EMERSON 50M56X-843 Universal Integrated Single Stage 120V Hot Surface Ignition Control Kit Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
- EMERSON 50M56X-843 Universal Integrated Single Stage 120V Hot Surface
- DESCRIPTION
- ELECTRICAL SPECIFICATIONS
- INSTALLER MUST READ
- MOBILE APP CONFIGURATION (PREFERRED)
- ON BOARD CONFIGURATION (7-SEGMENT OPTION)
- INSTALLATION
- MOUNTING
- APPLICATION & OPERATION NOTES
- APPLICATION & OPERATION NOTES
- WIRING DIAGRAM
- TROUBLESHOOTING
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
EMERSON 50M56X-843 Universal Integrated Single Stage 120V Hot Surface
Ignition Control Kit
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
50M56X-843 is an aftermarket universal replacement control kit for single stage furnace applications with PSC or ECMx (constant torque) blower motors. A HotRodTM 120V ignitor is included to replace ignitors in most furnaces as well as upgrade 80V systems to 120V. With 50M56X-843 no complex adapter harnesses are required, instead all connectors and terminals used in the major OEM brands are included on the control itself. This allows for OEM wiring to be connected directly to the control for a faster and easier installation.
ELECTRICAL SPECIFICATIONS
Specification | Value | Unit |
---|---|---|
Input Voltage | 18-30 | VAC |
Input Current | Max 800 | mA |
Line Frequency | 60 | Hz |
Inducer Relay at 120V | 2.8A | FLA |
Gas Valve Relay @ 30V | 1.5 | Amperes |
Ignitor Relay @ 120V | 1.2 | Amperes |
PSC Circulator Relay | 10 | FLA |
OPERATING TEMPERATURE RANGE: -40° to 176°F (-40° to 80°C)
HUMIDITY RANGE: 5 to 95% relative humidity (non-condensing)
GASES APPROVED: Natural, Manufactured, Mixed, Liquid Petroleum, and LP
Gas Air Mixtures
INSTALLER MUST READ
APPLICATION AND OPERATION NOTES ON
Included in the box:
- 1 – 50M56X-843 Ignition Control
- 1 – HotRodTM Ignitor
- 1 – Installation Instructions
- 4 – 1/2” Sheet Metal Mounting Screws
- 6 – 3/16” QC crimp on terminals
- 6 – 1/4” Female Spade Terminals
- 5 – Mounting Standoffs
View Installation Resources
WARNING
Failure to comply with the following warnings could result in personal injury or pro perty damage.
- Installation should be done by a qualified heating and air conditioning contractor or licensed electrician.
- All wiring must conform to local and national electrical codes and ordinances.
- Following installation or replacement, follow manufacturer’s recommended installation/service instructions to ensure proper operation.
FIRE HAZARD
- Do not exceed the specified voltage.
- rotect module from direct contact with water (dripping, spraying, rain, etc.).
- If the module has been in direct contact with water, replace the module.
- Label all wires before disconnection when servicing modules. Wiring errors can cause improper and dangerous operation.
- Route and secure wiring away from flame.
SHOCK HAZARD
- Disconnect electric power before servicing.
- Ensure proper earth grounding of appliance.
- Ensure proper connection of line neutral and line hot wires.
- Ensure module has ¼” clearance between all sides of module and grounded metal.
MOBILE APP CONFIGURATION (PREFERRED)
For fastest setup, use White-Rodgers Connect App:
- Download from iOS App Store or Google Play Store
- pen White-Rodgers Connect App
- Touch “Connect to Control” on the home page
- Place Device above NFC Logo on the Module, and wait for a checkmark
- Configure all settings in App
- Touch “Update Control”
- Place Device above NFC Logo on the Module, wait for check mark
- App tutorial available on the homepage of White-Rodgers Connect
- NFC is available on iOS 13 and greater (iPhone 7 and up) and all Android devices
ON BOARD CONFIGURATION (7-SEGMENT OPTION)
Condition| LED
Display
| Description
---|---|---
Module Power Up| 888| During power up, LEDs remain steady
Auto Configuration| dcF| Automatic Configuration Must Complete before entering
standby ~30 sec
Standby| 0n| Control ready to configure or respond to calls
Action| Module Status| Button Press
---|---|---
Enter Configuration Menu| In Standby Mode| OPTION
Advance 1 Option Menu Item| In Configuration Menu| OPTION
Enter Selections Menu Level| At Options Menu Level| SELECT
Advance 1 Selection Item| At Selections Menu Level| OPTION
Confirm Selection| On Chosen Selection| SELECT
Exit Configuration Menu| On No. 22 in Configuration Menu| OPTION
Note: See Table 1 on page 3 for Configuration Menu Options and Selections
INSTALLATION
Table 1: Configuration Menu Options | *Factory Default Setting |
---|---|
No. | Option Menu Item |
Description / Notes
1| Active Fault Menu| Err| “Exx”| Cycles through up to 4 active errors. XX=2
digit Fault Code ex. E01
2| Firmware Version| Cr| “rXX”| Displays Firmware Version Number
3| Display Selected Harness Configuration| dSH| “Hxx”| Displays Harness /
Connector (Auto) Configuration ex. H23
4| Reset to Factory| Rst| no, yES| Resets configurations to factory defaults
5| Clear Harness Configuration| CHC| no, yES| Clears Harness / Connector auto
configuration data from memory
6| Blower Motor Type Selection| bLr| PS2*, PS3, EC2, EC3, EC4, EC5, EC9|
Select according to OEM motor type either:
PS C-2 & 3 speed, or EC Mx 2, 3, 4, 5 or 9 speed
7| Pre-purge| PrE| 15, 30| Duration (Seconds)
8| Inter-purge| InT| 15, 30, 45, 60| Duration (Seconds)
9| Post purge| PST| 5, 10, 15, 25, 30, 90| Duration (Seconds)
10| Constant Fan Speed ECMx| FSd| Fxx (xx: Blower Speed Number) Default – F01|
Fan Speed Setting for ECMx Blower Connectors (6-Pins)
11| 1st Stage Cool Speed ECMx| CS1| Fxx (xx: Blower Speed Number) Default –
F04| Low Cool Setting for ECMx Blower Connectors (6-Pins)
12| 2nd Stage Cool Speed ECMx| CS2| Fxx (xx: Blower Speed Number) Default –
F05| High Cool Speed Setting for ECMx Blower Connectors (6-Pins)
13| Heat Speed ECMx| HSd| Fxx (xx: Blower Speed Number) Default – F01| Heat
Speed Setting for ECMx Blower Connectors (6-Pins)
14| Fan On Delay| Fnd| 0, 2, 5| Duration (Seconds)
15| Fan Off Delay| FFd| 0, 2, 60, 90, 120, 180| Duration (Seconds)
16| Cool On Delay| Cnd| 0, 2, 3, 5, 6| Duration (Seconds)
17| Cool Off Delay| CFd| 0, 2, 3, 5, 45, 60, 80, 90| Duration (Seconds)
18| Heat On Delay| Hnd| 15, 20, 22, 25, 30, 40,
45, 60, 66
| Duration (Seconds)
19| Heat Off Delay| HfD| 60, 90, 100*, 120, 135,
140, 150, 160, 180, 225
| Duration (Seconds)
20| Automatic Heat Staging (Hybrid Only)| AHS| OFF, 05, AUt| Staging Time for
Goodman Hybrid System – See Application Notes pg. 5
21| Rollout Input Bypass| rOb| no, yES| Bypass Rollout Input – See
Applications Notes pg. 6
22| Self-Test Mode| StE| no*, yES| Initiates Self-Test Mode
Table 1: Configuration Menu Options
Note: Table 1 shows every configuration option available on 50M56X-843. However, not all OEMs use the same configuration options. Once the automatic configuration process is complete, some settings not relevant to the detected OEM application may no longer appear in the control’s menu or WR Connect app.
Tip: Note the settings on the OEM control being replaced in the space in the margins of this manual or by circling the corresponding setting value in the selections menu column in Table 1.
NOTE: All wiring should be installed according to local and national electrical codes and ordinances
-
Disconnect electrical power and shut off gas supply to unit, then remove unit access panels.
-
Mark and disconnect all wires from the existing control, then remove existing control. Tip: Take a photo of the old control wiring for reference.
-
Mount 50M56X-843 in the unit using one of the mounting options noted in the Mounting section. Be certain not to damage any components such as wire harnesses or blower wheels when drilling or installing screws.
-
Identify the connector type on the board being replaced and/or the OEM wiring harness and attach it to the appropriate mating connector on the 50M56X-843 control. Note: Some mating connectors on the control have subtle differences such as pins vs sockets in the connector, see the Wiring Diagrams section for more info on proper OEM connector identification.
-
Connect all the remaining individual wires to the new 50M56X-843 control board referencing the Wiring Diagrams section as needed.
-
ensure all wires and connectors are secured to the control board and unused blower speed wires are attached to the PARK terminals. Note: PARK terminals are 3/16” spades but can be used to store unused PSC (1/4”) or ECMx (3/16”) speed taps since PARK terminals do not provide an electrical connection to the attached motor leads.
-
Use the WR Connect App or 7-Segment display to match the settings of the OEM control as described in the Configuration and Application Notes sections.
-
Install the included HotRodTM ignitor.
Note: This is recommended for all units but is required for all 80V controls listed in the Application Notes section. -
Allow the control to complete its Automatic Configuration sequence (takes about 30 seconds).
-
Reinstall unit access panels and reconnect electric power. Restore gas supply to the unit. Verify unit operation in heating, cooling, and fan only modes.
MOUNTING
50M56X-843 can be mounted in any orientation and has multiple mounting points designed to align with many common OEM designs. Take note of how the original control was mounted, and if possible utilize the same method for the replacement. However, an exact alignment with an OEM mounting pattern is not required as the control can be mounted to any suitable sheet metal surface in the furnace.
Mounting Tabs & Screws: Any of the 7 tabs around the perimeter of the control can be used to secure the control in conjunction with the included ½” self drilling sheet metal screws. Unless there is a specific OEM mounting method that is being replicated (which involves additional support points from the OEM bracket) a minimum of 2 sheet metal screws is recommended to adequality secure the control, but up to 4 can be used. The mounting tabs have been designed to be easily cut off with a pair of snips or sidecutters to gain additional mounting space if needed.
Mounting Holes & Standoffs: The included standoffs are designed to be used in conjunction with common OEM standoff mounting patterns. For standoff mounting, plug standoffs directly into the 4 corner holes on the back side of the plastic tray. Once standoffs are secured to the tray lock the standoffs into matching locations in the sheet metal bracket with firm even pressure on the control cover.
APPLICATION & OPERATION NOTES
Ignitor Replacement
The following cross reference control numbers are for 80V ignition systems
that must be upgraded to 120V by replacing the OEM ignitor with the included
HotRodTM ignitor. However, it is recommended to replace original 120V ignitors
as well.
10207720 | 23W5101 | 50A65-475 | 56L8401 | CNT07737 | D342359P01 |
---|---|---|---|---|---|
100925-01, -02, -03 | 30W25 | 50A65-476 | 69M08 | CNT07738 | D342359P02 |
102077-17 | 30W2501 | 50A65-5165 | 69M0801 | CNT3076 | D342359P03 |
10207720, S | 32M88 | 50A65-843 | 69M15 | CNT3742 | D342359P04 |
10M93 | 32M8801 | 50A66-843 | 69M1501 | CNT3798 | L43-226 |
10M9301 | 350836 | 50A67-476-01 | CNT03076 | CNT5164 | L46-846 |
12L69 | 3XA76 | 50A67-476-02 | CNT03742 | CNT5165 | PCBBF118, S |
12L6901 | 50A65-120, -121, |
-122, -123, -743
| 50A67-507-01| CNT03798| D341213P01| X13650818030
17W92| 50A65-143| 50A67-507-02| CNT04711| D341396P01|
17W9201| 50A65-288| 56L83| CNT05164| D341396P03
21D83M-843| 50A65-289| 56L8301| CNT05165| D341396P04
23W51| 50A65-474| 56L84| CNT06664| D341396P05
Goodman Hybrid 2-Stage Compatibility (Special Case)
The following cross references are for controls related to a unique system
known as the “Goodman Hybrid.” This “Hybrid” system is comprised of a furnace
with a 2-stage gas valve paired with a single speed (always high) inducer
motor and a single stage blower motor. 50M56X-843 is able to operate these
unique applications in addition to standard single stage furnaces. These
furnaces rely on logic in the control (rather than a 2-stage thermostat) to
shift between 1 and 2 stage heating. Configuration menu item number 20 allows
the control to utilize either a fixed timing (5 minutes) or an adaptive
algorithm for heat staging. Alternatively, the staging can be turned off
completely and the control will operate as standard 1-stage IFC.
Air Conditioner & Heat Pump
- Systems retrofitted with 50M56X-843 can be paired with either a 1 or 2 stage air conditioner or heat pump.
- When paired with a 1-stage unit, connect the Y output from the thermostat to Y/Y2 input on the control. For 2- stage units, connect the Y1 output from the thermostat to the Y1 input on the control and the Y2 output from the thermostat to the Y/Y2 input on the control.
50M56X-843 will provide auxiliary heating during a heat pump defrost cycle if it receives heat and cool calls simultaneously (W + any Y)
Dehumidification
Note: This feature requires a connection to a thermostat with a dehumidification function (DHUM terminal).
- DHUM input is reverse logic in that presence of a 24V signal = no dehumidify demand, and the absence of a 24V signal = dehumidify demand
- Dehumidify demand with a Y1 input runs the blower at the speed selected for the constant fan (heat speed is the default) for those applications that do not have a dedicated low cool speed
- Dehumidify demand with a Y / Y2 input runs the blower at the cool speed for 10 minutes, then reduces the blower speed from cool to low cool (constant fan) for 10 minutes, then returns to the cool speed for 10 minutes
- Alternating 10-minute cycles continue for as long as there is a call for High Stage cooling (Y/Y2)
- When the call for cool is satisfied and there is a dehumidify demand, the blower off delay is reduced to 5 seconds
Automatic Configuration Process
50M56X-843 automatically configures its functional operation (including
connector pinouts and certain menu options) to match that of the OEM furnace
and control being replaced across a variety of applications. This process
allows for plug-and-play wiring of multiple OEM harnesses with different
pinouts into the same physical connector on the 50M56X-843 control, and thus
the elimination of adapter harnesses from the kit. This process takes
approximately 30 seconds at first power up and must be allowed to complete to
ensure proper operation. Automatic configuration is discussed in further
detail below for informational and troubleshooting purposes.
Note: Most settings listed in the Configuration Menu table will remain user configurable and in their default state and may require further adjustment to match that of the OEM control. During the automatic configuration process the control is able to configure for specific OEM applications and harness pinouts by detecting differences in OEM wiring and which
APPLICATION & OPERATION NOTES
loads are present on specific connector terminals. It is critical that system wiring match one of the scenarios outlined in the Wiring Diagrams section and that all system components (such as inducer motors and pressure switches) are operating properly prior to automatic configuration taking place. Automatic configuration occurs during the first power-up and is verified at the next power-up. After the same application is detected 2 consecutive times, the corresponding configuration is written to memory and automatic configuration will no longer occur at power-up. However once stored, the automatic configuration can always be cleared using menu option 5 (CHC). If an automatic configuration error code (E41) is reported, verify all wiring connections are correct, all components in the system are present and functioning properly before power cycling the control and attempting another automatic configuration process.
Note: A single valid automatic configuration is sufficient to proceed with control installation and verification testing.
Blower Type Selection and Speed Settings
50M56X-843 is able to replace furnaces with PSC or ECM (constant torque)
blower motors. The motor type present in the furnace must be configured by the
installer based on the options in the Configurations Menu option number 6
(BLR). PSC options include 2-speed (heat & cool) or 3-speed (heat, cool, and
fan). ECM options include 2 (heat & hi-cool), 3 (heat, hi-cool, & fan), 4
(heat, lo-cool, hi-cool, & fan), 5, and 9 speed options. For 5 (F01 – F05) and
9 (F01-F09), speed blowers use the Configuration Menu to select the
appropriate speed for cool, heat, and fan. For 2-speed motors constant fan (G)
calls will default to the heat speed.
Note: If additional fan speed connections are available via the motor wiring but not in use, the system can be upgraded to operate with additional blower speeds in certain scenarios, for example, constant fan, dehumidification, and/or high and low cooling. Reference OEM literature for more information on fan speed connections and approximate CFM.
Roll Out Configuration
Certain Trane, American Standard, and York (including York P3UR / PCLU)
furnaces do not have an individually monitored rollout switch in their main
harness wiring configuration and instead place the rollout switch in series
with other limit switches for example the high limit (HL) switch. As these
models share the same connector #8 in the Wiring Diagrams with other OEMs that
utilize a separately monitored rollout switch between pins 5 and 11. Instead
of using a physical shunt jumper or wire accessory to bypass the rollout input
for these applications, changing Configuration Menu setting number 21 (rOb) to
Yes will digitally bypass the rollout inputs. Note: Failure to bypass the
rollout input for certain Trane, American Standard, and York furnaces that do
not require one will disable furnace operation and result in a rollout switch
open error (E07).
OEM Wiring Terminal Spacing Connector Retrofit (Special Case)
Some OEM furnaces, for example Trane and American Standard, have a plastic
connector housing that groups together line and neutral spade terminals. This
is done so they can plug onto OEM controls all at once saving time on the
manufacturer’s production line albeit at a cost of expanded spacing and
therefore limited room for additional accessory terminals such as electronic
air cleaners and 120V humidifiers.
If encountered during replacement, simply snip off the wire near the plastic connector housing, strip the insulation, and crimp on one of the provided ¼” female spade terminals. Then connect the black wires to Line terminals (Line-H, XFMR-H, & CIRC-H) and connect white wires to neutral terminals.
Note: The 3 line connections (Line-H, XFMR-H, & CIRC-H) are electrically continuous as are all neutral terminal connections. As such, the order of connection is arbitrary in a retrofit scenario as long as all 120V line connections (black wires) are connected to a line terminal and all 120V neutral connections (white wires) are connected to a neutral terminal.
FLAME SENSOR KIT Required on RHEEM/ RUUD Models (1994 and earlier)
If the control being replaced has 2 green lights (no amber light), and a date
code of 3294 or earlier, a Flame Sensor Kit, RHEEM part number 62-24044-71 is
required (not available through White-Rodgers).
Replacing Previously Installed Universal Controls
When replacing a failed Resideo/Honeywell H9200U1000, ICM ICM2812-KIT &
ICM-2812, or White-Rodgers 50M56U-843 & 50X57-843 (unlikely scenario),
identify and remove any wiring adapter harness between OEM furnace wiring and
the failed universal control prior to replacement with 50M56X-843.
Status Display During Active Calls
During an active call for heat, cool, or constant fan, the display will
alternate between up to 3 status indicators. As outlined in Table 2, the first
indicator will display the active call from the thermostat. If applicable the
active motor speed selection will also be displayed alongside flame current
(in heating mode only). If an active error code is present, it will be
displayed in an alternating pattern with the others discussed above.
WIRING DIAGRAM
Properly Matching OEM Wiring Harness Connectors with 50M56X-843 Connectors
- Identify connector type in OEM harness or on the OEM control and plug OEM wiring directly onto matching connector on 50M56X-843
- No adapter harnesses are necessary, remove previously installed adapter harnesses if present
- Take extra care with connectors that are visually similar such as 2 & 3, 5 & 6, 8 & 9, 10 & 11
- Black connectors on 50M56X-843 contain sockets (which mate with harnesses containing pins)
- White connectors on 50M56X-843 contain pins (which mate with harnesses containing sockets)
- White & black connectors on 50M56X-843 may mate with different colored harness connectors
- For 2 & 3: 2 is white indicating pins, 3 is black indicating sockets
- For 5 & 6: 5 does not have a latch, 6 does have a latch (see details below)
- For 8 & 9: 8 is white indicating pins, 9 is black indicating sockets
- For 10 & 11: 10 has 10 pins, 11 has 11 pins. Match OEM connector to proper pin number
6-Socket: Nordyne/Nortek Configuration 6-Socket: Rheem/Ruud Configuration
4-Pin: Goodman/Amana/Trane/American Standard/Lennox/ Allied Air/York/Coleman/Luxaire Configuration
4-Pin: Trane/American Standard Alt. Configuration
4-Socket: Lennox/Allied Air
2-Pin: Goodman/Amana Configuration 2-Pin: Carrier/Bryant/Payne/ICP Configuration
6-Pin Inline: Trane/American Standard
6-Pin Inline: Goodman/Amana
9-Socket: Goodman/Amana Configuration 9-Socket: Goodman/Amana Alt. Configuration
9-Socket: Nordyne/Nortek/Rheem/Ruud Configuration
12-Pin: Goodman/Amana/Trane/American Standard/Lennox/Allied Air/York/Coleman/Luxaire Configuration
12-Pin: Goodman Hybrid Configuration
12-Socket: Lennox/Allied Air
10-Pin Inline: Trane/American Standard 10-Pin Inline: Trane/American Standard Alt. Configuration
11-Pin Inline: Carrier/Bryant/Payne/ICP 11-Pin Detail: PIN 3 – Housing Pressure Switch Input 11-Pin Detail: PIN 3 – Not Connected 11-Pin Detail: PIN 3 – Inducer Ground
Thermostat Connections
Note: Detailed wiring diagrams for connectors 1-12 are only representative of the general interconnec-tion between control inputs and outputs (e.g. PSI & PSO) and system components (e.g. pressure switch). OEMs often place multiple limit devices and pressure switches in series. Reference OEM wiring diagrams for additional info. Wire colors may not match all systems.
TROUBLESHOOTING
Condition| LED 1| LED 2| LED 3| Comment/Troubleshoot
Step
---|---|---|---|---
Line Frequency Error / Internal Fault| E| 0| 0| Verify 60 Hz line frequency,
Replace control
Pressure Switch Open| E| 0| 1| Check pressure switch, inducer, and flue
Flame Detected When no Flame Should be Present| E| 0| 4| Check gas valve for
proper operation, check gas valve and safety limit wiring
Open Fuse| E| 0| 6| Locate & repair 24V fault, replace fuse
Rollout Switch Open| E| 0| 7| Check for rollout condition or failed switch
Pressure Switch Stuck Closed| E| 0| 9| Replace failed pressure switch
Gas Valve On Error| E| 1| 1| Check gas valve operation and wiring
Gas Valve Off Error| E| 1| 2| Check gas valve operation and wiring
Ignitor Relay Fault| E| 1| 3| Internal ignitor relay failure, replace control
Ignitor Open Failure| E| 1| 4| Replace failed ignitor
Grounding Error| E| 1| 5| Check control & furnace ground connections
Reversed Line Polarity| E| 1| 6| Hot and neutral wires are reversed
Twinning Error| E| 1| 7| Validate twin configuration for both units
High Limit Switch Open| E| 1| 8| Check for open/failed HL & any aux switches
Lockout – Retries Exceeded| E| 2| 1| Lockout after unsuccessful trial for
ignition
Lockout – Gas Valve Off| E| 2| 2| Gas valve relay internal error, replace
control
Lockout – Recycles Exceeded| E| 2| 3| Lockout after failed relight due to
flame loss
Lockout – Pressure Switch Open| E| 2| 4| Lockout due to open pressure switch
Lockout – HPS Open| E| 2| 5| Lockout for Housing P.S. on condensing units
HPS Stuck Closed| E| 3| 1| Housing P.S. stuck closed – condensing units
HPS Open| E| 3| 2| Housing P.S. not closing – condensing units
Auto Configuration Error| E| 4| 1| See Automatic Configuration Process Notes
NFC Connectivity Error| E| C| 1| NFC comm error, power cycle control & retry
Continuous Fan (G)| F| A| N| Active call for constant fan
Standby| O| n| | Ready to access menus or respond to calls
Control Power Up| 8| 8| 8| Displayed at initial power up
Blower on After Power up| b| O| n| Cool down after power loss with active call
Gas Heat (W) Present before pre-purge or during error conditions| h| t| P| Gas
heat call active before inducer pre purge or with error conditions that
prevent ignition
Gas Heat (W) with Pre-Purge Active| h| p| r| Gas heat call active during pre-
purge period
Gas Heat (W) with Inter-Purge Active| h| I| p| Gas heat call active during
inter-purge period
Gas Heat (W) with Post-Purge Active| h| P| o| Gas heat call active during
post-purge period
Gas Heat (W) Ignitor Warm-up Period Active| I| g| n| Gas heat call active
during ignitor warm-up period
Gas Heat (W) Trial for Ignition Period Active| t| F| I| Gas heat call active
during trial for ignition period
Gas Heat (W) after flame is active| h| t| | Gas heat call with flame present
Single Stage Gas Heat Active (W)| h| t| 1| 1st stage gas heating – Goodman
Hybrid only
Goodman Hybrid Only – 2nd Stage Gas Heat (Autostage)| h| t| 2| 2nd stage gas
heating – Goodman Hybrid only, 2nd stage timing based on AHS menu setting
Single / High Stage Cooling (Y/Y2)| C| L| | Call for high cooling with 1 or 2
stage AC/HP
Low Stage Cooling (Y1)| C| L| 1| Call for low cooling – For 2 stage AC/HP only
Low Flame Current Sense| F| L| o| Check Flame Quality, Clean/Replace Flame
Sensor
Auto Configuration in Progress| d| C| f| Allow 30 seconds for the control to
configure
Operation| Module Status| Action| Duration of Action|
LED Display| Extra Notes
---|---|---|---|---|---
Fault Code Recall
| ****
Standby
| ****
Hold OPTION and SELECT together
| ****
2-5 sec.
| ****
F L T
after 2 sec.
| • A maximum of 5 error codes are stored in the sequence they occur
• Press OPTION button < 1 second to advance to next fault code
• When OPTION button is pressed after last error code, LEDs return to current status of unit
• E n o will be displayed if there are no error codes stored
Fault Code Reset
| ****
Standby
| ****
Hold OPTION and SELECT together
| ****
5-10 sec.
| ****
Alternates between C L r and
F L t
after 5 sec.
| • Once both OPTION and SELECT are released after holding them together for 5-10 seconds, the LEDs will flash C L r 3 times to indicate the error codes have been erased, module will then return to current status
• Error codes are stored in the module’s memory for up to 14 days
Table 2: 7-Segment Display Codes
Note: Thermostat calls are ignored when module is in Error Code Recall or Reset modes
Control Reset
Control reset is automatic after 1 hour in lockout. Removing 24 VAC power to
the control for greater than 10 seconds will manually reset (power cycle) the
control.
Flame Current Display & Test Pins
50M56X-843 has an advanced flame current sense circuit that allows the control
to digitally measure and report flame current on the 7-segment display with
0.1 µA resolution. As discussed in Application & Operation Notes, flame
current is automatically displayed in an alternating pattern with other status
indications during a heat call. Flame current can also be measured with a
voltmeter using the test pins in the location noted in the wiring diagram.
When using this method set the meter to volts DC and place the probes on each
test pin. If a negative reading is observed, simply reverse the polarity of
the meter leads. The reading in volts is directly equivalent to a direct
microamp reading of the flame current (1VDC = 1 µA).
Self-Test Mode
Self-test mode allows the control to test most furnace components without
requiring a call for heat. Enter self-test mode through the configuration menu
option number 22 (StE)
NOTE: Control will terminate Self-Test mode and display the corresponding error code if any system fault occurs. Control will ignore any active thermostat calls during Self-Test.
Sequence is as follows:
- Upon self-test mode entry, the display will flash 3 sets of dashes (- – -) 3 times
- If any error codes have been stored, they will be displayed, if none are stored EnoEno will be displayed
- tSt will be displayed indicating test mode is active and will be alternated with an indicator code for the current step
- The inducer motor will turn on and remain on throughout test mode and Ind will be alternated with tst
- The ignitor will turn on for 15 seconds and Ign will be displayed alternating with tst
- The blower motor runs at the Fan, Heat, and Cool speeds (based on configuration settings) respectively for 10 seconds each. FAn, ht, and CL will be displayed when the corresponding blower speed is on alternating with tst
- Blower and Inducer motors turn off. Self-Test is complete, display will show On indicating Standby mode
TECHNICAL SUPPORT: 1-888-725-9797
Emerson and White-Rodgers are trademarks of Emerson Electric Co. ©2022 Emerson Electric Co. All rights reserved.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>