GEYA GRT8-At-Bt Single Function Time Relay Instruction Manual

June 15, 2024
GEYA

**GEYA GRT8-At-Bt Single Function Time Relay

**

General

  • Applications

    • Suitable for applications where function and time requirements are know.
    • Time switch , possible to be used for pump decay time after switching heating off , switching of fans.
  • Function Features

    • Single-function relay with possibility of time setting by a potentiometer.

    • Choice of 2 functions:
      A:Delay ON
      B:Delay OFF

    • Time scale 0.1 s – 10 days divided into 10 ranges..

    • Relay status is indicated by LED.

    • 1-MODULE,DIN rail mounting.

  • Model and connotation

General

Technical parameters

Technical parameters GRT8-A1/B1 GRT8-A2/B2 GRT8-At/Bt
Function A:delay ON;B:delay OFF
Supply terminals A1-A2
Voltage range W240 AC/DC 12-240V(50-60Hz)
Burden AC 0.09-3VA/DC 0.05-1.7W
Voltage range A230 AC 230V(50-60Hz)
Power input AC max.6VA/1.3W AC max.6VA/1.9W
Supply voltage tolerance -15%;+10%
Supply indication green LED
Time ranges 0.1s-10days,ON,OFF
Time setting potentionmeter
Time deviation 10%-mechanical setting
Repeat accuracy 0.2%-set value stability
Temperature coecient 0.05%/℃,at=20℃(0.05%℉,at=68℉)
Output 1×SPDT 2×SPDT 1×SPDT(del)+1×SPDT(ins)
Current rating 16A/AC1
Switching voltage 250VAC/24VDC
Min.breaking capacity DC 500mW
Output indication red LED
Mechanical life 1×10 (7)
Electrical life(AC1) 1×10 (5)
Reset time max.200ms
Operating temperature -20℃ to +55℃(-4℉ to 131℉)
Storage temperature -35℃ to +75℃(-22℉ to 158℉)
Mounting/DIN rail Din rail EN/IEC 60715
Protection degree IP40 for front panel/IP20 terminals
Operating position any
Overvoltage cathegory III.
Pollution degree 2
Max.cable size(mm²) solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG
  1. Tightening torque| 0.4Nm
    Dimensions| 90×18×64mm
    Weight| W240-61g,A230-61g| W240-81g,A230-80g
    Standards| EN 61812-1,IEC60947-5-1

Panel Diagram

Wiring Diagram

Wiring Diagram

Functions Diagram

Functions Diagram

Time Setting

| Knob 1: delay gear setting, “s” for second, “m” for minute, “h” for hour, “d” for day, “ON” for relay action (15-18/25-28 closed), “OFF” for relay open (15-18/25-28 open).
---|---

| Knob 2: fine adjustment of delay time, 10% ~ 100% adjustable.
Delay time = knob 1 × knob 2.
Example 1: it needs to be set for 5 seconds. You can set knob 1 to 10s, knob 2 to 50%, and delay time = 10s × 50% = 5s.
Example 2: it needs to be set for 8 minutes. You can set knob 1 to 10m, knob 2 to 80%, and delay time = 10m × 80% = 8m.

Dimensions(mm)

Disposal of Electrical Waste
All electrical waste should be disposed of in compliance with current WEEE regulations.

Caution
The products must be installed by qualified electricians. All and any electrical connections of the product shall comply with the appropriate safety standards.

http://www.geya.net

GEYA ELECTRICAL CO.,LTD

Add:Wenzhou Brige Industrial Zone,Beibaixiang Town, Yueqing,Zhejiang,China 325603

Tel:0086-577-62771036
Fax:0086-577-62711079
E-mail: [email protected]
Web: www.geya.net

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GEYA User Manuals

Related Manuals