Maretron PTS-0-1.5PSI-02 Submersible Pressure Transducer Installation Guide

June 15, 2024
Maretron

Maretron PTS-0-1.5PSI-02 Submersible Pressure Transducer

Installation Instructions

Maretron’s submersible pressure transducers are used for indicating tank levels and can be installed directly in the tank. Please follow these instructions to mount and connect a submersible pressure transducer to an NMEA 2000® network via a Maretron FPM100 Fluid Pressure Monitor. Maretron recommends one of two methods for mounting a submersible pressure transducer in a tank: 1) without a restraining tube (shown on left side of Figure 1) and, 2) with a restraining tube (shown on the right side of Figure 1).

  1. The submersible pressure transducers are designed for a tank with a 5-hole SAE J1810 fitting at the top. Install the mounting plate with cord grip onto the transducer cable, with the rounded hex section of the cord grip facing away from the transducer.

  2. Lower the pressure transducer into the tank such that the transducer lies at the lowest point of the tank and tighten the cord grip to secure the cable. On a tank with a flat bottom, the transducer may slide from side to side with the motion of the vessel but will not rotate due to the stiffness of the cable. It is also possible to mount the pressure transducer inside a restraining tube or focus tube (sold separately, Maretron part number TFT-5H). Please refer to Figure 1 for examples.Maretron-PTS-0-1.5PSI-02-Submersible-Pressure-Transducer-FIG-1

  3. Connect the two wires of the pressure transducer to a free pressure monitoring channel as shown in Figure 2 below. The diagram shows a connection to FPM100 channel #0, but connections to other channels are similar. Connect the red wire from the pressure transducer to the positive (+) terminal of the channel and connect the black wire from the pressure transducer to the negative (-) terminal of the channel. The example in Figure 1 shows the pressure transducer connected to switch channel 0 with the white wire connected to “P0+”, and the brown wire connected to “P0-”. Submersible pressure transducers have a small plastic vent tube in the connecting cable. Care must be taken not to kink or block this tube or pressure readings will be inaccurate.Maretron-PTS-0-1.5PSI-02-Submersible-Pressure-Transducer-FIG-2

  4. Use a Maretron DSM Series Display (firmware 1.4.7 or higher) or a PC running Maretron’s N2KAnalyzer software (version 1.4.19 or higher), to configure the connected channel(s) on the FPM100.
    | PTS-0-1.5PSI-02| PST-0-3PSI-02| PST-0-5PSI-02
    ---|---|---|---
    Value at 4mA:| 0 PSI (0 bar)| 0 PSI (0 bar)| 0 PSI (0 bar)
    Value at 20mA:| 1.5 PSI (0.103 bar)| 3.0 PSI (0.207 bar)| 5.0 PSI (0.345 bar)

  5. Supply power to the NMEA 2000 network and verify that the pressure channel indicates a valid pressure reading.

Mechanical Drawing

Maretron-PTS-0-1.5PSI-02-Submersible-Pressure-Transducer-
FIG-3

Pressure Transducer Specifications


Part Number

| ****

Operating Range

| Depth Range| ****

Cable Length

---|---|---|---
Water (1,000 kg/m 3)| Diesel (820 kg/m 3)| Gasoline/Petrol (750 kg/m 3)
PTS-0-1.5PSI-02| 0 to 1.5 PSI (0.103 bar)| 41.5” (1.05 m)| 50.7” (1.29 m)| 55.4” (1.41 m)| 14 ft (4.27 m)
PTS-0-3PSI-02| 0 to 3 PSI (0.207 bar)| 83.1” (2.11 m)| 101.3” (2.57 m)| 110.8” (2.81 m)| 17 ft (5.18 m)
PTS-0-5PSI-02| 0 to 5 PSI (0.345 bar)| 138.4” (3.51 m)| 168.9” (4.29 m)| 184.7” (4.69 m)| 25 ft (7.63 m)
Specification| Value
---|---
Sensor Type| Gauge (Vent Tube)
Output| 4 – 20 mA current loop, loop powered
Excitation Voltage| 8 VDC to 28 VDC
Compatible Fluids / Gases| Diesel, Diesel Exhaust Fluid (DEF), Gasoline/Petrol, Hydraulic Fluid, Kerosene, Motor Oil, Fresh Water, Sea Water, Waste Water
Operating Temperature| 14°F to 158°F (-10°C to 80°C)
Storage Temperature| -4°F to 176°F (-20°C to 80°C)
Accuracy| ±0.3% Full Scale typ. at 25°C
Total Error Band (TEB)| ±1.0% Full Scale typ. (-10°C to 70°C)
Non-Linearity, Hysteresis (NLH)| ±0.2% Full Scale typ. Best Straight Line (BSL) at 25°C
Temperature Compensation| 23°F to 122°F (0°C to 50°C)
Accuracy| ±1% Full Scale
Linearity| 0.5% Full Scale
Repeatability| 0.05% Full Scale
Full Scale Thermal Error| 0.04% Full Scale/°F (0.07% Full Scale/°C)
Long Term Stability| 0.2% Full Scale/year
Response Time| 150ms
Proof Pressure| 2 × Full Scale
Burst Pressure| 3 × Full Scale
Reverse Voltage Protection| ± 30V for 3 minutes
Construction| 316L stainless steel body and diaphragm, polyether polyurethane cable, chloroprene boot
EMC Compatibility| 10 Volts/meter per EN 61000-4-3
Weight| 24.8oz (703g)