ESBE ALF131 Linear Electric Drives Instruction Manual

June 16, 2024
ESBE

ALF131 Linear Electric Drives
Instruction Manual

ALF131 Linear Electric Drives

SBE ALF131 Linear Electric Drives SERIES ALFxx1 230V

INSTALLATION

SBE ALF131 Linear Electric Drives - INSTALLATION| SBE ALF131 Linear Electric Drives - INSTALLATION1
---|---

SBE ALF131 Linear Electric Drives - INSTALLATION2

  1. Mounting positions:
    A=Allowed mounting position with fluid temperature between –20ºC to +120ºC.
    B= Allowed mounting position with fluid temperature between 0ºC to +150ºC
    C=Not allowed mounting position.

  2. Mount flange nut (A) and then the square nut (B) on top of spindle.

  3. Bring the actuator into desired position by activating and turning the manual knob (more information on page 6), or reposition the valve itself.

  4. Put the actuator on top of the valve. Fasten it to the neck of the valve by means of the U-bolt. Firmly tighten all nuts!

  5. A : Stroke indicator B : Anti rotation guide

MANUAL OVERRIDE

SBE ALF131 Linear Electric Drives - OVERRIDE

MANUAL OVERRIDE
There is a manual operation handle on the actuator.
When handle is lowered manual operation is active, the power supply to the motor power stage circuitry is cut and the motor stop. The actuator can be operated manually and the valve positioned accordingly. The manual operation handle latches in position until it is raised again, then board and motor will be powered again. At the end of this operation the actuator moves to initial position (on the basis of DIP 1 setting) then it follows the control signal. When the manual override handle is engaged, the green and the red LED are on.
The actuator is supplied with the manual operation handle lowered/active.

CONNECTOR DESCRIPTIONS

SBE ALF131 Linear Electric Drives - DESCRIPTIONS

CONNECTOR DESCRIPTIONS
To avoid damages to electronic components caused by the PCB bending, do not press too much while fixing the terminal block.

| DESCRIPTION| FUNCTION| MIN WIRE AREA| MAX WIRE LENGTH
---|---|---|---|---
Lh
__N
Lc| 230VAC| Power supply*| 1,5mm2| 75 m
V+| 16 VDC| Voltage output (Max load 25mA)| 0.5 mm2| 200 m
---|---|---|---|---
M| 0V (Common)
U| 2-10VDC| Feedback output signal** (Max load 2mA)|

0.5 mm2

| __

200 m

M| 0V (Common)
Y| 0-10VDC ***| Modulating control signal| 0.5 mm2| 200 m
M| 0V (Common)
Y1
Y2| Not to be used

Connect (Lh+N) in modulating control mode; Connect (Lh+N) to “open” or (Lc+N) to “close” in 3-point floating control mode.
Only available in modulating control mode.
See Chapter 5 and DIP switch 4−6 for available modulating control signal types.
Connect the ground terminal to the proper screw labelled with the ground symbol as shown in picture (A)

ELECTRICAL CONNECTION

SBE ALF131 Linear Electric Drives - CONNECTION

ELECTRICAL CONNECTION
Connect the ground terminal to the proper screw labelled with the ground symbol. Use cable gland PG13,5 model (not supplied)

  1. 3-point floating control mode
    Connect wires, pict. A Connect (Lh+N) to extend (open) or (Lc+N) to retract (close) in floating control mode. Start a calibration.
    In floating control mode only DIP switch 2 is applicable. In floating control mode DIP switch 7 is used only to force manual calibration. During floating control mode the automatic calibration is not active.

  2. Modulating / proportional control mode
    Connect power wires, pict. B Connect control signal and if needed feedback signal, pict. C Set the DIP switches according to information in the following pages.
    Start a calibration.

SBE ALF131 Linear Electric Drives - CONNECTION1

DIP SWITCHES

SBE ALF131 Linear Electric Drives - DIP SWITCHES

DIP SWITCHES
It is not necessary to remove power supply to change DIP switch settings, but the 230V power supply must be consider. Before the cover on the actuator is removed and DIP settings are changed, the power to the actuator must be disconnected or manual operation handle active. After DIP settings are changed power up the actuator or inactivate manual operation handle to activate the new settings.

DIP SWITCH OFF ON
1 Normal direction, picture A Reverse direction, picture B
2 Modulating / proportional control mode, picture C 3-point floating

control mode, picture D
3| –| Sequence control mode
4| Modulating control signal 0-10 VDC| Modulating control signal 2-10 VDC
__5| Sequence control signal 0-5 VDC with DIP switch 4 in OFF mode Sequence control signal 2-6 VDC with DIP switch 4 in  ON mode| Sequence control signal 5-10 VDC with DIP switch 4 in OFF mode Sequence control signal 6-10 VDC with DIP switch 4 in ON mode
6| Voltage input signal (VDC)| Current input signal (4-20mA) Note: DIP switch 4 must be in ON mode
7| Automatic Calibration: the actuator updates the stroke range if an unexpected mechanical stop is detected for at least 10 seconds| Manual Calibration: the actuator calibration is started moving the switch from OFF to ON; if the switch is left in ON the actuator will never update the calibrated stroke value even when an unexpected endpoint is detected

*U= feedback signal

SBE ALF131 Linear Electric Drives - DIP SWITCHES1

DIAGNOSTIC / ALARM FUNCTION

| LED| ERROR| WHEN| ACTUATOR BEHAVIOUR| TYPICAL TROUBLE SHOOTING CONDITION| RESET PROCEDURE
---|---|---|---|---|---|---
| | | | Automatic Calibration Dip switch 7 is OFF mode| Manual Calibration Dip switch 7 is ON mode| |
1***| RED ON| Calibrated stroke valve less than 5 mm| Calibration

/ first installation

| The actuator pushes/ pulls 5 times (unexpected stall) trying to remove the possible obstacle. After 5 tries alarm is signaled (RED Led ON) and the actuator moves to initial position. Doesn’t respond to control signal. Stroke value is not updated because out of range|

The actuator pushes/pulls 2 times against endpoint during calibration. Alarm is signaled (RED led On) and the actuator moves to the initial position. Doesn’t respond to the control signal.

| Valve with a stroke length lower than 5 mm| Remove power and power up again
2***| RED ON| Stroke longer than 30/60 mm| Calibration

/ first installation

| The actuator exits the 30/60 mm stroke range and moves toward the new stroke limit signaling an anomaly (RED led on). The actuator doesn’t calibrate the stroke| The actuator pushes/pulls 2 times against endpoint during calibration. Alarm is signaled (RED led On) and the actuator moves to the initial position and then it doesn’t respond to the control signal.| Valve with a stroke length longer than 30/60 mm| Remove power and power up again
3 ***| RED quick   blinking + GREEN ON| Unexpected stall within the calibrated stroke range|

Normal operation

| The actuator tries 5 times against the new stall condition. After 10 sec. the actuator updates the new stroke length. During these 10 sec. RED led is ON| The actuator tries 5 times against the new stall condition. After 10 sec. the actuator doesn’t update the new stroke length| Valve stuck| Inverted control signal
4*| RED quick blinking + GREEN ON| Stroke longer than expected| Normal operation| The actuator moves toward the new stall condition with a lower speed; after 10 sec. the actuator updates the new stroke value; During these 10 sec. RED led is ON| The actuator moves toward the new stall condition with a lower speed. After 10 sec. the actuator doesn’t update the new stroke value| Stem connection loose or valve damaged| Inverted control signal
5| RED slow
blinking| Low Power Voltage| Normal operation| The actuator is still working but performance cannot be guaranteed| The actuator is still working but performance cannot be guaranteed| 1. Wrong transformer size| Correct Voltage Power
2. unstable power
6| RED

slow** blinking

| High Power Voltage| Normal operation| The actuator is still working but performance cannot be guaranteed| The actuator is still working but performance cannot be guaranteed| 1. Wrong transformer size| Correct Voltage Power
2. unstable power

  • Quick = 2 flash / second
    ** Slow = 1 flash / second
    * In case of valve stroke less than 5mm or longer than 30/60 mm the actuator tries 3 times to perform a new calibration.
    **
    Valid only in Modulating / proportional control mode. LED´s are placed on circuit board and are only visible when actuator cover is removed.

ACTUATOR STATUS

LED ACTUATOR STATUS
1 Green On The actuator arrived at the extreme point of the stroke read
2 Green Blinking The actuator arrived at the intermediate point of the

stroke read
3| Red Green Blinking| The actuator is reading the stroke or it is going to initial position
4| Red Green On| Manual operation active, the actuator ignores the control signal. ATTENTION! The PCB is electrically supplied

https://qrco.de/ESBEGroup
ESBE AB
Bruksgatan 22
SE‒333 75 Retile
www.esbe.eu Mtrl.nr. 9814 09 22 Ritn.nr.
6287 vers B • Rev. 2023‒08‒10