MESTEK GG-IOM-18 Tubular Gas Fired Direct Spark Propeller Unit Heaters Installation Guide

June 15, 2024
MESTEK

MESTEK logo INSTALLATION INSTRUCTIONS
AND PARTS IDENTIFICATION
Installation Guide

GG-IOM-18 Tubular Gas Fired Direct Spark Propeller Unit Heaters

TUBULAR GAS-FIRED DIRECT SPARK PROPELLER UNIT HEATERS
– FOR COMMERCIAL, INDUSTRIAL AND RESIDENTIAL INSTALLATIONS –
ATTENTION: READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE UNITS! CHECK UNIT DATA PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATIONS AND MAKE CERTAIN THAT THESE AGREE WITH THOSE AT THE POINT OF INSTALLATION. RECORD THE UNIT MODEL AND SERIAL No.(s) IN THE SPACE PROVIDED. RETAIN FOR FUTURE REFERENCE.
Unit No……………..
Serial No………….
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a phone outside of the building.
Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call your fire department. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, injury, or death. Read the installation, operating, and maintenance instruction thoroughly before installing or servicing this equipment.
APPROVED FOR USE IN CALIFORNIA
Install, operate, and maintain unit in accordance with the manufacturer’s instructions to avoid exposure to fuel substances, or substances from incomplete combustion, which can cause death or serious illness. The state of California has determined that these substances may cause cancer, birth defects, or other reproductive harm.
INSTALLER’S RESPONSIBILITY
Installer Please Note: This equipment has been test fired and inspected. It has been shipped free from defects from our factory. However, shipment and installation problems such as loose wires, leaks, or loose fasteners may occur. It is the installer’s responsibility to inspect and correct any problem that may be found.
RECEIVING INSTRUCTIONS
Inspect shipment immediately when received to determine if any damage has occurred to the unit during shipment. After the unit has been uncrated, check for any visible damage to the unit. If any damage is found, the consignee should sign the bill of lading indicating such damage and immediately file claim for damage with the transportation company.
NOTICE: It is the equipment owners responsibility to provide any scaffolding or other apparatus required to perform emergency service or annual/periodic maintenance to this equipment.

DESCRIPTION

The Tubular Gas-Fired Unit Heater is a factory assembled, power vented, low static pressure type propeller fan unit heater designed to be suspended within the space to be heated. THESE HEATERS ARE NOT TO BE CONNECTED TO DUCTWORK. These Tubular Unit Heaters are design certified under ANSI Z83.8 for Industrial/Commercial use and Residential use as a utility heater. The designs are certified by ETL as providing a minimum of 82% thermal efficiency, and approved for use in California. Do not alter these units in any way. If you have any questions after reading this manual, contact the manufacturer.
Figure 1 – Tubular 30 thru 120 Propeller Unit HeatersMESTEK GG IOM 18
Tubular Gas Fired Direct Spark Propeller Unit Heaters -
DESCRIPTIONThe following terms are used throughout this manual, in addition to the ETL requirements to bring attention to the presence of potential hazards, or to important information concerning the product:
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury, or substantial property damage.
Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury, or substantial property damage.
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or property damage.
NOTICE: Used to notify of special instructions on installation, operation, or maintenance which are important to equipment but not related to personal injury.

GENERAL SAFETY INFORMATION

Failure to comply with the general safety information may result in extensive property damage, severe personal injury, or death.
This product must be installed by a licensed plumber or gas fitter when installed within the Commonwealth of Massachusetts.
Installation must be made in accordance with local codes, or in absence of local codes, with the latest edition of ANSI Standard Z223.1 (N.F.P.A. No. 54) National Fuel Gas Code. All of the ANSI and NFPA Standards referred to in these installation instructions are those that were applicable at the time the design of this appliance was certified.The ANSI Standards are available from CSA Information Services 1-800-463-6727. The NFPA Standards are available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
If installed in Canada, the installation must conform with local building codes, or in the absence of local building codes, with CSA-B149.1 “Installation Codes for Natural Gas Burning Appliances and Equipment” or CSA-B149.2 “Installation Codes for Propane Gas  urning Appliances and Equipment.” These unit heaters have been designed and certified to comply with CSA 2.6.
Do not alter the unit heater in any way or damage to the unit and/or severe personal injury or death may occur!
Disconnect all power and gas supplies before installing or servicing the heater.
If the power disconnect is out of sight, lock it in the open position and tag it to prevent unexpected application of power. Failure to do so could result in fatal electric shock, or severe personal injury.
Ensure that all power sources conform to the requirements of the unit heater, or damage to the unit will result!
Follow installation instructions CAREFULLY to avoid creating unsafe conditions. All wiring should be done and checked by a qualified electrician, using copper wire only. All gas connections should be made and leak-tested by a suitably qualified individual, per instructions in this manual. Also follow procedures listed on “Gas Equipment Start-Up Sheet” located in this manual.
Use only the fuel for which the heater is designed (see rating plate). Using LP gas in a heater that requires natural gas, or vice versa, will create risk of gas leaks, carbon monoxide poisoning, and explosion.
Conversion to a fuel other than that listed on the rating plate is permitted only with a factory supplied, ETL approved conversion kit.
Make certain that the power source conforms to the
electrical requirements of the heater.
Do not depend upon a thermostat or other switch as sole means of disconnecting power when installing or servicing heater. Always disconnect power at main circuit breaker as described above. Failure to do so could result in fatal electric shock.
Special attention must be given to any grounding information pertaining to this heater. To prevent the risk of electrocution, the heater must be securely and adequately grounded. This should be accomplished by connecting a ground conductor between the service panel and the heater. To ensure a proper ground, the grounding means must be tested by a qualified electrician.
Do not insert fingers or foreign objects into heater or its air moving device. Do not block or tamper with the heater in any manner while in operation, or just after it has been turned off, as some parts maybe hot enough to cause injury.
This heater is intended for general heating applications ONLY. It must NOT be used in potentially dangerous locations such as flammable, explosive, chemical-laden, or wet atmospheres.
Do not attach ductwork to this product or use it as a makeup air heater. Such usage voids the warranty and will create unsafe operation.
In cases in which property damage may result from malfunction of the heater, a back-up system or temperature sensitive alarm should be used.
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.
The open end of gas piping systems being purged shall not discharge into areas where there are sources of ignition or into confined spaces UNLESS precautions are taken as follows: (1) by ventilation of the space, (2) control of the purging rate, (3) elimination of all hazardous conditions. All precautions must be taken to perform this operation in a safe manner!
The appliance is not to be used by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction. Children being supervised should not play with the appliance.
Unless otherwise specified, the following conversions may be used for calculating SI unit measurements:
1 foot = 0.305 m
1 inch = 25.4 mm
1 gallon = 3.785 L
1 pound = 0.453 kg
1 psig = 6.894 kPa
1 cubic foot = 0.028m3
1000 BTU/cu. ft. = 37.5 MJ/m3
1000 BTU per hour = 0.293 kW
1 inch water column = 0.249 kPa
liter/second = CFM x 0.472
meters/second = FPM ÷ 196.8
Table 1 – Performance and Dimensional Data – Tubular 30 thru 120 Propeller Unit Heater

Unit Size| 30| 45| 60| 75| 90| 105| 120
---|---|---|---|---|---|---|---
PERFORMANCE DATA†
Input – BTU/Hr.
(kW)
Output – BTU/Hr.
(kW)| ****

30,000
(8.8)
24,900
(7.2)

| ****

45,000
(13.2)
37,350
(10.9)

| ****

60,000
(17.6)
49,800
(14.5)

| ****

75,000
(22.0)
61,500
(18.0)

| ****

90,000
(26.4)
73,800
(21.6)

| ****

105,000
(30.8)
86,100
(25.2)

| ****

120,000
(35.2)
98,400
(28.8)

Thermal Efficiency (%)
Free Air Delivery – CFM
(cu. m/s)
Air Temperature Rise – °F
(°C)
Full Load Amps at 120V Minimum Circuit Ampacity| 83
370
(.175)
60
(33)
3.2
3.7| 83
550
(.260)
60
(33)
3.2
3.7| 83
740
(.349)
60
(33)
4.1
4.8| 82
920
(.434)
60
(33)
4.1
4.8| 82
1,100
(.519)
60
(33)
6.4
7.5| 82
1,300
(.614)
60
(33)
6.4
7.5| 82
1,475
(.696)
60
(33)
6.4
7.5
MOTOR DATA: Motor HP
Motor (kW)
Motor Type ODP † †
RPM
Motor Amps @ 115V| 1/20
(0.04)
SP
1650
1.9| 1/20
(0.04)
SP
1650
1.9| 1/12
(0.06)
SP
1050
2.6| 1/12
(0.06)
SP
1050
2.6| 1/10
(0.075)
SP
1050
4.2| 1/10
(0.075)
SP
1050
4.2| 1/10
(0.075)
SP
1050
4.2
DIMENSIONAL DATA – inches (mm)
“A” Jacket Height
“B” Overall Height
“C” Overall Depth| 12-3/8
(314)
13-1/4
(337)
25-7/8| 12-3/8
(314)
13-1/4
(337)
25-7/8| 15-7/8
(403)
16-13/16
(427)
26-3/16| 15-7/8
(403)
16-13/16
(427)
26-3/16| 22-5/8
(574)
23-9/16
(598)
26-3/8| 22-5/8
(574)
23-9/16
(598)
26-3/8| 22-5/8
(574)
23-9/16
(598)
26-3/8
“D1” Center Line Height of Flue*
“D2” Center Line Height of Air Intake
“E” Fan Diameter| (632)
8-1/2
(216)
8-1/2
(216)
10| (632)
8-1/2
(216)
8-1/2
(216)
10| (665)
10-3/8
(263)
8
(203)
14| (665)
10-3/8
(263)
8
(203)
14| (670)
13-5/8
(346)
8-5/8
(219)
16| (670)
13-5/8
(346)
8-5/8
(219)
16| (670)
13-5/8
(346)
8-5/8
(219)
16
“F” Discharge Opening Height
“G” Flue Vent Connection Diameter (Min.)
“H1” Center Line of Flue Connection From Side
“H2” Center Line of Air Intake From Side| (254)
10-13/16
(275)
4
(102)
7-1/4
(184)
2-3/4| (254)
10-13/16
(275)
4
(102)
7-1/4
(184)
2-3/4| (356)
14-7/16
(367)
4
(102)
7-1/4
(184)
2-3/4| (356)
14-7/16
(367)
4
(102)
7-1/4
(184)
2-3/4| (406)
21-3/16
(538)
4
(102)
7-3/4
(197)
3-1/2| (406)
21-3/16
(538)
4
(102)
7-3/4
(197)
3-1/2| (406)
21-3/16
(538)
4
(102)
7-1/4
(184)
3-1/2
Vent Size Requirements – Standard Combustion
Category III Horizontal
Category I & III Vertical
Vent Size Requirements – Separated Combustion
Exhaust Diameter
Intake Air Diameter| (70)
4
(102)
4
(102)
4
(102)
4| (70)
4
(102)
4
(102)
4
(102)
4| (70)
4
(102)
4
(102)
4
(102)
4| (70)
4
(102)
4
(102)”
4
(102)
4| (89)
4
(102)
4
(102)
5
(127)
5| (89)
4
(102)
4
(102)
5
(127)
5| (89)
4
(102)
4
(102)
5
(127)
5
Unit Weight – lbs.
(kgs)| (102)
60
(27)| (102)
65
(29)| (102)
80
(36)| (102)
85
(39)| (127)
95
(43)| (127)
105
(48)| (127)
110
(50)
Shipping Weight – lbs.
(kgs)| 70
(32)| 75
(34)| 90
(41)| 95
(43)| 110
(50)| 115
(52)| 120
(54)

  • For all installations, the flue collar is included with the unit and should be field installed per the instructions included with the unit.

†Ratings shown are for unit installations at elevations between 0 and 2,000 feet (0 to 610m). For unit installations in U.S.A. above 2,000 feet (610m), the unit input must be derated 4% for each 1,000 feet (305m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (NFPA No. 54), (also refer to Table 9).

For installations in Canada, any reference to deration at altitudes in excess of 2,000 feet (610m) are to be ignored. At altitudes of 2,000 feet to 4,500 feet (610 to 1372m), the unit must be derated and be so marked in accordance with the ETL certification. See Table 9 for USA and Canadian field deration information.

†† LEGEND: ODP = OPEN DRIP PROOF SP = SHADED POLE
Figure 2 – Dimensional Drawing – Tubular 30 thru 120 Propeller Unit Heater![MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters

Floor to Bottom of Unit “H” – Feet (m)| 30,000| 45,000| 60,000| 75,000| 90,000| 105,000| 120,000
---|---|---|---|---|---|---|---

Approximate Distance of Heat Throw – Feet (Meters)

8 (2.4)| 33 (10.1)| 33 (10.1)| 33 (10.1)| 40 (12.2)| 40 (12.2)| 60 (18.3)| 65 (19.8)
10 (3.0)| 28 (8.5)| 28 (8.5)| 28 (8.5)| 35 (10.7)| 35 (10.7)| 54 (16.5)| 56 (17.1)
12 (3.7)| NR| NR| NR| NR| NR| 44

(13.4)

| 46

(14.0)

15 (4.6)| NR| NR| NR| NR| NR| NR| NR

Notes:

  1. All throw data figures are approximations. Allowances should be made for optimum performance, altitude, etc.
  2. NR – Units not recommended at these mounting heights.

INSTALLATION

Do not install unit heaters in corrosive or flammable atmospheres! Premature failure of, or severe damage to the unit will result!
Avoid locations where extreme drafts can affect burner operation. Unit heaters must not be installed in locations where air for combustion would contain chlorinated, halogenated or acidic vapors. If located in such an environment, premature failure of the unit will occur!
Maximum altitude for this unit is 14,000 feet (4,267 meters) unless otherwise noted. For altitudes higher than 14,000 feet (4,267 meters), contact your customer service representative.
Since the unit is equipped with an automatic gas ignition system, the unit heater must be installed such that the gas ignition control system is not directly exposed to water spray, rain or dripping water.
NOTICE: Location of unit heaters is related directly to the selection of sizes. Basic rules are as follows:
RESIDENTIAL INSTALLATIONS: This unit heater is design certified under ANSI Z83.8 for residential use as a utility heater. A utility heater is defined as: a low-static unit heater for heating of non-living spaces that are attached to, adjacent to, or part of a structure that contains space for family living quarters.
MOUNTING HEIGHT: If the unit heater is installed in a garage, it must be installed with a minimum clearance above the floor of 18 inches (457mm).
PUBLIC GARAGES: In repair garages, unit heaters must be located at least 8 ft. (2.4m) above the floor.
Refer to the latest edition of NFPA 88B, Repair Garages.
PARKING STRUCTURES: In parking structures, unit heaters must be installed so that the burner flames are located a minimum of 18 in. (457mm) above the floor or protected by a partition not less than 18 in. (457mm) high. However, any unit heater mounted in a parking structure less than 8 ft. (2.4m) above the floor must be equipped with an OSHA approved fan guard. Refer to the latest edition of NFPA 88A, Parking structures.
In Canada, installation must be in accordance to the latest edition of CSA B149 “Installation Codes for Gas Burning Appliances and Equipment.”
AIR DISTRIBUTION: Direct air towards areas of maximum heat loss. When multiple heaters are involved, circulation of air around the perimeter is recommended where heated air flows along exposed walls. Satisfactory results can also be obtained where multiple heaters are located toward the center of the area with heated air directed toward the outside walls. Be careful to avoid all obstacles and obstructions which could impede the warm air distribution patterns.
Unit heaters should not be installed to maintain low temperatures and/or freeze protection of buildings.
A minimum of 50°F (10°C) thermostat setting must be maintained. If unit heaters are operated to maintain lower than 50°F (10°C), hot flue gases are cooled inside the heat exchanger to a point where water vapor (a flue gas by- product) condenses onto the heat exchanger walls. The result is a mildly corrosive acid that prematurely corrodes the aluminized heat exchanger and can actually drip water down from the unit heater onto floor surface.
Additional unit heaters should be installed if a minimum 50°F (10°C) thermostat setting cannot be maintained.
Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the appliance before shutting off the electrical supply.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace any gas control which has been underwater.
AIR FOR COMBUSTION: The unit heater shall be installed in a location in which the facilities for ventilation permit satisfactory combustion of gas, proper venting, and the maintenance of ambient air at safe limits under normal conditions of use. The unit heater shall be located in such a manner as not to interfere with proper circulation of air within the confined space. When buildings are so tight that normal infiltration does not meet air requirements, outside air shall be introduced per Sections 1.3.4.2 and 1.3.4.3 of ANSI Z223.1 (NFPA 54) for combustion requirements. A permanent opening or openings having a total free area of not less than one square inch per 5,000 BTU/Hr (1.5 kW) of total input rating of all appliances within the space shall be provided.
NOTICE: Unit Heater sizing should be based on heat loss calculations where the unit heater output equals or exceeds heat loss.
NOTICE: Unit should be installed in an area where the entering air does not exceed 104°F. Temperatures above 104°F will cause the propeller motor to trip on its thermal overload protection, requiring a cool down period before the motor can reset.
CLEARANCES: Each Gas Unit Heater shall be located with respect to building construction and other equipment so as to permit access to the Unit Heater. Clearance between vertical walls and the vertical sides of the Unit Heater shall be no less than 1 inch (25.4mm).
However, to ensure access to the control box and fan, a minimum of 18 inches (457mm) is required for the fan, and control box side. A minimum clearance of 1 inch (25.4mm) must be maintained between the top of the Unit Heater and the ceiling. The bottom of the Unit Heater must be no less than 1 inch (25.4mm) from any combustible.
The distance between the flue collector and any combustible must be no less than 1 inch (25.4mm). Also see AIR FOR COMBUSTION and VENTING sections.
NOTICE: Increasing the clearance distances may be necessary if there is a possibility of distortion or discoloration of adjacent materials. MOUNTING: The Unit Heater may be mounted with the vent outlet, gas and electrical connections to the right or left of the air moving fan. The Unit Heater is shipped with the connections to the right of the fan when looking in the direction of the air flow. If connections to the right are required, remove hanger brackets from face of unit and attach as pictured in Figure 3. If connections to the left are required, invert the heater (180°), mount the hanging brackets as above, and remove, invert, and replace the air discharge louvers.
The Unit Heater may be mounted by fastening the hanging brackets directly to ceiling joists or by suspending from four rods. See Figures 3, 4 and 5.
Make certain that the lifting methods used to lift the heater and the method of suspen-sion used in the field installation of the heater are capable of uniformly supporting the weight of the heater at all times. Failure to heed this warning may result in property damage or personal injury!
Make sure that the structure to which the unit heater is to be mounted is capable of safely supporting its weight. Under no circumstances must the gas lines, the venting system or the electrical conduit be used to support the heater; or should any other objects (i.e. ladder, person) lean against the heater gas lines, venting system or the electrical conduit for support. Failure to heed these warnings may result in property damage, personal injury, or death.
Unit Heaters must be hung level from side to side and from front to back, see Figures 3, 4 and 5. Failure to do so will result in poor performance and/or premature failure of the unit.
Ensure that all hardware used in the suspension of each unit heater is more than adequate for the job. Failure to do so may result in extensive property damage, severe personal injury, or death!
Refer to Figures 3, 4 and 5 for suspension of units.
MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
INSTALLATION GAS PIPING
To avoid damage or possible personal injury, do not connect gas piping to this unit until a supply line pressure/leak test has been completed. Connecting the unit before completing the pressure/leak test may damage the unit gas valve and result in a fire hazard.
Do not rely on a shut-off valve to isolate the unit while conducting gas pressure/leak tests. These valves may not be completely shut off, exposing the gas valve to excessive pressure and damage.
PIPE SIZING
To provide adequate gas pressure to the gas unit heater, size the gas piping as follows:

  1. Find the cu. ft./hr. by using the following formula:
  2. Refer to Table 3. Match “Length of Pipe in Feet” with appropriate “Gas Input – Cu. Feet/Hr.” figure. This figure can then be matched to the pipe size at the top of the column.
    Example:
    It is determined that a 67 foot (20.4m) run of gas pipe is required to connect a 75 MBTU gas unit heater to a 1,000 BTU/cu feet (0.29kW) natural gas supply.MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit
Heaters - jnjh Using Table 3, a 3/4 inch pipe is needed.

NOTE: See General Safety Information section for English/Metric unit conversion factors.
NOTICE: Propane tank must be properly sized for outdoor temperature and BTU requirement. (See NFPA 58)
NOTICE: If more than one unit heater is to be served by the same piping arrangement, the total cu. ft./hr. input and length of pipe must be considered.
NOTICE: If the gas unit heater is to be fired with LP gas, consult your local LP gas dealer for pipe size information.
NOTICE: HEATER INSTALLATION FOR USE WITH PROPANE (BOTTLED) GAS MUST BE MADE BY A QUALIFIED L.P. GAS DEALER OR INSTALLER. HE WILL ENSURE THAT PROPER JOINT COMPOUNDS ARE USED FOR MAKING PIPE CONNECTIONS; THAT AIR IS PURGED FROM LINES; THAT A THOROUGH TEST IS MADE FOR LEAKS BEFORE OPERATING THE HEATER; AND THAT IT IS PROPERLY CONNECTED TO THE PROPANE GAS SUPPLY SYSTEM.
Before any connection is made to the existing line supplying other gas appliances, contact the local gas company to make sure that the existing line is of adequate size to handle the combined load.
Table 3 – Gas Pipe Size
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less, and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)
(Based on a 0.60 Specific Gravity Gas)2023-12-12_2350141. Determine the required Cu. Feet/Hr. by dividing the input by 1000. For SI/Metric measurements: Convert BTU/Hr. to kilowatts. Multiply the units inputs (kW) by 0.0965 to determine Cu. Meters./Hr. 2. FOR NATURAL GAS: Select pipe size directly from the table. 3. FOR PROPANE GAS: Multiply the Cu. Feet/Hr. value by 0.633; then, use the table. 4. Refer to the metric conversion factors listed in the General Safety section for SI Unit measurement conversions.
PIPE INSTALLATION

  1. Install the gas piping in accordance with applicable local codes.

  2. Check gas supply pressure. Each unit heater must be connected to a gas supply capable of supplying its full rated capacity as specified in Table 4. A field LP tank regulator must be used to limit the supply pressure to a maximum of 14 inches W.C. (3.5 kPa).
    All piping should be sized in accordance with the latest edition of ANSI Standard Z223.1 (NFPA 54) National Fuel Gas Code; in Canada, according to CSA-B149. See Tables 1 & 3 for correct gas piping size, and also refer to Tables 4, 8 and 9. If gas pressure is excessive on natural gas applications, install a pressure regulating valve in the line upstream from the main shutoff valve.

  3. Adequately support the piping to prevent strain on the gas manifold and controls.

  4. To prevent the mixing of moisture with gas, run the take-off piping from the top, or side, of the main.

  5. Standard Unit Heaters are supplied with a combination valve which includes:
    a. Manual “A” valve
    b. Manual “B” valve
    c. Solenoid valve
    d. Pressure regulator
    Pipe directly into the combination valve (see Figure 6).

  6. Gas valve has a pressure test post requiring a 3/32 inch hex head wrench to read gas supply and manifold pressures. Open 1/4 turn counterclockwise to read, turn clockwise to close and reseat. A 5/16 inch ID hose fits the pressure post.

  7. Provide a drip leg in the gas piping near the gas unit heater. A ground joint union and a manual gas shutoff valve should be installed ahead of the unit heater controls to permit servicing. The manual shutoff valve must be located external to the jacket. (See Figure 6)

  8. Make certain that all connections have been adequately doped and tightened.

Table 4 – Gas Piping Requirements*

Gas Type Natural Gas Propane (LP) Gas

Manifold Pressure
Single Stage Application| (inch WC)| 3.5| 10.0
(kPa)| (0.87)| (2.49)
Two Stage Application – High Fire| (inch WC)| 3.5| 10.0
(kPa)| (0.87)| (2.49)
Two Stage Application – Low Fire| (inch WC)| 1.1| 3.8
(kPa)| (0.27)| (0.95)
Supply Inlet Pressure
Maximum| (inch WC)| 14.0| 14.0
(kPa)| (3.49)| (3.49)
Minimum| (inch WC)| 5.0| 11.0
(kPa)| (1.25)| (2.74)

  • Applicable for units installed at or below 2,000 feet (610 m) altitude.
    See High Altitude Deration information for altitudes greater than 2,000 feet (610 m).
    Do not over tighten the inlet gas piping into the valve. This may cause stresses that will crack the valve!
    NOTICE: Use pipe joint sealant resistant to the action of liquefied petroleum gases regardless of gas conducted.
    Check all pipe joints for leakage using a soap solution or other approved method.
    Never use an open flame or severe personal injury or death may occur!
    Figure 6 – Pipe Installation, Standard ControlsMESTEK GG IOM 18 Tubular Gas
Fired Direct Spark Propeller Unit Heaters - INSTALLATION
1 Never use an open flame to detect gas leaks. Explosive conditions may exist which may result in personal injury or death!
    The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system in excess of 1/2 psig (3.5 kPa).
    The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

ELECTRICAL CONNECTIONS

HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING. Failure to disconnect power before servicing can cause severe personal injury or death.
Standard units are shipped for use on 115 volt, 60 hertz,single phase electric power. The motor name-plate andelectrical rating of the transformer should be checkedbefore energizing the unit heater electrical system. Allexternal wiring must conform to the latest edition ofANSI/NFPA No. 70, National Electrical Code, andapplicable local codes; in Canada, to the CanadianElectrical Code, Part 1, CSA Standard C22.1.
The short-circuit current rating (SCCR) for this unit is 5kA.
Do not use any tools (i.e. screwdriver,pliers, etc.) across terminals to check for power. Usea voltmeter.
It is recommended that the electrical power supply toeach unit heater be provided by a separate, fused, andpermanently live electrical circuit. A disconnect switch ofsuitable electrical rating should be located as close to thegas valve and controls as possible. Each unit heater mustbe electrically grounded in accordance with the latest editionof the National Electrical Code, ANSI/NFPA No. 70, or CSAStandard C22.1. Refer to Figures 7, 8, 9, 10A, 10B, 10C.
THERMOSTAT WIRING AND LOCATION:
NOTICE: The thermostat must be mounted on a vertical, vibration-free surface, free from air currents, and in accordance with the furnished instructions.
Mount the thermostat approximately 5 feet (1.5m) above the floor, in an area where it will be exposed to a free circulation of average temperature air. Always refer to the thermostat instructions, as well as our unit wiring diagram, and wire accordingly. Avoid mounting the thermostat in the following locations:

  1. Cold Areas- Outside walls or areas where drafts may affect the operation of the control.
  2. Hot Areas- Areas where the sun’s rays, radiation, or warm air currents may affect the operation of the control.
  3. Dead Areas- Areas where the air cannot circulate freely, such as behind doors or in corners.

NOTICE: The start-up fan delay should not exceed 30 seconds from a cold start.
IMPORTANT: For all wiring connections, refer to the wiring diagram shipped with your unit (either affixed to the side jacket or enclosed in the installation instructions envelope). Should any original wire supplied with the heater have to be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C.
Figure 7 – Low-voltage Thermostat Wiring, Single StageMESTEK GG IOM 18
Tubular Gas Fired Direct Spark Propeller Unit Heaters -
ThermostatMESTEK
GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
ELECTRICALFigure 10B – Tubular Propeller Units 30-120 with Natural and Propane (LP) Gas with Single Stage Gas Control and UT Control BoardMESTEK GG IOM 18 Tubular Gas
Fired Direct Spark Propeller Unit Heaters - ELECTRICAL 1 NOTICE: See Figures 7, 8, 9, 10B, 10C for connecting the thermostat to the unit heater. If using a standard low voltage thermostat with a sub-base switch for fan control, connect the G terminal of the thermostat to the G terminal of the unit heater.
Figure 10C – Tubular Propeller Units 60-120 with Natural and Propane (LP) Gas with Optional Two Stage Gas Control and UT Control BoardMESTEK GG IOM 18
Tubular Gas Fired Direct Spark Propeller Unit Heaters - ELECTRICAL
3 NOTICE: See Figures 7, 8, 9, 10B, 10C, for connecting the thermostat to the unit heater. If using a standard low voltage thermostat with a sub-base switch for fan control, connect the G terminal of the thermostat to the G terminal of the unit heater.

VENTING – GENERAL GUIDELINES

NOTICE: This unit heater can be installed in either standard combustion or separated combustion (twopipe) configurations. With the addition of a Factory- available Combustion Air Inlet Kit, the unit can also be installed in a concentrically vented separated combustion configuration. Be sure to follow venting instructions that match the installation configuration needed.
All unit heaters must be vented! All Venting installations shall be in accordance with the latest edition of Part 7, Venting of Equipment of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54), or applicable provisions of local building codes. All venting of residential tubular unit heaters must comply with ANSI Z83.8 for Industrial/Commercial uses as a utility heater. Refer to notes* below for Canadian installations.
CARBON MONOXIDE! Your venting system must not be blocked by any snow, snow drifts, or any foreign matter. Inspect your venting system to ensure adequate ventilation exists at all times! Failure to heed these warnings could result in Carbon Monoxide Poisoning (symptoms include grogginess, lethargy, inappropriate tiredness, or flue-like symptoms).
When an existing heater is removed or replaced in venting system, the venting system may not be properly sized to vent the attached appliances. An improperly sized vent system can cause formulation of condensate or leakage or spillage of flue gases.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:

  1. Seal any unused openings in the venting system;
  2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.
  3. In so far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace damper.
  4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so that the appliance will operate continuously.
  5. After it has been determined that each appliance connected to the venting system properly vents when tested as outline above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-burning appliance to their previous condition of use.
  6. If improper venting is observed during any of the above tests, the venting system must be corrected immediately so that the system conforms with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54).

When resizing any portion of the venting system, the venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54).
The unit heater shall be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
Venting into an unlined masonry chimney is prohibited.
ADDITIONAL REQUIREMENTS FOR CANADIAN INSTALLATIONS
*The following instructions apply to Canadian installations in addition to installation and operating instructions.

  1. Installation must conform with local building codes, or in the absence of local codes, with current CSA-B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment, or CSA-B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment.
  2. Any reference to U.S. standards or codes in these instructions are to be ignored and the applicable Canadian standards or codes applied.

The following guidelines apply to all categories to follow.
Table 5

Vent Systems Termination Clearance Requirements

Structure/Object| Minimum Clearance for Termination Locations
USA| CANADA
Door, window, or gravity vent inlet; combustion air inlet for other appliances| 9 inches for 10,000 to 50,000 BTU/Hr input; 12 inches for input exceeding 50,000 BTU/Hr.| 9 inches (230mm) for 10,000 to 50,000 BTU/Hr input; 12 inches (305mm) for input exceeding 50,000 BTU/Hr.
Forced air inlet within 10 ft.| 3 feet above| 6 feet (1.8m)
Adjoining Building or parapet1| 10 feet| 10 feet (3.04m)
Adjacent public walkways| 7 feet above grade| 7 feet (2.1m) above grade
Electric, gas meters & regulators| 4 feet horizontal| 3 feet (0.9m) horizontally from meter/regulator asembly. 6 feet (1.8m), any direction, from a gas service regulator vent outlet
Above grade level2| 1 feet| 1 feet (0.3m)

*Notes:

  1. For USA installations: Per NFPA 54, sections 12.6.2.1 and 12.7.2.1a, buildings are required to be a minimum of 10 feet (3.05m) from the flue termination. When using B-vent in a Category I applications, this clearance can be reduced to 8 feet (2.44m).
    For Canadian installations: Per CSA B149.1 sections 8.14.2, 8.14.3, and 8.14.5, buildings are required to be a minimum of 10 feet (3.05m) from the flue termination in a Category I application, and a minimum of 6 feet (1.8m) in a Category III application.

  2. Minimum above maximum snow depth, or per local code, whichever is greater.

Do not damper or add heat recovery devices to the flue piping. Failure to open such a damper prior to operating the gas unit heater will result in the spillage of flue gas into the occupied space.
Avoid installing units in areas under negative pressure.
When required, a flue vent fan should be installed in accordance with the instructions included with the fan.
Vent connectors serving Category I and Category II heaters shall not be connected into any portion of mechanical draft systems operating under positive vent pressure.
Maintain clearance between the vent pipe and combustible materials according to vent pipe manufacturer’s instructions.
ANSI now organizes vented appliances into four categories.
Venting Categories

| Non Condensing| Condensing
---|---|---
Negative Vent Pressure|
I| II
Positive Vent Pressure|
III| **** IV

Category I
Includes non-condensing appliances with negative vent pressure, like the traditional atmospheric unit heater.
Category II
Groups condensing appliances with negative vent pressure.
Category III
Appliances are non-condensing and operate with a positive vent pressure.
Category IV
Covers condensing appliances with positive vent pressure.
NOTICE: Category II and IV do not apply to equipment specified within this manual.
STANDARD COMBUSTION
VERTICALLY VENTED, CATEGORY I
Observe the following precautions when venting the unit:

  1. Use flue pipe of the same size as the flue connection(s) on the gas unit heater 4 inches (102mm). All heaters must be vented with a UL 1738 listed, double or single wall vent, Type B vent, a factory built chimney, or a lined brick and mortar chimney that has been constructed in accordance with the National Building Code. All tables and dimensions assume double wall for the flue and single wall pipe or double wall for the connector.

  2. Each unit must have an individual vent pipe and vent terminal. Unit MUST NOT be connected to other vent systems or to a chimney.

  3. Category I units are limited to a maximum of 40 feet (12.19m) equivalent length of vent pipe. Equivalent length is the total length of straight sections PLUS 5 feet (1.5m) for each 90 degree elbow and 2.5 feet (0.75m) for each 45 degree elbow.

  4. A minimum vertical rise of 5 feet (1.5m) is required for Category I venting. The top of the vent pipe qshould extend at least 2 feet (0.61m) above the highest point on the roof within 10 feet (3.05m) of the termination. Consideration should be made for anticipated snow depth. Install an Amerivent Americap or Selkirk vent cap over the vent opening.

  5. Slope horizontal runs upward from the gas unit heater at least 1/4-inch per foot (21mm/m) minimum.
    Horizontal Vent Connector length should not exceed 75% of the vertical height of the vent pipe. Maximum vent connector length is 10 feet (3m). For exceptions see Ch. 10 of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54). Horizontal portions of the venting system shall be supported at minimum intervals of 4 feet (1.2m) (in Canada, support at 3 foot (1m) minimum intervals). Maintain clearance between the vent pipe and combustible materials per vent pipe manufacturer’s instructions.

  6. Use as few elbows as possible. A minimum horizontal run of 2 feet (0.61m) is required between the unit’s flue vent connection and the first elbow used.

  7. Seal all vent pipe joints and seams to prevent leakage. Use General Electric RTV-108, DowCorning RTV-732, or equivalent silicone sealant with a temperature rating of 500°F, or 3M #425 aluminum foil tape (or equivalent). See Figure 12A.

  8. Avoid running vent pipe through unheated indoor spaces. When this cannot be avoided, insulate the pipe to prevent condensation of moisture on the walls of the pipe. Insulate vent pipe runs longer than 10 ft (3m). Insulation should be a minimum of 1/2 inch (12.7 mm) thick foil faced.

MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
ELECTRICAL 4 STANDARD COMBUSTION
HORIZONTALLY VENTED, CATEGORY III
Observe the following precautions when venting the unit:

  1. Use flue pipe of the same size as the flue connection(s) on the gas unit heater, 4 inches (102mm). All heaters must be vented with a single or double wall pipe listed for category III positive pressure vent systems. (UL 1738 listed). For Canada only: Where allowed by code, appropriately sealed 26-gauge or heavier galvanized steel or equivalent single-wall pipe may be used.

  2. Each unit must have an individual vent pipe and vent terminal. Unit MUST NOT be connected to other vent systems or to a chimney.

  3. Category III units are limited to a maximum of 40 feet (12.19m) equivalent length of vent pipe. Equivalent length is the total length of straight sections PLUS 5 feet (1.5m) for each 90 degree elbow and 2.5 feet (.75m) for each 45 degree elbow.

  4. An Amerivent Americap or Selkirk vent cap must be supplied by the customer for each power vented unit.
    The vent pipe diameter must be 4 inches (102mm).

  5. The vent terminal must be at least 12 inches (305mm) from the exterior of the wall that it passes through to prevent degradation of the building materials by flue gasses.

  6. Through the wall venting for these appliances shall not terminate over public walkways, or over an area where the condensate or vapor could create a nuisance, hazard, or could be detrimental to the operation of regulators, relief valves, or other equipment. See Figures 13A, 14, 16 and Table 5.

  7. Maintain clearance between the vent pipe and combustible materials according to vent pipe manufacturer’s instructions.

  8. The vent system must be installed to prevent collection of condensate. Pitch horizontal pipes downward 1/4 inch per foot (21mm per meter) toward the outlet for condensate drainage. Install a tee with a condensate drain at the low point of the pipe (see Figure 13A). As an alternate, a 3/8 inch diameter hole may be drilled at the low point of the pipe for condensate drainage.

  9. Horizontal portions of the venting system shall be supported at minimum intervals of 4 feet (1.2m) to prevent sagging (in Canada, support at 3 foot (1m) minimum intervals).

  10. Avoid running vent pipe through unheated spaces.
    When this cannot be avoided, insulate the pipe to prevent condensation of moisture on the walls of the pipe. Insulate vent pipe runs longer than 10 feet (3m). Insulation should be a minimum of 1/2 inch (12.7mm) thick foil faced.

VERTICALLY VENTED, CATEGORY III
Observe the following precautions when venting the unit:

  1. Use flue pipe of the same size as the flue connection(s) on the gas unit heater, 4 inches (102mm). All heaters must be vented with a UL 1738 listed single or double wall pipe listed for positive pressure vent systems.
    For Canada only: Where allowed by code, appropriately sealed 26-gauge or heavier galvanized steel or equivalent single-wall pipe may be used.

  2. Each unit must have an individual vent pipe and vent terminal. Unit MUST NOT be connected to other vent systems or to a chimney.

  3. Category III units are limited to a maximum of 40 feet (12.19m) equivalent length of vent pipe.
    Equivalent length is the total length of straight sections PLUS 5 feet (1.5m) for each 90 degree elbow and 2.5 feet (.75m) for each 45 degree elbow.

  4. The top of the vent pipe should extend at least 2 feet (0.61m) above the highest point on the roof within 10 feet. Consideration should be made for anticipated snow depth. Install an Amerivent Americap or Selkirk vent cap over the vent opening. Slope horizontal runs upward from the gas unit heater at least 1/4-inch per foot (21mm/m) minimum. Horizontal portions of the venting system shall be supported at minimum intervals of 4 feet (1.2m) (in Canada, support at 3 foot (1m) minimum intervals). (See Figures 13B, 15 and 17)

  5. Avoid running vent pipe through unheated spaces.
    When this cannot be avoided, insulate the pipe to prevent condensation of moisture on the walls of the pipe.

MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
ELECTRICAL 5 VENTING (continued)MESTEK GG IOM 18 Tubular Gas Fired Direct Spark
Propeller Unit Heaters - VENTINGMESTEK GG IOM 18 Tubular Gas Fired Direct
Spark Propeller Unit Heaters - VENTING 1 *See Table 5 Vent Systems Termination Clearance Requirements for additional detail regarding adjacent buildings.
SEPARATED COMBUSTION – GENERAL GUIDELINES
CATEGORY III
NOTICE:
COMBUSTION AIR and EXHAUST VENTING sections below apply to all separated combustion installations. See SEPARATED COMBUSTION – TWO-PIPE or SEPARATED COMBUSTION – CONCENTRIC sections for installation instructions specific to those configurations.
COMBUSTION AIR
Never operate unit heaters without combustion air and flue gas piping in place or severe personal injury or death may occur!
CARBON MONOXIDE!
Your venting system must not be blocked by any snow, snow drifts, or any foreign matter.
Inspect your venting system to ensure adequate ventilation exists at all times! Failure to heed these warnings could result in Carbon Monoxide Poisoning (symptoms include grogginess, lethargy, inappropriate tiredness, or flu-like symptoms).

  1. The combustion air system installation must be in accordance with the current edition of the National Fuel Gas Code-NFPA 54 or ANSI Z223.1 National Fuel Gas Code. In Canada, installation must be in accordance with CSA-B149.1 “Installation Code for Natural Gas Burning Appliances and Equipment” and CSA-B149.2 “Installation Code for Propane Burning Appliances and Equipment”.

  2. If using a concentric venting configuration, a Combustion Air Inlet Kit (which includes a combustion air inlet box, air inlet screen, deflector disk and vent terminal) available from the manufacturer MUST be installed at the termination point of the combustion air/vent system. See Figures 21, 22, 23 and 24 and Table 7.

  3. Each unit heater MUST have its own combustion air system. It MUST NOT be connected to other air intake systems.

  4. Combustion air intake duct may be PVC, CPVC, Type B vent, single wall, double wall or other material approved by local code authority. Never use duct size other than diameter stated in Table 1.

  5. Long runs of single or double wall combustion air piping passing through an unheated space may require insulating if condensation becomes noticeable.

  6. The combustion air system must be installed to prevent collection of condensate. Pitch horizontal pipes downward 1/4 inch per foot toward the inlet cap to facilitate drainage. Vertical combustion air pipes should be piped as depicted in Figure 21.

  7. The equivalent length of the combustion air system must not be less than 5 feet (1.5m) and must not exceed 30 feet (9m), excluding flue pipe. Equivalent length equals the total length of straight pipe plus 5 feet (1.5m) for each 90° elbow and 2.5 feet (0.76m) for each 45° elbow.
    NOTICE: For optimum performance keep the combustion air system as straight as possible.

  8. Each slip joint must be secured with at least three corrosion resistant screws. Two full turns of 3M #425 Aluminum Foil Tape or its equivalent must then be used to seal each joint. General Electric RTV-108, Dow-Corning RTV-732 or an equivalent silicone sealant with a temperature rating of 500°F may be used instead of the tape.

  9. For horizontal combustion air systems longer than 5 feet (1.5m), the system must be supported from overhead building structures at 4 foot (1.2m) intervals in the U.S. and at 3 foot (0.91m) intervals in Canada.

EXHAUST VENTING
Never operate unit heaters without combustion air and flue gas piping in place or severe personal injury or death may occur!

  1. Vent system installation must be in accordance with the current National Fuel Gas Code-NFPA 54 or ANSI Z223.1 National Fuel Gas Code. In Canada installation must be in accordance with CSA-B149.1 “Installation Code for Natural Gas Burning Appliances and Equipment” and CSA-B149.2. “Installation Code for Propane Burning Appliances and Equipment”.

  2. If using a concentric venting configuration, a Combustion Air Inlet Kit (which includes a combustion air inlet box, air inlet screen, deflector disk and vent terminal) available from the manufacturer MUST be installed at the termination point of the combustion air/vent system. See Figures 221, 22, 23 and 24 and Table 7.

  3. Each unit heater MUST have it’s own vent system. It MUST NOT be connected to other vent systems or to a chimney.

  4. Use UL 1738 listed single or double wall pipe for thevent system. For installations in Canada, use corrosionresistant and gas-tight, listed vent pipe conforming withlocal building codes, or in the absence of local buildingcodes, with current CSA-B149.1, Installation Codesfor Natural Gas Burning Appliances and Equipmentor CSA-B149.2, Installation Codes for Propane GasBurning Appliances and Equipment. For residentialinstallations in the United States, vent pipe approvedfor Category III appliances must be used between theappliance and the combustion air inlet box.
    Never use pipe other than diameter stated in Table 1. Never use PVC, ABS or any other non-metallic pipe for venting! To do so may result in serious damage to the unit and or severe personal injury or death!

  5. Any run of single or double wall vent pipe passingthrough an unheated space must be insulated withan insulation suitable to 550° F.

  6. The vent system must be installed to preventcollection of condensate. Pitch horizontal pipesdownward 1/4 inch per foot (21mm per meter)toward the vent cap to facilitate drainage. Verticalvent pipes should be piped as depicted in Figure 21.

  7. The equivalent length of the flue vent system must not be less than 5 feet (1.5m) and must not exceed 30 feet (9m), excluding combustion air pipe. The equivalent length equals the total length of straight pipe plus 5 feet (1.5m) for each 90 degree elbow and 2.5 feet (0.76m) for each 45 degree elbow.

  8. For horizontal vent systems longer than 5 feet (1.5m), the system must be supported from overhead building structures at 4 foot (1.2m) intervals in the U.S. and at 3 foot (0.91m) intervals in Canada.

  9. The exhaust vent system must remain at a minimum distance of 1 inch (25mm) from all combustible materials. Any part of the vent system that passes through a combustible material must be properly insulated.

NOTICE: Increasing the clearance distances may be necessary if there is a possibility of distortion or discoloration of adjacent materials.
Table 6 – Access Panel Seal Gasket Lengths

Unit Size| Top/Bottom Gasket Length (in.)| Qty| Right/Left Gasket Length (in.)| Qty
---|---|---|---|---
030| 18-3/8| 2| 12-3/8| 2
045| 18-3/8| 2| 12-3/8| 2
060| 18-3/8| 2| 15-7/8| 2
075| 18-3/8| 2| 15-7/8| 2
090| 18-3/8| 2| 22-5/8| 2
105| 18-3/8| 2| 22-5/8| 2
120| 18-3/8| 2| 22-5/8| 2

SEPARATED COMBUSTION – TWO-PIPE
HORIZONTALLY VENTED UNIT HEATERS, CATEGORY III
NOTICE: Venting instructions below describe twopipe separated combustion venting. If ventingconcentrically, a Factory-available Combustion AirInlet Kit is required and instructions in theSEPARATED COMBUSTION – CONCENTRICsections should be followed.
The combustion air system installation must be inaccordance with the current edition of the National FuelGas Code-NFPA 54 or ANSI Z223.1 National Fuel GasCode. Horizontal venting arrangements are designed tobe used with single wall vent pipe. Horizontal ventingarrangements must terminate external to the buildingusing UL 1738 Listed and approved single wall or doublewall vent. For installations in Canada, use corrosion resistant and gas-tight, listed vent pipe conforming with local building codes, or in the absence of local buildingcodes, with current CSA-B149.1, Installation Codes forNatural Gas Burning Appliances and Equipment orCSA-B149.2, Installation Codes for Propane GasBurning Appliances and Equipment.
Do not use Type B (double wall) vent internally within the building on horizontally vented power vented units! This can result in death, serious injury or substantial property damage.
Single wall and double wall venting components whichare UL 1738 Listed and approved for Category IIIpositive pressure venting systems MUST be used.
For Canada only: Where allowed by code, appropriatelysealed 26-gauge or heavier galvanized steel orequivalent single-wall pipe may be used.
An Amerivent Americap or Selkirk vent cap must besupplied by the customer for each power vented unit. Thevent pipe diameter MUST be as specified in Table 1.
Install the access panel sealing gaskets by cutting the provided gasket to lengths listed in Table 6. Remove the paper backing and adhere to the access panel, making certain that the entire perimeter is covered. See Figure 18.
The vent terminal must be at least 12 in. (305mm) from the exterior of the wall that it passes through to prevent degradation of the building material by flue gases. Through the wall vent for these appliances shall NOT terminate over public walkways, or over an area where the condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment. See Table 5 for additional vent termination clearance requirements.
The flue pipe equivalent length must not exceed 30 ft. (9m), excluding combustion air pipe. Equivalent length is the total length of straight sections PLUS 5 ft. (1.5m) for each 90° elbow and 2.5 ft. (0.76m) for each 45° elbow.
Maintain clearance between the vent pipe and combustible materials according to vent pipe manufacturer’s instructions.
Seal all vent pipe joints and seams to prevent leakage.
Use General Electric RTV-108, Dow-Corning RTV-732 silicone sealant or equivalent sealant with a temperature rating of 500°F; or 3M #425 aluminum foil tape (or equivalent). The vent air system must be installed to prevent collection of condensate. Pitch horizontal pipes downward 1/4 inch per foot (21mm per meter) toward the outlet for condensate drainage.
Horizontal portions of the venting systems shall be supported at maximum intervals of 4 ft. (1.2m) to prevent sagging (in Canada, support at 3 ft. (1m) maximum intervals).
Insulate single wall vent pipe exposed to cold air or running through unheated areas.
Each unit must have an individual vent pipe and vent terminal! Each unit MUST NOT be connected to other vent systems or to a chimney.MESTEK GG IOM 18
Tubular Gas Fired Direct Spark Propeller Unit Heaters - VENTING
8 SEPARATED COMBUSTION – TWO-PIPE
VERTICALLY VENTED UNIT HEATERS, CATEGORY III
NOTICE: Venting instructions below describe twopipe separated combustion venting. If ventingconcentrically, a Factory-available Combustion AirInlet Kit is required and instructions in theSEPARATED COMBUSTION – CONCENTRICsections should be followed.
The combustion air system installation must be inaccordance with the current edition of the National FuelGas Code-NFPA 54 or ANSI Z223.1 National Fuel GasCode. Vertical venting arrangements are designed to beused with single wall vent pipe. Vertical ventingarrangements must terminate external to the buildingusing UL 1738 listed and approved single wall or doublewall vent. For installations in Canada, use corrosionresistant and gas-tight, listed vent pipe conforming with local building codes, or in the absence of local building codes, with current CSA-B149.1, Installation Codes forNatural Gas Burning Appliances and Equipment orCSA-B149.2, Installation Codes for Propane GasBurning Appliances and Equipment.
Do not use Type B (double wall) vent internally within the building on horizontally vented power vented units! This can result in death, serious injury or substantial property damage.
Single wall and double wall venting components whichare UL 1738 Listed and approved for Category IIIpositive pressure venting systems MUST be used.
For Canada only: Where allowed by code, appropriatelysealed 26-gauge or heavier galvanized steel orequivalent single-wall pipe may be used.
An Amerivent Americap or Selkirk vent cap must be supplied by the customer for each power vented unit. The vent pipe diameter MUST be as specified in Table

  1. Install the access panel sealing gaskets by cutting the provided gasket to lengths listed in Table 6. Remove the paper backing and adhere to the access panel, making certain that the entire perimeter is covered. See Figure 18.
    The top of the vent pipe should extend at least 2 feet (0.61m) above the highest point on the roof within 10 feet (3.05m) of the termination. Consideration should be made for anticipated snow depth. Install the vent cap over the vent opening. See Figure 20.
    Horizontal portions of the venting system shall be supported at minimum intervals of 4 feet (1.2m) to prevent sagging (in Canada, support at 3 foot (1m) minimum intervals).
    Vent system terminations for these appliances shall NOT terminate in an area where the condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment. See Table 5 for additional  vent termination clearance requirements.
    SEPARATED COMBUSTION – TWO-PIPE (continued)
    VERTICALLY VENTED UNIT HEATERS, CATEGORY III
    The flue pipe equivalent length must not exceed 30 ft. (9m). Equivalent length is the total length of straight sections PLUS 5 ft. (1.5m) for each 90° elbow and 2.5 feet (0.76m) for each 45° elbow.
    Maintain clearance between the vent pipe and combustible materials according to vent pipe manufacturer’s instructions.
    Seal all vent pipe joints and seams to prevent leakage.
    Use General Electric RTV-108, Dow-Corning RTV-732 silicone sealant or equivalent sealant with a temperature rating of 500°F; or 3M #425 aluminum foil tape (or equivalent). The vent air system must be installed to prevent collection of condensate. Slope horizontal runs upward from the gas unit at least 1/4″ per foot (21mm per meter) minimum.
    Insulate single wall vent pipe exposed to cold air or running through unheated indoor areas.
    Each unit must have an individual vent pipe and vent terminal! Each unit MUST NOT be connected to other vent systems or to a chimney.MESTEK GG IOM 18
Tubular Gas Fired Direct Spark Propeller Unit Heaters -
VERTICALLY SEPARATED COMBUSTION – CONCENTRIC
    NOTICE:
    Every unit to be installed in a concentrically vented separated combustion configuration MUST use the Factory-available Combustion Air Inlet Kit. See installation instructions included with kit for complete list of instructions. If you do not have this kit, contact the manufacturer ASAP to obtain one prior to installation.
    EXHAUST AIR COLLAR
    Secure 5-4 inch reducer to flue collar on rear panel of unit sizes 090, 105 and 120. Seal per exhaust venting instructions.
    ACCESS PANEL SEAL
    Cut provided gasket to lengths listed in Table 6. Remove paper backing and adhere to access panel, making certain that the entire perimeter is covered. See Figure 18.
    VERTICAL TERMINATION
    Select location on roof for vent terminal, ensuring adequate space inside the building/structure for combustion air inlet box. Terminal must be at least 10 feet (3.04m) from any wall or adjoining building. See Figure 21 and Table 5.
    Cut a hole through the roof for combustion air pipe.
    Combustion air inlet box is to be suspended from the underside of the roof using suitable brackets (field supplied). Before mounting box, cut a length of 7 inch (178mm) (sizes 030-075) or 9 inch (229mm) (sizes 090120) pipe so that dimension A, Figure 21, is equal to the dimension from the top of the box to the roof surface plus 2 feet (0.61m), plus expected snow depth,whichever is greater. Fasten pipe to combustion air inlet connection of combustion air inlet box and seal joint. Insert pipe through roof and fasten vent box in place. Flash and/or caulk pipe to roof. Install inlet air screen assembly and fasten to pipe with screws.
    Insert a 5 foot length of UL 1738 listed vent pipe through the combustion air inlet box opening (detail A, Figure 24) with the “UP” arrow pointing up. Position the pipe to extend 12 inches (305mm) beyond the inlet air screen. Seal the space between the vent pipe and opening of the combustion air inlet box using high temperature silicone sealant. Install deflector disk on UL 1738 listed metal vent pipe 2-1/2 inches above inlet air screen and fasten with screws. Seal joint between deflector disk and pipe with silicone sealant. Install vent terminal on top of UL 1738 listed vent pipe, fasten with screws and seal joint.
    Connect flue pipe and combustion air pipe from combustion air inlet box to unit. Joint between double wall vent pipe and single wall vent pipe must be sealed with high temperature silicone sealant. Collars on unit and on combustion air inlet box are sized so that crimped ends of combustion air pipes go toward the unit and crimped ends of flue pipes go away from the unit.
    HORIZONTAL TERMINATION
    Select a location on outside wall for vent terminal. In most applications, the terminal should be on level with the flue outlet of the unit less a 1/4 inch per foot pitch for condensate drainage toward the outside of the building.
    See Figure 22 and Table 5 for terminal clearance.
    Cut a hole through the wall for a 7 inch (178mm) sizes (030-075) or 9 inch (229mm) sizes (090-120) combustion air pipe. Install thimble if required by local codes or type of wall construction.
    Combustion air inlet box may be fastened directly to wall or spaced away from wall using suitable brackets (field supplied). Cut a length of pipe so that it will protrude 4 inches (102mm) through the wall when the box is mounted in position. Fasten pipe to box with sheet metal screws, using at least three screws per joint. Seal joint with high temperature silicone sealant.
    Insert pipe through wall and fasten adapter box in place so that the pipe pitches downward 1/4 inch per foot (21mm/m) toward the outside. Flash and/or caulk pipe on outside wall. Install inlet air screen assembly and fasten to pipe with screws. Insert a continuous length of 4 inch (sizes 030-075) or 5 inch (sizes 090-120) UL 1738 listed vent pipe through the combustion air inlet box opening (detail A, Figure 24). Position the pipe to extend a minimum 12 inches (305mm) beyond the inlet air screen.
    Seal the space between the vent pipe and opening of the combustion air inlet box using high temperature silicone sealant. Install deflector disk on UL 1738 listed metal vent pipe 2-1/2 inches (63.5mm) from inlet air screen and fasten with screws. Install vent terminal on end of UL 1738 listed vent pipe, fasten with screws and seal joint.
    Connect flue pipe and combustion air pipe from combustion air inlet box to unit. Joint between double wall vent pipe and single wall vent pipe must be sealed with high temperature silicone sealant. Collars on unit and on combustion air inlet box are sized so that crimped ends of combustion air pipes go toward the unit and crimped ends of flue pipes go away from the unit.![MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters
Unit Size Dimensions Inches (Nominal)
A B

Combustion Air Inlet Kit Number 11AS-X7- 4
30| 5-1/4| 4| 7| 9| 5| 13
45
60
75
Combustion Air Inlet Kit Number 11AS-X7-5
90| 6-1/4| 5| 9| 12| 5| 16
105
120

OPERATION

POWER VENTED PROPELLER UNITS DIRECT SPARK IGNITION
EXPLANATION OF CONTROLS:

  1. Each Unit Heater comes equipped with a power vent system that consists of a power venter motorand blower, pressure switch, and sealed fluecollector in place of the conventional draft diverter.

  2. The power venter motor is energized by the room thermostat through the integrated control board when a demand for heat is sensed. The pressure switch measures the flow through the vent system and energizes the direct spark ignition system beginning the pre-purge timing when the flow is correct.
    The pressure switch MUST NOT be bypassed. The unit MUST NOT be fired unless the power venter is operating. An unsafe condition could result.

  3. The direct ignition system consists of an ignition control module and a gas valve. When the pre-purge period ends, the spark ignition system is energized, and the gas valve opens to supply gas to the burner. When the thermostat is satisfied, the vent system is de-energized and the valve closes to stop the flowof gas to the unit.

  4. The limit switch interrupts the flow of electric current to the control board, interrupting the flow of gas to the gas valve if the unit heater becomes overheated.

  5. The flame roll-out switch interrupts the flow of electric current to the control board, interruptingthe flow of gas to the unit heater in the event of sustained flame roll-out from the burner area. If this switch trips, DETERMINE AND CORRECTTHE CAUSE of the flame roll-out.

  6. Once the thermostat is satisfied, or the limit switch interrupts the flow of electric current to the control board, the unit will begin a post-purge period.When the post-purge period ends, the powerventer motor is de-energized.

  7. The fan operation is delayed 30 seconds once the thermostat is closed, and continues operation for 30 seconds after the thermostat opens. The start-upfan delay must not exceed 30 seconds from acold start.

  8. The wall thermostat, supplied optionally, is a temperature sensitive switch that operates the vent system and ignition system to control the temperature of the space being heated. The thermostat must be mounted on a vertical, vibration-free surface free from air currents and in accordance with the furnished instructions (also refer to Electrical Section).

START-UP (Also refer to lighting instruction plate equipped on the unit)

  1. Open the manual gas valve in the gas supply line to the unit heater with union connection loose, purge air from the gas line. Tighten the union and check for leaks.
    Never use an open flame to detect gas leaks. Explosive conditions may exist which could result in personal injury or death.

  2. Open the manual valve on the unit heater.

  3. Turn ON the electrical power.

  4. The unit should be under the control of the thermostat. Turn the thermostat to the highest point and determine that the power venter motor starts and the burner ignite. Turn the thermostat to the lowest point and determine that the power venter motor shuts off and the burner is extinguished.

  5. Turn the thermostat to the desired position.

  6. See Gas Input Rate and Adjustments sections.

SHUT DOWN

  1. Turn the valve selector lever to the “OFF” position.
  2. Turn off the electricity.
  3. To relight, follow “start-up” instructions.
    See Figure 25 through 31 for parts/identification.

MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
OPERATION PRIMARY AIR ADJUSTMENT
Primary air adjustment is made at the factory. No field adjustments are necessary.

GAS INPUT RATE

Check the gas input rate as follows (Refer to General Safety Information section for metric conversions).
Never overfire the unit heater, as this may cause unsatisfactory operation, or shorten the life of the heater.

  1. Turn off all gas appliances that use gas through the same meter as the unit heater.
  2. Turn the gas on to the unit heater.
  3. Clock the time in seconds required to burn 1 cubic foot of gas by checking the gas meter.
  4. Insert the time required to burn one cubic foot of gas into the following formula and compute the input rate.

MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
Symbols 7For example:
Assume the BTU content of one cubic foot of gas is 1000, and that it takes 48 seconds to burn one cubic foot of gas. NOTICE: If the computation exceeds, or is less than 95% of the gas BTU/hr. input rating (see Table 1), adjust the gas pressure.
Adjust the gas pressure as follows:

  1. NATURAL GAS: Best results are obtained when the unit heater is operating at its full rated input with the manifold pressure of 3.5 inches WC (0.9 kPa).
    Adjustment of the pressure regulator is not normally necessary since it is preset at the factory.
    However, field adjustment may be made as follows:
    a. Attach manometer at the pressure tap plug below the control outlet.
    b. Remove the regulator adjustment screw cap, located on the combination gas valve.
    c. With a small screwdriver, rotate the adjustment screw counterclockwise to decrease pressure, or clockwise to increase pressure.
    d. Replace regulator adjustment screw cap.

  2. PROPANE GAS: An exact manifold pressure of 10.0 inches W.C. (2.5 kPa) must be maintained for proper operation of the unit heater. If the unit is equipped with a pressure regulator on the combination gas valve, follow steps “a” through “d” above. If the unit is not so equipped, the propane gas supply system pressure must be regulated to attain this manifold operating pressure.

  3. The adjusted manifold pressure should not vary more than 10% from pressure specified in Tables 8 and 9.

TUBULAR UNIT HEATER HIGH ALTITUDE DERATION
This Tubular Unit Heater has been manufactured utilizing standard burner orifices and a normal manifold pressure setting as per the specifications shown on your unit rating plate (refer to Tables 4, 8 and 9).
All unit deration must be done through field adjustments by a qualified technician (refer to Table 9). Once the proper adjustments are made in the field, attach label #J17-06459 to the unit, and record adjusted manifold pressure, altitude of the unit installation and the technician’s name and date on the label using a permanent marker.
**Table 8 – Main Burner Orifice Schedule***

INPUT IN 1000 BTU| HEAT EXCHANGER MATERIAL| STD. ALUMINIZED STEEL| 409 STAINLESS STEEL| NUMBER OF BURNER ORIFICES
---|---|---|---|---
TYPE OF GAS| NATURAL| PROPANE| NATURAL| PROPANE
HEATING VALUE| 1050 BTU/FT 3
(39.1 MJ/m 3)| 2500 BTU/FT 3
(93.1 MJ/m 3)| 1050 BTU/FT 3 **(39.1 MJ/m 3)| 2500 BTU/FT 3 **(93.1 MJ/m 3)
MANIFOLD PRESSURE| 3.5 inches WC (0.87kPA)| 10 inches WC

(2.49 kPA)

| 3.5 inches WC (0.87kPA)| 10 inches WC

(2.49 kPA)

30| FT3/HR| 29| 12| 29| 12| 1
ORIFICE DRILL| 38| 52| 39| 53
45| FT3/HR| 43| 18| 43| 18| 1
ORIFICE DRILL| 31| 48| 32| 49
60| FT3/HR| 57| 24| 57| 24| 1
ORIFICE DRILL| 27| 43| 28| 44
75| FT3/HR| 71| 30| 71| 30| 1
ORIFICE DRILL| 20| 40| 21| 41
90| FT3/HR| 86| 36| 86| 36| 1
ORIFICE DRILL| 16| 36| 17| 37
105| FT3/HR| 100| 42| 100| 42| 1
ORIFICE DRILL| 11| 32| 12| 33
120| FT3/HR| 114| 48| 114| 48| 1
ORIFICE DRILL| 6| 3.1mm| 7| 3.0 mm

*This schedule is for units operating at normal altitudes of 2000 feet (610m) or less.
When installed in Canada, any references to deration at altitudes in excess of 2000 feet (610m) are to be ignored. At altitudes of 2000 to 4500 feet (610 to 1372m), the unit heaters must be field derated and be so marked in accordance with ETL certification. See Table 9 for USA and Canadian field deration information.
Table 9
High Altitude Deration – United States

Altitude Manifold Pressure BTU Output 1
Natural Gas 2 Liquid Propane 3
Feet Meters Inches WC

Percentage
0-2,000| 0-610| 3.5| 872| 10| 2,491| 100%
2,001-3,000| 611-915| 3.2| 797| 9.2| 2,292| 96%
3,001-4,000| 916-1,220| 2.9| 722| 8.4| 2,092| 92%
4,001-5,000| 1,221-1,525| 2.7| 673| 7.7| 1,918| 88%
5,001-6,000| 1,526-1,830| 2.4| 598| 7| 1,744| 84%
6,001-7,000| 1,831-2,135| 2.2| 548| 6.4| 1,594| 80%
7,001-8,000| 2,136-2,440| 2| 498| 5.7| 1,420| 76%
8,001-9,000| 2,441-2,745| 1.8| 448| 5.1| 1,270| 72%
9,001-10,000| 2,746-3,045| 1.6| 399| 4.6| 1,145| 68%

Notes:

  1. Deration based on ANSI Z223.1 (NFPA 54).
  2. Table based on heating value of 1,050 BTU/Cu. ft. at sea level.
  3. Table based on heating value of 2,500 BTU/Cu. ft. at sea level.
  4. Consult local utility for actual heating value.

High Altitude Deration – Canada

Altitude Manifold Pressure BTU Output 1
Natural Gas 2 Liquid Propane 3
Feet Meters Inches WC

Percentage
0-2,000| 0-610| 3.5| 872| 10| 2,491| 100%
2,001-3,000| 611-915| 3.2| 797| 9.2| 2,292| 96%
3,001-4,000| 916-1,220| 2.9| 722| 8.4| 2,092| 92%
4,001-4,500| 1,221-1,371| 2.8| 697| 7.9| 1,968| 90%

Notes:

  1. Deration based on CGA 2.17-M91
  2. Table based on heating value of 1,050 BTU/Cu. feet at sea level.
  3. Table based on heating value of 2,500 BTU/Cu. feet at sea level.
  4. Consult local utility for actual heating value.

MAINTENANCE

PERIODIC SERVICE
NOTICE: The heater and vent system should be checked once a year by a qualified technician.
All Maintenance/Service information should be recorded accordingly on the Inspection Sheet provided in this manual.
Open all disconnect switches and disconnect all electrical and gas supplies and secure in that position before servicing unit. Failure to do so may result in personal injury or death from electrical shock.
Gas tightness of the safety shut-off valves must be checked on at least an annual basis.
To check gas tightness of the safety shut-off valves, turn off the manual valve upstream of the appliance combination control. Remove the 3/32 hex head plug on the inlet side of the combination control and connect a manometer to that tapping.
Turn the manual valve on to apply pressure to the combination control. Note the pressure reading on the manometer, then turn the valve off. A loss of pressure indicates a leak. If a leak is detected, use a soap solution to check all threaded connections. If no leak is found, combination control is faulty and must be replaced before putting appliance back in service.
Should maintenance be required, perform the following inspection and service routine:

  1. Inspect the area near the unit to be sure that there is no combustible material located within the minimum clearance requirements listed in this manual.
    Under no circumstances should combustible material be located within the clearances specified in this manual. Failure to provide proper clearance could result in personal injury or equipment damage from fire.

  2. Turn off the manual gas valve and electrical power to the unit heater.

  3. Remove service access panel.

  4. To clean or replace the burner, remove retainer from around manifold orifice, disconnect flame sensor and igniter from control board, remove burner assembly mounting screws. See Figure 25.

  5. With the burner removed, wire brush the inside surfaces of the heat exchanger.

  6. Remove any dirt, dust, or other foreign matter from the burners using a wire brush and/or compressed air.
    Ensure that all parts are unobstructed.

  7. Reassemble the unit heater by replacing all parts in reverse order.

  8. Complete the appropriate unit startup procedure as given in the “Operation” section of this manual. (See lighting instruction on the unit nameplate).

  9. Check the burner adjustment.

  10. Check all gas control valves and pipe connections for leaks.

  11. Check the operation of the automatic gas valve by lowering the setting of the thermostat, stopping the operation of the gas unit heater. The gas valve should close tightly, completely extinguishing the flame on the burner.

  12. Inspect and service motor/fan assembly. To maintain efficient air flow, inspect and clean the fan blades and guard to prevent buildup of foreign matter.

  13. Check lubrication instructions on motor. If oiling is required, add 1 or 2 drops of electric motor oil as follows:
    a. Light Duty – After three years or 25,000 hours of operation.
    b. Average Duty – Annually after 3 years or 8,000 hours of operation.
    c. Heavy Duty – Annually after one year or at least 1500 hours of operation.
    Never over oil the motor or premature failure may occur!

  14. Check and test the operational functions of all safety devices supplied with your unit.

Table 10 – Tubular Propeller Troubleshooting Guide

SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION
A. Flame pops back. 1. Burner orifice incorrect.
2. Low manifold Pressure. 1. Check for proper orifice size. Refer to

“Operation”.
2. Test and reset manifold pressure.
B. Noisy Flame.| 1. Irregular orifice causing whistle or resonance.
2. Excessive gas input.| 1. Replace orifice.
2. Test and reset manifold pressure.
C. Yellow tip flame (some yellow tipping on LP gas is permissible).| 1. Clogged burner.
2. Misaligned orifice.
3. Insufficient combustion air.
4. Possibly over fired.| 1. Clean main burner ports.
2. Align manifold assembly.
3. Clean combustion air inlet openings.
4. Check gas input and manifold pressures.
D. Floating flame.| 1. Blocked venting.
2. Insufficient combustion air.
3. Blocked heat exchanger.
4. Air leak into combustion chamber, flue collector or draft hood.| 1. Clean Flue. Refer to “Installation”.
2. Clean combustion air inlet openings.
3. Clean heat exchanger. Refer to “Installation”.
4. Determine cause and repair accordingly.
E. Gas odor.
Shut off gas supply immediately!| 1. Gas pipe leak.
2. Leaking gas test port on valve.
3. Blocked heat exchanger.
4. Blocked draft hood.
5. Negative pressure in the building.| 1. Inspect all gas piping and repair.
2. Check to ensure gas test ports are seated.
3. Clean heat exchanger/flue.
4. Clean flue collector.
5. See “Installation”.
F. Delayed ignition.| 1. Improper ground.
2. Bad or broken spark cable.
3. Faulty control.
4. Manifold pressure set too low.
5. Main burner orifice dirty.
6. Improper venting.| 1. Check grounding wires and spark bracket connections.
2. Inspect spark cable connections and cuts.
3. Check to ensure spark is energized after pre purge period.
4. Test and reset manifold pressure refer to “Operations”.
5. Clean or replace orifice.
6. Refer to “Installation”.
G. Failure to ignite.| 1. Gas supply is off.
2. No power supply to unit.
3. Thermostat not calling.
4. Defective high limit.
5. Defective drafter prove switch.
6. Loose wiring.
7. Improper ground.
8. Improper thermostat or transformer wiring.
9. Ignitor defective/damaged.
10. Misaligned ignitor.
11. Defective gas valve.
12. Blown fuse.| 1. Open all manual valves “check for leaks”.
2. Turn on power supply, check fuses and replace if bad.
3. Turn up thermostat, Check for 24v on terminals R and W1 on terminal strip.
4. Check switch for continuity if open with no heat present, replace.
5. Check switch operation to ensure switch closes after draftor purge period. If it does not make/check tubing connections/blockage.
6. Check all wiring per diagram.
7. Check all ground wires and connections.
8. Check both, for wiring according to diagram.
9. Replace ignitor.
10. Resecure ignitor bracket.
11. Check for 24V at gas valve terminals during trial for ignition period. If present with no manifold pressure. Replace valve.
12. Refer to symptom “Q”.
H. Condensation.| 1. Improper venting.
2. Unit under fired.
3. Building too cold.| 1. Refer to “Installation, Venting”.
2. Check gas supply pressures to unit. Refer to “Installation”.
3. Refer to “Installation”.

Table 10 – Tubular Propeller Troubleshooting Guide (continued)

SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION
I. Burner will not shut off. 1. Thermostat located incorrectly.

2. Improper thermostat wiring.
3. Shorted circuit.
4. Defective sticking gas valve.
5. Excessive gas supply pressure.| 1. Relocate thermostat away from outside wall or drafts.2
. Check thermostat circuit for open and close on terminal strip on heater “R” and “W”.
3. Check thermostat circuit for shorts “staples piercing wires”.
4. Check for 24v on gas valve terminals when thermostat is not calling.
5. Refer to “Installation”.
J. Rapid burner cycling.| 1. Loose electrical connections at thermostat or gas valve.
2. Excessive thermostat heat anticipator setting.
3. Unit cycling on high limit.
4. Poor thermostat location.| 1. Tighten all electrical connections.
2. Adjust heat anticipator setting for longer cycles. Refer to “Electrical Connections”.
3. Check for proper air supply across heat exchanger and proper gas supply.
4. Relocate thermostat.
K. Noisy power venter.| 1. Power venter wheel loose.
2. Power venter wheel is dirty.
3. Power venter wheel is rubbing on the housing.| 1. Replace or tighten.
2. Clean power venter wheel.
3. Realign power venter wheel.
L. Fan will not run.| 1. Loose electrical connections.
2. Defective motor or overload.
3. Defective control board.
4. Blown fuse.| 1. Check and tighten wires on fan circuit.
2. Test for 115v on terminal ACB Heat and “L2” if voltage is present replace motor.
3. Test for 115v on terminal ACB Heat and “L2” on the control board, if voltage is not present 45 seconds after trial for ignition replace board.
4. Replace fuse.
M. Fan motor turns on and off while burner is operating.| 1. Motor overload protection is tripping.
2. Loose wiring or connection.
3. Control board is defective.| 1. Check motor amps against motor name plate, check voltage, replace if found defective.”
2. Check for 115v between motor leads.
3. Check terminal ACB Heat for voltage if voltage not constant, replace board.
N. Fan will not stop.| 1. Control Board is in flame failure mode.
2. Fan improperly wired.
3. Defective board.| 1. Turn 115v power off to the unit, wait 10 seconds and reapply voltage to the unit.
2. Check wiring of fan circuit to wiring diagram.
3. If unit is not calling for heat and board is not in a flash code mode, replace board.
O. Not enough heat.| 1. Incorrect gas input.
2. Heater undersized.
3. Thermostat malfunction.
4. Heater cycling on limit.
5. Incorrect orifice size.| 1. Refer to “Operation”.
2. Is the heater output sized correctly for heat loss of the space. Has the space been enlarged?
3. Check thermostat circuit, 24v on terminals “R” and “W” on terminal strip.
4. Check air movement across heat exchanger. Check voltage and amps at the fan motor. Check gas input to ensure unit is not over fired. Check heat exchanger to ensure unit is not dirty.
5. Check orifice size, replace if undersized.
P. Too much heat.| 1. Unit is over fired.
2. Thermostat malfunction.
3. Heater runs continuously.| 1. Refer to “Operation”. Check orifice size. If too big replace.
2. Check thermostat for operation, to ensure circuit open and closes.
3. Check wiring per diagram; check operation at the gas valve, look for a short in thermostat circuit.
Q. Blown fuse.| 1. Electrical short.
2. Improper ground.
3. Defective gas valve.| 1. Refer to wiring diagram.
2. Check grounding wires.
3. Replace.

Table 10 – Tubular Propeller Troubleshooting Guide

SYMPTOMS POSSIBLE CAUSE(S) CORRECTIVE ACTION
R. Cold air is delivered during heater operation. 1. Incorrect manifold
pressure or input. 1. Refer to “Operation”.
S. High limit tripping. 1. Unit is over fired.

2. Air flow is low.
3. Defective switch.
4. Defective control board.| 1. Burner orifice may be too large, verify and replace.
2. Check for proper voltage, ensure fan blade is correctly positioned 1/3 inside venturi.
3. Check operation of switch, did the switch open when unit is running or is the switch open during start-up.
4. Check for 24v on line side of the high limit. Constant voltage should be recorded if not control board is suspect. Check flash code.
T. Power venter will not run.| 1. Loose wiring or connections.
2. Motor overload is tripped or bad motor.
3. Bad control board.| 1. Check all wring in the power vent circuit to ensure good connection, including “Neutral”.
2. Check for 115v between motor leads and check amp draw of motor. Replace if needed.
3. Check for continuous 115v on terminal “CBM Blower” and neutral during call for heat. If not present and all checks are normal, replace.
U. Power venter turns on and off during operation.| 1. Power venter improperly wired.
2. Motor overload cycling or defective motor.
3. Defective control board.| 1. Check power venter circuit per wiring diagram.
2. Check motor voltage and amp draw to motor name plate, replace if motor found defective.
3. Check for continuous 115v on terminal “CMB Blower” during call for heat, replace board if found defective.
V. Power venter will not stop.| 1. Power venter improperly wired.
2. Main burner did not light on call for heat.
3. Defective control board.
4. Loss of pressure. Pressure switch not made.| 1. Check power venter circuit per wiring diagram.
2. Heater is in lockout mode check flash code table for problem.
3. No flash codes present along with no call for heat, replace control board.
4. Check venting for blockage. Check tubing for blockage or hole. Check spud for blockage.

Line voltage power can cause product damage, severe injury or death.
Only a trained experienced service technician should perform this troubleshooting.

  1. Check the system thermostat to make sure it is calling for heat. (Do not cycle the thermostat on and off at this time.)
  2. Do not interrupt power to the control board by opening any electrically interlocked panels.
  3. Observe the LED indicator on the front panel (a green LED indicates system faults); check and repair system as noted in the chart to the right.

*NOTICE: Air flow proving switch and power venter hose barbs must be free of any dust or debris at all times. Periodically check these openings and/or if any problems occur.
Table 11A – Troubleshooting with LED Indicator Assistance for UT Control Board

LED STATUS INDICATES CHECK/REPAIR
Slow Flash Control OK, no call for heat. Not Applicable
Fast Flash Control OK, call for heat present. Not Applicable
Steady Off Internal control fault, or no power. 1. Line voltage on

terminals 120 and C on transformer.
2. Low voltage (24V) on terminals 24 and C on transformer.
3. 5 Amp fuse on circuit board.
Steady On| Control internal failure or bad ground.| 1. Common side of transformer grounded to chassis.
2. Loose spark ignitor.
2 Flashes| In lockout from failed ignitions or flame losses.| 1. Gas supply off or gas supply pressure too low.
2. Flame sense rod contaminated or loose wire.
3. Gas valve switch is off or wires are not connected.
4. Broken or cracked porcelain on flame probe or spark ignitor.
3 Flashes| Pressure Switch open with inducer on or closed with inducer off.| 1. Obstructions or restrictions in appliance air intake or flue outlet are preventing proper combustion airflow.
*2. Moisture or debris in tubing that connects pressure switch and draft inducer.
3. Airflow switch jumpered or miswired.
4 Flashes| Limit or rollout switch is open.| 1. Open high limit or manual reset rollout switch.
2. Gas pressure too high, over fire condition.
3. Incorrect airflow due to blockage or motor not operating.
5 Flashes| Flame sensed while gas valve is off.| 1. Flame probe miswired or shortened.
6 Flashes| On-board microprocessors disagree.| 1. Thermostat is interfering with con- trol board.

IDENTIFICATION OF PARTS

TUBULAR 30-120 MBH UNIT SIZESMESTEK GG IOM 18 Tubular Gas Fired Direct
Spark Propeller Unit Heaters - IDENTIFICATION

Item No. ItemDescription
1 Vestible Panel/Tube Assembly (Heat Exchanger)
2 Bracket/Gas Train
3 Manifold
4 Burner Assembly
5 *Standard Orifice

Natural Gas or Propane (LP) Gas
6| Spark Ignitor
7| Flame Sensor
8| Gas Valve
Natural or Propane (LP) Gas
9| Manual Rollout Safety Switch
10| Transformer, 50 VA, 115/24
11| Air Pressure Switch
12| Terminal Block Plate
13| High Limit Switch
14| Fan Motor
15| OSHA Fan Guard
16| Standard Fan
17| Fan/Guard/Motor Mount Hardware Kit
18| **Flue Collector
19| Power Venter (Drafter) Assembly
20| Flue Collar Assembly
21| Vinyl Tubing (Pressure Switch)
22| Power Venter Mounting Plate
23| Louver
24| Louver Spring
25| Control Board
26| Access Panel
27| Top Jacket Panel w/Insulation
28| Bottom Jacket Panel w/Insulation
29| Front Jacket Panel
30| Rear Jacket Panel
31| Bracket, Manifold
32| Tube Support Bracket
33| Green Ground Screw
34| Hanger Bracket
35| Manifold Clamp
36| Pipe Nipple
37| Left Side Panel
38| Manifold Support Bracket Kit
39| Spring
40| Grommet
41| Inlet Screen Assembly
42| Burner Box View Port

MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
IDENTIFICATION 1 HOW TO ORDER REPLACEMENT PARTS
Please send the following information to your local representative: if further assistance is needed, contact the manufacturer’s customer service department.

  • Unit Number
  • Serial Number
  • Part Description and Number as shown in Replacement parts Catalog

LIMITED WARRANTY

Power Vented Tubular Propeller Unit Heaters

  1. The “Manufacturer” warrants to the original owner at original installation site that the above model Gas-Fired Heater (“the Product”) will be free from defects in material or workmanship for (1) year from the date of shipment from the factory, or one and one-half (1-1/2) years from the date of manufacture, whichever occurs first. The Manufacturer further warrants that the complete heat exchanger, flue collector and burners be free from defects in material or workmanship for a period of ten (10) years from the date of manufacture. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective.

  2. This limited warranty does not apply:
    a. if the product has been subjected to misuse or neglect, has been accidentally or intentionally damaged, has not been installed, maintained, or operated in accordance with furnished written instructions, or has been altered or modified in any way by any unauthorized person.
    b. to any expenses, including labor or material, incurred during removal or reinstallation of the Product
    c. to any damage due to corrosion by chemicals, including halogenated hydrocarbons, precipitated in the air
    d. to any workmanship of the installer of the Product

  3. This limited warranty is conditional upon:
    a. advising the installing contractor, who in turn notify the distributor or manufacturer
    b. shipment to the Manufacturer of that part of the Product thought to be defective. Goods can only be returned with prior written approval of the Manufacturer. All returns must be freight prepaid.
    c. determination in the reasonable opinion of the Manufacturer that there exists a defect in material or workmanship

  4. Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.
    5. THIS LIMITED WARRANTY IS IN LIEU OF ALL WARRANTIES, EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY JURISDICTION.

In the interest of product improvement, we reserve the right to make changes without notice.
LOW PROFILE TUBULAR PROPELLER

UNIT NUMBER DESCRIPTION

MESTEK GG IOM 18 Tubular Gas Fired Direct Spark Propeller Unit Heaters -
Symbols 9 **Digit

1, 2 – Unit Type [UT]**

GG/BRT – Low Profile Tubular Propeller
Digit #3, 4, 5 – Capacity [CA]
030 – 30,000 BTU/HR
045 – 45,000 BTU/HR
060 – 60,000 BTU/HR
075 – 75,000 BTU/HR
090 – 90,000 BTU/HR
105 – 105,000 BTU/HR
120 – 120,000 BTU/HR
Digit #6 – Furnace Type [FT]
A – Right Side Access
Digit #7 – Furnace Material [FM]**
1 – Standard (Aluminized) Steel
2 – 409 Stainless Steel
Heat Exchanger Tube Material Only.
Digit #8 – Gas Type [GT]
N – Natural Gas
P – Propane Gas (LP)
Digit #9 – Altitude [AL]
S – 0–4,999 feet
T – 5,000–11,999 feet
Note: Installations over 2,000 feet require gas input deration in the field.
Refer to unit installation instructions.
Digit #10 – Direct Spark Gas Control [GC]
A – Single Stage (Standard)
B – Two Stage (Capacities [CA] 060 through 120 only)
Digit #11 – Supply Voltage [SV]
1 – 115/1/60
5 – 230/3/60
2 – 208/1/60
6 – 460/3/60
3 – 230/1/60
7 – 575/3/60
4 – 208/3/60
Z – Special
Note: Supply Voltages [SV] 2-7 include field mounted step down transformer.
Digit #12 – Motor Type [MT]
1 – Open Drip Proof (Standard)
2 – Totally Enclosed (Capacities [CA] 060 through 120 only)
Digit #13 – Development Level [DL]
C – Production Onset
Digit #14, 15+ – Accessories [AS]
FACTORY INSTALLED
S3 – 409 Stainless Steel Flue Collector
Z1 – Special
† FIELD INSTALLED (11AS-____ )
†Field Installed Accessories are not included in the Unit Number. All Field Installed Accessories are entered as a separate line item using the catalog number which utilizes “11AS” as a prefix. i.e: A7 becomes 11AS-A7.
A7 – High Pressure Regulator
A7 – 1/2-1 Regulator for 0.5-10 PSI
A7 – 3/8-1 Regulator for 10-20 PSI
A7 – 5/16-1 Regulator for 20-35 PSI
G1 – 1-Stage Mercury Free Thermostat (Round)
G2 – 1-Stage Mercury Free Thermostat w/Guard Kit
G3 – 1-Stage Mercury Free Thermostat/Fan Switch
G5 – 2-Stage Mercury Free Thermostat w/Fan Switch
G6 – Locking Thermostat Cover
G9 – 1-Stage Mercury Free Heating Only Thermostat
GW – WiFi Thermostat TH8321WF1001/U
P5 – 24V SPST Relay-Specify Purpose
T1 – Quick Swivel Mounting Bracket
VC-4 – 4″ Vent Cap
X2 – 30 Degree Downturn Nozzle
X3 – 60 Degree Downturn Nozzle
X4 – 90 Degree Downturn Nozzle
X7-4 – Combustion Air Inlet Kit (Capacities [CA] 030-075)
X7-5 – Combustion Air Inlet Kit (Capacities [CA] 090-120)
GAS EQUIPMENT
START-UP
Customer ____
Job Name & Number _____
PRE-INSPECTION INFORMATION**
With power and gas off.
Type of Equip:
Unit Heater
Serial Number _____
Model Number __
Name Plate Voltage: _

Name Plate Amperage: ___
Type of Gas:
Natural
LP Tank Capacity _
lbs.
Rating: ____ BTU @ °F ___ kg _ kw @ ____ °C
❐ Are all panels, doors, vent caps in place?
❐ Has the unit suffered any external damage? Damage


❐ Does the gas piping and electric wiring appear to be installed in a professional manner?
❐ Has the gas and electric been inspected by the local authority having jurisdiction?
❐ Is the gas supply properly sized for the equipment?
❐ Were the installation instructions followed when the equipment was installed?
❐ Have all field installed controls been installed?
❐ Do you understand all the controls on this equipment? If not, contact your wholesaler or rep.
(DO NOT START this equipment unless you fully understand the controls.)
GENERAL
With power and gas off.
❐ Make certain all packing has been removed.
❐ Tighten all electrical terminals and connections.
❐ Check all fans & blowers for free movement.
❐ Check all controls for proper settings.
FAN
With power on and gas off.
❐ Check voltage L1 L2 L3
❐ Check rotation of main fan.
❐ Check motor amps L1
L2 L3
GAS HEATING
With power and gas on.
❐ Inlet gas pressure    inch WC or  kPa
❐ Burner ignition
❐ Manifold gas pressure   inch WC or  kPa
❐ Cycle and check all other controls not listed.
❐ Cycle by thermostat or operating control.
❐ Entering air temperature °F or °C
❐ Discharge air temperature  (high fire)
°F or ____ °C
❐ Combustion readings:
Carbon Monoxide: 
PPM__
Carbon Dioxide:  _ %
Remarks: __

260 NORTH ELM ST.
WESTFIELD, MA 01085
TEL: 413-564-5540
FAX: 413-562-5311
www.mestek.com