance, and minimize possible equipment failure, it is essential periodic maintenance be performed on this equipment.
- The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.
- The only consumer service recommended or required is filter maintenance (Filter Assembly on).
WARNING ELECTRICAL SHOCK HAZARD
- Failure to follow this warning could result in personal injury or death.
- Disconnect all power to the unit before servicing the field wires or removing the control package.
- The disconnect (when used) on the access panel does not disconnect power to the line side of the disconnect, but does allow safe service to all other parts of the unit.
- The minimum maintenance requirements for this equipment are as follows:
- Inspect and clean or replace air filter each month or as required.
- Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary.
- Inspect blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
- Inspect electrical connections for tightness and controls for proper operation each heating and cooling season. Service as necessary.
CAUTION
CUT HAZARD
- Failure to follow this caution may result in personal injury.
- Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Filter Assembly
- To clean or replace air filter, push plastic connectors toward center of unit and remove filter access panel outward. Push filter up and back into unit. Then slide filter out.
- Clean filter by using cold water and mild detergent. Rinse and allow filter to dry. No oiling or coating of filter is required.
- New filters are available from your local distributor. Place filter in slot with cross-mesh binding up or facing cooling coil and replace filter access panel.
Cooling Coil, Drain Pan, and Condensate Drain
- The cooling coil is easily cleaned when it is dry. Inspect the coil and clean (if necessary) before each cooling season. To check or clean cooling coil, remove coil access panel. If coil is coated with dirt or lint, vacuum it with a soft brush attachment.
- Be careful not to bend coil fins. If coil is coated with oil or grease, clean it with a mild detergent and water solution. Rinse coil thoroughly with clear water. Be careful not to splash water on insulation.
- Inspect drain pan and condensate drain at the same time cooling coil is checked. Clean drain pan and condensate drain by removing any foreign matter from pan. Flush pan and drain tube with clear water.
- If drain tube is restricted, it can generally be cleared by high-pressure water. Cut plastic line and work outside condensate pan and away from coil to clean drain tube.
CAUTION UNIT DAMAGE HAZARD
- Failure to follow this caution may result in equipment damage.
- Do not use caustic household drain cleaners in the condensate pan or near the coil. Drain cleaners can quickly destroy a coil.
Blower Motor and Wheel
- Clean blower motor and wheel when cooling coil is cleaned.
WARNING ELECTRICAL SHOCK HAZARD
- Failure to follow this warning could result in personal injury or death.
- Disconnect electrical power before removing any access panels. Lock out and tag switch with a suitable warning label.
To clean blower motor or blower wheel:
- Remove blower access panel.
- Remove motor leads from fan coil control. Note lead location for ease of reassembly.
- Remove the two outside screws holding blower/motor assembly against blower deck flange and slide assembly out of cabinet.
- (If applicable) Remove screw in strap holding motor capacitor to blower housing and slide capacitor out from under strap. Remove screw with green wire from blower housing. Mark blower wheel, motor, and motor support in relation to blower housing before disassembly to ensure proper reassembly. Note position of blades on wheel.
- Loosen setscrew holding blower wheel onto motor shaft.
- Remove the three bolts holding motor mount to blower housing and slide motor and mount out of housing. Further disassembly should not be necessary as adequate clearance is available.
- Remove blower wheel from housing by removing cutoff plate from blower housing outlet. Note wheel orientation and cutoff location for reassembly. The blower motor and wheel may be cleaned by using a vacuum with a soft brush attachment.
- Remove grease with a mild solvent such as hot water and detergent.
- Be careful not to disturb balance weights (clips) on blower-wheel vanes. Also, do not drop or bend wheel, as balance will be affected.
To reassemble blower:
- Place blower wheel back into housing. Be sure to position correctly for proper location.
- Reassemble cutoff plate to housing using identified holes from disassembly procedure.
- Position motor and mount in same position as when blower housing was in unit. Secure motor mount on housing, using removed bolts.
- Make sure mount or motor is grounded to blower housing.
- Locate blower wheel setscrew over flat on motor shaft. Rotate wheel in housing. It should not rub housing and should be centered in inlet opening. If not, loosen setscrew and align as necessary.
- Attach green wire to blower housing with screw.
- (If applicable). Secure motor capacitor under strap and tighten strap screw.
- Slide blower assembly to blower deck. Be sure (once blower is within the unit casing) to force blower assembly toward control box while sliding assembly into unit to ensure that blower assembly engages deck properly.
- Fasten blower assembly to deck with screws previously removed.
- Reconnect electrical leads to fan coil control.
- Reconnect electrical power to unit and test fan for proper rotation.
FF1E, FFMA, FMA
The minimum maintenance requirements for this equipment are as follows
- Inspect and clean or replace air filter each month or as required.
- Inspect cooling coil, drain pan, and condensate drain each cooling season for cleanliness. Clean as necessary.
- Inspect blower motor and wheel for cleanliness each heating and cooling season. Clean as necessary.
- Inspect electrical connections for tightness and controls for proper operation each heating and cooling season. Service as necessary.
CAUTION CUT HAZARD
- Failure to follow this caution may result in personal injury.
- Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
Air Filter
- The air filter should be replaced as needed.
UNIT DAMAGE HAZARD
- Failure to follow this caution may result in equipment damage.
- Never operate unit without a filter.
Cooling Coil, Drain Pan, and Condensate Drain
- The cooling coil is easily cleaned when it is dry. Inspect coil and clean (if necessary) before each cooling season. To check or clean cooling coil, remove blower/heater access panel to gain full access to cooling coil. If coil is coated with dirt or lint, vacuum with a soft brush attachment.
- Be careful not to bend coil fins. If coil is coated with oil or grease, clean it with a mild detergent and water solution. Rinse coil with clear water.
- Be careful not to splash water onto insulation.
- Inspect drain pan and condensate drain at same time cooling coil is checked. Clean drain pan and condensate drain by removing any foreign matter from pan. Flush pan and drain tube with clear water.
- If drain tube is restricted, it can generally be cleared by high-pressure water. Cut plastic line and work outside condensate pan and away from coil to clear drain tube.
- NOTE: There MUST be a trap in the condensate line. The trap must be at least 3-in. deep, not higher than the bottom of unit condensate drain opening, and pitched downward to an open drain or sump.
UNIT DAMAGE HAZARD
- Failure to follow this caution may result in equipment damage.
- Do not use caustic household drain cleaners in the condensate pan or near the coil. Drain cleaners can quickly destroy a coil.
Blower Motor and Wheel
Clean blower motor and wheel when cooling coil is cleaned.
To clean or service wheel or motor, proceed as follows:
- Pull unit disconnect (when used) and remove blower access panel.
- Disconnect motor electrical leads from control box and capacitor. Mark location of wires for reassembly.
- Remove the three bolts holding motor mount to blower housing while supporting motor shell with hand.
- Pull motor inlet ring and blower wheel assembly out of blower housing.
- With blower wheel, inlet ring, and motor mount still attached to motor, place motor on flat, horizontal surface, shaft up. Mark position of wheel on motor shaft for reassembly.
- Loosen blower wheel setscrew and remove blower wheel from motor shaft.
- NOTE: Further disassembly of motor and mount is not necessary as adequate clearance is available to clean motor.
- Clean blower motor and wheel using a vacuum with a soft brush attachment. Remove grease with a mild solvent such as hot water and detergent. Be careful not to disturb balance weights (clips) on blower wheel vanes. Do not drop or bend wheel as balance will be affected.
To reassemble unit, proceed as follows:
- Place motor with mount attached on flat, horizontal surface with shaft up.
- Set inlet ring on top of motor mount grommets. Center inlet ring flush on all three grommets.
- Slide blower wheel onto motor shaft with setscrew upward and aligned with shaft flat portion. Vertically position wheel along shaft to position marked during disassembly.
- NOTE: If previous shaft was not marked or if replacing previous motor, set blower wheel position by sliding blower wheel along motor shaft to 1-1/8-in. above rubber grommets (Fig. 24).
- Hold blower wheel in place and carefully tighten setscrew.
- Position motor and blower wheel assembly to blower housing as originally oriented.
- Secure motor mount to blower housing using bolts previously removed.
- Attach green wire to blower housing with screw.
- Connect electrical and capacitor leads to original terminals.
- Replace blower access door and tighten all four screws.
- Reinsert disconnect pullout only after blower access door is secured. Test blower for proper operation.
Refrigerant Flow-Control Devices
- Thermostatic Expansion Valves (TXV)
- NOTE: 2023 models (FJ4) use a mechanical TXV. Refer to the TXV
- Installation Instructions. Torque the equalizer fitting to 10–20ft-lb; do not exceed 20 ft-lb.
- The FX4, FV4, FF1E, and FE4 Fan Coils are factory equipped with a hard shutoff (HSO) TXV. The hard shutoff TXV has no bleed port and allows no bleed-through after system is shutdown.
- The TXV is a bi-flow metering device that is used in condensing and heat pump systems to adjust to changing load conditions by maintaining a preset superheat temperature at outlet of evaporator coil. The volume of refrigerant metered through valve seat is dependent upon the following:
- Superheat temperature sensed by sensing bulb on suction tube at outlet of evaporator coil. As long as this bulb contains some liquid refrigerant, this temperature is converted into pressure pushing downward on the diaphragm, which opens the valve via push rods.
- The suction pressure at outlet of evaporator coil is transferred via the external equalizer tube to underside of diaphragm.
- The bi-flow TXV is used on split system heat pumps. In cooling mode,
- TXV operates the same as a standard TXV previously explained.
- However, when system is switched to heating mode of operation, refrigerant flow is reversed.
- The bi-flow TXV has an additional internal check valve and tubing.
- These additions allow refrigerant to bypass TXV when refrigerant flow is reversed with only a 1-psig to 2-psig pressure drop through device.
- When heat pump switches to defrost mode, refrigerant flows through a completely open (not throttled) TXV. The bulb senses the residual heat of outlet tube of coil that had been operating in heating mode (about 85° F and 155 psig).
- This temporary, not-throttled valve decreases indoor pressure drop, which in turn increases refrigerant flow rate, decreases overall defrost time, and enhances defrost efficiency.
Problems Affecting TXV
Low Suction Pressure
- Restriction in TXV
- Low refrigerant charge
- Low indoor load
- Low evaporator airflow
High Suction Pressure
- Overcharging
- Sensing bulb not secure to vapor tube
- High indoor load
- Large evaporator face area
- NOTE: When installing or removing TXV, wrap TXV with a wet cloth.
- When reattaching TXV, make sure sensing bulb is in good thermal contact with suction tube.
- The needle valve on pin carrier is spring-loaded, which also exerts pressure on underside of diaphragm via push rods, which closes valve. Therefore, bulb pressure equals evaporator pressure at outlet of coil plus spring pressure.
- If load increases, temperature increases at bulb, which increases pressure on topside of diaphragm, which pushes pin carrier away from seal, opening valve and increasing flow of refrigerant.
- The increased refrigerant flow causes increased leaving evaporator pressure which is transferred via the equalizer tube to underside of diaphragm, with which the pin carrier spring
pressure closes valve. The refrigerant flow is effectively stabilized
to load demand with negligible change in superheat.
Aluminum Coil Unit TXV’s
- The distributor used on the all-aluminum coils is also made of aluminum. The TXV connection to the distributor is accomplished with a 3/4″ Chatleff nut (Fig. 25). The threads are coated with Loctite Heavy
- Duty Anti-Seize which is a graphite/calcium fluoride formulation, for applications that is free from copper, lead and sulfur. This product is typically used in applications with an operating range of -20° F to +2400° F.
- When replacing a TXV it is recommended to reapply with the same thread sealer.
- Extra care should be taken during brazing of copper equalizer on the aluminum coils to prevent the braze material from splattering on the aluminum.
- Also, route the copper equalizer so that it doesn’t touch the aluminum components.
Piston Body Cleaning and Replacement
- CAUTION ENVIRONMENTAL HAZARD
- Failure to follow this caution may result in environmental damage.
- Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
- CAUTION UNIT DAMAGE HAZARD
- Failure to follow this caution could result in equipment damage.
- Damage may occur to the scroll compressor if operated at a negative suction pressure during a system pumpdown.
- Pump down outdoor unit. Close service valves at outdoor unit.
- Recover remaining refrigerant from tubing and coil through gage port on vapor-tube service valve. Disconnect refrigerant (liquid) tube from piston body (Fig. 26).
- Avoid damaging seal ring or machined surfaces on piston, bore, and retainer.
- Using small wire with a hook on end of it, remove piston from body.
CAUTION UNIT DAMAGE HAZARD
- Failure to follow this caution could result in equipment damage.
- When cleaning the piston orifice, be careful not to scratch or enlarge the opening, as this will affect operation.
- Install new or cleaned piston into body.
- Replace seal ring on retainer.
- The threads are coated with Loctite Heavy Duty Anti-Seize. It is recommended to reapply with the same thread sealer.
- Reconnect refrigerant tube to piston body.
- Pressurize tubing and coil, then leak check.
- Evacuate tubing and coil as necessary.
CAUTION UNIT DAMAGE HAZARD
- Failure to follow this caution could result in equipment damage.
- Use a backup wrench and do not over tighten, as deformation of the piston body will occur, causing the piston to lodge in a partially open or closed position.
UNIT DAMAGE HAZARD
- Failure to follow this caution could result in equipment damage.
- Use a backup wrench and do not over tighten, as deformation of the piston body will occur, causing the piston to lodge in a partially open or closed position.
Liquid Tube Strainer
- In R-22 all units, the TXV and refrigerant flow-control device is protected on the indoor coil by a wire mesh strainer.
- It is located inside the 3/8″ liquid tube at field braze joint just outside unit casing. Access to strainer is through field braze joint.
Aluminum Coil Repair
- Repairing leaks on aluminum coils is possible using the aluminum brazing method. Specific braze and flux materials designed for aluminum are necessary for aluminum brazing.
- A kit containing all materials necessary for making and aluminum braze repair is available through Replacement Components (kit No. 337748-751).
- Do not use a previously-used wire brush to clean copper when preparing an aluminum braze site. Copper particles in contact with an aluminum coil may cause premature failure.
- Service aluminum coils are also available as a coil repair option.
- NOTE: Replacement of an indoor slope or A-coil must include recovery and recycling of refrigerant currently in the system.
- Provided the refrigerant has not been contaminated with moisture, acid, solid particulate, or non-condensibles, it may be recovered by following the procedures listed below.
- However, if the refrigerant is contaminated, recycling or reclaiming methods are required.
- If leaks are present in the system, meaning the refrigerant may be contaminated, recycling or reclaiming methods MUST be used. Installation of new filter drier(s) is required.
- The filter drier-type will depend upon the contaminants in the system. See Split-System Residential Air Conditioners and Heat Pumps Service Manuals for further information.
WARNING PERSONAL INJURY HAZARD
- Failure to follow this caution may result in personal injury.
- Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves.
Pre-Installation
- Except for coils only used with TXV fan coils, all-aluminum replacement coils are shipped with a piston body distributor, piston, and 90 degree inlet tube with piston retainer (including Teflon seal).
- Coil sizes used only with TXV fan coils include the TXV as part of the replacement coil.
- Before installation of replacement coil, verify the piston is the correct orifice size. The correct size should be on the outdoor unit rating plate. If in doubt, reuse the piston from the old indoor coil.
- Use two wrenches to separate the 13/16″ Chatleff nut from the distributor body. The threads will contain Loctite anti-seize, do not remove this from the threads.
- Install the piston and reattach nut to finger tight plus 1/2 turn.
- The distributor used on the all-aluminum replacement coil is also made of aluminum. The distributor threads are coated with Loctite Heavy
- Duty Anti-Seize which is a graphite/calcium fluoride formulation, for applications that is free from copper, lead and sulfur. This product is typically used in applications with an operating range of -20° F to +2400° F (Fig. 27). When replacing a TXV it is recommended to reapply with the same thread sealer. Extra care should be taken during brazing of copper equalizer on the aluminum coils to prevent the braze material from splattering on the aluminum.
- Also, route the copper equalizer so that it doesn’t touch the aluminum components.
Old Copper or Tin-Plated Coils with TXV
- The all-aluminum replacement coil with piston will also be used for TXV style coils by reusing the original TXV. An adapter is provided to connect the replacement coil distributor to the original TXV (Fig. 28).
- Insulation is also provided to wrap the copper adapter tube and brass nuts to prevent any copper or brass particles from coming in contact with the aluminum coil.
- Even if the adapter tube is not in contact with the aluminum coil dripping condensation from the adapter tube can be a mechanism of particulate transport.
If it is preferred to install the old TXV external to the cabinet due to access, follow the steps below:
- Field fabricate a piece of 3/8″ OD copper tubing with flare and nut to attach to the TXV outlet.
- The piston in the replacement coil must be removed. Use two wrenches to separate the 13/16″ Chatleff nut from the distributor body. The threads will contain Loctite anti-seize, do not remove this from the threads.
- Remove the piston
- Reattach the inlet tube and tighten the nut finger tight plus 1/2 turn.
- Remove the old coil and install replacement coil per instructions below. Reinstall the fitting door to the cabinet.
- Field fabricate a 3/8″ OD copper tubing with flare and nut.
- Braze this tubing and nut onto the liquid stub out.
- Attach flare and nut to TXV outlet by tightening to finger tight plus 1/2 turn with two wrenches.
- Drill equalizer hole into suction line and braze the equalizer into the hole.
- Attach the TXV bulb onto the suction line and insulate.
- Insulate the entire TXV body and outlet tubing to prevent sweating.
Old All-Aluminum Coils with TXV
When replacing a previous all-aluminum coil that contains a TXV, the old TXV can be reused and mounted inside the cabinet.
- After removal of the distributor inlet tube and piston, the old TXV is attached to the distributor with 13/16″ Chatleff nut. The threads contain Loctite anti-seize that can be reused.
- Tighten the nut finger tight plus 1/2 turn.
- The vapor header contains a small diameter stub tube for the equalizer line.
- Cut the end of the stub tube.
- Insert TXV equalizer and braze together. Caution must be taken to avoid braze splatter from the aluminum surfaces of the new coil.
- Caution must be taken to avoid heating the factory joint of the stub tube to the vapor header.
- The vapor header contains an indentation for the TXV bulb. Attach the bulb and insulate.
Installation – A-Coil Units Only
- Recover system refrigerant.
- a. Attach gage/manifold set to service valves.
- b. Start the unit in cooling mode.
- c. Front seat (close) liquid line service valve.
- d. Operate unit until vapor pressure reaches 5 psig (35kPa), or until suction line LPS opens.
- e. Turn off the electrical supply to the outdoor unit.
- f. Front seat (close) vapor service valve.
- g. Recover any remaining refrigerant.
- NOTE: All condenser coils hold only a factory-supplied amount of refrigerant. Excess refrigerant, such as in long-line applications, may cause the compressor’s internal pressure relief valve to open (indicated by a sudden rise in vapor pressure) before refrigerant is recovered. If this occurs, turn off the electrical supply to the outdoor unit immediately, front seat (close) vapor service valve, and recover any remaining refrigerant.
- Turn off the electrical supply to the indoor unit.
- Disconnect the condensate drain line.
- WARNING PERSONAL INJURY HAZARD
- Failure to follow this caution may result in personal injury.
- Use of a torch may cause oil to catch fire, resulting in personal injury or death. To remove components use a tubing cutter only.
- Disconnect liquid and vapor lines from the indoor coil. Use a tubing cutter to cut the lines.
- Remove the coil access panel.
- Remove clip clip-securing fitting panel to condensate the drain pan and remove the fitting panel.
- Remove all shipping clips (if present), including the horizontal pan clip. Slide coil and condensate pan assembly out of the unit.
- Remove the horizontal condensate drain pan from the coil (if present) and condensate pan assembly (Fig. 29).
- Remove 4 coil brackets if present (Fig. 29).
- Remove screws at the delta plates and remove the coil from the vertical condensate drain pan (Fig. 29).
- Horizontal Applications Only—Remove drain connections and J-shaped tubes from the original coil, and install them in the same position on the new coil (Fig. 29).
- Place the coil assembly in a plastic condensate pan and secure it with 4 screws through the delta plate (Fig. 29).
- Horizontal and Upflow Applications Only—Attach 4 coil brackets to coil and pan assembly (Fig. 29).
- Horizontal Applications Only—Place horizontal condensate pan into position on coil and pan assembly.
- NOTE: Installation of a horizontal condensate pan is not necessary for upflow or downflow applications.
- Slide completed assembly into the unit.
- Reinstall the fitting panel and reconnect the clip securing the fitting panel to the condensate drain pan.
- Horizontal Applications Only—Reinstall the horizontal pan clip and secure it with 1 screw (Fig. 29).
- Reinstall the coil access panel.
- Reconnect liquid and vapor refrigerant lines and condensate drain lines. Install new filter drier(s).
- NOTE: If a torch is used to unbrace the line set, protect the fitting panel with a wet cloth or braze shield as necessary.
- Evacuate line set and indoor coil to 500 microns, back seat (open) liquid and vapor service valves.
- Turn on electrical supplies to indoor and outdoor units.
- Check system refrigerant charge and operation. See Split-System Residential Air Conditioners and Heat Pump Service Manuals for further information.
Installation – Slope Coil Units Only
- Recover system refrigerant.
- a. Attach gage/manifold set to service valves.
- b. Start the unit in cooling mode.
- c. Front seat (close) liquid line service valve.
- d. Operate unit until vapor pressure reaches 5 psig (35kPa), or until suction line LPS opens.
- e. Turn off the electrical supply to an outdoor unit.
- f. Front seat (close) vapor service valve.
- g. Recover any remaining refrigerant.
- NOTE: All condenser coils hold only a factory-supplied amount of refrigerant. Excess refrigerant, such as in long-line applications, may cause the compressor’s internal pressure relief valve to open (indicated by a sudden rise in vapor pressure) before refrigerant is recovered. If this occurs, turn off the electrical supply to the outdoor unit immediately, front seat (close) vapor service valve, and recover any remaining refrigerant.
- Turn off the electrical supply to the indoor unit.
- Disconnect the condensate drain line.
- WARNING PERSONAL INJURY HAZARD
- Failure to follow this caution may result in personal injury.
- The use of a torch may cause oil to catch fire, resulting in personal injury or death. To remove components use a tubing cutter only.
- Disconnect liquid and vapor lines from the indoor coil. Use a tubing cutter to cut the lines.
- Remove coil access and fitting panels.
- Remove 1 screw securing the coil to the unit casing.
- Remove the coil/pan assembly from the unit.
- Place the assembly on a flat surface. On units manufactured prior to 1996, remove two screws securing coil support columns to the pan (Fig. 30).
- Rotate columns 90°, pull away from the coil, and remove columns from the assembly.
- Remove two screws securing coil to condensate pan (Fig. 30 and Fig. 31).
- Remove the coil from the condensate pan.
- Attach the newly painted Top Seal to the new coil using brass-colored screws included with the packaging (Fig. 30 and Fig. 31).
- Remove the screw at the bottom of the coil extension and reuse to attached Coil Baffle in the same location. Long side of the baffle toward the pan (Fig. 30 and Fig. 31).
- Install new coil into condensate pan using two original screws and two support columns.
- Install a new coil pan assembly into a unit and secure it with one screw previously removed from the unit casing (Fig. 30).
- Reinstall the coil access panel.
- Reconnect liquid and vapor refrigerant lines and condensate drain lines. Install new filter drier(s).
- NOTE: If a torch is used to unbrace the line set, protect the fitting panel with a wet cloth or braze shield as necessary.
- Evacuate line set and indoor coil to 500 microns, back seat (open) liquid and vapor service valves.
- Turn on electrical supplies to indoor and outdoor units.
- Check system refrigerant charge and operation. See Split-System Residential Air Conditioners and Heat Pump Service Manuals for further information.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>