OMNTEC PROTEUS-K Series Outdoor Tank Gauging and Leak Detection System Owner’s Manual

June 15, 2024
OMNTEC

OMNTEC logo PROTEUS®
OUTDOOR TANK GAUGING AND
LEAK DETECTION SYSTEM
OEL8000IIIK-SS SERIES

PROTEUS-K Series Outdoor Tank Gauging and Leak Detection System

Building upon the foundation of reliability and performance that has made our PROTEUS a trusted name, we are now offering a NEMA 4X stainless steel weatherproof enclosure.
The PROTEUS-K Series can simultaneously monitor product levels, water levels, temperature, leaks and much more in up to eight tanks. The flexibility of PROTEUS makes it ideal for a variety of tank gauging and leak detection applications.
The PROTEUS-K accepts up to 16 of OMNTEC’s Bright Eye (BX Series) sensors for distinguishing product from water or for simply detecting the presence of liquid. A distinct advantage of Bright Eye sensors is they are networked and utilize 4 wire bus technology.
PROTEUS does not require sensor or probe input modules, bringing ease to ordering and installation. A built-in microprocessor gives each sensor the ability to identify itself and its location, which is displayed along with alarm conditions on the PROTEUS’s color 7-inch graphic display with capacitive touch screen.
With OMNTEC’s proven reliability, the PROTEUS offers an attractive, comprehensive and user-friendly system that can open doors to endless possibilities.
OMNTEC Mfg., Inc. has been certified by DQS Inc. to ISO 9001:2015; Registration Number 10017970.

FEATURES

  • Accepts up to 8 magnetostrictive probes
  • Accepts up to 16 Bright Eye sensors
  • Sensors networked using state of the art 4 wire bus technology
  • Color 7-inch graphic display with capacitive touch screen
  • Sunlight visible
  • Large user-friendly icons
  • Easy to read leak and level alarms
  • Built in web server
  • Built in VPN capability
  • Flash based non-volatile memory for program storage (does not require a battery)
  • 1 RS-232 port
  • Up to 2 configurable RS-232/RS-485 ports (1 included)

– NEMA 4X WEATHERPROOF ENCLOSURE
– RETAIL AND COMMERCIAL APPLICATIONS

  • Ethernet / TCP/IP standard
  • E-mail / Text capability standard
  • Network printing capable
  • Up to 5 built in programmable relays
  • Up to 8 additional external dry contact relays
  • SD memory card slot (for extended logging)
  • VLD standard
  • CITLD upgradeable
  • MODBUS RTU & TCP upgradeable
  • Remote display option
  • Compatible with Tank Active™ remote tank inventory monitoring app
  • Remote software update capable

SPECIFICATIONS

Input Power 100-240 VAC +/- 10% 50/60 Hz 60 watts
Voltage to Sensors 12 VDC
Voltage to Probes 28 VDC

Display
Audible alarm
System status| Color 7-inch graphic display with capacitive touch screen
85 dB piezoelectric horn
3 LED’s (Power, Warning, Alarm)
Relay Outputs| 5 standard, 6 A – 30 VDC / 250 VAC RES
Low-voltage Outputs| 12 VDC @ 225 mA
Operating Temperature| -22° to 140° F (-30° to 60° C)
Outdoor Rating| NEMA 4X
Standard Communications| TCP/IP I RS-485 I RS-232
Models Available| OEL8000111K4-5-SS (accepts 4 level probes and 16 sensors) OEL8000111K8-5-SS (accepts 8 level probes)
Optional Features| CITLD Upgradeable I Modbus RTU and TCP I Tank Active’ App
Compatible Sensors| BX-Series sensors (refer to document no. 900106)
BX-Series Sensor Cable| OMNTEC EC-4 – 4 conductor 22 AWG shielded twisted pair cable with drain or equivalent. Maximum length 2,000 feet (610m).
Compatible Probes| MTG-RS Series
MTG-FL Series
MTG-FB Series| Rigid Gauging Probe (refer to document no. 900194)
Flexible Fixed Top Probe (refer to document no. 900166)
Flexible Fixed Bottom Probe (refer to document no. 900162)
MTG Probe Cable| OMNTEC EC-2 (Belden 8761) – 2 conductor 22 AWG shielded twisted pair cable with drain. Low Inductance: equal or less than 0.2 microhenries per foot. Maximum length 1,000 feet (305m). Consult factory for longer wire runs.
Accessories| MMRD7 Series DDL Series RAS Series XC-R8-4X X232-420 MB-232/485 C232-BAC C485-BAC WRS-232| Mini-Me remote display
Delivery Defender Lite universal remote overfill alarm Remote annunciators
External relay expansion in Nema 4X enclosure
External RS-232 to 4-20 mA converter Configurable RS-232 or RS-485 option board
RS-232 BACnet TCP/IP converter RS-485 BACnet TCP/IP converter Wireless link
Weight| 20 lbs. (9.07 kg)
Dimensions| (h) 13.82″ (w) 17.62″ (d) 6.24″
Approvals| UL-listed, CUL-listed, ATEX, IECEx

IMPORTANT: Specifications subject to change without notice, verify with manufacturer.OMNTEC PROTEUS-K Series Outdoor Tank Gauging and Leak Detection
System - parts

PROTEUS-K Outdoor Application

OMNTEC PROTEUS-K Series Outdoor Tank Gauging and Leak Detection System -
parts1

OMNTEC Mfg., Inc.
2420 Pond Road,
Ronkonkoma, NY 11779
+1.631.981.2001
+1.631.981.2007
[email protected]
www.omntec.com
Document No. 900235 rev2351