PRODUCT

Specifications

  • Catalog Number: 6ASF
  • Material: Steel, Spring Steel
  • Finish: Electrogalvanized, nVent CADDY Armour
  • Rod Size (RS): 3/8
  • Width (W): 2 1/4
  • A: 1.300
  • Static Load (F): 100 lb

Product Usage Instructions

Installation

  1. Ensure the surface where the rod hanger will be installed is clean and free from debris.
  2. Insert the shot-fire bracket into the desired location on the surface.
  3. Align the holes of the rod hanger with the holes of the shot-fire bracket.
  4. Push the rod hanger into the shot-fire bracket until it is securely in place.

Additional Product Details The rod hanger uses Powers Fasteners, Inc. part number 50032.

The static load capacity of the rod hanger was established based on a 1″ (25.4 mm) embedment depth and 3,000 psi (20.68 MPa) lightweight concrete. For variations in embedment depth and material, please consult anchors.dewalt.com.

For shot-fired supports in seismic design category D, E, or F,the maximum load is the lesser of 90 lb (400 N) or the published load.

Diagrams

Warning nVent products should only be installed and used as indicated in nVent’s product instruction sheets and training materials. Improper installation, misuse, misapplication, or failure to follow nVent’s instructions and warnings may cause product malfunction, property damage, serious bodily injury, and death, and may also void your warranty.

Contact Information

  • Europe Netherlands: +31 800-0200135 France: +33 800 901 793
  • Europe Germany: 800 1890272 Other Countries: +31 13 5835404
  • APAC Shanghai: +86 21 2412 1618/19 Sydney: +61 2 9751 8500

Brands Our powerful portfolio of brands:

  • nVent.com
  • CADDY
  • ERICO
  • HOFFMAN
  • RAYCHEM
  • SCHROFF
  • TRACER

All trademarks and registered trademarks are the property of their respective owners.

nVent reserves the right to change specifications without notice.

FAQ

Q: Can I use a different rod size with this rod hanger?
A: No, the rod hanger is designed for use with a specific rod size of 3/8″.
Q: What is the maximum load for shot-fired supports in seismic design category D, E, or F?
A: The maximum load is the lesser of 90 lb (400 N) or the published load.

PUSH INSTALL ROD HANGER WITH SHOT-FIRE BRACKET

FEATURES

  • Suspends plain rod from horizontal structures
  • Complete with shot-fire bracket and pre-assembled drive pin from DEWALT®
  • Quickly and easily attaches to concrete, steel or composite metal decking
  • Integrated pin installs easily using powder-actuated or single-shot gas-actuated tools ICC-ES ESR-2024 evaluation report available for drive pin from DEWALT®

SPECIFICATIONS

Catalog Number| Material| Finish| Rod Size(RS)| Width(W)| A| Static Load(F)
---|---|---|---|---|---|---
6ASF| Steel, Spring Steel| Electrogalvanized

, nVent CADDY Armour

|

3/8″

|

2 1/4″

|

1.300″

|

100 lb

ADDITIONAL PRODUCT DETAILS

Uses Powers Fasteners, Inc. part number 50032.
Static load was established based on a 1” (25.4 mm) embedment depth and 3,000 psi (20.68 MPa) lightweight concrete. For variations in embedment and material please consult anchors.dewalt.com.
Pre-assembled drive pin from Powers Fasteners, Inc. works with Powers® C4CZ, Simpson® GCN-MEPKT, SPIT® P1000, P200,P2201, P3500 / PA3500, P35s, P45, P60, P7201, Sniper; Ramset® 721, Cobra, D45 / D60 / D60L, M70, SA270, T3SS, TS750P,TS60P, Viper; Hilti® DX35, DX350 / DX351 / DX36M, DX100 / DX200, DX460, DXA40, DXA41, DXE72 / DX400; Würth® Diva-1,BST-1, BST-2 or equivalent nailers.
For shot-fired supports in seismic design category D, E, or F, maximum load is the lesser of 90 lb (400 N) or the published load.

DIAGRAMS

WARNING
nVent products shall be installed and used only as indicated in nVent’s product instruction sheets and training materials.
Instruction sheets are available at www.nvent.com and from your nVent customer service representative. Improper installation,misuse, misapplication or other failure to completely follow nVent’s instructions and warnings may cause product malfunction,property damage, serious bodily injury and death and/or void your warranty.

North America
+1.800.753.9221
Option 1 – Customer Care
Option 2 – Technical Support

Europe
Netherlands:
+31 800-0200135
France:
+33 800 901 793

Europe
Germany:
800 1890272
Other Countries:
+31 13 5835404

APAC
Shanghai:
+ 86 21 2412 1618/19
Sydney:
+61 2 9751 8500

Our powerful portfolio of brands:

nVent.com CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACER

© 2023 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals