a-Tronix ECS2900 10kW Hybrid Inverter Instruction Manual

June 16, 2024
a-Tronix

a-Tronix logo

ECS2900 10kW Hybrid Inverter
Instruction Manual
LFP Battery System

Tools Required

The following tools will be required to install BS and CS.

a-Tronix ECS2900 10kW Hybrid Inverter - Tools Required

Packing List

For BS

a-Tronix ECS2900 10kW Hybrid Inverter - Packing List

For BM

a-Tronix ECS2900 10kW Hybrid Inverter - For BM

No. Items
C Mounting screw pack
D Fixing bracket
E Footstand
F Communication cable (BMS-inverter)
G Grounding cable
H DC output cable
I Installation guide & User manual
J Expansion tube2 &Expansion screw2
K Waterproof cover
L RJ45

Terminals

For BS

a-Tronix ECS2900 10kW Hybrid Inverter - Terminals For BM

a-Tronix ECS2900 10kW Hybrid Inverter - For Bs

Installation Steps

Step 1:
Install a BS with four footstand(Item E )and place it on the ground and adjust it to the level.
After installing the footstand, use a track level bar to confirm the level. Insert the waterproof cover (Item J) into the bottom of the battery and lock it in place with the clip.

a-Tronix ECS2900 10kW Hybrid Inverter - Installation
Steps Step 2:
Place the battery 20mm against the wall.

Note:
Please make sure the Operating St-atus LED is on your left handside when you facing the battery model.

Step 3:
Stack the batteries one by one. Step 4:
Place the two fixing brackets (Item D) close to the wall and install them on both sides of the battery. Step 5:
Mark the wall through the bracket hole.
Step 6:
Punch after removing the BM. Drill holes with electric drill, make sure the holes are at least 50mm deep, and then tighten the expansion tubes (Item J).
Step 7:
After stacking BM again, fix the battery on the wall. Schritt 8:
Fix the mounting screw packs on both sides of the battery, the installation is over. Note: Please make sure each system including 1 BM and 1 BS.BS less than 6(1~6) pieces:

Wiring Steps

A: Connect the inverter and make sure the wiring position is correct, as shown in the figure below.
Note : Inverter wiring refer to the inverter user manual.
For outdoor use,please use item L and proceed as follows
Connection steps:
Strp 1:Prepare a standard network cable and cable connector, then insert the network cable through the cable connector.

Step 2: Crimp the cable with a Rj45 plug which is inside of the cable connector.

a-Tronix ECS2900 10kW Hybrid Inverter - network cableIf the usage is indoor, please use item F
Step 3: Insert the cable connector into BMS port at the bottom of inverter and screw it tightly.

a-Tronix ECS2900 10kW Hybrid Inverter - tightlyB: Connect the grounding cable. The figure is shown in below.

System Start Up

  • When the grid-connected system is put into operation, the inverter should be switched on first to prevent the current pulse of the inverter from rising to the battery pack.
  • All installations and operation must comply with local electrical standards.
  • Check all power cables and communication cables carefully.
  1. Turn on the POWER switch.
    • Turn on DC switch and press the POWER switch, firstly Master LED will light up once, and then the BMS Status LED will light up for 0.5s,Operating Status LED will light up for 1s at the same time,it means that the system works normally.

                a-Tronix logo10-203-00349-00
V1.0.1

Documents / Resources

| a-Tronix ECS2900 10kW Hybrid Inverter [pdf] Instruction Manual
AX 5.76kWh, ECS2900, ECS2900 10kW Hybrid Inverter, 10kW Hybrid Inverter, Hybrid Inverter, Inverter
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

a-Tronix User Manuals

Related Manuals