AprilAire 56 Automatic Whole House Humidifier Control Instruction Manual

June 15, 2024
Aprilaire

AprilAire 56 Automatic Whole House Humidifier Control

Product Information

  • Product Name: Humidifier
  • Model: 56
  • Automatic Humidifier Control

Warnings
Sharp edges may cause injury from cuts. Use care when cutting plenum openings and handling ductwork. Always wear glasses/goggles and gloves when installing the unit.

Notice
Excess condensation on the inside of any windows in unheated living spaces.

Product Usage Instructions

Step 1: Unpack the Humidifier Control Carton

  1. Make sure all components are present (see FIGURE 1).
    • A. Humidifier Control
    • B. Outdoor Temperature Sensor
    • C. Manual Mode Label
    • D. Manual Mode Resistor Case

Step 2: Disassemble the Humidifier Control
Remove door from the Humidifier Control by pulling the bottom of the door straight out.

Step 3: Check the Mode Switch
With the door removed, notice the switch labeled BYPASS and POWER (partially covered by the enclosure). Use the following guide to determine the correct setting for your humidifier model.

  • POWER SETTING : Models 110, 112, 445, 448, 760, 700 (almond-colored), 768, 800 (steam humidifier)
  • BYPASS SETTING : Models 220, 224, 400, 440, 500, 550, 558, 560, 568, 600, 700 (gray-colored)

Product Info & Digital Manual

  • Use the OFF setting to turn the Water Panel Change indicator OFF.
  • Use setting A for Model 400 humidifiers. The indicator will light after 75 hours of inlet valve operation, which corresponds to approximately 300 hours of humidifier operation.
  • Use setting B for Model 600 and 700 humidifiers when the heating season is 3 months or less, or if hard water is used. The indicator will light after 300 hours of humidfier operation.
  • Use setting C for Model 600 and 700 humidifiers when the heating season is longer than 3 months. The indicator will light after 600 hours of humidfier operation.

Step 5: Determine Location for Humidifier Control and Mount It
The Humidifier Control must be mounted in the return duct. For proper operation, the Humidifier Control must be at least 6 inches upstream of any of the following:

  • 6 MIN. RETURN DUCT
  • HUMIDIFIER CONTROL
  • FRESH AIR INTAKE
  • BYPASS CONNECTION

After the location for Control is selected, use the perforated Humidifier Control template (attached to these instructions) to mark the duct opening and cut it. Use 4 sheet metal screws (not provided) to mount the Humidifier Control in the duct opening and make sure Humidifier Control is sealed tightly to duct.

Step 6: Determine Location for Outdoor Temperature Sensor

The location of the Outdoor Temperature Sensor must meet these three requirements

  1. Must be mounted on North, East or West side of house out of direct sunlight.
  2. Must be at least 3 feet from all exhaust vents.
  3. Must be above expected snow line (see FIGURE 4).

Step 7: Locate Existing Access Hole to Outside
A convenient way to get the sensor wire outside is to make use of unused wires running to the A/C condensing unit (if applicable). Other ways are to use existing holes for cable TV lines, telephone lines, A/C lines, etc. Read all equipment instructions beforehand for possible conflicts and warnings.

Specifications

  • Model : 56
  • Control Type : Automatic

Frequently Asked Questions (FAQ)

  • Q: How often should I change the water panel?
    A: The water panel should be changed according to the instructions provided for your specific model. Refer to the product manual for more information.

  • Q: Can I install the humidifier control in any location?
    A: No, the humidifier control must be mounted in the return duct at least 6 inches upstream of certain components. Follow the installation instructions provided to ensure proper operation.

  • Q: Where should I mount the outdoor temperature sensor?
    A: The outdoor temperature sensor should be mounted on the North, East, or West side of the house, out of direct sunlight. It should also be at least 3 feet away from all exhaust vents and above the expected snow line.

SAFETY AND INSTALLATION INSTRUCTIONS

Mode l 56
Automatic Humidifier Control

THESE INSTALLATION INSTRUCTIONS ARE FOR THE APRILAIRE® AUTOMATIC HUMIDIFIER CONTROL ONLY. FOR APRILAIRE® HUMIDIFIER INSTALLATION, FOLLOW APRILAIRE HUMIDIFIER INSTALLATION INSTRUCTIONS.

WARNING

  • ATTENTION INSTALLER : Read this manual before installing. Improper installation or maintenance may cause property damage or injury. It is recommended that installation, service, and maintenance be performed by a trained service technician. This product must be installed in compliance with all local, state, and federal codes.
  • ELECTRIC SHOCK HAZARD : 120 volts may cause serious injury from electric shock. Disconnect electrical power to the HVAC system and humidifier before starting installation or servicing. Leave power disconnected until installation/service is completed.

CAUTION
SHARP EDGES MAY CAUSE INJURY FROM CUTS
Use care when cutting plenum openings and handling ductwork. Always wear glasses/goggles and gloves when installing the unit.

NOTICE

CONDENSATION DAMAGE OR MOLD CAN OCCUR.

  • Do not set the humidifier control higher than recommended.
  • Lower the humidity setting on the humidifier control if there is excess condensation on the inside of any windows in unheated living spaces.

CONTROLLER DAMAGE OR MALFUNCTION MAY OCCUR IF INSTALLATION INSTRUCTIONS ARE NOT FOLLOWED

  • Install the humidifier control on return plenum only.
  • Install the humidifier control upstream of the bypass outlet.
  • Do not install the humidifier control facing downward.
  • When installing the humidifier control on the return duct of a downflow furnace, ensure the blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the humidifier control.
  • Do not use solvents or cleaners on or near the display and circuit board. Chemicals can damage components.
  • Do not apply 120 VAC to the humidistat. The humidistat is powered by 24 VAC. Disconnect power to the humidistat prior to separating humidistat from its base.

STEP 1: UNPACK THE HUMIDIFIER CONTROL CARTON
Make sure all components are present (see FIGURE 1)

  • A. Humidifier Control
  • B. Outdoor Temperature Sensor
  • C. Manual Mode Label
  • D. Manual Mode Resistor Case

Product Info & Digital Manual

STEP 2: DISASSEMBLE THE HUMIDIFIER CONTROL
Remove door from the Humidifier Control by pulling the bottom of the door straight out.

STEP 3: CHECK THE MODE SWITCH

  • With the door removed, notice the switch labeled BYPASS and POWER (partially covered by the enclosure). Use the following guide to determine the correct setting for your humidifier model.
  • POWER SETTING : Models 110, 112, 445, 448, 760, 700 (almond-colored), 768, 800 (steam humidifier)
  • BYPASS SETTING : Models 220, 224, 400, 440, 500, 550, 558, 560, 568, 600, 700 (gray-colored)

STEP 4: CHECK THE CHANGE WATER PANEL® INDICATOR SETTING
This setting will control when the indicator light turns on, reminding you to change your water panel. If your Control came with a humidifier, the Control is pre-set. If the installation site has a 3-month or shorter heating season or very hard water, you may want to adjust the setting (see FIGURE 2). The Control must be energized to reset the Water Panel® Indicator.

STEP 5: DETERMINE LOCATION FOR HUMIDIFIER CONTROL AND MOUNT IT
The Humidifier Control must be mounted in the return duct. For proper operation, the Humidifier Control must be at least 6 inches upstream of any of the following

  • Humidifier
  • Humidifier Bypass Ductwork (if applicable)
  • Fresh Air Intake Ductwork (if applicable)(see FIGURE 3)

After location for Control is selected, use the perforated Humidifier Control template (attached to these instructions) to mark the duct opening and cut it. Use 4 sheet metal screws (not provided) to mount the Humidifier Control in the duct opening and make sure Humidifier Control is sealed tightly to duct.

STEP 6: DETERMINE LOCATION FOR OUTDOOR TEMPERATURE SENSOR
The location of the Outdoor Temperature Sensor must meet these three requirements

  1. Must be mounted on North, East
  2. or West side of house out of direct sunlight.
  3. Must be at least 3 feet from all exhaust vents. Must be above expected snow line (see FIGURE 4).

Incorrect humidity levels will result if these requirements are not met.

STEP 7: LOCATE EXISTING ACCESS HOLE TO OUTSIDE
A convenient way to get the sensor wire outside is to make use of unused wires running to the A/C condensing unit (if applicable). Other ways are to use existing holes for cable TV lines, telephone lines, A/C lines, etc. Read all equipment instructions beforehand for possible conflicts and warnings.

STEP 8: ALTERNATE LOCATION FOR OUTDOOR TEMPERATURE SENSOR

The Sensor can also be mounted in the center of either

  •  2 inch PVC fresh air intake pipe for the furnace
    OR

  • 6 inch fresh air intake duct. Mount the sensor with a #8 galvanized screw.

In both cases, the Sensor must be no more than 3 feet from the outside wall. See FIGURE 5.
If it is not feasible to use the Outdoor Temperature Sensor in any of the ways described, the Humidifier Control can be installed for Manual operation. See FIGURE 6 for details

FIGURE 6: INSTALLING THE HUMIDIFIER CONTROL FOR MANUAL OPERATION

If it is not feasible to use the Outdoor Temperature Sensor, the Humidifier Control can be operated in Manual Mode.

  1.  Connect the Manual Mode Resistor Case wires to the terminals labeled ODT on the Humidifier Control.
  2.  Snap the Manual Mode Resistor Case into the slot provided so that Resistor Case sticks out from the bottom edge of the base.
  3. Remove the control knob and apply the Manual Mode label to the cover, aligning the sticker and knob holes. Re-install the knob.

STEP 9: ROUTE THE WIRE FROM CONTROL TO SENSOR
Run wire to the outdoor temperature sensor. Sensor is not affected by lead length. In either case, do not run outdoor temperature sensor alongside wires carrying high voltage (120 VAC or higher). Secure the sensor bracket with a #8 galvanized screw.

STEP 10: ATTACH SENSOR WIRE TO HUMIDIFIER CONTROL
Strip wire 1/4”, and insert the wires from the Sensor into the terminals labeled ODT on the Humidifier Control. See FIGURE 7 for location of terminals.

STEP 11: DETERMINE POWER SOURCE FOR HUMIDIFIER CONTROL
Determine where you will get 24 VAC to power the Humidifier Control based on the 2 options below.

OPTION 1 : FURNACES WITH ACCESSORY TERMINALS

If the accessory terminals provide

  • 24 VAC: Wire these directly to the R and C terminals on the Humidifier Control.
  • 120 VAC : Wire to a 24 VAC transformer, which in turn connects to the R and C terminals on the Humidifier Control.

In either case, the voltage to the Humidifier Control must be between 22 VAC and 30 VAC.

OPTION 2 : EXTERNAL 24 VAC TRANSFORMER

Wire into a power source other than the furnace blower circuit. The transformer can be powered off the 120 VAC line at the junction box before it enters the furnace. The 24 volt side of the transformer is connected to the R and C terminals on the Humidifier Control.

NOTES

  • The Humidifier Control will operate properly with either a switched or continuous power source.
  • Whether using Accessory Terminals or an External Transformer, the minimum VA required is; 2.0 VA for humidifiers using the Power setting [Models 110, 112, 445, 448, 760, 700 (almond-colored), 768, 800 (steam humidifier)]; or 10.0 VA for humidifiers using the Bypass setting [Models 220, 224, 400, 440, 500, 550, 558, 560, 568, 600, 700 (gray-colored)].
  • When power is connected for the first time, the red and green LEDs will light momentarily.

STEP 12: HUMIDIFIER WIRING

Strip the wires used for all the Humidifier Control terminal connections 1/4”.

  • If Furnace Accessory Terminals are used, wire the humidifier solenoid valve in series with the H terminals on the Humidifier Control without using a Model 50 Relay. See furnace manual for operation of accessory terminals (FIGURE 8).
  • If an External Transformer is used, a Model 50 Current Sensing Relay must be connected to the solenoid valve and the H terminals on the Humidifier Control to allow the humidifier to operate only when the blower is on (FIGURE 9). Wire the Model 50 Relay into the H circuit only.

Bypass and Power units are wired to the AHC in the same fashion.
NOTE : This control does not support intelligent communication with other products.

SYSTEM CHECKOUT

  1.  For system Test/Reset, be sure that 24 VAC is applied to the R and C terminals of Humidifier Control.
  2.  Snap the door back onto the Humidifier Control Base.
  3.  Activate furnace blower and be sure thermostat is calling for heat.
  4.  Rotate the control knob of Humidifier Control clockwise to the TEST/RESET position. When the knob is set in the TEST/RESET position, the green Change Water Panel light will blink. Make sure the knob is not left in the TEST/RESET position when the installation is done. Rotating knob to TEST position resets the water panel change timer to zero. The Control must be energized to reset the Water Panel indicator.
  5.  If all is set up properly, you should be able to hear the solenoid valve click open. In TEST/RESET mode, the AprilAire Humidifier will operate for 1 minute.
  6. If the humidifier does not activate with the Humidifier Control in the TEST/RESET position, refer to the troubleshooting guide.
  7.  Setting the Humidifier Control:
    • If home is occupied, set Humidifier Control to NORMAL (for Manual operation, set to 35%).
    • If home is vacant, set Humidifier Control to OFF.
  8. Inform homeowner to refer to the AprilAire Owner’s Manual for the initial adjustment period.
  9.  Make sure the red diagnostic light is not lit. If the red diagnostic light is lit, re-check your wiring.

CAUTION
SHARP EDGES MAY CAUSE INJURY FROM CUTS
Use care when cutting plenum openings and handling ductwork. Always wear glasses/goggles and gloves when installing the unit.

NOTICE

  • Install the humidifier control on return plenum only.
  • Install the humidifier control upstream of the bypass outlet.
  • When installing the humidifier control on the return duct of a downflow furnace, ensure the blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the humidifier control.

TROUBLESHOOTING GUIDE

Applies to both Automatic and Manual operation unless indicated otherwise.

TABLE 1 : MODEL 56 TROUBLESHOOTING GUIDE

“CHANGE WATER PANEL” INDICATOR IS LIT
Call your installer to have your water panel changed, or visit your installer to purchase a new AprilAire water panel. Follow the instructions on the water panel box.

HUMIDIFIER DOES NOT OPERATE IN “TEST” MODE

  • Make sure furnace blower is operating and thermostat is calling for heat.
  • Make sure the Outdoor Temperature Sensor is connected to the ODT terminals of the control. (For Manual operation, make sure Manual Mode Resistor Case is in place.)
  • Check main wiring diagram for correct Humidifier Control installation.
  • If connected to a Model 400 Humidifier, make sure both floats in the bottom of the scale control insert are in the down position. If necessary, dump out water to lower floats.
  • Check voltage at Humidifier Control R and C terminals. Voltage should be 22 VAC minimum to 30 VAC maximum.
  • Check Model 50 Current Sensing Relay (if used) for correct installation (see Model 50 instructions). Do not use Model 50 Relay in transformer circuit or R and C circuit of Humidifier Control. Model 50 relay is to be used in the H circuit only.
  • In TEST mode, humidifier will operate for 1 minute only. DO NOT LEAVE IN TEST MODE AS HUMIDIFIER WILL NOT OPERATE.
  • Make sure saddle valve is open.

HUMIDIFIER OPERATES ONLY IN “TEST” MODE

  • If outdoor temperature is greater than 60°F or less than -30°F, the Humidifier Control will only operate in the TEST mode (for one minute).
  • If the humidity level in the home is higher than the knob setting, the Humidifier Control will not operate the Humidifier.
  • Check the resistance of the sensor by removing the leads of the Outdoor Temperature Sensor from the terminals and measuring the resistance across the wires with an ohmmeter. Compare reading to outdoor temperature in TABLE 2. (For Manual operation, verify that resistance across the leads of Manual Mode Resistor Case is between 44,000 and 48,000 ohms).
  • Make sure the Outdoor Temperature Sensor is mounted completely outside the house on the North, East, or West side of the house and out of direct sunlight (automatic mode only).
  • If Outdoor Temperature Sensor is mounted in fresh air intake duct, make sure the probe is no more than 36 inches from the outside wall (automatic mode only).
  • Make sure the Outdoor Temperature Sensor is located at least 3 feet away from all exhaust vents (automatic mode only).

TABLE 2

Outdoor Temperature (°F)| -30| -20| -10| 0| 10| 20| 30| 40| 50| 60| 70| 80| 90| 100
Resistance (kΩ)| 230.6| 163.8| 117.6| 85.4| 62.6| 46.3| 34.6| 26.1| 19.9| 15.3| 11.9| 9.4| 7.4| 5.9

TABLE 1: MODEL 56 TROUBLESHOOTING GUIDE

HUMIDIFIER OPERATES CONSTANTLY

  • If the humidity level in the home is less than the knob setting, the Humidifier Control will operate the Humidifier until the humidity level is higher than the knob setting.
  • In the TEST mode, verify unit will operate for approximately one minute.
  • Check the resistance of the Outdoor Temperature Sensor as instructed above.
  • Make sure the Outdoor Temperature Sensor is mounted completely outside the house on the North, East, or West side of the house and out of direct sunlight (automatic mode only).
  • Rotate the Humidifier Control knob counterclockwise to the OFF position, and observe whether the humidifier turns off. If the humidifier still operates in the OFF position, perform the following:
    1. Check summary wiring diagram for correct Humidifier Control Installation.
    2. Remove wires from Humidifier Control’s H terminals. If Humidifier continues to operate, replace solenoid valve.

HUMIDIFIER OR HUMIDIFIER CONTROL “CHATTERS” OR CLICKS ON AND OFF RAPIDLY

  • Check for steady 22 VAC to 30 VAC with voltmeter.
  •  Make sure Outdoor Temperature Sensor wiring is not run alongside wires carrying high voltage (120 VAC or higher) (automatic mode only).

RED DIAGNOSTIC LIGHT IS ON

  • Check that the wiring is correct.
  • Measure the resistance of the Outdoor Temperature Sensor by removing the leads from the terminal and measuring the resistance across the wires with an ohmmeter. Confirm the reading with the temperature in TABLE 2. (For Manual operation, verify that the resistance across the leads of the Manual Mode Resistor Case is between 44,000 and 48,000 ohms).

HUMIDIFIER CONTROL TEMPLATE

4-3/4” x 3”

  1.  Cut out template along edges.
  2. Place template on the return plenum upstream of (before) the humidifier connection.
  3. Trace outside edges of template.
  4. Remove template and accurately cut plenum opening.
  5. Using 4 sheet metal screws, install Humidifier Control in plenum opening.
  • B2202617D
  • 10005402
  • 08.23 © 2023 AprilAire
  • aprilairepartners.com 
  • 800.334.6011
  • AprilAire reserves the right to change specifications without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals