Maytag P6SD-X Air Conditioner Packaged Owner’s Manual
- June 15, 2024
- Maytag
Table of Contents
- IMPORTANT INFORMATION
- FEATURES and BENEFITS
- MODEL IDENTIFICATION CODE
- DIMENSIONS
- SPECIFICATIONS
- BLOWER PERFORMANCE
- Heater application matrix
- ELECTRICAL DATA
- ACCESSORIES
- COOLING EXPANDED RATINGS
- GENERAL TERMS OF LIMITED WARRANTY
- CUSTOMERS SUPPORT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Maytag P6SD-X Air Conditioner Packaged
IMPORTANT INFORMATION
The P6 Series single packaged air conditioners are high efficiency self contained cooling units that can be installed on a roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLC listed.
FEATURES and BENEFITS
- State-of-the-art Copeland Scroll compressor is standard equipment.
- Proven, Industry Standard Components Easier service and availability.
- TXV Externally Equalized Provides precise refrigerant control under varying load conditions.
- High and Low Pressure Switches Added compressor protection.
- Liquid Line Filter Drier Insures clean and dry refrigeration system.
- Externally Accessible Service Ports Quick access to refrigerant system without disrupting operation.
- Compact Footprint/Low Profile Easy to handle and transport.
- Convertible Air Delivery Horizontal or downflow to accommodate rooftop or horizontal application.
- Heavy-Gauge, Full Perimeter Base Rails Facilitates forklift handling and curb mounting.
- Galvanized Steel Cabinet Polyurethane finish provides 950 hours salt spray protection.
- Wire Guard Coated with Earth Friendly Epoxy and Mesh Hail Guard Will never rust and protects the coil from being damaged by balls, lawnmowers, hail etc.
- Corrosion-Resistant Drain Pan Quickly drains away evaporator condensate.
- Quiet Operation and Low Vibration 20″ fan blade combined with custom venture condenser fan.
- Access to Controls and Major Components Easy in and out service.
- Service Access Panels Allows easy access to all major components and the compressor. Designed to make servicing easier for the Contractor.
- Easy to Install Electric heat strip provides up to 20 KW of heat output.
- Accessories Roof curbs, economizers, fresh air dampers and more.
MODEL IDENTIFICATION CODE
DIMENSIONS
Top View
Top View
Model Number P6SD| Unit Weight| Center of Gravity| Height
(in inches) C
---|---|---|---
A| B| with base rails
X36| 405| 29.5| 26.0| 35.0
X48| 415| 29.5| 26.5| 35.0
X60| 480| 30.0| 27.5| 43.0
Back (Duct) View
SPECIFICATIONS
Model Number | P6SD |
---|---|
X36K | X48K |
Performance
Capacity -Cooling BTUH| 34,200| 46,000| 58,000
Efficiency – SEER| 13.3| 13.0| 13.3
EER (Btuh/watt)| 11.2| 11.5| 11.0
Electrical Rating – 60 Hz
Phase| 1| 1| 1
Operating Voltage Range| 187 – 253| 187 – 253| 187 – 253
Compressor Data
Volts| 208 / 230| 208 / 230| 208 / 230
Rated Load Amps| 18.6| 24.3| 29.3
Lock Rotor Amps| 79| 117| 134
Indoor Blower
Type / No. of Speeds| DD / 3| DD / 3| Fixed Torque / 5
Motor – HP / RPM| 1/4 – 1075| 1/2 – 1080| 3/4
Motor – Amps| 1.3| 3.1| 6.0
Outdoor Fan
Motor – HP / RPM| 1/4 – 1100| 1/4 – 1100| 1/4 – 1100
Motor – Amps| 1.2| 1.2| 1.2
Fan Diameter / CFM| 20/3600| 20/3800| 20/3800
Refrigerant Charge – Oz.| 110| 168| 192
Shipping Weight| 415| 425| 490
BLOWER PERFORMANCE
Model Number | External Static Pressure Drop – inches water column |
---|---|
P6SD- | 0.1 |
0.7 | 0.8 |
X36 ***** | High |
Medium | 1367 |
Low | 1153 |
X48 ***** | High |
Medium | 2026 |
Low | 1584 |
**X60*** | Tap T1 |
1160
Tap T2| 1580| 1520| 1460| 1400| 1300| 1280| 1260| 1230
Tap T3| 1740| 1690| 1650| 1600| 1360| 1500| 1460| 1390
Tap T4| 1960| 1910| 1840| 1820| 1540| 1740| 1700| 1600
Tap T5| 2090| 2050| 2010| 1975| 1780| 1900| 1850| 1790
- Denotes factory set cooling speed
- Denotes factory set electric heating speed
NOTE: Airflow performance is with a dry coil
MODEL IDENTIFICATION CODE
Heater application matrix
TONNAGE & PHASE| UNIT| Nominal **KW| HEATER KIT
MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED**
---|---|---|---|---|---
3 Ton, Single Phase| P6SD| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
4 Ton, Single Phase| P6SD| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
20| H3HK020H-01B| 917170B| 2
20| H3HK020H-21B| 917173B| None
5 Ton, Single Phase| P6SD| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| 2
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
20| H3HK020H-01B| 917170B| 3
20| H3HK020H-21B| 917173B| 1
ELECTRICAL DATA
P6SD SERIES – 208/230V – SINGLE PHASE MODELS
MODEL NUMBER P6SD-| HEATER INSTALLED NOMINAL KW|
SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
mica| mop| CIRCUIT A (C ompressor & F an )|
CIRCUIT B (B lower & H eater )
mica| mop| mica| mop
X36K| 0| 25.8| 40| –| –| –| –
5| 26.5| 40| –| –| –| –
8| 41.2| 45| –| –| –| –
10| 51.6| 60| –| –| –| –
15| 76.6| 80| 50.0| 60| 26.6| 30
X48K| 0| 32.9| 50| –| –| –| –
5| 32.9| 50| –| –| –| –
8| 41.2| 50| –| –| –| –
10| 51.6| 60| –| –| –| –
15| 76.6| 80| 51.6| 50| 26.6| 30
20| 101.6| 110| 50| 50| 51.6| 60
MODEL NUMBER P6SD-| HEATER INSTALLED Nominal KW|
SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
mica| mop| CIRCUIT A (C ompressor , B lower ,
& F an )| CIRCUIT B (H eater o nly )|
CIRCUIT C (H eater o nly )
mica| mop| mica| mOP| mCA| mOP
X60K| 0| 43.8| 70| –| –| –| –| –| –
5| 43.8| 70| –| –| –| –| –| –
8| 43.8| 70| –| –| –| –| –| –
10| 51.5| 70| 43.8| 70| 50| 60| –| –
15| 76.5| 80| 51.5| 70| 25| 30| –| –
20| 101.5| 110| 43.8| 70| 50| 60| 50| 60
NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on different circuits when adding a heater kit.
COPPER WIRE SIZE — AWG (1% Voltage Drop)
Supply Wire Length-Feet| Supply Circuit Ampacity
200| 150| 100| 50
6| 8| 10| 14| 15
4| 6| 8| 12| 20
4| 6| 8| 10| 25
4| 4| 6| 10| 30
3| 4| 6| 8| 35
3| 4| 6| 8| 40
2| 3| 4| 6| 45
2| 3| 4| 6| 50
Wire Size based on N.E.C. for 60° type copper conductors.
ACCESSORIES
Description | Part Number |
---|---|
Roof Curb (8”) | 547830 |
Roof Curb (14”) | 547831 |
Roof Curb (18”) | 547850 |
Roof Curb (24”) | 547851 |
Supply/return transition, 16” | 547834 |
Supply/return transition, 18” | 547835 |
Concentric diffuser, flush, 16” | 547836 |
Concentric diffuser, flush, 18” | 547837 |
Concentric diffuser, step down 16” | 547838 |
Concentric diffuser, step down 18” | 547839 |
Manual Fresh Air Damper | 547832 |
Motorized Fresh Air Damper | 547840 |
Economizer, downflow w/filter (does not require filter kit) modulating | 558870 |
Economizer, horizontal modulating | 547841 |
Power Exhaust, downflow economizer (special order) | 547842 |
Power Exhaust horizontal economizer (special order) | 547843 |
Hood Type Hail Guard 34” X 76” P6SD-X36, P6SD-X48 | 547846 |
Hood Type Hail Guard 38” X 76” P6SD -X60 | 547847 |
Duct Smoke Detector Photo Elec | 558863 |
Multi Signal Control | 558866 |
Sampling Tube DST5, 2-4′ | 558864 |
Sampling Tube DST5, 4-8′ | 558865 |
Filter Rack, All Downflow Applications (not required with economizer) | 547885 |
Filter Kit (not required with economizer) P6SD-X36, P6SD-X48 | 547887 |
Filter Kit (not required with economizer ) P6SD-X60 | 547888 |
Universal Hard Start Kit | 912933 |
Low Ambient Kit | 918837 |
Skirt Trim Kit | 919729 |
Heater Kit – 4-Pole single circuit adaptor | 913350 |
Heater Kit – 6-Pole single circuit adaptor | 913556 |
Heater Kit – Circuit breaker single phase (2-pole) | 913554 |
Freeze stat Kit | 917108 |
Outdoor Testa Kit | 913852 |
Duct Adapter, 12″ Round (2 each) | 913811A |
Duct Adaptor, 14″ Round (2 each) | 913812A |
Control, CO2 sensor, wall mount | 547848 |
COOLING EXPANDED RATINGS
P6SD-X36
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFm | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. | |||
900 | 80 | 62 | 32.7 | 26.3 |
3.64
80| 67| 35.6| 21.3| 2.70| 33.9| 20.7| 2.98| 32.1| 20.2| 3.30| 30.1| 19.5| 3.67
80| 72| 38.9| 16.3| 2.75| 37.1| 15.8| 3.03| 35.2| 15.2| 3.34| 33.1| 14.7| 3.71
75| 63| 33.1| 21.0| 2.68| 31.5| 21.1| 2.95| 29.8| 21.0| 3.28| 28.0| 20.6| 3.64
1000| 80| 62| 33.5| 28.0| 2.68| 31.9| 29.0| 2.96| 30.3| 29.0| 3.28| 28.7|
28.7| 3.65
80| 67| 36.2| 22.5| 2.71| 34.4| 22.0| 2.99| 32.6| 21.4| 3.31| 30.7| 20.9| 3.67
80| 72| 39.6| 17.1| 2.76| 37.8| 16.6| 3.04| 35.8| 16.0| 3.35| 33.7| 15.5| 3.72
75| 63| 33.7| 23.1| 2.68| 32.0| 22.9| 2.96| 30.4| 22.8| 3.28| 28.6| 22.2| 3.65
1100| 80| 62| 34.7| 31.2| 2.69| 33.1| 31.3| 2.97| 31.6| 31.6| 3.30| 29.9|
29.9| 3.66
80| 67| 37.3| 24.5| 2.73| 35.5| 23.9| 3.00| 33.6| 23.2| 3.32| 31.6| 22.6| 3.69
80| 72| 40.7| 18.2| 2.77| 38.8| 17.7| 3.05| 36.7| 17.2| 3.37| 34.5| 16.6| 3.73
75| 63| 34.8| 26.0| 2.70| 33.1| 25.6| 2.97| 31.3| 24.9| 3.29| 29.4| 24.2| 3.66
P6SD-X48
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFm | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
1250
| 80| 62| 44.1| 35.7| 3.45| 42.2| 36.0| 3.84| 40.0| 37.1| 4.27| 37.8| 36.6|
4.77
80| 67| 47.9| 28.8| 3.50| 45.5| 28.0| 3.87| 43.1| 27.2| 4.31| 40.6| 26.7| 4.80
80| 72| 52.1| 21.9| 3.54| 49.5| 21.2| 3.92| 46.9| 20.5| 4.35| 44.2| 19.8| 4.85
75| 63| 52.1| 16.3| 3.54| 49.5| 16.7| 3.92| 47.0| 16.7| 4.35| 44.2| 16.4| 4.85
1400
| 80| 62| 45.2| 38.2| 3.46| 43.1| 39.5| 3.85| 41.0| 39.5| 4.29| 39.0| 39.0|
4.78
80| 67| 48.7| 30.6| 3.51| 46.3| 29.8| 3.88| 43.9| 29.4| 4.32| 41.4| 28.6| 4.81
80| 72| 52.9| 23.1| 3.54| 50.4| 22.4| 3.93| 47.7| 21.6| 4.36| 44.9| 20.9| 4.86
75| 63| 53.1| 18.2| 3.55| 50.5| 18.2| 3.93| 47.7| 17.9| 4.36| 45.0| 17.4| 4.86
1550
| 80| 62| 46.2| 41.8| 3.47| 44.2| 41.9| 3.86| 42.2| 42.2| 4.30| 40.1| 40.1|
4.80
80| 67| 49.6| 32.7| 3.51| 47.1| 32.0| 3.89| 44.6| 31.2| 4.33| 42.0| 30.4| 4.82
80| 72| 53.8| 24.2| 3.55| 51.1| 23.5| 3.95| 48.4| 22.8| 4.37| 45.5| 22.0| 4.86
75| 63| 53.8| 20.3| 3.55| 51.1| 19.8| 3.95| 48.4| 19.2| 4.37| 45.5| 18.4| 4.87
P6SD-X60
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFm | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
1600
| 80| 62| 56.7| 45.9| 4.53| 54.1| 46.1| 5.02| 51.3| 47.5| 5.57| 48.4| 46.7|
6.19
80| 67| 61.2| 37.4| 4.62| 58.1| 36.4| 5.09| 55.0| 35.3| 5.65| 51.7| 34.2| 6.26
80| 72| 66.6| 28.6| 4.72| 63.1| 27.7| 5.20| 59.5| 26.8| 5.75| 55.7| 25.7| 6.36
75| 63| 57.0| 36.9| 4.54| 54.2| 37.0| 5.02| 51.2| 36.7| 5.57| 48.2| 36.0| 6.18
1750
| 80| 62| 57.8| 48.3| 4.59| 55.1| 49.9| 5.07| 52.2| 49.9| 5.62| 49.3| 49.2|
6.24
80| 67| 62.0| 39.2| 4.67| 58.9| 38.1| 5.14| 55.7| 37.0| 5.70| 52.3| 35.8| 6.31
80| 72| 67.1| 29.8| 4.77| 63.5| 28.8| 5.24| 59.9| 27.8| 5.79| 56.2| 26.8| 6.41
75| 63| 57.8| 40.1| 4.59| 54.9| 39.8| 5.07| 51.9| 39.1| 5.62| 48.8| 38.1| 6.23
1900
| 80| 62| 58.7| 52.1| 4.64| 56.0| 52.2| 5.13| 53.1| 53.0| 5.68| 50.4| 50.4|
6.30
80| 67| 62.7| 40.9| 4.72| 59.6| 39.8| 5.20| 56.3| 38.7| 5.75| 52.8| 37.5| 6.36
80| 72| 67.5| 30.9| 4.81| 64.0| 29.9| 5.29| 60.5| 28.8| 5.84| 56.7| 27.7| 6.46
75| 63| 58.5| 43.5| 4.64| 55.6| 42.7| 5.12| 52.5| 41.6| 5.66| 49.3| 40.3| 6.28
GENERAL TERMS OF LIMITED WARRANTY
Nortek Global HVAC, LLC will furnish a replacement for any part of this product which fails in normal use and service within the terms and conditions of the warranty.
For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the Nortek Global HVAC, LLC warranty department for a copy.
Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (10/2015)
CUSTOMERS SUPPORT
800C-1014 (Replaces 800C-0910)
®/TM/© Maytag. All rights reserved. Manufactured under license by Nortek
Global HVAC, LLC, Missouri,
USA. Limited warranty provided by the manufacturer. © Nortek Global HVAC, LLC.
All rights reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>