Honeywell FS20X Fixed Flame Detector User Guide
- June 16, 2024
- Honeywell
Table of Contents
Honeywell FS20X Fixed Flame Detector
Product Information
Specifications
- Spectral Sensitivity :
- FS24X Plus: 3IR
- Sensitivity (feet ):
- FS24X Plus : 200
- FS20X: 200
- FS10 : 8
- FS7 : 200
- Response Time :
- FS24X Plus : 10 seconds
- FS20X : 6 seconds
- FS10 : 5 seconds
- FS7 : 6 seconds
- Enclosures :
- FS24X Plus : 2
- FS20X : 3
- FS10 : 4
- FS7 : 6
- Field of View (Conical):
- FS24X Plus: 5000
- FS20X: 200
- FS10 : 200
- FS7 : 200
- Communication:
- All models have standard communication options
- Certifications:
- FS24X Plus : SIL Rating available on request
- Mounting Bracket :
- All models have mounting brackets
- Conduit Entries :
- All models have conduit entries
- Operating Temperature :
- All models have standard operating temperature range
- Analog Output (4-20mA):
- All models have analog output
- Relays :
- All models have relays
- Diagnostics :
- All models have diagnostic features
- Fault Event Logs :
- All models have fault event logs
- FirePicsTM :
- All models have FirePicsTM feature
Product Usage Instructions
Step 1 : Mounting the Flame Detector
To ensure proper installation, follow these steps:
- Select a suitable location for mounting the flame detector based on the specific application and the detector’s field of view.
- Use the provided mounting bracket to securely attach the flame detector to a stable surface.
- Ensure that the conduit entries are properly aligned for easy wiring.
Step 2 : Wiring the Flame Detector
Follow these steps to wire the flame detector:
- Connect the appropriate wires to the conduit entries of the flame detector.
- Route the wires through the conduit to the control panel or monitoring system.
- Make sure to follow the wiring diagram provided in the product manual for proper connections.
Step 3 : Setting up Communication
If required, set up communication between the flame detector and the control panel or monitoring system using the provided communication options.
Step 4 : Testing and Calibration
Before putting the flame detector into operation, it is important to perform testing and calibration:
- Ensure that power is supplied to the flame detector.
- Activate the test mode on the flame detector to simulate a fire event.
- Observe the response of the flame detector and verify that it detects the simulated fire.
- If necessary, adjust the sensitivity or other settings according to the product manual for optimal performance.
FAQ
Q: What is the spectral sensitivity of the FS24X Plus flame detector?
A : The FS24X Plus flame detector has a spectral sensitivity of 3IR, allowing it to respond to hydrocarbon and hydrogen fires.
Q: Can the FS Series detectors be used in offshore drilling platforms?
A : Yes, the FS Series detectors, including the FS24X Plus, are suitable for use in offshore drilling platforms.
Q: Do the FS Series detectors have diagnostic features?
A : Yes, all models in the FS Series have diagnostic features to help monitor the detector’s performance and detect any faults.
FLAME PRODUCT GUIDE
FS SERIES FLAME DETECTORS
QUICK REFERENCE
- See product manual for full details
- Standard option
- SIL Rating : FMEDA available on request
- Contact Honeywell for availability
INDUSTRIAL APPLICATIONS
FS24X PLUS
ADVANCED FLAME DETECTOR
Honeywell’s FS24X Plus 3IR flame detector responds to hydrocarbon and hydrogen fires in a solid field of view, providing fast and reliable protection against a wide range of fires.
Enhance your overall fire and gas safety by deploying reliable flame detection that can see through rain, fog and smoke better than other technologies. Designed for demanding industrial applications, the FS24X Plus helps businesses protect people, plants, and processes should a detectable fire occur.
FEATURES
- WideBand IR Technology
- Selectable detection sensitivities
- 90° cone of vision; 120° cone of vision (50% on axis range)
- Real-time clock for accurate time dating of events
- FirePic — pre-fire event data storage
- Event log with date and time stamp
- HART® and Modbus communication standard
- Sink, Source or Isolated 4-20 mA analog output
- Alarm, Fault and Auxiliary relays
- Automatic optical path and electronic self-test
- Wide operating temperature range
- Electronics module with components protection for easy plug-in terminations and field installation
- Two 3/4″ NPT or M25 conduit entries
- Aluminum or stainless steel housing
- FM, ATEX, CE mark approvals
- IEC61508 SIL 2 Certified
- FlameManager software for programming, diagnostics, and downloading of FirePics and event log
BENEFITS
- Delivers robust flame and fire protection
- Maintains coverage while operating in challenging, low-visibility conditions, due to it has advanced solid-state, wide-band sensors
- Uses advanced diagnostics, including window clarity, to maintain site protection
- Enables simple mechanical installation when combined with the included sunshade and SM4 mounting bracket (a marine-version mount is also available)
- Allows quick electrical installation, with its two cable inlets and plug in connections
- Quick and easy to set up with the included PC software
- Integrates easily into your systems because it has multiple userselectable outputs, including 4-20mA, Relays, HART® and Modbus
- Clearly communicates current status, even from a distance, with a high-visibility LED HALO ring: Green (Normal), Yellow (Fault/ Warning) or Red (Alarm)
- Requires minimal maintenance for trouble-free operation: internal diagnostics and warnings drive maintenance; simple test lamp allows quick and easy testing at distance (no need to climb to the instrument); replaceable electro-optics modules enable convenient field replacement
MARINE CERTIFICATIONS
- ABS
- Lloyds
- BV
- DNV
- MED
- USCG
FS24X PLUS
FS24X PLUS 3IR FLAME DETECTOR
PART NUMBER | DESCRIPTION |
---|---|
FS24XP-ANGXX | 3IR – AL – 3/4″ NPT kit includes mount and sunshade |
FS24XP-AMGXX | 3IR – AL – M25 kit includes mount and sunshade |
FS24XP-SNGXX | 3IR – SS – 3/4″ NPT kit includes mount and sunshade |
FS24XP- SMGXX | 3IR – SS – M25 kit includes mount and sunshade |
FS24XP-ANGXM | 3IR – AL – 3/4″ NPT kit includes marine mount and sunshade |
FS24XP-AMGXM | 3IR – AL – M25 kit includes marine mount and sunshade |
FS24XP- SNGXM | 3IR – SS – 3/4″ NPT kit includes marine mount and |
sunshade
FS24XP-SMGXM| 3IR – SS – M25 kit includes marine mount and sunshade
ACCESSORIES
PART NUMBER | DESCRIPTION |
---|---|
SM4 | Stainless steel swivel mounting assembly |
SM4-M | Stainless steel swivel mounting assembly – Marine Version |
TL- 2055 | Test lamp for FSX and FSX Plus, explosion proof, includes |
universal charger
TL- 1055| Test lamp for FSX and FSX Plus, non-explosion proof,
includes universal charger
FS24XP-NFPA-KIT| NFPA conversion kit (terminal blocks)
SH- 001| Stainless steel sunshade
SPARE PARTS
PART NUMBER / DESCRIPTION
- FS24XP-PUCK/ FS24X Plus – 3IR – Spare Puck Kit
- FSX-A006 /Replacement bulb for TL-1055 or TL-2055
FS20X
MULTI-SPECTRUM FLAME DETECTOR
The FS20X is part of the FSX family of advanced technology Electro-Optical Flame Detectors and is a quantum leap in integrating infrared and ultraviolet sensing technologies.
Based on the foundation of the highly successful and reliable SS4 detector, the FS20X is a multi-spectrum (UV/Dual IR/VIS) fire and flame detector with a proven UV solar-blind Sensor. The FS20X exhibits fast false-alarm-free response to fires over a wider temperature range and with long detection distance.
FEATURES
- WideBand IR Infrared combined with Ultraviolet
- Detection range greater than 200 feet to 1 square foot heptane fire
- Electronic Frequency Analysis
- Visible sensor for optimum false alarm rejection
- Selectable detection sensitivities
- Solar blind 90° cone-of-vision
- Dual microprocessors for reliable performance
- Real-time clock for accurate time dating of events
- FirePic — up to 6 pre-fire event data storage
- Event log — up to 200 events with date and time stamp
- Built-in RS-485 Modbus Communication
- Built-in non-isolated 4-20 mA analog output (sink or source)
- Alarm, Fault and Fire Verification relays
- Automatic Optical Path and Electronic Self-Test
- Wide operating temperature range
- Electronics Module for components protection with plug-in terminations for easy field installation
- Two 3/4 inch NPT or 25 mm conduit entries
- FM, ATEX, CE mark approvals
- Meets SIL 2 requirements
BENEFITS
- Detects hydrocarbon and non‑hydrocarbon fuel fires in tough environmental conditions
- Minimal maintenance for trouble-free operation
- PC software and Interface Module (FSIM) for fault diagnostics real-time graphs (RTGs) and downloading of FirePics and event log
- Suitable for a wide variety of applications
FS20X SERIES
FS20X-211 SERIES, STANDARD TEMPERATURE RANGE -40° TO 85°C
PART NUMBER | DESCRIPTION |
---|---|
FS20X-211-21- 2 | Dual IR/UV copper-free aluminum enclosure with (2) |
3/4″ NPT entries, FM, cFM for Class I, Division 1, Groups A, B, C, D; Class
II, Division 1, Groups E, F, G; Class III
FS20X-211-22- 2| Dual IR/UV 316 stainless steel enclosure with (2)
3/4″ NPT entries, FM, cFM for Class I, Division 1, Groups A, B, C, D; Class
II, Division 1, Groups E, F, G; Class III
FS20X-211-23- 3| Dual IR/UV copper-free aluminum enclosure with (2)
M25 entries, FM, cFM, ATEX, IECEx for Class I, Zone 1
FS20X-211-24- 3| Dual IR/UV 316 stainless steel enclosure with (2)
M25 entries, FM, cFM, ATEX, IECEx for Class I, Zone 1
FS20X-211-21- 4| Dual IR/UV copper-free aluminum enclosure with (2)
3/4″ NPT entries, INMETRO
FS20X-211-22- 4| Dual IR/UV 316 stainless steel enclosure with (2)
3/4″ NPT entries, INMETRO
FS20X-211-23- 4| Dual IR/UV copper-free aluminum enclosure with (2)
M25 entries, INMETRO
FS20X-211-24- 4| Dual IR/UV 316 stainless steel enclosure with (2)
M25 entries, INMETRO
FS20X-212 SERIES W ITH HART®, STANDARD TEMPERATURE RANGE -40° TO 85°C
PART NUMBER | DESCRIPTION |
---|---|
FS20X-212-21- 2 | Dual IR/UV copper-free aluminum enclosure with (2) |
3/4″ entries, FM/cFM, HART® module factory installed
FS20X-212-22- 2| Dual IR/UV 316 stainless steel enclosure with (2)
3/4″ entries, FM/cFM, HART® module factory installed
FS20X-212-23- 3| Dual IR/UV copper-free aluminum enclosure with (2)
M25 entries, ATEX/IECEx, HART® module factory installed
FS20X-212-24- 3| Dual IR/UV 316 stainless steel enclosure with (2)
M25 entries, ATEX/IECEx, HART® module factory installed
FS20X-212-21- 4| Dual IR/UV copper-free aluminum enclosure with (2)
3/4″ NPT entries, INMETRO, HART® module factory installed
FS20X-212-22- 4| Dual IR/UV 316 stainless steel enclosure with (2)
3/4″ NPT entries, INMETRO, HART® module factory installed
FS20X-212-23- 4| Dual IR/UV copper-free aluminum enclosure with (2)
M25 entries, INMETRO, HART® module factory installed
ACCESSORIES
PART NUMBER | DESCRIPTION |
---|---|
FVR- 01 | Field of View Restrictor |
PSU- 12 | Universal charger for Test Lamps for 110-240 VAC with |
international plugs
SH-001| Stainless Steel Sunshade
SM4| Stainless Steel Swivel Mounting Assembly
TL- 1055| Test lamp for FSX and FSX Plus, non-explosion proof,
includes universal charger
TL-2055 Test lamp for FSX and FSX Plus, explosion proof, includes universal charger
REPLACEMENT DETECTOR MODULE
PART NUMBER DESCRIPTION
FS20X-211-10/ FS20X Replacement Detector Module
FS20X-212-10 /FS20X Replacement Detector Module with HART®
SPARE PARTS
PART NUMBER | DESCRIPTION |
---|---|
FSX-A006 | Replacement bulb for TL-1055 or TL-2055 |
FSX-A011 | Grill kit |
PW-3123-0005 | Battery pack for FT-2145/TL-1055/TL-2055 Test Lamp |
FS10
MULTI-SPECTRUM FLAME DETECTOR
A high-speed microprocessor based fire detection and process control system specially designed for liquid and powder coating applications, the FS10 System quickly detects the presence of a flame, reacts by initiating a shutdown of the electrostatic finishing process in a matter of milliseconds and effectively interrupts the fire before residues and wet paint films can ignite. The FS10 System, for liquid paint spray and electrostatic powder coating applications, is a two-stage response system: an Alert for spray gun “fireball” type of fires and a Fire Alarm in 4-5 seconds if the fire continues.
FEATURES
- Multi-spectral digital electro-optical infrared fire detector
- Meets requirements of NFPA 33
- Unique two-stage Alert and Fire Alarm response
- 90° field-of-view with a 15 ft. detection range
- Built-in automatic “through the lens” self-test
- Digital communications with RS-485 interface
BENEFITS
- Resistant to false alarms caused by arcs or corona discharges
- Not sensitive to background radiant energy sources such as paint heaters
- Not affected by absorbing smoke or paint solvent mist in liquid pant spray booths
- Sees through paint, powder or oil residue on the detector’s lens
CERTIFICATIONS
- Explosion-Proof; Class I, Div. 1 & 2, Groups B, C, & D Class II, Div. 1 & 2, Groups E, F, & G, Class III
- FM
FS10 SYSTEMS
CARD CONTROLLER WITH FS10 ELECTRO-OPTICAL FLAME DETECTOR
Includes PC software and manual. Requires backplane card and 24 Vdc.
PART NUMBER | DESCRIPTION |
---|---|
Option- 2FL | 2FL system: liquid paint spray line applications with |
(2) fire signal relay levels
Option-2GF| 2GF system: general finishing applications with process
control and fire alarm signal relays
Option-2WE| 2WE system: powder coating and paint spray line applications
with (2) fire signal relay levels
Option- 2WL| 2WL system: paint spray line applications with (3) fire
signal relay levels
Option-2GE| 2GE system: powder coating and paint spray line applications
with (2) fire signal relay levels
BP- 1| Backplane for 1 card controller
BP- 2| Backplane for 2 card controller
BP-4-L9| Backplane for 4 card controller
SPARE PARTS – FS10 WALL MOUNT CONTROLLER & CARD CONTROLLER
PART NUMBER | DESCRIPTION |
---|---|
SW-5143-001 | Replacement keypad for FS10 wallmount |
FS10-CARD-2FL | Liquid paint spray line applications with (2) fire signal |
relay levels
FS10-CARD-2GE| Powder coating and paint spray line applications with (2)
fire signal relay levels
FS10-CARD-2GF| General finishing applications with process control and
fire alarm signal relays
FS10-CARD-2WL| Paint spray line applications with (3) fire signal relay
levels
FS10-DETECTOR| Model FS10 fire detector for use with wall mount
controller or card controller
FS10-DET-MODULE| Replacement electronics module for fire detector for
the above systems
DETECTOR CABLES – CARD CONTROLLER WITH FS10 ELECTRO-OPTICAL FLAME DETECTOR
PART NUMBER DESCRIPTION
CAB-50 50/ ft. card controller cable; connects fire detector to controller
CAB-100 /100 ft. card controller cable; connects fire detector to controller
FS10 STAND ALONE (UNITIZED)
PART NUMBER | DESCRIPTION |
---|---|
FS10-R30 | Copper-free aluminum housing includes Alert/Fire Early Warning |
Relay, 30 ft. sensitivity (latching alert and alarm relays)
FS10-R30-SS| 316 stainless steel housing includes Alert/Fire Early
Warning Relay, 30 ft. sensitivity (latching alert and alarm relays)
FS10-R30-EC| Copper-free aluminum housing includes Alert/Fire Early
Warning Relay, 30 ft. sensitivity (latching alert and alarm relays), normally
energized with normally closed contacts
FS10-R45| Copper-free aluminum housing, 45 ft. sensitivity (latching
alarm relays)
FS10-R45-SS| 316 stainless steel housing, 45 ft. sensitivity (latching
alarm relays)
FS10-RN30| Copper-free aluminum housing includes Alert/Fire Early
Warning Relay, 30 ft. sensitivity (non-latching alert and alarm relays)
FS10-RN30-SS| 316 stainless steel housing includes Alert/Fire Early
Warning Relay, 30 ft. sensitivity (non-latching alert and alarm relays)
FS10-RN45| Copper-free aluminum housing, 45 ft. sensitivity (non-
latching alarm relays)
FS10-RN45-SS| 316 stainless steel housing, 45 ft. sensitivity (non-
latching alarm relays)
Includes Alarm and Fault relays, 24 Vdc input with temperature range -40°C to
+85°C.
Approvals: FM; Class I, Div. 1 & 2; Groups B, C, & D; Class II, Div. 1 & 2;
Groups E, F, G and Class III.
SPARE PARTS – FS10 STAND ALONE (UNITIZED)
PART NUMBER | DESCRIPTION |
---|---|
FS10-R30-MOD | Replacement electronics module for Model FS10-R30 stand |
alone fire detector (latching alert and alarm relays)
FS10-R30-EC- MOD| Replacement electronics module for Model FS10-R30
stand alone fire detector (latching alert and alarm relays), normally
energized with normally closed contacts
FS10-R45-MOD| Replacement electronics module for Model FS10-R45 stand
alone fire detector (latching alarm relay)
FS10-RN30-MOD| Replacement electronics module for Model FS10-RN30 stand
alone fire detector (non-latching alert and alarm relays)
FS10-RN45-MOD| Replacement electronics module for Model FS10-RN45 stand
alone fire detector (non-latching alarm relay)
Card Controller with FS10 Stand Alone (Unitized)
FS10R-GR-Kit| Stainless steel grill kit for FS10-R and FS10-CS Detectors
(Killark housing) includes:
(1) SS grill, (2) SS brackets, and (2) SS screws
RS-232 Cable| RS232 computer cable for connection from FS7-130-SX,
S7-2175, option-1 or option-2 controllers or interface box to PC
PSU-12| Universal charger for Test Lamps; for 110-240 VAC with
international plugs
ACCESSORIES – FS10 STAND ALONE (UNITIZED)
PART NUMBER | DESCRIPTION |
---|---|
SM4 | Stainless Steel Swivel Mounting Assembly |
FT-S7 | Test lamp, battery operated for testing FS10 and FS7 |
EXPL-1 | DPC-12 extension pole for placing and removing disposable |
protective covers on FS10 detectors
DPC-12| Disposable protective covers for use with FS10 only; keeps
powder or paint off window lens of the FS10 fire detector; 12 per bag
DASA1- P| Air shield for powder applications protects FS10 fire
detector window lens from powder build-up; supplied with fitting for 1/4″
tubing; can also be used with FS24X, FS20X
DASA6- N| Air shield for powder applications protects FS10 fire
detector window lens from powder build-up; supplied with fitting for 6 mm
tubing
FS7
MULTI-SPECTRUM FLAME DETECTOR
The FS7 provides a two-stage response to semiconductor wet bench fires: an Alert to a small fire with a 3 kW heat energy output and an Alarm if the fire grows to a 13 kW heat energy output.
The FS7 Flame Detector system first sends an Alert in response to a small fire (the equivalent of a 4-inch diameter polypropylene pool fire) which may self- extinguish. If the fire does not self-extinguish and grows to the factory mutual specified heat energythreshold of 13 kW (the equivalent of an 8-inch diameter polypropylene pool fire) then the second stage is activated and sends an Alarm in response.
The FS7-2173 is used with FS7-130-SX Controller which supplies power, monitors status and communicates with detectors via the digital RS-485 communication channel. FS7-2173 is supplied with a standard 20 ft. cable connector. Detectors are connected to the controller using the self-locking connectors and junction boxes. This allows for fast and easy connections and eliminates wiring problems. Each detector can store up to six time and date stamped FirePics (pre-event, multi-spectral sensor array data) in non-volatile memory. A controller can also store an event history table in the non-volatile memory which also contains the time and date stamped alert, alarm
FEATURES
- Multi-spectral digital electro-optical radiant energy infrared fire detector
- Unique two-stage fire detection response
- Rugged leak-proof, heat-sealed, acid-resistant, injection-molded polypropylene housing
- Wide 120° field-of-view
- Digital communication withRS-485 interface
- FirePic – time and date-stamped digital fire signatures
- Built-in detector automatic self-test
- Unitized model design for stand-alone operation
BENEFITS
- Resistant to false alarm sources
- Detects hydrocarbon and nonhydrocarbon fires
- Not affected by absorbing smoke, gasses or chemical vapors
- Not sensitive to background radiant energy from electric heaters and ovens
FS7
DETECTOR PARTS
PART NUMBER | DESCRIPTION |
---|---|
FS7-2173 | Viton O-ring for use with FS7-130-SX Controller |
FS7-2173-2RP | Viton O-ring for use with non-latching Alert and Alarm |
relays.
FS7-2173-2RP-K| Kal-rez O-ring for use with non-latching Alert and Alarm
relays
FS7-2173-KALO| Kal-rez O-ring for use with FS7-130-SX Controller
CONTROLLER SYSTEMS
PART NUMBER/ DESCRIPTION
- FS7-130-SX
- Multi-zone Compact Controller designed for fire panels installation; monitors up to (12) Model FS7-2173 detectors; programmable up to 4 zones with relay outputs for Alert and Alarm; requires 24 VDC; FM and CSFM approvals
ACCESSORIES
- PART NUMBER / DESCRIPTION
- FT-S7
- Test lamp, battery operated for testing FS10 and FS7
- FS7-2179
- Junction box for connecting Model FS7-2173 fire detectors in a daisy chain or star configuration; includes (4) Lemo female connectors; required for Model FS7-130-SX applications
INTERCONNECTION CABLES
PART NUMBER | DESCRIPTION |
---|---|
CBMM-5 | 5 ft. cable with Male/Male Lemo connectors (Junction box to |
Junction box)
CBMM-10| 10 ft. cable with Male/Male Lemo connectors (Junction box to
Junction box)
CBMO-20| 20 ft. cable with Male Lemo connector/open pigtail (Junction
box to Model FS7-130-SX Controller or Model S7-2175 Control Panel)
CBMO-50| 50 ft. cable with Male Lemo connector/open pigtail (Junction
Box to Model FS7-130-SX Controller or Model S7-2175 Control Panel)
SPARE PARTS
PART NUMBER / DESCRIPTION
- PSU-12
- Universal charger for test lamps; for 110-240 VAC with international plugs
- PW-3123-0002
- Replacement battery for FT-S7 Tester
QUICK REFERENCE
SPECIFICATIONS | FSL100 UV | FSL100 UV/IR | FSL100 IR3 |
---|---|---|---|
Range (feet)1 | 75 | 75 | 115 |
Cone of vision | 90° | 90° | 90° |
Operating temperature | -40° C to +70° C | -40° C to +70° C | -40° C to +70° C |
Operating temperature – ATEX and FM Class 3611 | -25° C to +70° C | -25° C to | |
+70° C | -25° C to +70° C | ||
IP rating | IP65 | IP65 | IP65 |
Alarm response time | 8 to 30 seconds | 8 to 30 seconds | 8 to 30 seconds |
- See product manual for full details
COMMERCIAL APPLICATIONS
Key :
- Not recommended
- Suitable (pending end-user review)
- Recommended
FSL100 SERIES
FLAME DETECTOR
The FSL100 Series utilizes sophisticated sensing and signal analysis to detect fires quickly while also rejecting false alarms. FSL100 products may be small and lightweight for easy installation but they are designed to work in tough environments both indoors and outdoors. With a large field of view, they can detect a range of different types of fires including hydrocarbon and non hydrocarbon.
The FSL100 series consists of UV, UV/IR and IR3 flame detectors and is the latest generation of mid-market flame detectors from Honeywell.
UV (ULTRAVIOLET) FLAME DETECTOR
For more information
sps.honeywell.com
HART is a registered trademark of FieldComm Group, Inc. HIS-CT- FlamePrdctGuide-EN-LTR-2V0-16may2023 © 2023 Honeywell International Inc.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>