Dwyer SVT Series Solenoid Valve Enclosure with Timer Instruction Manual
- June 4, 2024
- Dwyer
Table of Contents
Dwyer SVT Series Solenoid Valve Enclosure with Timer
The Series SVT Solenoid Valve Enclosure with Timer is a compact, reliable and
economic package designed for small to medium filtration systems. It combines
a timer board and solenoid valve enclosure into one package, eliminating the
need for separate enclosures and wiring. The SVT is available with 2, 4 or 6
valves. For larger systems expansion modules can be daisy chained to the SVT
for a maximum of 60 outputs. The universal power supply accepts 90-240 VAC at
either 50 or 60 Hz for both domestic and international requirements. On-Demand
Cleaning or Down Time Cleaning functions can be selected with a simple dip-
switch. Time-On and Time-Off settings are selected using two potentiometers.
For on demand systems, a Dwyer® A3000 Photohelic® gage or Series 1950 pressure
switch may be used with the SVT.
APPLICATIONS
- Dust collection
- Pneumatic conveying
- Down draft tables
- Industrial vacuums
Dimenssion
Installation
WARNING Before installation make sure all air pressure has been released,
electric power has been turned off, and air pressure sources have been closed.
Turn power on and increase pressure only after installation in completed.
Location
Select a location that will not exceed the ambient temperature specifications.
The system must be located in area that meets enclosure ratings. The SVT can
be mounted in any position. For optimum life and performance it is recommended
that the unit is mounted horizontal and upright to reduce the chance of
foreign matter accumulating in the valves.
Pneumatic Connections
Verify that the supply pressure is within the required specification. Do not
turn on the system before installation is complete. Make sure that there is no
dirt or other particles between the RDCV diaphragm valve and the connections
of the SVT remoted solenoid valve, which would cause a restriction of airflow.
There should be no condensed water in the piping. The use of a filter may be
required to avoid this problem. Leak testing should be done prior to
installation only.
SPECIFICATIONS
- Service: Compatible gases, filtered and oil free.
- Wetted Materials: Pilot body: Brass; Spring: 302 SS; O-ring: NBR. Temperature Limits: 14 to 122°F (-10 to 50°C).
- Pressure Limit: 116 psi (8 bar).
- Power Requirements: 90-240 VAC 50-60 Hz, 24 VAC 50-60 Hz, 24 VDC ±10%.
- Power Consumption: 25 VA/25 W.
- Fuse: 90-240 VAC 0.5 A delayed, 24 VAC/DC 1.5 A delayed.
- Electrical Connection: 2 DIN A 43652 connectors.
- Enclosure Rating: NEMA 4X (IP66).
- Enclosure Material: Polyamide with carbon fiber, polycarbonate, TPE rubber.
- Process Connection: 1/4 ̋ OD push to connect.
- Mounting Orientation: Any position.
- On-Time: 150 ms to 700 ms.
- Off-Time: 4 s to 210 s.
- Agency Approvals: CE.
Wiring Connections
The SVT is used in conjunction with an external pressure switch or relay for
on-demand cleaning or down-time cleaning. A simple on-off system can be
established with a single pressure switch connected to pin 3-4. A Dwyer®
Photohelic® high and low limit switch gage can be used to achieve better
control. These switches must be isolated contact. The common must not be
connected to the equipment contacts or protected ground, since these may
introduce electrical noise and cause improper operation or possible damage to
the control relays. See Figure 1.
Wiring SVT/SVTE (2 DIN Connectors)
- Remove center screw and pull wiring assembly from body.
- Remove gasket and place small screw driver in slot to pry out the terminal block from the body.
- Thread wire through the gland nut, gland gasket, washer and connector cover.
- Connect wires to proper terminals on the terminal block.
- Snap terminal block back onto the body. Reinstall the center screw and screw back into the SVT/SVTE body.
Note: Do not change the power supply DIN (Black) with the switch input DIN (Gray). The black DIN connector is specially designed for the power supply, changing DIN connectors can damage the SVT/SVTE.
The SVT can be expanded up to 60 valves with the use of the SVTE expander module. A maximum of 9 SVTE can be daisy chained to the SVT. The SVT will automatically detect the expander modules and make their valves available. See Figure 2 for wiring.
Rotating Potentiometer to set the Time On:
- Working Time
- Min: 150 msec
- Max: 700 msec
Dip-switches for various options:
- SW#1: OFF = Clean On Demand ON = Clean On Demand
- SW#2: OFF = Start Cleaning with Open Contact ON = Start Cleaning with Closed Contact
- SW#3: Not used
- SW#4: ON = TEST (pause time 1 second). OFF = Normal (pause time set by the potentiometer
MAINTENANCE
warning! To prevent the possibility of death, serious injury or property damage, turn off electrical power, depressurize system and unit before servicing.
The SVT/SVTE should be cleaned periodically. The amount of time between cleanings depends on the application. Preventive maintenance includes keeping media clean of material and oil free, and periodic testing to insure proper operation and to look for wear or damage.
Warranty
Upon final installation the Series SVT Solenoid Valve Enclosure with Timer and the series SVTE Expansion Module, no routine maintenance is required. A periodic check of the system calibration is recommended. The series SVT and SVTE are not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a returns goods authorization number before shipping.
System Setup
On-Demand Cleaning/Down-Time Cleaning/Test
The SVT controls (dip-switch, 2 potentiometers) are accessed by removing the
transparent plastic cover. The On-Demand Cleaning/Down-Time Cleaning and Test
/ Normal Operation are set with the four pin dip switch. Dip switch one
changes the cleaning function. Down-time cleaning will start when the circuit
between pin 3-4 is opened/closed, when the circuit opens/closes the system
will complete 5 cycles, then shut down. On-demand cleaning will start when the
circuit between pin 3-4 is closed and stop cleaning when the circuit
opens/closes. All cleaning cycles start the subsequent channel where the last
cleaning cycle left off. Dip switch 2 changes the type of circuit required to
start the cleaning function. Dip switch 4 controls a test function. Dip switch
3 is not used.
Time Off and Time On Setup
Time off defines the period of time between solenoid activations. This
function has 15 settings ranging from 4 seconds and 210 seconds. Time on
defines the solenoid on time. This function may be set between 150 msec and
700 msec. If adjustments are made while the system is in operation, the new
setting will take effect in the following solenoid cycle. Do not use excessive
force to turn the potentiometers, this will damage the unit.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219-879-8000
Fax: 219-872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com