neptronic TMA54-EXT1 Thermostat Instruction Manual

June 4, 2024
neptronic

TMA54-EXT1 Thermostat
Instruction Manual

Features

TMA54-EXT1

  • Selectable analog output
  • Selectable Fahrenheit or Celsius scale
  • Manual Night Set Back override
  • Multi-level lockable access menu
  • Lockable Set point
  • Selectable internal or external temperature sensor (10k Ω type 3)
  • The selectable proportional control band
  • Proportional-integral-derivative (PID) controller
Technical Data TMA54-EXT1
Outputs 2 Analog Cooling outputs (0-10Vdc)

2 Analog Heating outputs (0-10Vdc)
0 or 22 Vdc, TPM, (Time proportional modulation) 250 mA max.
Power supply| 22 to 26 Vac 50/60Hz
Power consumption| 2 VA
Set point range| 0°C to +60°C [32°F to +140°F]
Internal Temperature Sensor| Range: 0°C to +50°C [32°F to +122°F]
External Temperature Sensor| 10k 0 type 3 I Range: -40°C to +100°C [-40°F to +212°F]
Control accuracy| Temperature: +/-0.2°C [0.4°F]
Proportional band| 0.5 °C to 20°C [1 °C to 40°F] adjustable
Electrical connection| 0.8 mm2 [18 AWG] minimum
Operating temperature| 0°C to +50°C [32°F to +122°F]
Storage temperature| -30°C to +50°C [-22°F to +122°F]
Relative Humidity| 5 to 95 % noncondensing
Degree of protection of housing| IP 30 to EN 60529
Weight| 85 g. [0.2 lb]
Dimensions
A = 3.00″ I 78mm
B = 3.00″ I 78mm
C = 1.00″ I 24mm
D = 2.36″ I 60mm|

Presentation

neptronic TMA54-EXT1 Thermostat - Figure 2

Mounting Instructions

neptronic TMA54-EXT1 Thermostat - Figure 3

CAUTION: Risk of malfunction. Remove power prior to separating the thermostat cover from its base.
A. Remove the screw (captive) holding the base and the front cover of the thermostat.
B. Lift the front cover of the thermostat to separate it from the base.
C. Pull wire through the base hole.
D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
E. Mount the control module on the base and secure using the screw.

Terminal Descriptions

Terminals TMA54-EXT1
1 Common
2 24 Vac
3 Exterior temperature sensor
4 Night set back input*
5 Heating 1st ramp
6 Heating 2nd rampt
7 Cooling 1st ramp
8 Cooling 2nd ramp
9 TPM (time proportional modulation)
  • For a replacement in an existing night set back (NSB) loop with thermostat PTA, the NSB input, terminal #4, of the TMA should be isolated for good performance.

    • For controlling an electric heater with a modulating signal (0-10Vdc), use terminal 6 (Heating 2nd ramp)

Settings on PC Board

neptronic TMA54-EXT1 Thermostat - Figure 5

Programming Mode

When in this mode this symbol is displayed. Please press on the button to advance to the next program function and press on O or ▽to change the value. You can exit programming mode at any time, changed values will be recorded.

neptronic TMA54-EXT1 Thermostat - Figure 6neptronic TMA54-EXT1 Thermostat - Figure
7neptronic TMA54-EXT1 Thermostat - Figure
8

Typical Application

Thermostat for controlling an electric heater in a Make-Up Air unit.

neptronic TMA54-EXT1 Thermostat - Figure 9

Recycling at end of life

At end of life, please return the thermostat to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.