PHILIPS T8 MainsFit LED Tube Installation Guide

June 15, 2024
Philips

PHILIPS T8 MainsFit LED Tube

PHILIPS-T8-MainsFit-LED-Tube-PRODUCT

  • Unlike fluorescent lamps that require a ballast to illuminate, the Philips Mains Fit LED tube is designed to operate on AC line voltage ( 120 – 277V) without the need of a ballast/driver.
  • This installation guide provides important installation steps for proper safe operation and installation of Philips MainsFit LED tube. If you have any questions or comments, please feel free to contact Signify at 1800-555-0050 (USA), 1800-668-9008 (Canada).
  • Philips MainsFit LED tube is suitable to replace (either TS orT12) fluorescent lamps in fixtures containing G 13, FAS or R 17d’ lampholders.
  • G 13, FAS or RI 7d lampholders are the most common in TS orTl2 fluorescent fixtures.

Philips Mains Fit LED T8 Tube

En1ur11 all parts and accessories are in the package, including instructions guide, field-applied label and MainsFit LED tube,

Retrofit Instructions

  1. Before installation starts, please make sure power to the fixture is switched off at the circuit breaker panel.

  2. Remove fluorescent lamps and ballast cover from the fixture.

  3. Cut all wires to the ballast. Please cut wires as close to the ballast as possible since these wires will be reused.

  4. Ensure lampholders are in good condition, with no corrosion or blackened marks, and firmly secured. L.ampholders should be shunted type (mostly used with instant-start ballasts). In case, lampholders are non-shunted type, they can be used by adding a jumper wire to short two terminals (see adjacent figure).

  5. Philips MainsFit LED tube is dual ended, meaning it requires AC power from both sides. Connect the AC line hot wire (typically black) to one lampholder, and neutral wire (typically white) to the opposite side lampholder.
    Note : All wire connections and un-used wires must be properly capped. Ensure fixture remain properly grounded.

  6. Reinst.all the ballast cover removed in step 2 above. Affix the provided field label at a visible location on fixture for future installers to know that the fixture has been modified to accommodate LED lamp1 •

  7. Inst.all Philips MainsFit LED tube in the lampholders. Ensure tube pins are firmly seated in the lampholders.

  8. Switch on power to the fixture.

Luminare Description

  • Philips LED TS tubes can’t retrofit original luminaries which use remote Starter.
  • Please make sure the existed luminaire dimensions are not less than dimension described in below table.

PHILIPS-T8-MainsFit-LED-Tube- \(5\)

  1. It is recommended to convert all fluorescent lamps to LED TS tubes in a luminaire. Affixing a label on a partially converted luminaire can communicate misleading message to future installers. PHILIPS-T8-MainsFit-LED-Tube- \(1\)

Figure shows two lamps with one ballast. For other configurations, please contact Philips Lighting.

PHILIPS-T8-MainsFit-LED-Tube- \(2\)Figure showing how to convert a non-shunted lampholder to a shunted lamp holder using a jumper wire.

PHILIPS-T8-MainsFit-LED-Tube- \(3\)Figure shows two lamps with one ballast. For other configurations, please contact Philips Lighting.

PHILIPS-T8-MainsFit-LED-Tube- \(4\)

WARNINGS, CAUTIONS AND OPERATING INSTRUCTIONS
WARNING: “THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZA RDS INVOLVED.”

Philips MainsFit LED T8 Tube

  1. Risk of fire or electric shock. The electrical rating of these products are I 20~277V, the installer must determine whether they have I 20-277V at the luminaire before installation.
  2. Risk of fire or electric shock. Luminaires wiring, ballasts, or other electrical parts may be damaged when installing of reflector kit hardware. Check for enclosed wiring and components.
  3. Risk of fire or electric shock. LED Retrofit kit installation requires knowledge of fluorescent lighting luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
  4. WARNING- RISK OF FIRE OR ELECTRIC SHOCK. INSTALL THIS KIT ONLY IN THE LUMINAIRES THAT HAS THE CONSTRUCTION FEATURES AND DIMENSIONS SHOWN IN THE PHOTOGRAPHS AND/OR DRAWINGS AND WHERE THE INPUT RATING OF THE RETROFIT KIT DOES NOT EXCEED THE INPUT RATING OF THE LUMINAIRE.
  5. To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
  6. Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
  7. Installers should examine all parts that are not intended to be replaced by the retrofit kit for damage and replace any damaged parts prior to installation of the retrofit kit.
  8. Installers should not disconnect existing wires from lampholder terminals to make new connections at lampholder terminals Instead installers should cut existing lampholder leads away from the lampholder and make new electrical connections to lampholder lead wires by employing applicable connectors.
  9. THIS RETROFIT KIT IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE
    THE SUITABILITY OF THE COMBINATION SHALL BE DETERMINED BY AUTHORITIES HAVING JURISDICTION. PRODUCT MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH THE APPLICABLE AND APPROPRIATE ELECTRICAL CODES. THE INSTALLATION GUIDE DOES NOT SUPERSEDE LOCAL OR NATIONAL REGULATIONS FOR ELECTRICAL INSTALLATIONS.

SUITABLE FOR DRY OR DAMP LOCATIONS.

  • THIS DEVICE IS NOT INTENDED FOR USE WITH EMERGENCY EXITS.
    THIS DEVICE COMPLIES WITH PARTIS OF THE FCC RULES AND INDUSTRY CANADA LICENCE- EXEMPT RSS STANDARD(S).OPERATION IS SUBJECT TOTHE FOLLOWINGTWO CONDITIONS
  1. THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE,AND
  2. THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
  • CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE PARTY RESPONSIBLE FOR COMPLIANCE COULD VOID THE USER’S AUTHORITYTO OPERATE THE EQUIPMENT.
  • This device has been tested and found to comply with the limits for a Class B digital device pursuant to Part I 5 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This device generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this device does cause harmful interference to radio or television reception, which can be determined by turning the device off and on, the user is encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna Increase the separation between the device and receiver Connect the device into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio/television technician for help.
  • This Class B digital apparatus complies with Canadian ICES-005

© 2021 Signify Holding

  • @ignify
  • Signify reserves the right to make changes in specifications and/or to discontinue any product at any time without notice  or obligation and will not be liable for any consequences  resulting from the use of this publication.
  • 04/21 www.philips.com/lighting
  • Philips and the Philips shield emblem are registered trademarks of Koninklijke Philips N.V.
  • Signify NorthAmerica Corporation 400 Crossing Blvd, Suite 600 Bridgewater, NJ 08807, USA
  • lmporte par : Signify Canada Ltlle. 281 Hillmount Road,
  • Markham, ON, Canada L6C 253

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals