Anern AN EVO 3600 Hybrid Inverter User Manual

May 15, 2024
Anern

Anern logo

AN-SCI-EVO-3600
AN-SCI-EVO-6200
HYBRID INVERTER

Anern AN EVO 3600 Hybrid Inverter

ABOUT THIS MANUAL

1.1 Purpose
This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.
1.2 Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.

SAFETY INSTRUCTIONS

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all appropriate sections of this manual.

  2. CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.

  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.

  4. Toreduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
    Turning off the unit will not reduce this risk.

  5. CAUTION — Only qualified personnel can install this device with battery.

  6. NEVER charge a frozen battery.

  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It’s very important to correctly operate this inverter/charger.

  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.

  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.

  10. One piece of 150A fuse is provided as over-current protection for the battery supply.

  11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.

  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.

  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

INTRODUCTION

This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

3.1 Features
Pure sine wave inverter
Configurable input voltage range for home appliances and personal computers via LCD setting
Configurable battery charging current based on applications via LCD setting
Configurable AC/Solar Charger priority via LCD setting
Compatible to mains voltage or generator power
Auto restart while AC is recovering
Overload/ Over temperature/ short circuit protection
Smart battery charger design for optimized battery performance
Cold start function

3.2 Basic System Architecture
The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:
Generator or Utility.
PV modules
Consult with your system integrator for other possible system architectures depending on your requirements.
This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Anern AN EVO 3600 Hybrid Inverter - Fig 1

Figure 1 Hybrid Power System
3.3. Product Overview

Anern AN EVO 3600 Hybrid Inverter - Fig 2

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons
  6. Power on/off switch
  7. AC input
  8. Main output
  9. Second output
  10. Battery input
  11. PV input
  12. Anti dust kit
  13. RS-232 communication port /WiFi-port

INSTALLATION

4.1 Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:
The unit x 1
User manual x 1
4.2 Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.
4.3 Mounting the Unit
Consider the following points before selecting where to install:
Do not mount the inverter on flammable construction materials.
Mount on a solid surface

Install this inverter at eye level in order to allow the LCD display to be read at all times.
For proper air circulation to dissipate heat, allow a clearance of approx. 20 om to the side and approx. 50 cm above and below the unit.
The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
The recommended installation position is to be adhered to the wall vertically.
Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It’s recommended to use M6 screws.
4.4 Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it’s still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

Recommended battery cable size:

Model Wire Size Cable (mm²) Torque value (max)
3.6KW/6.2KW 1 x 2AWG 25 2 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as below chart.Anern AN EVO 3600 Hybrid Inverter - Fig 5
  4. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver

Anern AN EVO 3600 Hybrid Inverter - Fig 6

WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection
CAUTION! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A for 3.6KW and SOA for 6.2KW .
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires

Model Gauge Cable (mm2) Torque Value
3.6KW 12 AWG 4 1.2 Nm
6.2KW 10 AWG 6 1.2 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.

  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.

  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws.Anern AN EVO 3600 Hybrid Inverter - Fig 7 WARNING:
    Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.Anern AN EVO 3600 Hybrid Inverter - Fig 8

  5. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.Anern AN EVO 3600 Hybrid Inverter - Fig 9

  6. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioner are required at least 2-3 minutes to restart because it’s required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
4.6 PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Model Gauge Cable (mm2) Torque Value
3.6KW/6.2KW 1x12AWG 4 1.2 Nm

PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL 3.6KW 6.2KW
Max. PV Array Open Circuit Voltage 500Vdc
PV Array MPPT Voltage Range 90Vdc-450Vdc

Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.

Solar Panel Spec. (reference)
– 250Wp
– Vmp: 30.1Vdc – Imp: 8.3A
– Voc: 37.7Vdc – Isc: 8.4A
– Cells: 60| SOLAR INPUT| Q’ty of panels| Total input
power
---|---|---|---
(Min in serial: 6 pcs, max. in serial: 13 pcs)
6 pcs in serial| 6 pcs| 1500W
8 pcs in serial| 8 pcs| 2000W
12 pcs in serial| 12 pcs| 3000W
13 pcs in serial| 13 pcs| 3250W
8 pieces in serial and 2 sets in parallel| 16 pcs| 4000W
10 pieces in serial and 2 sets in parallel| 20 pcs| 5000W
10 pieces in serial and 2 sets in parallel| 20 pcs| 6200W
12 pieces in serial and 2 sets in parallel| 24 pcs| 6500W
10 pieces in serial and 3 sets in parallel| 30 pcs| 7500W

PV Module Wire Connection
Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector.

Recommended tool: 4mm blade screwdriver

Anern AN EVO 3600 Hybrid Inverter - Fig 11

4.7 Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
4.8 Communication Connection

  1. Wi-Fi cloud communication (option):
    Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to “Wi-Fi Plug Quick Installation Guideline” to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

  2. GPRS cloud communication (option):
    Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to “GPRS RTU Quick Installation Guideline” to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.

RGB Light (option )

  1. Battery Mode:red Light
  2. Utility Mode:blue Light
  3. PV Mode:purple Light

OPERATION

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.

5.2 Operation and Display Panel
The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.

Anern AN EVO 3600 Hybrid Inverter - Fig 13

LED Indicator

LED Indicator Messages
INV/AC Green
Flashing Output is powered by battery or PV in battery mode.
CHG Green
Flashing Battery is charging.
FAULT Red
Flashing Warning condition occurs in the inverter.

Function Keys

Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode

5.3  LCD Display Icons

Icon Function description

Input Source Information
| Indicates the AC input.
| Indicates the PV input
| Indicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.6KW models), charger power, battery voltage.
Configuration Program and Fault Information

| Indicates the setting programs.
| Indicates the warning and fault codes.
Warning: flashing with warning code.
Fault: lighting with fault code
Output Information
| Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Battery Information
|
Load Information

| Indicates overload.
Mode Operation Information
| Indicates unit connects to the mains.
| Indicates unit connects to the PV panel.
| Indicates load is supplied by utility power.
| Indicates the utility charger circuit is working.
| Indicates the DC/AC inverter circuit is working.
Mute Operation
| Indicates unit alarm is disabled.

5.4 LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to exit.

Setting Programs:

Program Description Selectable option
0 Exit setting mode
1 Output source priority: To configure load power source priority

will provide power to the loads as first priority.
Solar and battery energy will provide power to the loads only when utility power is not available.
| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, utility will supply power to the loads at the same time.
Battery provides power to the loads only when any one condition happens:
– Solar energy and utility is not available.
– Solar energy is not sufficient and utility is not available.
| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
| Solar energy provides power to the loads as frist priority , if solar energy is not sufficient
to power all connected loads , utility energy will supply power to the loads at the same time. The battery only supplies energy to the load as a backup power.
2| Maximum charging current: To configure total charging current for solar and utility chargers.
(Max. charging current = utility charging current + solar charging current)|
---|---|---
Anern AN EVO 3600 Hybrid Inverter - Symbol 22
3| AC input voltage range| | If selected, acceptable AC input voltage range will be within 90-280VAC.
If selected, acceptable AC input voltage range will be within 170-280VAC.
5| Battery type|
|
If “User-Defined” is selected, battery charge voltage and low DC cut- offvoltage can be set up in program 26, 27 and 29.
When the solar energy exists,Set this item to LIB, and the lithiumbattery will be activated for 3 second.
6| Auto restart when overload occurs|
7| Auto restart when over temperature occurs
9| Output frequency
10| Output voltage
11| Maximum utility charging current
Note: If setting value in program 02 is smaller than that in program in 11, the inverter will apply charging current from program 02 for utility charger.| Anern AN EVO 3600 Hybrid Inverter - Symbol 28
---|---|---
12| Setting voltage point back to utility source when selecting “SBU priority” or “Solar first” in program 01.| Anern AN EVO 3600 Hybrid Inverter - Symbol
29
13| Setting voltage point back to battery mode when selecting “SBU priority” or
“Solar first” in program 01.| Anern AN EVO 3600 Hybrid Inverter - Symbol
30
---|---|---
16| Charger source priority: To configure charger source priority| If this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below:
---|---|---
| Solar energy will charge battery as first priority.
Utility will charge battery only when solar energy is not available.
Solar energy and utility will charge battery at the same time.
Solar energy will be the only charger source no matter utility is available or not.
If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it’s available and sufficient.
18| Alarm control|
19| Auto return to default display screen| | If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage /output voltage) after no button is pressed for 1 minute.
If selected, the display screen will stay at latest screen user finally switches.
20| Backlight control|
22| Beeps while primary source is interrupted|
---|---|---
23| Overload bypass:
When enabled, the unit will transfer to line mode if overload occurs in battery mode.
25| Record Fault code
26| Bulk charging voltage (C.V voltage)| If self-defined is selected in program 5, this program can be set

up. Setting range is from 25.0V to 29.0V for 3.6KW model and

48.0V to 58.0v for 6.2KW model. Increment of each click is 0.IV.

27| Floating charging voltage|
If self-defined is selected in program 5, this program can be set up.Setting range is from 25.0V to 29.0V for 3.6Kw model and 48.0V to 58.0V for 6.2KW model. Increment of each click is 0. IV.
29| Low DC cut-off voltage|
| | If self-defined is selected in program 5, this program can be set up. Setting range is from 20.0V to 24.0V for 3.6KW model and
40.0V to 48.0V for 6.2KW model. Increment of each click is
0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
---|---|---
30| Battery equalization|
If “Flooded” or “User-Defined” is selected in program 05, this program can be set up.
31| Battery equalization voltage|
Setting range is from 25.0V to 31.5V for 3.6KW model and 48.0V
to 61.0V for 6.2KW model. Increment of each click is 0.1V.
33| Battery equalized time|

| Setting range is from 5min to 900min. Increment of each click is 5min.
34| Battery equalized timeout| Setting range is from 5min to 900 min. Increment of each click is 5 min.
35| Equalization interval| Setting range is from 0 to 90 days. Increment of each click is 1 day
36| Equalization activated immediately|
If equalization function is enabled in program 30, this program can be set up. If “Enable” is selected in this program, it’s to activate battery equalization immediately and LCD main page will shows “ “. If “Disable” is selected, it will cancel equalization function until next activated equalization time arrives based on program 35 setting. At this time, “ ” will not be shown in LCD main page.
37| GRID-tie operation| | Inverter operates only in off-grid mode. Solar energy provides powerto the loadsas first priority and charging second
Inverter operates hybrid mode. Solar energy provides power to the loads as first priority and charging second Excess energy feed to grid.
38| GRID-tie current|
---|---|---
39| Led pattern light
41| Dual output
42| Enter the dual output functional voltage point|
Setting range is from 20.0V to 23.0V for 24VDC model and 40.0V to 46.0 V for 48VDC model. Increment of each click is 0.1V.

5.5 Display Setting
The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Waitt, DC discharging current, main CPU Version.

Selectable information LCD display

Charged state, and the power is less than lkw
Input voltage=222V ,
PV voltage=168V,
Battery voltage=25V, Output voltage=222V, Load in Watt=188W,
Chg(Flashing), Inv/ac(bright)|
Input voltage=223V ,
PV current=2.3A,
Battery current=20A,
Output voltage=224V, Load in VA=188VA,
Chg(Flashing), Inv/ac(bright)
Input voltage=223V ,
Pv ntc temperture=71.0°C, Battery voltage= 25V,
Inv ntc temperture=35.0°C, Load percentage=12%, Chg(Flashing), Inv/ac(bright)
Input frequency=50.0Hz , PV power=0.434KWh, Battery current=20A, Output frequency=50.0Hz, Load in watt=188W, Chg(Flashing), Inv/ac(bright)|
---|---
Charged state, and the power is greater than 1kw
Input voltage=222V , PV voltage=168V, Battery voltage=25V, Output voltage=222V, Load in Watt=1.18KW, Chg(Flashing), Inv/ac(bright)| Anern AN
EVO 3600 Hybrid Inverter - Symbol 50
Input voltage=224V , PV current=8.6A, Battery current=12.5A, Output voltage=222V, Load in VA=1.88KVA, Chg(Flashing), Inv/ac(bright)
Input voltage=223V , Pv ntc temperture=71.0°C, Battery voltage=25V, Inv ntc temperture=35.0°C, Load percentage=82%, Chg(Flashing), Inv/ac(bright)
Input frequency=50.0Hz , PV power=1.434KWh, Battery current=20A, Output frequency=50.0Hz, Load in watt=1.88KW, Chg(Flashing), Inv/ac(bright)
Discharged state, and the power is less than 1kw

Input voltage=0V ,
PV voltage=0V,
Battery voltage=25V,
Output voltage=222V,
Load in Watt=188W,
Chg(turn off), Inv/ac(Flashing)| Anern AN EVO 3600 Hybrid Inverter - Symbol
51
Input voltage=O0V ,
PV current=0A,
Battery current=12.5A,
Output voltage=222V,
Load in VA=188VA,
Chg(turn off), Inv/ac(Flashing)
Input voltage=0V ,
Pv ntc temperture=60.0°C,
Battery voltage=24V,
Inv ntc temperture=36.0°C,
Load percentage=13%,
Chg(turn off), Inv/ac(Flashing)
Input frequency=0Hz ,
PV power=0KWh,
Battery current=12A,
Output frequency=50.0Hz,
Load in watt=188W,
Chg(turn off), Inv/ac(Flashing)
Discharged state, and the power is greater than 1kw

Input voltage=0V ,
PV voltage=0V,
Battery voltage=25V,
Output voltage=222V,
Load in Watt=1.88KW,
Chg(turn off), Inv/ac(Flashing)| Anern AN EVO 3600 Hybrid Inverter - Symbol
52
Input voltage=0V ,
PV current=0A,
Battery current=111A,
Output voltage=222V,
Load in VA=1.88KVA,
Chg(turn off), Inv/ac(Flashing)
Input voltage=0V ,
Pv ntc temperture=68.0°C,
Battery voltage=24V,
Inv ate temperture=30.0°C,
Load percentage=81%,
Chg(turn off}, Inv/ac(Flashing)
Input frequency=0Hz ,
PV power=0KWh,
Battery current=111A,
Output frequency=50 .0Hz,
Load in watt=1.21KW,
Chg(turn off), Inv/ac(Flashing)
Main CPU version checking

5.6 Operating Mode Description

Operation mode Selectable information LCD display
Stanby mode Input voltage=222V , PV voltage=210V, Battery voltage=25V, Output
voltage=0V, Load in Watt=OW, Chg(Flashing), Inv/ac(bright) ![Anern AN EVO

3600 Hybrid Inverter - Symbol 53](https://manuals.plus/wp- content/uploads/2023/12/Anern-AN-EVO-3600-Hybrid-Inverter-Symbol-53.jpg)When working in Grid-Tie mode,the will be flash 3S/times.
Input voltage=223V , PV voltage=OV, Battery voltage=25V, Output voltage=OV, Load in Watt=OW, Chg(Flashing), Inv/ac(bright)
Input voltage=0V , PV voltage=210V, Battery voltage=25V, Output voltage=OV, Load in Watt=0W, Chg(Flashing)
Line mode| Input voltage=224V , PV current=8.6A, Battery current=12.5A, Output voltage=222V, Load in VA=1.88KVA, Chg(Flashing), Inv/ac(bright)
Input voltage=224V , PV voltage=OV, Battery voltage=25V, Output voltage=222V, Load in Watt=188W, Chg(Flashing), Inv/ac(bright)
Grid-Tie Operation| Input voltage=224V , PV current=8.6A, Battery current=12.5A, Output voltage=222V, Load in VA=1.88KVA, Chg(Flashing), Inv/ac(bright)
Battery mode| Input voltage=OV ,
PV voltage=180V,
Battery voltage=25V,
Output voltage=230V,
Load in Watt=388w,
Inv/ac(Flashing)|
Input voltage=OV ,
PV voltage=180V,
Battery voltage=25V,
Output voltage=230V,
Load in Watt=388W,
Chg(Flashing), Inv/ac(Flashing)

5.7 Battery Equalization Description
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top.
Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it’s recommended to equalize battery periodically.
How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Anern AN EVO 3600 Hybrid Inverter - Fig 15

Equalize charging time and timeout
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

Anern AN EVO 3600 Hybrid Inverter - Fig 16

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

Anern AN EVO 3600 Hybrid Inverter - Fig 17

5.8 Fault Reference Code

Fault Code Fault Event Icon on
1 Fan is locked when inverter is off. ![Anern AN EVO 3600 Hybrid Inverter -

Fig 18](https://manuals.plus/wp-content/uploads/2023/12/Anern-AN-EVO-3600 -Hybrid-Inverter-Fig-18.jpg)
2| Over temperature
3| Battery voltage is too high
4| Battery voltage is too low
5| Output short circuited or over temperature is detected by internal converter components.
6| Output voltage is too high.
7| Overload time out
8| Bus voltage is too high
9| Bus soft start failed
51| Over current or surge
52| Bus voitage is too low|
53| Inverter soft start failed
55| Over DC voltage in AC output
57| Current sensor failed
58| Output voltage is too low
59| PV voltage is over limitation

5.9 Warning Indicator

Warning Code| Warning Event| Audible Alarm| Icon flashing
---|---|---|---
1| Fan is locked when inverter is on.| Beep three times every second|
3| Battery is over-charged| Beep once every second
4| Low battery| Beep once every second
7| Overload| Beep once every 0.5 second
10| Output power derating| Beep twice every 3 seconds
15| PV energy is low.| Beep twice every 3 seconds
| Battery equalization| None
| Battery is not connected| None

CLEARANCE AND MAINTENANCE FOR ANTI-DUST KIT

6.1 Overview
Every inverter is already installed with anti-dusk kit from factory. Inverter will automatically detect this kit and activate internal thermal sensor to adjust internal temperature. This kit also keeps dusk from your inverter and increases product reliability in harsh environment.
6.2 Clearance and Maintenance
Step 1: Please loosen the screw in counterclockwise direction on the top of the inverter. Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.

Anern AN EVO 3600 Hybrid Inverter - Fig 24

Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.

SPECIFICATIONS

Table 1 Line Mode Specifications

INVERTER MODEL 3.6KW 6.2 KW
Input Voltage Waveform Sinusoidal (WM ty or generator)
Nominal Input Voltage 230Vac
Low Loss Voltage 170Vact7V (UPS);

90Vac:k7V (Appliances)
Low Loss Return Voltage| 180Vact7V (UPS);
100Vac±7V (Appliances)
High Loss Voltage| 280Vaci7V
High Loss Return Voltage| 270Vac:k7V
Max AC Input Voltage| 300Vac
Nominal Input Frequency| 50Hz / 60Hz (Auto detection)
Low Loss Frequency| 4011Hz
Low Loss Return Frequency| 42±1Hz
High Loss Frequency| 65±1Hz
High Loss Return Frequency| 63e1Hz
Output Short grant Protection| arcuit Breaker
Efficiency (Line Mode)| >95% ( Rated R load, battery full charged )
Transfer Time| 10ms typical (UPS);
20ms typical (Appliances)
Output power derating:
When AC input voltage drops to 170V, the output power will be derated.| Anern AN EVO 3600 Hybrid Inverter - Fig 25

Table 2 Inverter Mode Specifications

INVERTER MODEL 3.6KW 6.2KW
Rated Output Power 3.6KW 6.2KW
Output Voltage Waveform Pure Sine Wave
Output Voltage Regulation 230Vac:t5%
Output Frequency 50Hz
Peak Efficiency 93%
Overload Protection 3s@2150% load; 5s@101%-150% load
Surge Capacity r rated power for 5 seconds
Nominal DC Input Voltage 24Vdc 48Vdc
Cold Start Voltage 23.0Vdc 46.0Vdc

Low DC Warning Voltage @ load < 50%
@ load a 50%| 22.0Vdc
21.0Vdc| 44.0Vdc
42.0Vdc
Low DC Warning Return Voltage @ load < 50%
@ load ? 50%| 22 5Vdc
22.0Vdc| 45.0Vdc
44.0Vdc
Low DC Cut-off Voltage @ load < 50%
@ load a 50%| 20.5Vdc
20.0Vdc| 41.0Vdc
40.0Vdc
High DC Recovery Voltage| 32Vdc| 62Vdc
High DC Cut-off Voltage| 33Vdc| 63Vdc
No Load Power Consumption| 30W| 50W

Table 3 Two Load Output Power

INVERTER MODEL 3.6KW 6.2KW
Full Load 3600W 6200W
Maximum Main Load 3600W 6200W
Maximum Second Load(battery model) 1200W 2066W
Main Load Cut Off Voltage 22VDC 44VDC
Main Load Return Voltage 26VDC 52VDC

Table 4 Charging Mode Specifications

Utility Charging Mode|
---|---
INVERTER MODEL| 3.6KW| | 6.2KW
Charging Algorithm| | 3-Step
AC Charging Current (Max)| 100Amp (@Vup=230Vac)| 100Amp (@Vup=230Vac)
Bulk Charging Voltage| Flooded Battery| 29.| | 58.
AGM / Gel Battery| 28.| | 56.
Floating Charging Voltage| 27Vdc| | 54Vdc
Charging Curve| Anern AN EVO 3600 Hybrid Inverter - Fig
26
MPPT Solar Charging Mode|
INVERTER MODEL| 3.6KW| | 6.2KW
Max. PV Array Power| 6200W| | 6500W
Nominal PV Voltage| 240Vdc| | 360Vdc
PV Array MPPT Voltage Range| | 90Vdc-450Vdc
Max. PV Array Open Circuit Voltage| | 500Vdc
Max Charging Current
(AC charger plus solar charger)| 120Amp| | 120Amp

Table 5 Grid – Tie Operation

INVERTER MODEL 3.6KW 6.2KW
Nominal Output Voltage 220/230/240VAC
Feed-in Grid Voltage Range 195 -253VAC
Feed-in Grid Frequency Range 49-51+1Hz/59-61±1Hz
Nominal Output Current 15.7A 26.9A
Power Factor Range >0.99
Maximum Conversion Efficiency (DC/AC) 97%

Table 6 General Specifications

INVERTER MODEL 3.6KW 6.2KW
Safety Certification CE
Operating Temperature Range -10°C to 50°C
Storage temperature -15°C- 60°C
Humidity 5% to 95% Relative Humidity (Non-condensing)
Dimension (DWH), mm 420350110mm 450`350*110mm
Net Weight, kg 9 10

TROUBLE SHOOTING

Problem| LCD/LED/Buzzer| Explanation / Possible cause| What to do
---|---|---|---
Unit shuts down automatically
during startup process.| LCD/LEDs and buzzer will be active for 3 seconds and then complete off.| The battery voltage is too low (<1.91V/Cell)| 1.Re-charge battery.
2.Replace battery.
No response after power on.| No indication,| 1.The battery voltage is far too low. (<1.4V/Cell)
2.Internal fuse tripped.| 1.Contact repair center for replacing the fuse.
2.Re-charge battery.
3.Replace battery.
Mains exist but the
unit works in mode. battery| Input voltage is displayed as 0 on the LCD and green LED is flashing.| Input protector is tripped| Check if AC breaker is tripped and AC wiring is connected well
Green LED is flashing.| Insufficient quality of AC power. (Shore or Generator)| 1.Check if AC wires are too thin and/or too long.
2.Check if generator (if applied) is working well or if input voltage range setting is correct. (UPSOAppliance)
Green LED is flashing.| Set “Solar First” as the priority of output source.| Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.| LCD display and LEDs are flashing| Battery is di nnected.| Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.| Fault code 07| Overload error. The inverter is overload 110% and time is up.| Reduce the connected load by switching off some
equipment
Fault code 05| Output short drcuited.| Check if wiring is connected well and remove abnormal load.
Temperature of internal converter component is over 120°C.| Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02| Internal temperature of inverter component is over 100°C.
Fault code 03| Battery is over-charged.| Return to repair center.
The battery voltage is too high.| Check if spec and quantity of batteries are meet requirements.
Fault code 01| Fan fault| Replace the fan.
Fault code 06/58| Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)| 1.Reduce the connected load.
2.Return to repair center
Fault code
08/09/53/57| Internal components failed.| Return to repair center.
Fault code 51| Over current or surge.| Restart the unit, if the error happens again, please return to repair center.
Fault code 52| Bus voltage is too low.
Fault code 55| Output voltage is unbalanced.

Appendix: Approximate Back-up Time Table

Model| Load (W)| Backup Time @ 24Vdc 100Ah (min)| Backup Time @ 24Vdc 200Ah (min)
---|---|---|---
3.6KW| 300| 449| 1100
600| 222| 525
900| 124| 303
1200| 95| 227
1500| 68| 164
1800| 56| 126
2100| 48| 108
2400| 35| 94
2700| 31| 74
3200| 28| 67
3600| 25| 60
4200| 22| 53
Model| Load (W)| Backup Time @ 48Vdc 100Ah (min)| Backup Time @ 48Vdc 200Ah (min)
---|---|---|---
6.2KW| 500| 613| 1288
1000| 268| 613
1500| 158| 402
2000| 111| 271
2500| 90| 215
3200| 76| 182
3500| 65| 141
4000| 50| 112
4500| 44| 100
5000| 40| 90
6200| 36| 80
7200| 30| 65

Note:

  1. Backup time depends on the quality of the battery, age of battery and type of battery.
    Specifications of batteries may vary depending on different manufacturers.

  2. The final interpretation right of this product belongs to the company.

Anern logo Web:anern-group.com 