John Wood 540P Indoor Gas Tankless Water Heater Owner’s Manual

June 15, 2024
John Wood

540P Indoor Gas Tankless Water Heater

On-Demand Water Heater Installation Manual and Owner’s

Guide

SPECIFICATIONS

Model: 540P Indoor 540P Outdoor (AT-H3P-DV) (AT-H3P-OS)

Natural Gas Input (Operating Range): Min: 15,000 BTU/h, Max:
199,000 BTU/h

Propane Input (Operating Range): Min: 13,000 BTU/h, Max: 199,000
BTU/h

Gas Connection: 3/4 NPT

Water Connections: 3/4 NPT

Water Pressure* Natural gas Inlet Pressure: Min 4.0 psi (0.1
MPa), Max. 10.5 psi (2.61 kPa)

Propane Inlet Pressure: Min 8.0 psi (1.99 kPa), Max. 13.0 psi
(3.23 kPa)

Weight: 61.0 lbs. (27.7 kg)

Dimensions: H 22.4 x W 17.7 x D 10.7 inch (H 570 x W 450 x D 272
mm)

Ignition: Electric Ignition

Supply: 120 VAC / 60 Hz

Electric Consumption: With pump – 108.6 W / 1.34 A, Without pump
– 87.6 W / 1.10 A

Installation Manual

CONGRATULATIONS

Congratulations and thank you for choosing our tankless water
heater. Before use, we recommend that you read through this
installation manual carefully. Keep this manual for future
reference. If you need an additional manual, contact the
manufacturer or your local distributor. You may also download a
manual from our website. When you call, please tell us the product
name and the serial number of your unit written on the rating plate
of the water heater.

Owner’s Guide

OPERATING SAFETY

To ensure safe operation of the water heater, please follow
these guidelines:

  • Do not store or use gasoline or other flammable vapors and
    liquids in the vicinity of this or any other appliance.

  • Installation and service must be performed by a qualified
    installer, service agency, or the gas supplier.

MAINTENANCE AND SERVICE

To maintain the performance and efficiency of your water heater,
regular maintenance and service are required. Please refer to the
following sections for instructions:

INLET WATER FILTER CLEANING

Regularly clean the inlet water filter to prevent clogging and
ensure proper water flow. Follow these steps:

  1. Turn off the water supply to the heater.

  2. Locate the inlet water filter, usually located near the water
    inlet connection.

  3. Remove the filter and clean it using water and a soft
    brush.

  4. Inspect the filter for any damage and replace if
    necessary.

  5. Reinstall the filter and turn on the water supply.

UNIT DRAINING & POWER OUTAGE (FREEZE PROTECTION)

In case of a power outage or if you need to drain the water
heater, follow these steps:

  1. Turn off the power supply to the water heater.

  2. Close the gas valve to stop the gas supply.

  3. Attach a hose to the drain valve and place the other end in a
    suitable drain location.

  4. Open the drain valve to allow the water to drain from the
    unit.

  5. Once the unit is drained, close the drain valve and remove the
    hose.

  6. Restore power supply and gas flow to the water heater.

MEASURING INLET GAS PRESSURE

It is important to measure the inlet gas pressure to ensure
proper operation of the water heater. Follow these steps:

  1. Turn off the gas supply to the water heater.

  2. Locate the gas inlet pressure tap on the gas valve.

  3. Attach a manometer to the pressure tap.

  4. Turn on the gas supply and observe the manometer reading.

  5. The inlet gas pressure should be within the specified range
    mentioned in the specifications section.

  6. If the pressure is not within the range, contact a qualified
    installer or service agency for adjustment.

TROUBLESHOOTING

If you encounter any issues with your water heater, refer to the
troubleshooting section in the manual for possible solutions. If
the problem persists, contact a qualified installer or service
agency for further assistance.

ERROR CODES

The water heater may display error codes in case of
malfunctions. Refer to the error codes section in the manual for a
list of codes and their corresponding meanings. If you need
assistance in resolving the error, contact a qualified installer or
service agency.

General

This section provides general information about error codes and
their troubleshooting steps.

Single unit installation

If you have a single unit installation, refer to this section
for specific error code information and troubleshooting steps.

How error codes display in an Easy-Link system

If you have an Easy-Link system installed, this section explains
how error codes are displayed and provides troubleshooting
steps.

Fault analysis

This section provides detailed fault analysis for each error
code. Use this information to diagnose and resolve the issue.

COMPONENTS DIAGRAM

Refer to the components diagram in the manual to familiarize
yourself with the various parts of the water heater.

PARTS LIST

The parts list section provides a comprehensive list of all the
parts included with the water heater. Use this list for reference
when ordering replacement parts or during maintenance.

OUTPUT TEMPERATURE CHART

The output temperature chart in the manual shows the temperature
range that can be achieved with the water heater based on the input
settings. Use this chart to set the desired water temperature.

FAQ

Q: Can I store flammable liquids near the water heater?

A: No, it is not safe to store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other
appliance.

Q: Who should perform the installation and service of the water

heater?

A: Installation and service must be performed by a qualified
installer, service agency, or the gas supplier.

Q: How often should I clean the inlet water filter?

A: The inlet water filter should be cleaned regularly to prevent
clogging. It is recommended to clean it at least once every six
months or as needed depending on the water quality.

Q: What should I do in case of a power outage or if I need to

drain the water heater?

A: In case of a power outage or if you need to drain the water
heater, follow the instructions provided in the “UNIT DRAINING
& POWER OUTAGE (FREEZE PROTECTION)” section of the manual.

Q: How can I measure the inlet gas pressure?

A: To measure the inlet gas pressure, follow the instructions
provided in the “MEASURING INLET GAS PRESSURE” section of the
manual.

Q: What should I do if I encounter an error code on the water

heater?

A: If you encounter an error code, refer to the “ERROR CODES”
section of the manual for troubleshooting steps. If the problem
persists, contact a qualified installer or service agency.

On-Demand Water Heater Installation Manual and Owner’s Guide

RD
R
ANSI Z21.10.3 · CSA 4.3

Models
540P Indoor 540P Outdoor

If the information in these

instructions is not followed

exactly, a fire or explosion may

WARNING

result causing property damage, personal injury or death.

Gas Tankless Water HeaterTM
Suitable for combination potable water heating and space heating. Please refer to local codes for
space-heating compliance.

– Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not touch any electric switch; do not use any phone in your building. · Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. · If you cannot reach your gas supplier, call the fire department.
– Installation and service must be performed by a qualified installer, service agency or the gas supplier.

FEATURING · INTEGRATED RECIRCULATION PUMP · ENDLESS HOT WATER · ON-DEMAND USAGE · COMPACT, SPACE SAVING · ENERGY CONSERVATION · COMPUTERIZED SAFETY · NO PILOT LIGHT · Complies with SCAQMD Rule
1146.2 for natural gas NOx emissions of 14 ng/J or 20 ppm. · EASY-LINK SYSTEM

If you have any questions, please call or write to
USA: 500 Tennessee Waltz Parkway Ashland City, TN 37015
Toll Free: 1-877-737-2840
CANADA: 599 Hill Street West Fergus, ON N1M 2X1 1-888-479-8324

Keep this manual near the water heater for future reference whenever maintenance, adjustment or service is required.

Contents

CONTENTS
Installation Manual
SPECIFICATIONS ………………………………………4
INTRODUCTION………………………………………. 5 SAFETY GUIDELINES……………………………….6 SAFETY DEFINITION………………………………6 GENERAL……………………………………………… 6 INCORPORATED RECIRCULATION PUMP …….7 INSTALLATION …………………………………………8 CLEARANCES ………………………………………10 INCLUDED ACCESSORIES……………………..10 OPTIONAL ITEMS ………………………………..10 WARNING FOR INSTALLATIONS……………12 HIGH-ALTITUDE INSTALLATIONS ………….13 VENTING INSTRUCTIONS FOR INDOOR..14
Vent termination clearances ………………..15 Clearances for sidewall terminations …….16 Clearances for rooftop terminations ……..17 Combustion air supply…………………………18 Exhaust vent (ABS,PVC,CPVC, or polypropylene vent) ……………………………22 DIP switch settings for vent length (ABS,PVC,CPVC, or polypropylene vent)…23 Exhaust vent (Stainless steel vent) ………..27 DIP switch settings for vent length (Stainless steel vent)……………………………27 Common venting system ……………………..30 GAS SUPPLY AND GAS PIPE SIZING ………32 General ……………………………………………..32 Gas connections …………………………………32 Natural Gas supply piping…………………….33 Propane (LP) supply piping…………………..33 WATER CONNECTIONS ………………………..34 Recirculation pump mode ……………………35 Installation w/ dedicated return line……..35 Installation w/o recirculation ……………….36 Domestic and space heating ………………..36 Dual purpose water heating for the State of Massachusetts ………………….38 Pressure relief valve ……………………………39 CONDENSATE DRAIN …………………………..39 ELECTRICAL CONNECTIONS …………………41 TEMPERATURE REMOTE CONTROLLER …..41 Included accessories……………………………41 EASY-LINK SYSTEM …………………………………..43 Easy link connection procedures …………..43 INITIAL OPERATION ……………………………….45 Initial test run ……………………………………. 45

Owner’s Guide
OPERATING SAFETY ……………………………….48
NORMAL OPERATION ……………………………. 50 BUILT-IN CONTROLLER AND REMOTE CONTROLLER ………………50 GENERAL……………………………………………. 50 OUTLET WATER TEMPERATURE SETTING ……………………………………………..51 TEMPERATURE TABLE OF CONTROLLER .51 SETTING THE TIME ……………………………..52 PUMP OPERATION TIMERS………………….52 Setting pump timers ……………………………53 Selecting a pump timer ……………………….55 Display example………………………………….56 Pump operation test……………………………57 On-demand pump operation………………..57 ADDITIONAL FEATURES……………………….59 Information mode ………………………………59 Unit conversion mode …………………………59 SETTING TEMPERATURE ON THE PCB ……….60 FLOW …………………………………………………. 60 FREEZE PROTECTION SYSTEM …………….. 61
MAINTENANCE AND SERVICE ……………… 62 INLET WATER FILTER CLEANING ………………. 62 UNIT DRAINING & POWER OUTAGE (FREEZE PROTECTION) ………………………………………. 63 MEASURING INLET GAS PRESSURE ………….. 63
TROUBLESHOOTING………………………………. 64 ERROR CODES …………………………………….66 General ……………………………………………..66 Single unit installation ………………………… 66 How error codes display in an Easy-Link system………………………………………………. 67 Fault analysis ……………………………………..68
COMPONENTS DIAGRAM ……………………….70
PARTS LIST…………………………………………….74
OUTPUT TEMPERATURE CHART ……………… 76

2 Page

Installation Manual
Installation Manual
CONGRATULATIONS
Congratulations and thank you for choosing our tankless water heater. Before use, we recommend that you read through this installation manual carefully. Keep this manual for future reference. If you need an additional manual, contact the manufacturer or your local distributor. You may also download a manual from our website. When you call, please tell us the product name and the serial number of your unit written on the rating plate of the water heater.
3 Page

Installation Manual Specifications

SPECIFICATIONS

Model

540P Indoor 540P Outdoor (AT-H3P-DV) (AT-H3P-OS)

Natural Gas Input (Operating Range)

Propane Input (Operating Range)

Gas Connection
Water Connections
Water Pressure* Natural gas Inlet Pressure Propane Inlet Pressure Weight

Dimensions

Ignition

Supply

BTU/h BTU/h
psi (MPa) ” W.C. (kPa) ” W.C. (kPa)
lbs. (kg) inch mm
VAC / Hz

Min: 15,000 Max.: 199,000 Min: 13,000 Max.: 199,000
3/4″ NPT 3/4″ NPT 15 – 150 (0.1 – 1)
Min 4.0 (1.00) Max. 10.5 (2.61)
Min 8.0 (1.99) Max. 13.0 (3.23)
61.0 (27.7) H 22.4 x W 17.7 x D 10.7 H 570 x W 450 x D 272
Electric Ignition 120 / 60

Electric Consumption

Operation

With pump Without pump

W / A W / A

108.6 / 1.34 87.6 / 1.10

Standby

W / A

4.6 / 0.10

Freeze-Protection

W / A

192.3 / 1.63

Water heater Category**

Category IV

N/A

Maximum Pipe length***
(Hot Water supply line and Dedicated Return line)

Pipe Diameter

3/4″ ( 19 mm)
1/2″ ( 13 mm)

500 ft (152.4 m) 200 ft (61.0 m)

*40 psi or above is recommended for maximum flow.

**Water heater Category — water heaters of other than direct vent type, for outdoor installation, are divided into four

categories based on static pressure produced in the vent and flue loss.

Category IV – a water heater that operates with a positive vent static pressure and with a vent gas temperature that

may cause excessive condensate production in the vent.

***These are equivalent lengths that include head loss for elbows, tees, unions, etc. Refer to page 35 for additional

information available pipe on length. NOTE:

· Check the rating plate to ensure that this product matches your specifications.

· The manufacturer reserves the right to discontinue, or change at any time, specifications or designs

without notice and without incurring obligation.

4 Page

Installation Manual Introduction
INTRODUCTION
· This manual provides information necessary for the installation, operation, and maintenance of the water heater.
· The model description is listed on the rating plate which is attached to the side panel of the water heater.
· Please read all installation instructions completely before installing this product. · If you have any problems or questions regarding this equipment, consult the manufacturer or
its local representative. · This equipment is an on-demand, tankless water heater designed to efficiently supply endless
hot water when properly sized and installed. · This heater incorporates a recirculation pump for homes with an installed circulation system. · These high efficiency models have a built-in secondary heat exchanger that absorbs latent
heat from the exhaust gas. · The 540P Indoor model is only to be installed indoors. The 540P Outdoor model is only to be
installed outdoors. · The 540P Indoor model is categorized as Category IV when it isn’t installed in the direct vent
installation.
· The principle behind tankless water heaters is simple:

Exhaust thermistor

Secondary HX

Thermistor
Bypass valve
Thermistor Water control valve
Flow sensor Recirculation pump
Thermistor Thermistor

Burners

Primary HX
Gas valves Fan motor Computer board Condensate drain port

Hot water

Gas

Return line

Cold water

*This diagram illustrates tankless water heater design concepts only and does not accurately represent the water heater’s physical description.

1. A hot water fixture is turned on. 2. Water enters the heater. 3. The water flow sensor detects the water flow. 4. The computer initiates the fan motor and sends a signal to the igniter to create an ignition spark. 5. The gas ignites and flames appear within the burner chamber. 6. Water circulates through the heat exchanger and then gets hot. 7. Using thermistors to measure temperatures throughout the water heater, the computer modulates
the gas and water valves to ensure proper output water temperature. 8. When the fixture is turned off, the unit shuts down.

5 Page

SAFETY GUIDELINES
SAFETY DEFINITION

Installation Manual Safety Guidelines

Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. DANGER
Indicates an imminently hazardous situation which, if not avoided, could result in death or serious injury. WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION
NOTICE Indicates information considered important but not hazard related.
GENERAL
1. Follow all local codes, or in the absence of local codes, follow the current edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the USA or B149.1 Natural Gas, Propane Installation Code in Canada.
2. Properly ground the unit in accordance with all local codes or in the absence of local codes, with the National Electrical Codes: ANSI/NFPA 70 in the USA or CSA standard C22.1 Canadian Electrical Code Part 1 in Canada.
3. Carefully plan where you intend to install the water heater. Please ensure: · Your water heater will have enough combustible air and proper ventilation. · Locate your heater where water leakage will not damage surrounding areas. (Please refer to page 9.)
4. Check the rating plate for the correct GAS TYPE, GAS PRESSURE, WATER PRESSURE and ELECTRIC RATING. *If this unit does not match your requirements, do not install and consult with the manufacturer.
5. If any problem should occur, turn off all hot water taps and turn off the gas. Then call a trained technician or the Gas Company or the manufacturer.

6 Page

Installation Manual Installation

· Water temperatures over 125 °F (52 °C) can cause severe burns instantly or death from

scalding. The water temperature is set at 120 °F (50 °C) from the factory to minimize

any scalding risk. Before bathing or showering, always check the water temperature.

· To reduce the risk of scalding, install Thermostatic Mixing Valves (temperature limiting

valves) at each point of use.

· Do not store or use gasoline or other flammables, vapors, or liquids in the vicinity of

WARNING

·

this appliance. Do not reverse the water and/or gas connections as this will damage the gas valves

and can cause severe injury or death. Follow the diagram on page 36 when installing

your water heater.

· Should overheating occur or the gas supply fails to shut off, turn off the manual gas

control valve to the appliance.

· Do not use this appliance if any part has been in contact with or been immersed in

water. Immediately call a qualified installer or service agency to replace a flooded

water heater. Do not attempt to repair the unit. It must be replaced.

· Do not disconnect the electrical supply if the ambient temperature will drop below

freezing unless the water has been drained from the water heater. The Freeze

Protection System only works if the unit has electrical power. The warranty will not

be covered if the heat exchanger is damaged due to freezing. Refer to the section on

the Freeze Protection System on page 61 and Unit draining & power outage (Freeze

protection) on page 63 for more information.

· Failure to observe these warnings could result in severe personal injury or death.

INCORPORATED RECIRCULATION PUMP
This heater incorporates a recirculation pump for homes with an installed circulation system. The pump provides several useful features:
· The built-in controller and the remote controller (100276687/TM-RE43) offer two timer settings for pump operation: PUMP TIMER 1 and PUMP TIMER 2. The pump will operate during the times set for TIMER 1 and/or TIMER 2.
· The pump automatically turns on and off during set times depending on the set temperatures for pump operation. The set point temperature can be set by the built-in controller or the remote controller (100276687/TM-RE43).
· Instead of the timers, the pump can operate by pressing the PUMP button on the built-in controller or the remote controller (100276687/TM-RE43). A DIP switch must be turned on to use this control. (Refer to page 57.)
The maximum pipe length for the combined hot water supply line and return line is: · 1/2″ (13 mm) pipe: 200 ft (61.0 m) · 3/4″ (19 mm) pipe: 500 ft (152.4 m)
These are equivalent length that includes head loss for elbows, tees, unions, etc for smooth wall copper tube. Other water tube materials have different head loss characteristics. When other materials are used, the installer shall consult with the water tube manufacturer to conduct a head loss calculation to make sure the installed pump will flow at least 2 gpm. Please refer to the manufacturer’s specification sheet for pump head loss information. An additional pump may be necessary for circulation systems with longer equivalent pipe lengths.

7 Page

Installation Manual Installation
INSTALLATION
1. Follow all local codes, or in the absence of local codes, follow the current edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the USA or B149.1 Natural Gas, Propane Installation Code in Canada.
2. All gas water heaters require careful and correct installation to ensure safe and efficient operation. This manual must be followed exactly. Read the “Safety Guidelines” Section.
3. The manifold gas pressure is preset at the factory. It is computer controlled and should not need adjustment.
4. Maintain proper space for servicing. Install the unit so that it can be connected or removed easily. Refer to the “Clearances” Section on page 10 for proper clearances.
5. The water heater must be installed in a location where the proper amount of combustion air will be available to it at all times without obstructions, or the indoor heater must be direct vented. See pages 14 to 29.
6. Install the water heater so it is level (left-to-right & front-to-back) and plumb (vertically). 7. Electrical service to the water heater requires a means of disconnection. This will allow power to
the water heater to be shut off for servicing and safety purposes. 8. Do not install the unit where the exhaust vent is pointing into any opening in a building or where
the noise may disturb your neighbors. Make sure the vent termination meets the required clearance from any doorway or opening to prevent exhaust from entering a building. (Refer to pages 9, 12, 15 and 16.) Check local code requirements prior to installation. 9. Carefully plan the installation location of the heater and vent terminations. Contaminants such as aerosols, lint, and fine powders (including flour) can clog the air intake and reduce the operation of the fan. This, in turn, can cause improper combustion and reduce the life of the water heater. Regularly ensure that the area around the water heater, vent termination, and air intake is free of dust, debris, and other contaminants. In environments with a high level of contaminants (laundry facilities, hair salons, pet salons, chemical plants, commercial kitchens, etc.), direct venting is required. 10. The Indoor model is to be installed indoors only. This water hetaer equipped with a thermistor and hi-limit switch for the exhaust gas, detecting excess temperatures within the flue and enabling the unit to safely stop operations if needed. These components are always monitoring exhaust gas conditions in order to prevent heat damage to ABS, PVC, CPVC, or polypropylene (Plastic) venting if ABS, PVC, CPVC, or polypropylene is used. If the exhaust gas temperature exceeds 140 °F (60 °C), these components will enable the unit to safely stop operations. These components are not installed on the outdoor models since the exhaust vent is built-in.
· If the water heater is used as a direct-vent appliance, the unit requires 3″ or 4″ combustion air supply pipe. The intake pipe must be sealed airtight. Refer to pages 14 to 29 for more detail.
· Terminating the venting through a sidewall is recommended for the direct- vent system. · Running the exhaust vent and the intake pipe parallel is recommended. · Terminating the exhaust and intake on the same wall/surface is recommended. Terminating
in the same pressure zone allows for pressure balancing, which prevents nuisance shutdowns. · Only install the water heater in a heated area where below freezing temperatures cannot
occur. The warranty does not cover damage caused by freezing. · The water heater must be securely mounted to a wall or other suitable structure. · The venting system shall be installed in accordance with the water heater manufacturer’s and
venting system manufacturer’s instructions. 11. The Outdoor models must only be installed outdoors and only in an area with mild, temperate
climates. The Outdoor model shall be wall-mounted or mounted on a stand. Locate the Outdoor model in an open, unroofed area and maintain the following minimum clearances: There is a 3 in (76 mm) clearance from the left and right sides of the unit to combustible and non-combustible surfaces.
8 Page

Installation Manual Installation

· Installation and service must be performed by a qualified installer (for example, a licensed plumber or gas fitter). Otherwise, the warranty will be void.
· The installer (licensed professional) is responsible for the correct installation of the water heater and for compliance with all national, state/provincial, and local codes.
· The manufacturer does not recommend installing the water heater in a pit or location WARNING where gas and water can accumulate.
· Do not attach the gas line to the water heater until after the gas line system pressure test for leaks has been completed. See page 32 for additional information.
· Do not install or locate the vent terminal pointing toward any operating window, door, opening into a building or other area where people gather, where combustion gases could create a nuisance or hazard or cause property damage.
· Do not install the air intake next to any source of airborne debris, such as a clothes dryer, that can cause debris to be trapped inside the combustion chamber, unless the system is direct-vented.
· Do not install the unit where water, debris, or flammable vapors may get into the flue terminal or the air intake line.
· The manufacturer does not recommend installing the water heater in an attic due to safety issues. If you install the water heater in an attic: – Make sure the unit will have enough combustion air and proper ventilation. Failure to do so could lead to carbon monoxide poisoning or death. – Keep the area around the water heater clean. When dust collects on the flame sensor the water heater will shut down on an error code. – Place the unit where it will allow easy access for service and maintenance. – A drain pan, or other means of protection against water damage, is recommended to be installed under the water heater in case of leaks. See the NOTICE below.
· The water heater must be securely mounted to a wall or other suitable structure so that it is level (left-to-right & front-to-back) and plumb (vertically).
· Failure to observe these warnings could result in severe personal injury, death, and/or property damage.

NOTICE

· The warranty will not cover damage caused by water quality. – Only potable water can be used with this water heater. Do not introduce pool or spa water, or any chemically treated water into the water heater. – Water hardness levels must not exceed 7 grains per gallon (120 ppm) for single family domestic applications or more than 4 grains per gallon (70 ppm) for all other types of applications. Water hardness leads to scale formation and may affect/damage the water heater. Hard water scaling must be avoided or controlled by proper water treatment. – Water pH levels must be between 6.5 and 8.5. – Well water must be treated.
· The manufacturer recommends direct venting when the water heater is installed in beauty salons, dry cleaners or any other locations in which such chemicals are present in the air. Some chemicals used in beauty salons or dry cleaners may affect the flame sensor. In such cases, the water heater may not work properly.
· Although the water heater is designed to operate with minimal sound, the manufacturer does not recommend installing the unit on a wall adjacent to a bedroom, or a room that is intended for quiet study or meditation, etc.
· Locate your water heater close to a drain where water leakage will not do damage to surrounding areas. As with any water heating appliance, the potential for leakage at some time in the life of the product does exist. A drain pan, or other means of protection against water damage, is recommended to be installed under the water heater in case of leaks. In addition, you may install an active water leak detector with a shutoff valve which can turn off the water supply in the event of a leak. The manufacturer is not responsible for damage due to water leaks. If you install a drain pan under the unit, ensure that it will not restrict the combustion air flow.
9 Page

CLEARANCES

Installation Manual Installation
Top

WARNING

Maintain all clearances around the water heater. Failure to do so could create a fire hazard, potentially leading to death, serious injury, and/or property damage.

Side Front

Boom

Back Side

Model 540P Indoor*

Top

Bottom Front

Back

Sides

12 in

12 in

4 in** 0.5 in

3 in

(305 mm) (305 mm) (102 mm) (13 mm) (76 mm)

540P Outdoor

36 in

12 in

24 in

0.5 in

3 in

(914 mm) (305 mm) (610 mm) (13 mm) (76 mm)

*Standard indoor installations and direct-vent indoor installations have the same clearances. **24 inches (610 mm) recommended for maintenance.
INCLUDED ACCESSORIES

Check that these items below are included with the water heater.

Installation manual Temperature remote controller kit* Bird screen

and owner’s guide Outdoor model only

Indoor model only

Qty: 1 *Refer to pp. 10 and 38.

100276687 (TM-RE43)

OPTIONAL ITEMS

Model

Temperature remote controller

Pipe cover

3. Neutralizer kit

3″ PVC concentric termination

Recess box

6. Non-return valve

7

4″ PVC Adapter (for non-return valve)

540P Indoor

10 Page

Qty: 2 100282480
540P Outdoor

Installation Manual Installation

1. Temperature remote controller: 100276687 (TM-RE43) The temperature remote controller has the following features: · Adjusts set water temperature · Controls the pump operation · Works as a diagnostic tool · provides a concise error code whenever there is a
problem with the unit.
Refer to pages 50 to 59 for more information. See the Troubleshooting Section (pages 64 to 69) for information on possible error codes.

2. Pipe cover: 100112718 (TH-PC03)
The pipe cover protects the plumbing pipes to the water heater from unexpected adjustments. This pipe cover is fixed to the bottom of the water heater, which hides the plumbing and improves the visual aspects of the whole installation for the water heater.

3. Neutralizer kit: 100112159
The neutralizer assembly neutralizes the condensate (acidic water) that forms in the secondary heat exchanger of the water heater. It connects to the condensate drain port of the water heater by using connectors included with the neutralizer kit. (Refer to pages 39 and 40.)

4. 3″ PVC concentric termination: 100112163 Used when terminating direct-vent (sealed combustion) systems, with Indoor models that require a 3 intake and a 3 exhaust. This concentric termination provides the convenience of only having to make one penetration through a sidewall instead of two separate penetrations for the intake and exhaust piping. The termination includes a bird screen, restricting small animals, pests, and foreign objects from entering into the vent system.

5. Recess box: It allows for “clean” installations. The water heater fits inside the recess box, which hides and protects the whole water heater and plumbing. The recess box will fit between most wall studs.

Outdoor recess box for retrofit

applications -no flange

100298009

Outdoor recess box for new
construction applications 100306285 -with flange

6. Non-return valve for common venting : 100113130 7. 4″ PVC Adapter: 100113129

It is a required item for common venting system. It prevents the escape of combustion gas through non-operating appliances. (Refer to pages 30 and 31.)

This adapter transitions from the Non-return valve outlet to 4″ schedule 40 PVC pipe.

11 Page

Installation Manual Installation
WARNING FOR INSTALLATIONS

FOR YOUR SAFETY, READ BEFORE INSTALLATION:

Do not install the heater where water, debris or flammable vapors may get into the flue terminal. This may cause damage to the heater and void the warranty.

Do not have the vent terminal pointing toward any opening into a building. Do not locate your heater in a pit or location where gas and water can accumulate.

Prohibited

Prohibited

Ensure that you meet the minimum clearances shown below for a direct vent termination:

Ensure that you meet the minimum clearances shown below for Outdoor vent termination:

USA: 1 ft (30 cm) min. Canada: 3 ft (91 cm) min.

USA: 1 ft (30 cm) min. Canada: 3 ft (91 cm) min.

USA: 1 ft (30 cm) min. Canada: 3 ft (91 cm) min.

USA: 1 ft (30 cm) above grade and above ancipated snow level Canada: 1 ft (30 cm) above grade
Ancipated snow level

4 ft min.

4 ft min. 4 ft min.

Locate the outdoor water heater so it’s vent termi-
nal meets the following clearances. Locate the vent
terminal of an indoor heater to meet the following
clearances: 2 ft (61 cm) from an inside corner 2 ft (61 cm) from an outside corner 3 ft (91 cm) below a soffit/overhang

Do not install next to a dryer or any source of airborne debris that can be trapped inside the combustion chamber, unless the system is direct-vented.

Outside corner
2 ft (61 cm)

3 ft (91 cm)

Inside corner

2 ft (61 cm)

12 Page

Installation Manual Installation

HIGH-ALTITUDE INSTALLATIONS

WARNING

· To adjust high altitude settings, adjust only the No. 2, No. 3, and No. 4 DIP switches in the MIDDLE bank of DIP switches. (See below.) DO NOT adjust the other DIP switches.
· Turn off the power supply to the water heater before changing the DIP switch settings.
· Failure to observe these warnings could lead to carbon monoxide poisoning or death.

Check the elevation where your water heater is installed. Set DIP switches shown in the table below depending on the altitude.
Indoor model

Altitude DIP switches

0 to 2,000 ft 2,001 to

3,001 to

5,001 to

7,501 to

(0 to 610 m) 3,000 ft

5,000 ft

7,500 ft

10,100 ft

(DEFAULT) (611 to 914 m) (915 to 1,524 m) (1,525to2,286m) (2,287to3,078m)

ON 1234 56
ON 1234 56
ON 1234 56
ON 1234 56
ON 1234 56

Middle bank of DIP switches

No. 2 : OFF No. 3 : OFF No. 4 : OFF

No. 2 : OFF No. 3 : ON No. 4 : OFF

No. 2 : OFF No. 3 : OFF No. 4 : ON

No. 2 : OFF No. 3 : ON No. 4 : ON

No. 2 : ON No. 3 : ON No. 4 : ON

Outdoor model
Altitude DIP switches
Middle bank of DIP switches

ON 1234 56
ON 1234 56
ON 1234 56

0 to 2,000 ft (0 to 610 m)
(DEFAULT)
No. 2 : OFF No. 3 : OFF No. 4 : OFF

2,001 to

4,001 to

4,000 ft

6,000 ft

(611 to 1,219 m) (1,220to1,829m)

No. 2 : OFF No. 3 : OFF No. 4 : ON

No. 2 : ON No. 3 : OFF No. 4 : ON

Installation altitude
The maximum certified or allowable installed altitude is 10,100 ft (3,078 m) for indoor model and 6,000 ft (1,829 m) for outdoor model.

NOTE: The dark squares indicate the correct DIP switch positions.

Upper bank of DIP switches Middle bank of DIP switches
Lower bank of DIP switches

13 Page

Installation Manual Installation
VENTING INSTRUCTIONS FOR INDOOR
· Improper venting of this appliance can result in excessive levels of carbon monoxide which can result in severe personal injury or death.
· Improper installation can cause nausea or asphyxiation, severe injury or death from carbon monoxide and flue gases poisoning. Improper installation will void product
WARNING warranty. · When installing the vent system, all applicable national and local codes must be followed. If you install thimbles, fire stops or other protective devices and they penetrate any combustible or noncombustible construction, be sure to follow all applicable national and local codes.
The Indoor model must be vented in accordance with the section “Venting of Equipment” of the current edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the United States and/or Section 8 of the B149.1 Natural Gas and Propane Installation Code in Canada, as well as applicable local building codes. The use of venting materials approved for Category III/IV appliances is recommended whenever possible. However, the Indoor model may also be vented with plastic pipe materials such as ABS, PVC (solid core), CPVC (solid core), or polypropylene. For details, please refer to the Exhaust Vent (ABS, PVC, CPVC, or Polypropylene Vent) Section on page 22. Vent installations in Canada which utilize plastic vent systems must use venting that complies with ULC S636.
General rules for venting water heaters: · Place the water heater as close as possible to the vent termination. · The vent collar of the water heater must be fastened directly to an unobstructed vent pipe. · Do not weld the vent pipe to the water heater’s vent collar. · Do not cut or alter the vent collar of the unit. · The vent must be easily removable from the top of the water heater for normal service and inspection of the unit. · The water heater vent must not be connected to any other gas appliance or vent stack except an approved common-venting system. Refer to pages 30 and 31. · Avoid using an oversized vent pipe or using extremely long runs of the pipe unless it is part of an approved common vent system. · Air supply pipe can be made of ABS, PVC (solid core), CPVC (solid core), polypropylene, corrugated stainless steel, or Category lll/IV stainless steel. Regarding exhaust pipe, refer to pages 22 to 29. · Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenylsulfone) in nonmetallic venting systems is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. · Sidewall venting is recommended for the Indoor model. Vertical venting (roof termination) is acceptable. · Slope horizontal venting sections 1/4″ upwards for every 12″ (300 mm) toward the termination or according to local and state codes, or in the absence of local or state codes, the current edition of the National Fuel Gas Code, ANSI Z223.1 (NFPA 54). · The manufacturer recommends running the exhaust vent and the intake pipe as parallel as possible. · For rooftop venting, a rain cap or other form of termination that prevents rain water from entering into the water heater must be installed. · Do not terminate vent into a chimney. If the vent must go through the chimney, the vent must run all the way through the chimney with approved vent pipe. · The water heater shall not be connected to a chimney flue serving a separate appliance, designed to burn solid fuel. · When an existing Category I appliance is removed or replaced, the original venting system may no longer be sized to properly vent the attached water heater. An improperly sized venting system may cause formation of condensate, leakage, and spillage and so on.
General rules for vent terminations: · Avoid locating the water heater vent termination near any air intake devices. These fans can pick up the exhaust flue products from the water heater and return them to the building. This can create a health hazard. · Locate the vent termination so that it cannot be blocked by any debris, at any time. Most codes require that the termination be at least 12 in (305 mm) above grade and anticipated snow level, but the installer may determine if it should be higher depending on the job site condition and applicable codes. · A proper sidewall termination is recommended when the water heater is vented through a sidewall. · Regarding the clearances from the exhaust termination to the air inlet or opening, refer to pages 12, 15 and 16.
14 Page

D E

-Vent termination clearances-

Installation Manual Installation

Inside corner detail
G
V
A

Legend: V = Vent terminal X = Air supply inlet = Area where terminal is not permied
H

L

B

C

V

Fixed closed

Operable

FV

B

B

B Fixed

V

V Operable closed

B X

V

B A

J

I

15

M

X

V

K

Regulator vent outlet In the event no regulator is present, H and I can be disregarded

Canada Installations1

Direct vent and other than direct vent

A Clearance above grade, veranda, porch, deck, or balcony

1 ft (30 cm)

Direct vent

US Installations2 Other than direct vent 1 ft (30 cm)

B Clearance to window or door that may be opened

3 ft (91 cm)

1 ft (30 cm)

4 ft (1.2 m) below or to side of opening;
1 ft (30 cm) above opening

C Clearance to permanently closed window

0

0

0

Vertical clearance to ventilated soffit located above D the terminal within a horizontal distance of 2 ft (61
cm) from the center line of the terminal

3 ft (91 cm)

3 ft (91 cm)

3 ft (91 cm)

E Clearance to unventilated soffit

3 ft (91 cm)

3 ft (91 cm)

3 ft (91 cm)

F Clearance to outside corner

2 ft (61 cm)

2 ft (61 cm)

2 ft (61 cm)

G Clearance to inside corner

2 ft (61 cm)

2 ft (61 cm)

2 ft (61 cm)

H

Clearance to each side of center line extended above meter/regulator assembly

3 ft (91 cm) within a height of 15ft(4.6m)

I Clearance to service regulator vent outlet

3 ft (91 cm)

Clearance to non-mechanical air supply inlet to J a building or the combustion air inlet to any other
appliance.
K Clearance to mechanical air supply inlet

3 ft (91 cm) 6 ft (183 cm)

1 ft (30 cm)

4 ft (1.2 m) below or to side of opening;
1 ft (30 cm) above opening

3 ft (91 cm) above if within 10 ft (3 m) horizontally.

L

Clearance above paved sidewalk or paved driveway located on public property

7 ft (213 cm)**

7 ft (213 cm)

7 ft (213 cm)

M Clearance under veranda, porch deck, or balcony

1 ft (30 cm)***

1 ft (30 cm)***

1 ft (30 cm)***

*Clearance in accordance with local installation codes and the requirements of the gas supplier.

**A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves

both dwellings.

***Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

The vent for condensing water heaters shall not terminate:

· over public walkways; or

· near soffit vents or crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or cause property damage; or

· where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other

equipment.

Notes:

  1. In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

  2. In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

  3. If locally adopted installation codes specify clearances different than those illustrated, then the most stringent clearance shall prevail.

  4. Blocking air supply and exhaust vent by snow may cause incomplete combustion and an appliance failure. Install the termination by

providing sufficient clearance from anticipated snow line in accordance with local code or manufacture’s instructions and make sure

there in no blockage.

  1. Provide an appropriate clearance between a vent termination and a building to prevent degradation to building materials caused by

flue gases.

  1. Water heaters installed outdoors follow the Other Than Direct Vent clearances.

15 Page

Installation Manual Installation
-Clearances for sidewall terminations-

Improper installation can result in carbon monoxide poisoning or death. Follow all local
and national codes in regards to proper termination clearances. In the absence of such
codes, the clearances below can be used as guidelines. Local codes supersede these WARNING guidelines.

(30m15ifmnt.m) (61m02imfnt.m)

TerEmxAhinnaauttisictoinpat(e30dm51Simfntn.mo)w

level cInosrindeer

Multiple Sidewall Terminations An exhaust termination must be at least 1 ft (305 mm) away from another exhaust termination. An exhaust termination must also be at least 2 ft (610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall.)

2 ft (610 mm) min.

Exhaust termination

Combined intake and exhaust termination

2 ft

1 ft (305 mm)

(610 mm) min.

min.

1 ft

(305 mm)

min. Anticipated Snow

level Inside

corner

Multiple DV Sidewall Terminations
A direct vent (DV) termination must be at least 1 ft (305 mm) away from other direct vent terminations. A direct vent termination must also be at least 2 ft (610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall.)

<Case 1> Exhaust

For direct vent sidewall terminations that use two separate penetrations for the intake and exhaust, keep the termination clearances shown in the diagrams on the right.

Intake
1 ft (305 mm) min.

Exhaust Intake
0.5 ft (159 mm) min.

Exhaust and/or direct vent sidewall terminations should be at least 2 ft (610 mm) away from an opposite surface/wall. Do not place the termination directly in front of an opening into a building.
0.5 ft (159 mm)
min.

<Case 2> Exhaust
1 ft (305 mm) min. Intake

Exhaust Intake
0.5 ft (159 mm) min.

16 Page

Installation Manual Installation
-Clearances for rooftop terminations-

Follow all local and national codes in regards to proper termination clearances. In the absence of such codes, the clearances below must be met. Local codes supersede these WARNING clearances. Failure to observe this warning may result in severe personal injury or death.

NOTICE

Canadian requirements differ from the guidelines in this section. In Canada, follow the requirements of B149.1 (Natural Gas and Propane Installation Code, current edition) as well as local and provincial codes. Contact your local code enforcement agency for direction.

Angled roof termination

2 ft (610 mm) min.
Exhaust

1 ft (305 mm)
min.

Intake

1 ft (305 mm)
min.

1 ft (305 mm)
min.

Flat roof termination

Intake

3 ft (914 mm) min.

Exhaust

1 ft (305 mm)
min.

1 ft (305 mm)
min.

Anticipated snow level

Anticipated snow level

Multiple angled roof terminations

Multiple flat roof terminations

1 ft (305 mm)
min.
1 ft (305 mm)
min.
Anticipated snow level

Exhaust
3 ft (914 mm)
min.

1 ft (305 mm)

Exhaust

min.

1 ft (305 mm)
min.

2 ft (610 mm)
min.

Exhaust

Exhaust

Intake
1 ft (305 mm)
min.

Intake

2 ft (610 mm)
min.

1 ft (305 mm)
min.

1 ft (305 mm)
min.

3 ft (914 mm)
min.

Intake

Ancipated snow level

Intake

· ·
WARNING · ·

Exhaust terminations must be at least 1 ft (305 mm) away from any obstructions. Minimum spacing between multiple terminals:
· intake terminals: 1 ft (305 mm) spacing between each · exhaust terminals: 1 ft (305 mm) spacing between each The exhaust termination must be a horizontal distance of at least 2 ft (610 mm) from a wall or surface unless specified differently by local code. Failure to observe this warning may result in severe personal injury or death.

17 Page

-Combustion air supply-

Installation Manual Installation

WARNING

This gas water heater requires an adequate source of clean air for combustion and ventilation. Without sufficient air, your water heater may not operate properly and may emit excessive and abnormal amounts of carbon monoxide which may result in carbon monoxide poisoning or death.

· The guidelines in this section apply to installations within the United States. All

NOTICE

U.S. installations must conform to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (current edition) and local codes.

· Canadian requirements differ from the guidelines in this section. In Canada, follow the requirements of B149.1 (Natural Gas and Propane Installation Code, current edition) as well as local and provincial codes. Contact your local code enforcement agency for direction.

Before installing the water heater, you must determine the amount of air needed to supply this water heater and any other gas appliances in the same area and provide adequate air for combuson and venlaon. Consult a qualified person if you’re unsure of the proper way to supply air to your water heater.
Check for Chemicals: Air for combuson and venlaon must be clean and free of corrosive chemicals. If corrosive chemicals, such as sulfur, fluorine, or chlorine are present, the water heater must be direct vented. Failure due to these corrosive chemicals is not covered by the warranty.
WARNING! In all cases, ensure that corrosive chemicals are not present at the air intake. Presence of such chemicals at the air intake could result in death, personal injury, or property damage. Examples of locaons that require outside air due to chemicals include:
· Beauty salons
· Photo processing labs
· Indoor pools · Laundry, hobby, or craft rooms · Chemical storage areas
· Restaurants
Products such as aerosol sprays, detergents, bleaches, cleaning solvents, gasoline, air fresheners, paint and varnish removers, and refrigerants should not be stored or used near the water heater.
Does your installation space have sufficient combustion air?
Venlaon with outside air is recommended for all installaons. Even if the water heater is installed in a large, open room inside the house, outdoor air is usually needed because modern homes are very ghtly sealed and often do not supply enough air to the water heater. However, when installed in a large indoor space, it may be possible to provide enough air without outside venlaon. If you are unsure if your installaon locaon has enough venlaon, contact your local gas ulity company or code officials for a safety inspecon or direct vent the water heater. The following instrucons will help determine if it may be possible to install the water heater without outside venlaon.
Calculate total BTU/h rang of all appliances. To calculate the combuson air and venlaon required, add up the total BTU/h rangs of all gas burning appliances (e.g., water heaters, furnaces, clothes dryers) in the same area. Do not include appliances that are direct vented. Refer to the following example.
18 Page

Installation Manual Installation

Your water heater’s BTU/h rating is on the rating plate. The BTU/h ratings should be on the other appliances’ rating plates. If you have trouble determining the BTU/h ratings, contact the manufacturer or have a qualified person determine the ventilation requirements.
NOTICE: If you are replacing your old water heater with one that has a higher BTU/h rang, the amount of venlaon required may be greater.

Example:

Gas Burning Appliance
Gas Water Heater Furnace Dryer

BTU/h Rang
199,000 75,000 20,000

Your appliances:

Gas Burning Appliance Gas Water Heater

BTU/h Rang

Total

294,000

Total

Calculate the air volume of the room Air requirements depend on the size of the room.
Room Volume (ft3) = Floor Area (ft2) X Ceiling Height (ft) If there are large objects in the room (e.g., refrigerator, furnace, car), subtract their volume from the volume of the room to get a beer esmate of the air available.
Air Volume = Room Volume – Object Volume
NOTE: Adjoining rooms with permanently opened doorways can be counted as part of the calculaon.
Calculate required air volume
A water heater installed in an unconfined attic, garage, or space requires that the space be at least 50 ft3 (1.42 m3) per 1,000 BTU/h of the total input for all gas burning appliances in the same area.
Required Air Volume (ft3) =Total Appliance Energy Rang (btu/h) X 50 ft3 / 1000 (btu/h) Example:
(294,000 / 1000) x 50 = 14,700 ft3
If the air volume of the room is less than the required air volume, you must direct vent the water heater or provide permanent outside air openings that draw in sufficient air. Go to “Install with outside venlaon” if you want to provide combuson air with outside venlaon.
If the air volume of the room is greater than the required air volume, it may be possible to install the water heater without outside venlaon. However, be sure to consider the effects of exhaust fans. Exhaust fans can affect the amount of combuson air that is available in your home. Appliances such as furnaces, whole house fans, and clothes dryers draw air out of your home. If they draw air out faster than it can be replaced, your water heater may not have enough oxygen to fire properly. Back-drafting may also result, which is when negave air pressure pulls air backwards through chimneys or appliance vents. These events can cause unsasfactory water heater performance. The best soluon is to direct vent the water heater or install an adequate number of make-up air vents. (See “Install with outside venlaon”.) For more informaon, consult a qualified technician or your local gas ulity.
Install with outside ventilation
Venlaon with outside air is recommended, and, for most installaons, is needed. There may be exisng venlaon that is adequate, or you may need to add more venlaon.
Supplying outside air to the water heater typically requires two openings. One opening must be within 12 in (305 mm) from the floor and the second opening must be within 12 in (305 mm) from the ceiling. Although a single opening is not preferred, you may use a single opening to outside air if the minimum free area is sized according to Table 1. Two openings must be used when venlang with air from another room. The outside air can be taken from a crawl space or attic open to the outdoors and adequately venlated. You may use vercal or horizontal ducts.
19 Page

Installation Manual Installation

Determine type of ventilation
There are several types of venlaon that can be used. The various opons are listed below. See also the illustraons on the next page.
1. Direct to outdoors
2. Vercal ducts 3. Horizontal ducts
4. Single opening (not recommended; must be at least 100 in2 (645 cm2) . Not appropriate for confined spaces smaller than 50 ft3 (1.42 m3) per 1,000 BTU/h or when getting air from another room.)
5. From a larger room inside the house (not recommended ­ refer to “Calculate the air volume of the room”
above to determine if the combined volume of the rooms may be adequate).
Determine minimum free area required for each vent opening
The size of the vent openings depends on the total BTU/h rang of all appliances in the space (use your calculaon from “Before beginning”) and the type of vent used. Table 1 provides the minimum free area for each vent opening depending on the type of venlaon.
Calculate minimum size of vent openings and ducts
The vent cross-seconal area needed to provide the free area depends on the covering on the vent openings. Typical vents use louvers or grilles to protect the opening. The louver or grill itself blocks some of the free area, so the opening may need to be larger to meet the minimum free area requirements. Use the following formula to calculate the required cross-seconal area:
Cross-seconal area = minimum free area required ÷ percent free area of covering (in decimals ­ e.g., 60 % = 0.6) For example, an installaon area that requires openings with 100 in2 (645 cm2) of free area would need 134 in2 (865 cm2) openings if using metal louvers rated at 75% free area (100 in2 ÷ 0.75 = 134 in2). If you do not know the % free area for your louver or grill, use the following values:
· For wood louvers or grilles: 25% · For metal louvers or grilles: 75% Follow these rules to ensure that vents and ducts provide adequate air flow: · Each vent opening must be no smaller than 100 in2 (645 cm2). · Ducts must have the same cross-seconal area as free area of the opening. · Rectangular ducts must have a minimum dimension of no less than 3 in (76 mm). · All screens must have mesh ¼” or larger. · Moveable louvers must be locked open or interconnected with the equipment so that they open automa-
cally during operaon. · Keep louvers and grills clean and free of debris or other obstrucons.
Check that air source is clean and free of chemicals
Air for combuson and venlaon must be clean and free of corrosive or flammable chemicals. A failure due to corrosive chemicals in the air is not covered by the warranty. Combuson air must be free of acid-forming chemicals such as sulfur, fluorine, and chlorine. Be sure that air at the vent inlets is free of such chemicals.

Table 1

Minimum Free Area of Permanent Openings for Venlaon and Combuson Air Supply ­ Air from outdoor or

indoor spaces.

Based on the total BTU/h input rang for all gas burning appliances within a confined space.

Opening Source

Minimum Free Area

Direct to outdoors*

1 in2 (6.5 cm2) per 4,000 BTU/hr (see Figure 1, 2)

Vercal ducts

1 in2 (6.5 cm2) per 4,000 BTU/hr (see Figure 3)

Horizontal ducts

1 in2 (6.5 cm2) per 2,000 BTU/hr (see Figure 4)

Single Opening

1 in2 (6.5 cm2) per 3,000 BTU/hr (see Figure 5)

Two permanent openings

1 in2 (6.5 cm2) per 1,000 Btu/hr (see Figure 6)

to another room**

Opening: 100 in2 (645 cm2) Min

Minimum dimension of air openings:

no less than 3 in (76 mm)

*These openings connect directly with the outdoors through a venlated attic, a venlated crawl space, or through

an outside wall.

**United States: For direcon on combining spaces in different stories within the structure, refer to the current edi-

on of the Naonal Fuel Gas Code ANSI Z223.1/NFPA 54. In Canada, contact your local code enforcement agency for

direcon.

See graphics on next page.

20 Page

Combuson air supply opons

Confined Space

Gable vent to outdoors
Install above insulation
Outlet air to attic 1 in2 (6.5 cm2) per 4,000 btu/h

Alternate Air Inlet

Inlet air from the crawl space

1 in2 (6.5 cm2) per 4,000 btu/h

Open foundation vent

Figure 1 – Direct to outdoors openings

Confined Space

Gable vent to outdoors Install above insulation

12″ (305 mm) maximum

Outlet air to attic 1 in2(6.5 cm2) per 4,000 btu/h Inlet air duct 1 in2 (6.5 cm2) per 4,000 btu/h

Figure 3 – Vercal duct openings

Installation Manual Installation

12″ (305 mm) maximum

Two permanent Openings
1 in2 (6.5 cm2) per 4,000 btu/h

Confined Space 12″ (305 mm) maximum

Figure 2 – Direct to outdoors openings Two permanent openings

Confined Space

1 in2 (6.5 cm2) per 2,000 btu/h
Outlet Outdoor Air Ducts
Inlet

1 in2 (6.5 cm2) per 2,000 btu/h
Figure 4 – Horizontal duct openings

CSpoancfiened

Alternative Opening Location
1 in2 (6.5 cm2) per 3,000 btu/h

12″ (305 mm) maximum
Confined Space

Two permanent Openings

1 in2 (6.5 cm2) per 1,000 btu/h

12″ (305 mm) maximum

Figure 5 – Single opening

Figure 6 – Two permanent openings
21 Page

Installation Manual Installation

-Exhaust vent (ABS, PVC, CPVC, or polypropylene vent)-

The Indoor model can be vented with ABS, PVC, CPVC, or polypropylene (temperature rated up to 149 °F). Vent material certified to ULC S636 standards is recommended in the USA. In Canada, plastic venting must be certified to ULC S636 standards.

Item

Material

Schedule 40 PVC

Exhaust pipe and Fittings

PVC-DWV Schedule 40 CPVC Schedule 40 ABS-DWV

Polypropylene

PVC

Pipe Cement/Primer

CPVC

United States ANSI/ASTM D1785 ANSI/ASTM D2665 ANSI/ASTM F441 ANSI/ASTM D2661
UL-1738 ANSI/ASTM D2564 ANSI/ASTM F493

Canada
ULC S636 Certified Materials Only

ABS

ANSI/ASTM D2235

Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenylsulfone) in non-metallic venting systems is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited.

· The maximum length of exhaust vent piping must not exceed 70 ft (21.3 m) for 3″ (76 mm) venting, which depends on the elevation where the water heater is installed, and 100 ft (30.5 m) for 4″ (102 mm) venting (deducting 5 ft (1.5 m) for each elbow used in the venting system). Do not use more than 5 elbows. See the table below.
· When the horizontal vent run exceeds 5 ft (1.5 m), support the vent run at 3 ft (0.9 m) intervals with overhead hangers.

Diameter Max. No. of Elbows Max. Vertical and Horizontal (Total) Vent Length*

3 in

5

70 ft (21.3 m)

4 in

5

100 ft (30.5 m)

*For each elbow added, deduct 5 ft (1.5 m) from max. vent length.

Max. Vertical or Horizontal (Total) Vent Length

No. of Elbows*

0 to 3,000 ft (0 to 914 m)

3″ venting
3,001 to 6,000 ft 6,001 to 10,100 ft (915 to 1,829 m) (1,830 to 3,078 m)

0

70 ft (21.3 m) 40 ft (12.2 m) 25 ft (7.6 m)

1

65 ft (19.8 m) 35 ft (10.7 m) 20 ft (6.1 m)

2

60 ft (18.3 m) 30 ft (9.1 m)

15 ft (4.6 m)

3

55 ft (16.8 m) 25 ft (7.6 m)

10 ft (3.0 m)

4

50 ft (15.2 m) 20 ft (6.1 m)

N/A

5

45 ft (13.7 m)

N/A

N/A

Excludes vent terminators, termination elbows, or rain caps.

4″ venting
0 to 10,100 ft (0 to 3,078 m) 100 ft (30.5 m) 95 ft (29.0 m) 90 ft (27.4 m) 85 ft (25.9 m) 80 ft (24.4 m) 75 ft (22.9 m)

For details on the vent connection, refer to pages 24 to 25. *For each elbow added, deduct 5 ft (1.5 m) from max. vent length.

22 Page

Installation Manual Installation

-DIP switch settings for vent length-
Typical installaons using PVC, CPVC, ABS, or polypropylene vent

·
· WARNING
·

To adjust vent length, adjust only the No. 3 and No. 4 DIP switches in the LOWER bank of DIP switches. (See below.) DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.

<Two-pipe, direct-vent installaon>

Horizontal Installaon

Vercal Installaon

Wall Hanger
Hanger

Roof Roof
flashing

Fire stop
Connect between exhaust vent collar and piping. See the instrucons on the next page.
For details on the vent components, refer to the vent manufacturer’s instructions.

Set DIP switches shown in the table below depending on the vent diameter and length.

DIP switch settings : Two-pipe, Direct vent installations

Vent diameter

3″ venting*

4″ venting

Vent 5 to 20 ft

5 to 50 ft

DIP

length

(1.5 to 6.1 m)

21 to 40 ft (6.2 to 12.2 m)

41 to 70 ft (12.3 to 21.3 m)

(1.5 to 15.2 m)

51 to 100 ft (15.3 to 30.5 m)

switches

(DEFAULT)

(DEFAULT)

Lower bank of DIP switches

ON 1234 5678
ON 1234 5678
ON 1234 5678
ON 1234 5678
ON 1234 5678

Lower bank of
DIP switches
No. 3 : O N No. 4 : OFF

No. 3 : OFF No. 4 : OFF

No. 3 : O N No. 4 : O N

No. 3 : O N No. 4 : OFF

No. 3 : OFF No. 4 : OFF

*PVC concentric termination (100112163) installation is applied to the DIP switch settings of 3″ venting. (Refer to page 11.)
23 Page

Installation Manual Installation
<How to install intake and exhaust venting (two-pipe, direct-vent) with the indoor model> 3″ vent connecon for PVC/CPVC venng only 4″ vent connecon for PVC/CPVC venng only

3″ straight pipe

3″ straight pipe

Intake vent collar with 3″ adapter* (Female)

Exhaust vent collar with 3″ adapter* (Female)

4″straight pipe

4″ straight pipe 3″ x 4″ increaser

· PVC adapter will accept 3″ straight pipe.
3″ vent connecon for other venng without 3″ PVC adapter

3″ x 4″ increaser
3″straight pipe no more than 12″ (305 mm)
Intake vent collar with

3″ straight pipe no more than 12″ (305 mm)
Exhaust vent collar with 3″ adapter* (Female)

3″ adapter* (Female)

3″ adapter*

3″ adapter*

Intake vent collar

(Female)

Exhaust vent collar

Screws

(Female)

1. Insert no more than 12″ (305 mm) of 3″ straight

pipe into the exhaust/intake vent collar with 3″

1. Remove each screw from 3″ adapter to detach the

adapter.

adapters from each vent collar.

2. Connect 3″ x 4″ increasers to straight pipes.

3. Connect 4″ straight pipes to the increasers.

3″ straight pipe

3″ straight pipe

Intake vent collar (Female)

Exhaust vent collar (Female)

NOTICE *3″ PVC adapters are not

2. Connect 3″ straight pipes directly on the exhaust and intake vent collar of the water heater.

approved for use in Canada.

Horizontal Installaon
Wall Hanger

Vercal Installaon
Roof Roof
flashing

Elbow

Elbow

Fire stop

Connect between exhaust vent collar and piping. See the instrucons on the next page.
For details on the vent components, refer to the vent manufacturer’s instructions.

·
· WARNING
·

Adjust only the No. 3 and No. 4 DIP switches in the LOWER bank of DIP switches for vent length. (Refer to the following page.) DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.

24 Page

Set DIP switches shown in the table below depending on the vent diameter and length.

DIP switch settings: Single vent pipe installations

Vent diameter

3″ venting

4″ venting

Vent 5 to 45 ft

5 to 50 ft

DIP

length

(1.5 to

13.7

m)

46 to 70 ft (13.8 to 21.3 m)

(1.5

to 15.2 m)

51 to 100 ft (15.3 to 30.5 m)

switches

(DEFAULT)

(DEFAULT)

Installation Manual Installation
Lower bank of DIP switches

ON 1234 5678
ON 1234 5678
ON 1234 5678
ON 1234 5678

Lower bank of
DIP switches
No. 3 : O N No. 4 : OFF

No. 3 : OFF No. 4 : OFF

No. 3 : O N No. 4 : OFF

No. 3 : OFF No. 4 : OFF

3″ vent connecon for PVC/CPVC venng only

3″ street elbow with bird screen

3″ straight pipe

Intake vent collar with 3″ adapter* (Female)

Exhaust vent collar with 3″ adapter* (Female)

1. Connect spigot end of 3″ street elbow into the intake vent collar with 3″ adapter. Be sure to insert bird screen into the hub side.
2. Connect 3″ straight pipe into the exhaust vent collar with 3″ adapter.
3″ vent connecon for other venng -without 3″ PVC adapter

3″ adapter*

Intake vent collar with 3″ adapter* (Female)

Screw

Exhaust vent collar (Female)

1. Remove the screw from the 3″ adapter on the

exhaust vent collar, then remove the adapter.

4″ vent connecon for PVC/CPVC venng only
4″ straight pipe

3″ x 4″ increaser

3″ street elbow with bird screen

3″ straight pipe no more than 12″ (305 mm)

Intake vent collar with 3″ adapter* (Female)

Exhaust vent collar with 3″ adapter* (Female)

1. Insert no more than 12″ (305 mm) of 3″

straight pipe into the exhaust vent collar with

3″ adapter.

2. Connect a 3″ x 4″ increaser into the 3″ straight

pipe.

3. Connect 4″ straight pipe into the increaser.

4. Connect spigot end of 3″ street elbow into the

intake vent collar with 3″ adapter. Be sure to

insert bird screen into the hub side.

3″ street elbow with bird screen

3″ straight pipe or Appliance adapter

Intake vent collar with 3″ adapter* (Female)

Exhaust vent collar (Female)

2. Connect spigot end of 3″ street elbow into the

intake vent collar with 3″ adapter. Be sure to insert

bird screen into the hub side.

3. Connect 3″ straight pipe or appliance adapter to the

exhaust vent collar.

NOTICE *3″ PVC adapters are not approved for use in Canada.

25 Page

Installation Manual Installation
<How to remove 3″ PVC adapter from the intake/exhaust collar>

Remove the 3″ adapter when using vent material other than PVC or CPVC.

3″ adapter*
Intake vent collar (Female)
Screws

3″ adapter*
Exhaust vent collar (Female)

1. Remove each screw from 3″ adapter to detach the adapters from each vent collar.

NOTICE *3″ PVC adapters are not approved for use in Canada.

POLYPROPYLENE VENTING
WARNING! Do not mix parts or fittings of different material types, and do not mix pipe, fittings, or joining methods from different manufacturers. Combustion exhaust can contain carbon monoxide and must be properly vented outside. Breathing abnormal amounts of carbon monoxide can result in serious injury or death.

Centrotherm Innoflue polypropylene venting is approved for use with these water heaters. Follow the instructions in this manual and in the vent manufacturer’s instructions when installing vent pipe.

Description
4”/6” x 39″ (990 mm) Concentric Wall 101 mm to 3″ Adapter

Centrotherm Part No. (Trade Name
InnoFlue)
ICWS4639

Description
3”/5” x 13” (330 mm) Concentric Wall Termination SS

Centrotherm Part No. (Trade Name
InnoFlue)
ICWS3513

ISA010103 3” Twin Pipe to 3”/5” Concentric Adapter ICTC0335

101 mm to 4″ Adapter

ISA010104

26 Page

Installation Manual Installation

-Exhaust vent (Stainless steel vent)-

This is a Category IV appliance and must be vented accordingly. The vent system must be sealed airtight. All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed aluminum adhesive tape having a minimum temperature rating of 160 °F (71 °C). For best results, a vent system should be as short and straight as possible.

· The Indoor model is a Category IV appliance and must be vented accordingly with any 4″ (106 mm) vent approved for use with Category III/IV or Special BH type gas vent.
· The manufacturer recommends the NovaVent® or Z-Vent® venting manufactured by Z-Flex® U.S. and are listed to UL 1738.
· Follow the vent pipe manufacturer’s instructions when installing the vent pipe. · The maximum length of exhaust vent piping must not exceed 100 ft (30.5 m) (deducting 5 ft (1.5
m) for each elbow used in the venting system). Do not use more than 5 elbows. · When the horizontal vent run exceeds 5 ft (1.5 m), support the vent run at 3 ft (0.9 m) intervals
with overhead hangers.

Diameter Max. No. of Elbows Max. Vertical and Horizontal (Total) Vent Length*

4 in

5

100 ft (30.5 m)

*For each elbow added, deduct 5 ft (1.5 m) from max. vent length.

No. of Elbows

Max. Vertical or Horizontal Vent Length

0

100 ft (30.5 m)

1

95 ft (29.0 m)

2

90 ft (27.4 m)

3

85 ft (25.9 m)

4

80 ft (24.4 m)

5

75 ft (22.9 m)

Excludes vent terminators, termination elbows, or rain caps.

-DIP switch settings for vent length-
Typical installaons using stainless steel vents

Horizontal Installaon

Vercal Installaon

Wall Hanger
Hanger

Roof

Rain cap

Roof flashing

Fire stop Sidewall vent terminaon
For details on the vent components, refer to the vent manufacturer’s instructions.
27 Page

Installation Manual Installation

·
· WARNING
·

Adjust only the No. 3 and No. 4 DIP switches in the LOWER bank of DIP switches for vent length. (See below.) DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.

Set DIP switches shown in the table below depending on the vent diameter and length.

DIP switch settings : Single pipe and Direct vent installations

Lower bank of DIP switches

Vent diameter

4″ venting

Vent length DIP switches

5 to 50 ft (1.5 to 15.2 m)
(DEFAULT)

51 to 100 ft (15.3 to 30.5 m)

ON 1234 5678
ON 1234 5678

Lower bank of
DIP switches

No. 3 : O N No. 4 : OFF

No. 3 : OFF No. 4 : OFF

3″ adapter*

*USA indoor models only: Before installation, remove the

screws from the 3″ adapters and remove the adapters from Intake vent collar

each vent collar.

(Female)

Screw

3″ adapter*
Exhaust vent collar (Female)

4″ vent connecon for direct-vent installaon

4″ stainless steel vent straight pipe or appliance adapter
Intake vent collar (Female)

4″ stainless steel vent straight pipe or appliance adapter
Exhaust vent collar of the Indoor models (Female)

4″ vent connecon for single vent installaon

4″ stainless steel

4″ elbow with bird screen

vent straight pipe or appliance adapter

Intake vent collar (Female)

Exhaust vent collar of the Indoor models (Female)

· Connect 4″ stainless steel vent straight pipes to the exhaust/intake vent collar.

1. Connect a 4″ stainless steel vent straight pipes to the exhaust vent collar.
2. Connect a 4″ elbow to the intake vent collar.

· Regarding the clearances from the exhaust terminal to the air inlet or opening, refer to pages 12, 15, and 16.
· Follow all vent system manufacturer’s instructions and all local codes. · Use 4″ Category III/IV approved or Special BH, single or double wall stainless steel vent WARNING pipe, listed to UL 1738. · Do not mix parts or fittings of different material types, and do not mix pipe, fittings,
or joining methods from different manufacturers. Combustion exhaust can contain carbon monoxide and must be properly vented outside. Breathing abnormal amounts of carbon monoxide can result in serious injury or death.
28 Page

Installation Manual Installation

Approved Category IV, Single Wall, Venting Suppliers and Part Numbers

Description

Heater Vent

Z-FLEX®

Kits

Nova VENT®

Z-VENT®

4″ Adjustable straight pipe – 10″-18″ (254 – 457 mm) adjustability 100112405 2NVAL4

2SVSPA04

4″ Sidewall termination (4″ Termination Hood)

100112419 2NVTH4

2SVSHTX04

4″ Vent termination tee

100112547 2NVTT4

2SVSTTF04

4″ Rain Cap

100112415 2NVRC4

2SVSRCF04

4″ Extreme weather rain cap
4″ 3-in-1 adapter (F-F adaptor, condensate drain, & back-flow preventer)
4″ F-F adapter

100112548 2NVWC4 2SVSHRC04 100112549 2NVBFA4 2SVBFDPA04 100112399 2NVAFF4 2SVEEWCF0445

4″ Backflow preventer w/ F-F adapter
4″ exhaust/3″ intake DV concentric termination – 5″-10″ (127 – 254 mm) adjustability
4″ exhaust/3″ intake DV concentric termination – 12″-18″ (305 – 457 mm) adjustability
4″ Sidewall termination, adjustable pipe
4″ exhaust/3″ intake concentric termination – 5″ to 10″ (127 – 254 mm) adjustability
4″ exhaust/3″ intake concentric termination – 12″ to 18″ (305 – 457 mm) adjustability
4″ exhaust / 4″ intake concentric termination – 5″ to 10″ (127 – 254 mm)adjustability
4″ exhaust/4″ intake concentric termination – 12″ to 18″ (305 – 457 mm) adjustability

100112416 2NVBFU4

2ZVB04

100112550 2NVHTC43S 2SVSHTC43S

100112551 2NVHTC43 2SVSHTC43

100187853 2NVBV4

n/a

100112550 2NVHTC43S 2SVSHTC43S

100112551 2NVHTC43 2SVSHTC43

100112552 2NVHTC44S 2SVSHTC04S

100112553 2NVHTC44S 2SVSHTC04

NOTICE

Refer to heater manufacturer literature/website and the vent manufacturer for available components.

29 Page

Installation Manual Installation
-Common-venting system-
The Indoor model can be vented together using the same exhaust and intake venting. · Up to 8 water heaters can be common-vented together. · A non-return valve (100113130) must be used for each water heater that is part of the system. · The water heaters must all be direct-vented. · ANSI Z223.1/NFPA 54 and/or B149.1, Natural Gas and Propane Installation Code (Current Editions), local codes, and the venting manufacturer’s instructions. · 240H/340H/240HX3/340HX3/540HX3 models do not have Easy-Link or Multi-Unit capability. · For common-venting pieces and components, the manufacturer recommends Centrotherm’s vent line.
Allowable models for common-venting
240H, 340H, 540H, 240HX3, 340HX3, 540HX3, 540P, CT-199

Only the models listed in the table above can be common-vented together. Other models cannot be common-vented. WARNING Failure to observe these warnings could lead to carbon monoxide poisoning or death.

Typical common-vent installaon examples

Roof

Exhaust

Roof

Intake

Condensate drain port

wall

Condensate drain port

Exhaust

Non-Return Valve
Roof
Condensate drain port

Non-Return Valve
Exhaust

Intake wall

Intake

Non-Return Valve
wall

NOTICE

For details on the installation of a common-vent system, please refer to “Common Venting Tankless Gas Water Heaters.” It is a manual which is available on the water heater manufacturer’s website.
30 Page

Installation Manual Installation

To determine the dimension of a common-venng system

Determine the vent diameter (D) and the total vent length based on the number of water

heaters installed. The total vent length (L) consists of the horizontal width (W) and the vercal

height (H). See the table below.

Elbow terminal

· Total vent length (L)=”H”+”W”+

Exhaust

Elbow terminal

(Number of Elbows X 5)

· Vent diameter=”D”

“H”

Intake

“D” “W”

NOTICE

· Regarding the clearances
between the exhaust terminaon and the intake terminaon, refer to pages 15 to 17.
· Insert bird screen in elbow
terminations.

Non-Return Valve

WARNING

· A Non-Return Valve must be installed for each water heater. This prevents the escape of combustion gas through non-operating appliances.
· For detailed instructions on the common-venting system, refer to the instructions that are packaged with the vent parts or web site.

Vent Diameter*
(D)

Common-venting system

Max. No. of water heaters

DIP switch settings

Max. Vertical and Horizontal
(Total) Vent Length** (L)

540P Indoor (Lower bank of DIP switches)

4 in

2

2 5 in
3

2

3

6 in

4

5

6

3

4

5 8 in
6

7

8

5

6 10 in
7

8

25 ft (7.6 m) 50 ft (15.2 m) 20 ft (6.1 m) 100 ft (30.5 m) 75 ft (22.9 m) 50 ft (15.2 m 25 ft (7.6 m) 20 ft (6.1 m) 100 ft (30.5 m) 100 ft (30.5 m) 85 ft (25.9 m) 65 ft (19.8 m) 50 ft (15.2 m) 41 ft (12.5 m) 100 ft (30.5 m) 100 ft (30.5 m) 100 ft (30.5 m) 100 ft (30.5 m)

ON 1234 5678

No. 3: ON No. 4: OFF

WARNING
· For common-venting, adjust only the No. 3 and No. 4 DIP switches in the LOWER bank of DIP switches. (Refer to page 28 for the location of the DIP switches.)
· Turn off the power supply to the water heater before changing the DIP switch settings.
· Failure to observe these warnings could lead to carbon monoxide poisoning or death.

*Diameters of pipes are in accordance with Centrotherm’s specifications. **One elbow is equivalent to 5 ft (1.5 m) linear length, and the maximum number of elbows is 5.
31 Page

Installation Manual Installation

GAS SUPPLY AND GAS PIPE SIZING
-General-

· Check that the type of gas matches the rating plate first. · Ensure that any and all gas regulators used are operating properly and providing gas
pressures within the specified range shown below. Excess gas inlet pressure may cause serious accidents. WARNING · Conversion of this unit from natural gas to propane or vice versa will void all warranty. Contact your local distributor to get the correct unit for your gas type. The manufacturer is not liable for any property and/or personal damage resulting from gas conversions. In Canada, contact tech support at 888.479.8324 for options. · Failure to observe these warnings could result in severe personal injury, carbon monoxide poisoning, or death.

· The minimum and maximum inlet gas pressures are:

Gas type Natural Gas
Propane

Inlet gas pressure Min 4.0″ W.C. (1.00 kPa) ­ Max. 10.5″ W.C. (2.61 kPa) Min 8.0″ W.C. (1.99 kPa) ­ Max. 13.0″ W.C. (3.23 kPa)

· Inlet gas pressures that fall outside the range of values listed above may adversely affect the performance of the water heater. These pressures are measured when the water heater is in full operation.
· Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range will cause dangerous operating conditions and damage to the unit.
· Until testing of the main gas line supply pressure is completed, ensure the gas line to the water heater is disconnected to avoid any damage to the water heater.
· If the gas supply pressure to the heater is greater than the specified maximum, a field-supplied regulator is required. The regulator must lower the gas pressure within the approved range.
· Install the gas regulator according to the manufacturer’s instructions. · The regulator must be sized for the water heater input and provide the specified pressures that are
listed on the rating plate. · In the absence of minimum install distance stated by the regulator manufacturer, it is recommended
that there is at least 3 ft (1 m) of piping between the regulator outlet and the water heater’s inlet gas connection.
-Gas connections-
1. Install a manual gas shutoff valve between the water heater and the gas supply line. 2. When the gas connections are completed, it is necessary to perform a gas leak test either by applying
soapy water to all gas fittings and observing for bubbles or by using a gas leak detection device. · The water heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). · The water heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
3. Always purge the gas line of any debris and/or water before connecting to the gas inlet.

NOTICE

Size the gas pipe appropriately to supply the necessary volume of gas required for the water heater using ANSI Z223.1/NFPA 54 in the USA or B149.1 in Canada or

local codes. Otherwise, flow capabilities and output temperatures will be limited.

32 Page

Installation Manual Installation

-Natural gas supply piping-

Maximum delivery Capacity in Cubic Feet of Gas per Hour (based on IPS Pipe carrying Natural Gas with 0.60 Specific

Gravity with a Pressure Drop of 0.5″ W.C.).

Based on Energy Content of 1,000 BTU/Cubic ft: The water heater requires 199 Cubic ft/hr for the 540P model.

The following tables are from NFPA 54.

Unit: Cubic feet per hour

Pipe Size

Length

Diameter

10′ (3 .0 m)

20′ (6.1 m)

30′ 40′ 50′ 60′ 70′ 80′ 90′ 100′ 125′ 150′ 200′ (9.1 m) (12.2 m) (15.2 m) (18.3 m) (21.3 m) (24.4 m) (27.4 m) (30.5 m) (38.1 m) (45.7 m) (61.0 m)

1/2″ 172 118 95 81 72 65 60 56 52 50 44 40 34

3/4″ 360 247 199 170 151 137 126 117 110 104 92 83 71

1″

678 466 374 320 284 257 237 220 207 195 173 157 134

1-1/4″ 1,390 957 768 657 583 528 486 452 424 400 355 322 275

1-1/2″ 2,090 1,430 1,150 985 873 791 728 677 635 600 532 482 412

2″ 4,020 2,760 2,220 1,900 1,680 1,520 1,400 1,300 1,220 1,160 1,020 928 794

-Propane (LP) supply piping-

Maximum Capacity of Propane (LP) Based on 11″ W.C. supply pressure at a 0.5″ W.C. pressure drop

Unit: kBTU per hour

Pipe Size

Length

Diameter

10′ (3 .0 m)

20′ (6.1 m)

30′ 40′ 50′ 60′ 70′ 80′ 90′ 100′ 125′ 150′ 200′ (9.1 m) (12.2 m) (15.2 m) (18.3 m) (21.3 m) (24.4 m) (27.4 m) (30.5 m) (38.1 m) (45.7 m) (61.0 m)

1/2″ 268 184 148 126 112 101 93 87 82 77 68 62 53

3/4″ 567 393 315 267 237 217 196 185 173 162 146 132 112

1″ 1,071 732 590 504 448 409 378 346 322 307 275 252 213

1-1/4″ 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 440

1-1/2″ 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787 675

2″ 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496 1,260

Gas sizing example (Natural Gas)

Water heater 199,000 BTU/h

Dryer 35,000 BTU/h

5′ (1.5 m)Length 1-1/4″ Pipe size
A
5′ (1.5 m) Length 1-1/4″ Pipe size
Gas meter

10′ (3 m)Length 3/4″ Pipe size
B

15′ (4.6 m)Length 1″ Pipe size

10′ (3 m)Length 1/2″ Pipe size

10′ (3 m )Length 10′(3 m)Length 1″ Pipe size 3/4″ Pipe size

15′ (4.6 m)Length 1/2″ Pipe size
C

Furnace 120,000 BTU/h

Range 65,000 BTU/h

Based on Energy Content of 1,000 BTU/Cubic ft: Divide each appliance’s BTU/h requirement by 1,000 BTU/ft3 to get the appliance’s ft3/h requirement. Take into account the distance the appliance is from the gas meter, look in the above gas chart to properly size the line. For sections of the gas line supplying gas to more than one appliance (Ex: Point A to Point B), add up the cubic ft per hour requirements of the appliances that are being supplied by that section, and size to the farthest appliance. For Example: The section from A to B supplies gas to the furnace, range and dryer. Adding up the BTU/h requirements and dividing by 1,000 yields a cubic ft per hour requirement of 220 cubic ft of gas per hour. The farthest appliance is the range, which is 50 ft away from the meter. Looking at the above chart, and under the column of 50 ft, Section A to B needs to be 1″ in order to supply 220 cubic ft.
33 Page

WATER CONNECTIONS

Installation Manual Installation

Do not use this appliance if any part has been under water. Immediately contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced! WARNING

NOTICE

Do not reverse the hot outlet and cold inlet connections to the water heater. If you reverse the connections, the water heater will not activate properly.

Determine the type of water pipes in your home. Most homes use copper water pipes, but some use CPVC or cross-linked polyethylene (PEX). Use fittings appropriate for the type of pipe in your home. Do not use iron or PVC pipe ­ they are not suitable for potable water. All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for potable water systems. Also, an automatic air vent or air separator must be installed when the water heater operates in a closed loop system such as a recirculation system. Trapped air bubbles in the water system can cause a pump to cavitate or damage the water heater’s heat exchanger. This equipment must be installed according to its manufacturer’s instructions. · A manual shutoff valve must be installed on the cold water inlet to the water heater between the main
water supply line and the water heater. · A thermal expansion tank or code approved device to handle thermal expansion must be installed. · Connect the cold water supply using 3/4 inch National Pipe Thread “NPT” to the fitting marked “C”
(COLD). · For ease of removing the water heater for service or replacement, connect the water pipes with a
coupling called a union. We recommend using a dielectric-type union (available at your local plumbing supplier). Dielectric unions can help prevent corrosion caused by tiny electric currents common in copper water pipes and can help extend the life of the water heater. · Connect the hot water supply using 3/4 inch NPT to the fitting marked “H” (HOT). Follow the same connection guidelines as for the cold water supply. · In addition, a manual shutoff valve is also recommended on the hot water outlet and return inlet of the unit. · Double check to make sure the hot and cold water pipes are connected to the correct hot and cold water fittings on the water heater. · If needed, install (or adjust) the home’s Pressure Reducing Valve and a thermal expansion tank or code approved device to handle thermal expansion must be installed. · Before installing the water heater, flush the water line to remove all debris, and after installation is complete, purge the air from the line. Failure to do so may cause damage to the heater. · There is a wire mesh filter within the cold inlet and return inlet to trap debris from entering your heater. This will need to be cleaned periodically to maintain optimum flow. (Refer to page 62.) · Install insulation (or heat tape) on the water pipes especially if the indoor installation area is subject to freezing temperatures. Insulating the hot water and return pipes will reduce heat loss. · If water hammer is evident install water hammer arrestors on the inlet side.
IF YOU HAVE COPPER PIPES: If your home has copper water pipes, you can solder the water pipe connections or use compression fittings which don’t require soldering. Compression fittings are easier to install than soldering pipe. Check with local plumbing officials to determine what types of pipe materials are suitable for your location. Do not use lead-based solder.
NOTE: Do not solder pipes while they are attached to the water heater. The water heater contains non-metallic parts which could be damaged. The proper way to connect the water heater to copper water pipes is as follows:
· Solder a short length of pipe (about a foot or so) to a threaded adapter using only 95/5 tin antimony or equivalent solder.
· Attach the threaded adapters to the water heater’s connections (using thread sealant tape or pipe joint compound).
· Connect the home’s water pipes by soldering, keeping the connections at the water heater cool with wet rags.
34 Page

Installation Manual Installation

-Recirculation pump mode-
540P comes with an integrated recirculation pump. The water heater has two recirculation mode options; Recirculation with a dedicated return line (default), On-Demand mode compliant with California’s Title 24. Details of the operation are listed below. In each mode, the heater’s pump only operates when there is not any demand from the home’s fixtures. The water heater will stop the pump if there is a call for demand from one of the home’s fixtures.

1. Recirculation with a Dedicated Return Line (Default Mode) – In this mode, the water heater will operate the pump in order to keep your water lines warm, reducing the time it takes for the hot water to arrive at the fixture. The user can configure 2 Pump Timer ON periods where the heater will operate the pump. It is recommended to set the Pump Timers to ON during times when the home is occupied. The water heater will operate as an on-demand water heater during Pump Timer Off periods, though there may be a delay getting hot water to the fixture. See p. 52 to set the Pump Timers.
2. On-Demand Mode – In this mode, the pump will only activate when the user pushes the “Pump” button on the heater’s built in controller or accessory remote controller. See p. 57 for additional information. This mode is compliant with California’s Title 24.
3. Crossover Valve – These valves cannot be used with the water heater. If used, the heater will go into a 441 error code.

-Installation with dedicated return line-

Model

540P Indoor

540P Outdoor

Maximum Pipe length*

Pipe

3/4″

(Hot Water supply line and Dedicated Return line)

Diameter 1/2″

500 ft (152.4 m) 200 ft (61.0 m)

*These are equivalent length that includes head loss for elbows, tees, unions, etc for smooth wall copper tube.

Other water tube materials have different head loss characteristics. When other materials are used, the installer

shall consult with the water tube manufacturer to conduct a head loss calculation to make sure the installed pump will flow at least 2 gpm. Please refer to the manufacturer’s specification sheet for pump head loss information. An

additional pump may be necessary for circulation systems with longer equivalent pipe lengths.

NOTICE

· Check valves must be installed on both of the cold water line and return line. Please refer to the following diagram.
· Insulate the hot water supply line and dedicated return line to prevent heat loss. · The recirculation flow rate should not exceed 4.2 gpm (16 L/min).

-Standard recirculation-

LEGEND
THERMOSTATIC MIXING VALVE
PRESSURE RELIEF VALVE
CIRCULATION PUMP
BALL VALVE
CHECK VALVE COLD HOT BUILDING RETURN GAS

BUILDING RETURN

HOT WATER TO FIXTURES

STANDARD RECIRCULATION SINGLE UNIT PIPING CONFIGURATION

GAS

COLD WATER SUPPLY
EXPANSION TANK

35 Page

Installation Manual Installation

-Installation without recirculation-

NOTICE

· PUMP TIMER 1 and PUMP TIMER 2 must be set to OFF if you use this installation method.
· Cold water supply line must be connected to the “Return inlet”. · The “Cold water inlet” must be capped.

Use this method when recirculation is not used (such as when the return line will be installed later or if this water heater supplies hot water to a hydronic air handler). Before the water heater is put into service, ensure that no timers are set to activate the pump. See “Pump Operation Timers.”
Once the return line is installed, follow the instructions in the previous section, “Installation with dedicated return line.” Complete those instructions BEFORE you set PUMP TIMER 1 and PUMP TIMER 2 to operate. · Install the water supply line to the “Return inlet” water
connection. · Install a 3/4″ end cap to the “Cold water inlet” connection.

Gas inlet

Hot water outlet

Return inlet

“Cold water inlet” must be capped.

Cold water supply line must be connected to the “Return inlet”.

-Domestic and Space Heating-
· This water heater is suitable for combination water (potable) heating & space heating and not suitable for space heating applications only.
· This water heater shall not be connected to any heating system or component(s) previously used with non-potable water where any chemicals were added to the
WARNING water heating appliances. · Toxic chemicals used in boiler treatments such as alcohol, glycerol, and glycol groups must not be introduced into the water system. · When the system requires water for space heating at temperatures higher than required for other uses, Thermostatic Mixing Valves (temperature limiting valves) shall be installed at each point-of-use. Water temperatures over 125°F (52°C) can cause severe burns instantly or death from scalding. When installed per the valve manufacturer’s instructions, they automatically mix hot and cold water to limit the temperature at the tap. · Failure to observe these warnings could result in severe personal injury or death.
Care must be taken by the installing contractor or design engineer to size the components of the system appropriately for flow rate and temperature. In addion to sizing the water heater for the domesc potable water, the installer must size the water heater to provide the flow rate required by the manufacturer of the air handler. Refer to the air handler manufacturer’s instrucons and specificaon documents for this flow rate. The pump, field supplied or provided by the air handler manufacturer, must be able to provide this minimum flow rate.
When sizing the pump, the installer must take into account the pressure drop of the following: · Hydronic air handler. Refer to the manufacturer for this informaon. · Water heater. Refer to the water heater’s specificaon sheet for pressure drop informaon. At 3.5 gpm (13.2 l/m), the pressure drop of the water heater is: 11.8 ft (5.1 psi) · Water tubing size, length, and material. Refer to the water tubing manufacturer for pressure drop informaon as it differs from one material to the next and at different sizes. There may be addional applicaon requirements by the water tubing manufacturer. · Fittings. Refer to the fitting manufacturer for pressure drop informaon.
36 Page

Installation Manual Installation
Addional consideraons are: · Installing an air eliminaon device to remove air that may cause cavitaon in the pump. · A thermostac mixing valve for the domesc system. Refer to the mixing valve manufacturer for proper selecon and installaon. To reduce the risk of scalding, install Thermostac Mixing Valves (temperature liming valves) at each point of use. · A priority control device, such as a flow switch, to priorize the domesc water system over the heang system.
Below is a suggested piping layout. The installer must properly install the system per manufacturers instrucons and local codes. (Refer to Installaon without recirculaon on the previous page.)

LEGEND
THERMOSTATIC MIXING VALVE
PRESSURE RELIEF VALVE
CIRCULATION PUMP TEMPERATURE CONTROL PROBE
BALL VALVE
CHECK VALVE CAPPED LINE
COLD HOT GAS

TEMPERED HOT WATER TO FIXTURE
GAS

P-1 AIR HANDLER

COLD WATER SUPPLY
EXPANSION TANK

37 Page

Installation Manual Installation
-Dual Purpose Water Heating for the State of Massachusetts-

Diagrammatic layout of radiant heating and domestic water heater.

All water piping should be insulated

in accordance with 780 CMR

(Massachuses energy code)

3-inch gas exhaust

Automac tempering device

Cold water supply

vent (Discharge must comply with local and

must be installed below the top of the water heater as per manufacturer’s recommendaons

Apply correct thermal expansion tank-size per applicaon

Shutoff valve

Check valve will have 1/8-inch hole drilling in clapper oponal

state codes.) Cannot be common vented with other appliances in Massachuses.

Hot water outlet Cold water inlet Gas inlet

Piping loop between water heater and fan coil shall be in compliance with 248 CMR

Tempered water to plumbing fixtures. Must meet temperature requirements of 248 CMR
Thermostac mixing valve

Pressure gauge

Atmospheric vacuum breaker
Hot water supply and return to

Drain Water plug filter

Unions 120 VAC

Heang Coil (used with air-handler)

Check valves Shutoff valves

heang coil Ball Valve

Isolation Valve

switch or outlet

Shutoff valves

Check valve

System installed with reverse acng aquastat to shut off fan. Suggested but not required by 248 CMR
50′-0″ maximum distance from water heater to fan coil. (Developed length) Not including coil in heang unit

NSF-61 product approved pump

T-handle gas shutoff valve

Electronically controlled pump mer. Acvates every 6 hours for 60 seconds. Wire to product approved pump

An approved temperature and pressure relief valve. Tie to locaon approved by local codes and must meet BTU rang of water heater model used

The recirculation pump is to provide no less than 2 GPM (7.5 L/min) and no more than 4 GPM (15 L/min) through each activated unit in the system

NOTICE

· Priority Control Devices such as a flow switch, an Aquastat or other electronic controller can be used to prioritize the domestic water system over the heating system.
· Follow all local codes, or in the absence of local codes, follow the current edition of the National Standard Code, ANSI Z21.10.3 · CSA 4.3.
· This illustration is a concept design only. The reference to the 1/8th hole in check is only for the State of Massachusetts. There are a wide variety of variations to the application of controls and equipment presented. Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practice. For more details, contact the manufacturer.
· The built-in pump may not provide sufficient flow for the heating coil. An additional field-supplied pump may be necessary.

38 Page

Installation Manual Installation
-Pressure relief valve-
The water heater has a high-temperature shutoff switch built in as a standard safety feature (called a Hi-Limit switch) therefore a “pressure only” relief valve is required. · This unit does not come with an approved pressure relief valve. · An approved pressure relief valve must be installed on the hot water outlet. · The pressure relief valve must conform to ANSI Z21.22/CSA 4.4 and installation must follow local codes. · The discharge capacity must be at least 199,000 BTU/h for the 540P model. · The pressure relief valve needs to be rated for a maximum of 150 psi (1 MPa). · The discharge piping for the pressure relief valve must be directed so that the hot water cannot splash outward
and cause damage or personal injury. · Attach the discharge tube to the pressure relief valve and run the end of the tube to within 6 in (152 mm) from
the floor. This discharge tube must allow free and complete drainage without any restrictions. WARNING! Do Not plug the pressure relief valve. · If the pressure relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or a local plumbing professional on how to correct this situation. Do not plug the pressure relief valve. · The pressure relief valve must be manually operated periodically to check for correct operation. Before operating the valve manually, check that it will discharge in a place for secure disposal. · No valve must be placed between the relief valve and the water heater.
Hot water could be released. Before operating the pressure relief valve manually, check that it will discharge in a safe place. If water does not flow freely from the end of the discharge pipe, turn the gas supply and power OFF and call a qualified person to determine the cause. WARNING Refer to the pressure relief valve manufacturer’s instructions for inspection and maintenance requirements.
CONDENSATE DRAIN
This high efficiency water heater produces acidic condensate that must be properly drained per local codes. The water heater does not have a built-in neutralizer to raise the pH level. A neutralizer is available from the water heater manufacturer, if needed. Follow the instrucons in this secon in order to install the condensate drain line. · All preventave measures and safety pracces must be adhered to when draining condensate. The
manufacturer will not be responsible for any damage caused by condensate. · A drain pan, or other means of protecon against water damage, is recommended to be installed under
the water heater in case of leaks. · Discharge condensate (acidic water) in accordance with all local codes and common safety pracces. In
the absence of applicable local codes and regulaons, the manufacturer recommends that a condensate neutralizer is installed and dispose the condensate into a drain. See picture on page 40. · Use corrosion resistant pipe, such as PVC, for the condensate drain line. Do not use metallic pipe. · The condensate drain does not require a trap. · A field-supplied bypass is required if a neutralizer is installed. · The condensate drain is at atmospheric pressure (non-pressurized) and therefore must be allowed to drain freely with gravity only. Ensure that the condensate drain tube is not plugged, blocked, or kinked. Ensure that it slopes downward to allow condensate to flow freely. All porons of the condensate drain (neutralizer and drain tube) must be at a lower elevaon than the water heater to prevent condensate water from building up inside the heat exchanger. · Do not connect the condensate drain line directly to a condensate pump. · The condensate drain system must be inspected regularly to make sure it drains properly and in accordance with local codes or the part manufacturer’s instrucons. · Condensate cannot be effecvely neutralized if the neutralizer elements inside the Neutralizer accessory have been completely consumed. If this happens, condensate will remain acidic and can possibly cause damage to items such as pipes, concrete, etc. · The actual life of the neutralizer may vary, depending on the applicaon and usage. Replace the cartridge when the condensate pH goes below 6.0. This can be tested using litmus pH test strips. · Please ensure that the cartridge is properly replaced before the neutralizer elements have been completely consumed.
39 Page

Installation without neutralizer

Installation Manual Installation
Installation with neutralizer

1/2″ Condensate drain tube*

1/2″ MPT Condensate connection

1/2″ Condensate drain tube*

Overflow bypass* (1/2″ Condensate
drain tube)

1/2″ MPT Condensate connection
1/2″ Condensate drain tube
1/2″ MPT x 3/8″ FPT (Included with Neutralizer accessory) Neutralizer cartridge (Included with Neutralizer accessory)
1/2″ FPT x 1/2″ HB (Included with Neutralizer accessory)
1/2″ Condensate drain tube

2″ (50 mm) MIN. distance**

2″ (50 mm) MIN. distance**
Floor drain, standpipe, pump, or other acceptable drain

2″ (50 mm) MIN. distance**
Floor drain, standpipe, pump, or other acceptable drain

*Maintain downward slope, including installations in which the drain is not directly below the heater. **A 2″ (50 mm) minimum distance must be maintained between the condensate line and drain to allow full flow of the condensation.

40 Page

ELECTRICAL CONNECTIONS

Installation Manual Installation

· Follow the electrical code requirements of the local authority having jurisdiction. In the absence of such requirements, follow the current edition of the National Electrical Code ANSI/NFPA 70 in the U.S. or the current edition of CSA C22.1 Canadian Electrical Code Part 1 in Canada.
WARNING · When servicing or replacing parts within the water heater, label all wires prior to disconnection to facilitate an easy and error-free reconnection. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
· Failure to observe these warnings could result in personal injury or death.

Indoor model comes with a power plug instead of a junction box. The following procedure is for outdoor model only.

1. The water heater must be electrically grounded. Do not attach the ground wire to either the gas or the water

piping.

2. The water heater requires a 120 VAC, 60 Hz electrical power supply that is properly grounded.

· A proper disconnect (i.e. on/off switch, power plug, etc.) controlling the main power to the water

heater must be provided for service reasons. (Must comply with local codes.)

· Connect the power supply to the

water heater exactly as shown in the wiring diagram. 3. A green screw is provided in the junc-

Outdoor model

Green screw

Connect Power supply 120VAC, 60Hz

tion box to ground the connection.

4. The water heater can be hardwired or wired to a plug-in.

Ground

5. The use of a surge protector is recom-

mended in order to protect the unit

from power surges.

Boom view of water heater

View of electrical connections in the junction box.

TEMPERATURE REMOTE CONTROLLER

-Included accessories – Outdoor model only

· The remote control is an optional accessory that can be installed in a hall, closet, etc., to allow for temperature adjustment without having to go to the heater.
· When installed, the remote will take priority over the built-in controller of indoor models.

Verify that the items listed below are included with the remote controller.

Temperature remote controller

Screws

Fork terminals

Manual

Remote controller cable*

Qty: 1

Qty: 2

Qty: 1

Qty: 4

Qty: 1

100276687 (TM-RE43) It is also an optional accessory as a second remote for the indoor model. Refer to pages 10 and 11. *The optional remote controller (100276687/TM-RE43) has no remote controller cable.

· This remote controller is NOT waterproof. · The water heater can only have one remote controller. · Do not install in high temperature environments, high humidity conditions outdoors, in WARNING direct sunlight, or within the reach of children. · Make sure the remote controller does not come into contact with water or oil. · Failure to observe these warnings could result in personal injury or electrical shock.

41 Page

Installation Manual Installation

NOTICE

· Do not place the remote controller cable close to other wires from other products.
· Cables used for the remote controller connection must be: Minimum 20 gauge wire (No polarity) Maximum 400 ft (122 m) long

1. Take the Frame off of the remote controller with a flat head screwdriver. (Fig. A and B)

2. Attach the Metal plate on the wall with two provided screws. (Fig. B)

3. If you use another cable, crimp the Fork terminals to the wires. (Fig. C)

Fig. A
Twist

Fig. B Attached short screws Metal plate

3-1/4 inch (83.5 mm)

Main unit

Press and twist flat head screwdriver against the cutout.

Frame

A

A + B

Fig. C

1-3/8 Inch (35 mm)

Fork Terminals

B Hook B to the Fixing bracket on A.

1-5/8 Inch (41 mm) Remote controller cable

Cut out (removed during later steps).

4. Open the Plastic cover and tighten the two Fork terminals

beneath the two Remote controller terminal screws on Fig. D-1 the back of the Main unit (Fig. D-1). Cut out the inlet for the cable from the bottom of the main unit (Fig. D-2).

Back side of the remote
Remote controller terminals

Pcolavsetric

Insert the cable through the inlet.

5. Close the Plastic cover and then hook the Main unit to the

Fixing bracket on the Metal plate. (Fig. B)

6. Attach the Frame back onto the remote.

Two fork terminals

Remote controller cable

1\. Disconnect power supply from the water heater.

Fig. D-2

2. Take off the water heater’s front cover.

Inlet for the remote

3. Locate the remote controller terminals. See the diagrams controller cable

below.

Cut out

4. Take off the back plate from the remote controller, and then attach the two fork terminals to con-

nector base on the backside of the remote controller with two screws. Make sure the terminals are

firmly fixed. (See the above instructions for installation of the remote controller.)

5. Pull the remote controller cable through the hole at the bottom of the water heater’s casing.

6. Properly attach the remote controller cable to the remote controller terminal on the computer board

(No polarity). * Do NOT jump or short-circuit the cable, or the computer will be damaged.

7. Replace the front cover securely.

100276687 (TM-RE43)

Connect other end to these terminals
42 Page

Installation Manual Installation

EASY-LINK SYSTEM
The 540P model water heater can be connected to 540H/CT-199 models as only a PARENT unit in an Easy-Link System.
· The built-in Easy-Link System allows up to 4 units to manifold together. · Only one 540P can be installed in an Easy-Link System. · A communication cable (gray color) comes with each 540H/CT-199 model. You can manifold from 2 to 4 units. A 4-unit system has full automatic modulation between 13,000 BTU/h (Propane) or 15,000 BTU/h (Natural gas)to 796,000 BTU/h.

Type of unit PARENT

Model 540P

Allocated No. from controller
1

Return Line Gas In
Cold In

CHILD-1/2/3

540H CT-199

2,3,4*

*Each CHILD unit is allocated the above num-

ber from controller, which indicates on the Hot Out display of the controller on the unit. (Refer

to page 67.)

· The Easy-Link System is limited to up to 4 units. If you connect more than 4 units, only the first 4 units will work as a part of the Easy-Link System. The other additional units
NOTICE will not work. · In the Easy-Link System, one unit must be designated as a PARENT unit by changing one of its DIP switch settings. The other units are CHILD units. The 540P model must be a PARENT unit and cannot be a CHILD unit. (The 540H/CT-199 model can be either a PARENT unit or a CHILD unit.) · A 540P model only can be connected to 540H/CT-199 models when 540P is a PARENT unit in the system. · A remote controller is not required for an Easy-Link System. However, it does provide for more temperature options and ease of maintenance. · If a remote controller is used, the temperature on all the units in the system will automatically be set to the same temperature that is set on the remote. · When a remote is used in an Easy-Link System, it must be connected to the parent unit. · Only one remote can be connected.
-Easy-Link connection procedures for 540P & 540H/CT-199 models-
1. Make sure the power to the heaters are off. 2. Verify the DIP switch set temperatures of all units within the system. Every single water heater
must be set to the same set temperature. If a remote controller is used, it should be installed to the “PARENT” unit. The remote will set the temperature for the entire system. When the 540P model is the “PARENT” unit, the only controller that can be used is the 100276687 (TM-RE43). 3. Select 540P unit to be the “PARENT” unit. The “PARENT” unit should be one of the end units. 4. “PARENT” unit: On the 540P that you select to be the “PARENT” unit, locate the three banks of DIP switches at the upper left of the computer board. Change DIP switch No. 1 on the middle bank of DIP switches to the ON position. See the computer board diagram as shown on the next page. Do not change any DIP switches on any of the “CHILD” units.
43 Page

Installation Manual Installation

5. Between the “PARENT” and the “CHILD-1” units: Connect the “PARENT” connector of the “PARENT” unit to the “1” connector of the “CHILD-1” unit using the supplied linking cable.
6. Between the “CHILD-1” and the “CHILD-2” units: Connect the “2” connector of the “CHILD-1” unit to the “1” connector of the “CHILD-2” unit.
7. Between the “CHILD-2” and the “CHILD-3” units: Connect the “2” connector of the “CHILD-2” unit to the “1” connector of the “CHILD-3” unit.
8. Verify that all cables are connected like the diagram on the next page (B). 9. Turn on power to the “PARENT” unit.
Turn on “CHILD-1”. When the (remote and/or built-in) controller displays a number, turn on “CHILD-2”. When the (remote and/or temperature) controller displays a number, turn on “CHILD-3”. Make sure the (remote and/or temperature) controller display the unit #. The numbering system automatically allocates the unit # to each water heater in the Easy-Link System, in accordance with the table above.
(A) 540P model computer board

·
· WARNING ·
·

To change the DIP switch settings for the Easy-Link System, locate the MIDDLE bank of DIP switches at the upper left of the 540P computer board. (See diagrams below.) DO NOT adjust any other DIP switches . Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe this warning could result in carbon monoxide poisoning or death.

Upper bank of DIP switches Middle bank of DIP switches
Lower bank of DIP switches

Easy-Link
connector is
idenfied by a label.

(B) Basic diagram of connections between the Easy-Link System units

PARENT UNIT 540P

CHILD UNIT 540H/CT-199

CHILD UNIT 540H/CT-199

CHILD UNIT 540H/CT-199

Connectors

Built-in or
remote controller

Connectors

Connectors

Connectors

2 1 PARENT
1 23456
ON OFF
2 1 PARENT
1 23456
ON OFF
2 1 PARENT
1 23456
ON OFF
PARENT

1 23456
ON OFF

MDIiPddswleitbcahneks of

LDoIPwsewr ibtachneksof

LDoIPwsewr ibtachneksof

LDoIPwsewr ibtachneksof

Communication cable

NOTICE

· The dark squares indicate the correct position of the DIP switch. · Either a built-in controller or a remote controller is required for the Easy-Link System
for ease of usage and maintenance.
44 Page

INITIAL OPERATION

Installation Manual Initial operation

FOR YOUR SAFETY, READ BEFORE OPERATING
· Check the GAS and WATER CONNECTIONS for leaks before firing unit for the first time. · Open the main gas supply valve to the unit using only your hand to avoid any spark. Never use
tools. If the knob will not turn by hand, do not try to force it; call a qualified service technician. Forced repair may result in a fire or explosion due to gas leaks. · Be sure to check for the presence of leaking gas toward the bottom of the unit because some gases are heavier than air and may settle towards the floor. · Check the GAS PRESSURE. Refer to page 32. · Do not try to light the burner manually. It is equipped with an electronic ignition device which automatically lights the burner. · Check for PROPER VENTING and COMBUSTIBLE AIR to the water heater. · Purge the GAS and WATER LINES to remove any air pockets. · Do not use this appliance if any part has been under water. Immediately contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced!

WARNING

IF YOU SMELL GAS: · Do not try to start the water heater. · Do not touch any electric switches; do not use any phone in your building. · Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions. · If you cannot reach your gas supplier, call the fire department. · Failure to observe these warnings could lead to fire or an explosion, resulting in
severe injury or death.

Initial Test Run

1. Turn on the 120 VAC, 60 Hz power supply to the water heater.

Open the valve on the inlet water and wait for all pipes to fill with water.

3. Clean filter of any debris. Refer to page 62 for instructions.

Open a hot water tap to verify that water is flowing to that tap, then close the hot water tap.

5. Open the manual gas valve.

45 Page

Installation Manual Initial operation
Initial Test Run
Start pump operation test by built-in controller or remote controller.

Press the ON/OFF button on the controller so the STAND BY LED or
turns off.

Press and hold “INFO.” and “PUMP” simultaneously for at least

6. three seconds, then the integrated pump starts operation for

or

five minutes.

A segment of the zero is lighting as follows in clockwise order during pump operation test.

During the pump operation test, open and close a faucet in the loop
7. several times to relieve air in the pipe. If air is stuck in the pump, it
can cause pump failure or decreased water flow.

Check recirculation water flow. Refer to page 59. Make sure the flow

rate is approx. 2 to 3 GPM. If the flow rate is less than 2 GPM, there is a possibility that air is stuck in the pump. Open and close the faucet

again to relieve air.

Water flow (EX.: 3.0 GPM)

After finishing the pump operation test, complete the following

procedures (Refer to pages 51 to 55.):

· OUTLET WATER TEMPERATURE SETTING · SETTING THE TIME

· SETTING PUMP TIMERS

· SELECTING A PUMP TIMER

NOTE: To reduce the risk of scalding, install Thermostatic Mixing Valves (temperature limiting valves) at each point of use.

46 Page

Owner’s Guide Operating Safety
Owner’s Guide
CONGRATULATIONS
Congratulations and thank you for choosing our tankless water heater. Before use, we recommend that you read through this owner’s guide carefully. Keep this manual for future reference. If you need an additional manual, contact the manufacturer or your local distributor. You may also download a manual from our website. When you call, please tell us the product name and the serial number of your unit written on the rating plate of the water heater.
47 Page

OPERATING SAFETY

Owner’s Guide Operating Safety

FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not touch any electric switch; do not use any phone in your building. · Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. · If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to turn the gas shutoff valve. Never use tools. If the valve will not turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately contact a qualified installer or service agency to replace a flooded water heater. Do not attempt to repair the unit! It must be replaced!
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label. 2. Turn off all electric power to the appliance. 3. Do not attempt to light the burner by hand. 4. Turn the gas shutoff valve located on the outside of the unit to the closed position. 5. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the
safety information above on this label. If you don’t smell gas, go to the next step. 6. Turn the gas shutoff valve located on the outside of the unit to the open position. 7. Turn on all electrical power to the appliance. 8. If the appliance will not operate, follow the instructions in “To Turn Off Gas to Appliance,” and
call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance if service is to be performed. 2. Turn the gas shutoff valve located on the outside of the unit to the closed position.

48 Page

Owner’s Guide Operating Safety

DANGER
Vapors from flammable liquids will explode and catch fire causing death or severe burns. Do not use or store flammable products such as gasoline, solvents or adhesives in the same room or area near the water heater.

Flammable Vapors

Do not install water heater where flammable products will be stored or used unless the main burner is at least 18″ above the floor. This will reduce, but not eliminate the risk of vapors being ignited by the
main burner.

FLAMMABLES

Read and follow water heater warnings and instructions. If the owner’s manual is missing, contact the retailer or manufacturer.

Keep flammable products:

Vapors:

1. Far away from heater.

1. Cannot be seen.

2. In approved containers.

2. Are heavier than air.

3. Tightly closed and out of reach of children.

3. Go a long way on the floor.

4. Water heater has a main burner, which may 4. Can be carried from other rooms to the main

come on at any time and will ignite flammable

burner by air currents.

vapors.

DANGER

1. Water temperature over 125°F (52°C) can cause severe burns instantly or death from

scalds. 2. Children, disabled and elderly are at highest risk of being scalded. 3. Feel water before bathing or showering.

HOT CHAUDE
BURN HOT BRÛLURE

4. Temperature limiting valves are available. See manual.

5. To reduce the risk of scalding, install Thermostatic Mixing Valves (temperature limiting valves) at each

point of use.

6. The outlet temperature of the water heater is set at 120°F (50°C). If you require water temperatures

below this setting, follow the instruction manual.

7. Use this heater at your own risk. Test the water before bathing or showering. Do not leave children or

an infirm person unsupervised. See your local water supply company [plumbing hardware retailer] for

temperature limiting valves that are available.

A pressure relief valve listed as complying with the standard for Relief Valve and Automatic Gas Shutoff Devices for Hot Water Supply System, ANSI Z21.22 CSA 4.4, shall be installed at the time of installation of the water heater in the location specified by the manufacturer. Local codes shall govern the installation of relief devices for safety operation of the water heater. The relief valve must not be removed or plugged.
No valve shall be placed between the relief valve and the water heater. The relief from the discharge of
the pressure relief valve shall be disposed of in a suitable place where it will cause no damage. Also, there
shall be no other reducing coupling or other restrictions installed on the discharge line to restrict flow. See Installation Manual heading “PRESSURE RELIEF VALVES” for installation and maintenance of relief valve discharge line and other safety precautions.

49 Page

Owner’s Guide Normal Operation

NORMAL OPERATION
BUILT-IN CONTROLLER and REMOTE CONTROLLER
The illustraon below shows an example of the controllers. The exact display may differ from examples.

Built-in controller

Remote controller

5

6

7

5

68

8 9

1

2

2

3

9 3 4

47

1

No. Description

Note

No. Description

Note

1

“ON/OFF” Button

Press this button to start or stop operation.

5

2

“HOT” Button

Press the “HOT” button or the 6
“COLD” button to set the outlet

3

“COLD” Button

water temperature, the current

time, and PUMP TIMER.

7

“TIME” Button
LCD
“PUMP” Button

Press this button to set the current time.
The current time, set temperature, error code and other information are displayed.
Press this button to set and control the pump operation.

4

“INFO.” Button

Press the “INFO.” button to display the inlet & outlet water tem-

8

IN USE LED The LED lights during combustion.

perature and water flow and set

the outlet temperature, pump 9 STAND BY LED The LED lights when power is on.

choosing, and unit conversion.

NOTICE

· When the remote controller is installed it will take priority over the built-in controller. · The controller has an energy saving mode. Five minutes after the water heater stops
operating, the backlight of the controller turns off. · The backlight of the remote will turn back on once the water heater begins firing again.

GENERAL

· Temperatures above 125 °F (52 °C) can cause severe burns or death from scalding.

Children, disabled and the elderly are at high risk of being injured.

· To reduce the risk of scalding, install Thermostatic Mixing Valves (temperature limit-

ing valves) at each point of use.

WARNING

°F °C Time to produce serious burn

120
49
more than 5 min.

125 52
1½ to 2 min.

130 54
about 30 sec.

135 57
about 10 sec.

140 145 60 63
less than less than 5 sec. 3 sec.

150 66
about 1½ sec.

155 68
about 1 sec.

1. Open a cold water 2. Mix hot water with the cold water 3. When finished, close the

fixture.

to get the correct temperature water. water fixtures.

NOTICE

· Flow rate to activate the water heater: 0.5 gallon per minute at the default set temperature (1.9 L/min.)
· Flow rate to keep the water heater running: 0.4 gallon per minute (1.5 L/min.)
50 Page

Owner’s Guide Normal Operation

OUTLET WATER TEMPERATURE SETTING

-Set temperature-

Operation

Controllers
Built-in controller Remote controller

1. Turn on the 120 VAC power supply to the unit.

Press the “ON/OFF” button on the controller in order to turn the controller on.

3. When ON, the STAND BY LED is lit.

It shows the set temperature of output water on its display as shown in the picture on the right. (EX.: 120 °F)

Press the “HOT” button or the “COLD” button to set the temperature setting of the unit.
WARNING! Higher temperatures increase the risk of scalding,
5. but even at 120 °F (50 °C), hot water can scald (page 6).
Increasing temperature from 120 °F (50 °C) to 125 °F (52 °C) : To reduce the risk of scalding, install Thermostatic Mixing Valves (temperature limiting valves) at each point of use. 1. Press the “HOT” button to set 120 °F (50 °C). 2. Press and hold the “INFO” button and the “HOT” button for
at least 3 seconds. The remote will change to 125 °F (52 °C). 3. Press the “HOT” button to set up to 140 °F (60 °C).

(EX.: 120 °F)

TEMPERATURE TABLE OF CONTROLLER

°F 100 105 110 115 120 125 130 135 140 °C 38 40 43 45 50 52 55 57 60 *Factory setting (Default): 120 °F (50 °C)

NOTICE

· The controllers have an energy saving mode. Five minutes after the water heater stops operating, the backlight of the controllers turns off.
· The backlight of the controllers will turn back on once the water heater begins firing again.
51 Page

Owner’s Guide Normal Operation

SETTING THE TIME

Operation

Controllers

Built-in controller

Remote controller

1. Turn on the 120 VAC power supply to the unit.

Press the “TIME” button on the controller in order to set the time. This operation is available regardless of ON/ OFF of the controller.
2.
The time in the display will flash. The controllers can only have 24 hours indication of time.

Press the “HOT” button or “COLD” button to set the time. Press and hold the “HOT” or “COLD” button to adjust the
3. time more quickly.
NOTICE: The time is displayed in twenty-four hour clock time. For example, 11:00 is 11:00 a.m. and 23:00 is 11:00 p.m.
Press the “TIME” button on the controller in order to save and exit.

4. When the remote is on, the current time and set

temperature are displayed.

OR

When the remote is off, the display turns off.

PUMP OPERATION TIMERS
The built-in controller and remote offer two timer settings for the pump operation: PUMP TIMER 1 and TIMER 2. The pump will only operate during the times set for TIMER 1 and TIMER 2. There are four options for pump timer operation.
1. Both PUMP TIMER 1 and PUMP TIMER 2 are activated. 2. Neither PUMP TIMER 1 nor PUMP TIMER 2 are activated.
(The recirculation pump will never operate in this mode.) 3. Only PUMP TIMER 1 is activated. 4. Only PUMP TIMER 2 is activated.
NOTICE: Set the time for PUMP TIMER 1 and PUMP TIMER 2 before you select a pump timer option. Follow the steps in SETTING THE TIME, then complete the steps in Setting pump timers.
52 Page

PUMP TIMERS 1 & 2 activated
NO PUMP TIMER activated
Only PUMP TIMER 1 activated
Only PUMP TIMER 2 activated

Owner’s Guide Normal Operation

– Setting pump timers –

Operation

Controllers

Built-in controller

Remote controller

1. Turn on the 120 VAC power supply to the unit.
Press and hold the “PUMP” button on the controller for at least 3 seconds to enter the pump timer setting mode. This operation is available regardless of ON/OFF of the controller.
2.
The ON time for PUMP TIMER 1 will flash, indicating that you can set the start time.

Press the “HOT” button or “COLD” button to select the time. Press and hold the “HOT” or “COLD” button to
3. adjust the time more quickly.
NOTICE: The time is displayed in twenty-four hour clock time. For example, 11:00 is 11:00 a.m. and 23:00 is 11:00 p.m.

Press the “PUMP” button when the desired time flashes on the display.
4.
The OFF time for PUMP TIMER 1 will flash, indicating that you can set the end time.

Press the “HOT” button or “COLD” button to select the time. Press and hold the “HOT” or “COLD” button to
5. adjust the time more quickly.
NOTICE: The time is displayed in twenty-four hour clock time. For example, 11:00 is 11:00 a.m. and 23:00 is 11:00 p.m.
Press the “PUMP” button when the desired time flashes on the display.
6.
The ON time for PUMP TIMER 2 will flash, indicating that you can set the start time.

53 Page

Owner’s Guide Normal Operation

Operation

Controllers

Built-in controller

Remote controller

Press the “HOT” button or “COLD” button to select the time. Press and hold the “HOT” or “COLD” button to
7. adjust the time more quickly.
NOTICE: The time is displayed in twenty-four hour clock time. For example, 11:00 is 11:00 a.m. and 23:00 is 11:00 p.m.

Press the “PUMP” button when the desired time flashes on the display.
8.
The OFF time for PUMP TIMER 2 will flash, indicating that you can set the end time.

Press the “HOT” button or “COLD” button to select the time. Press and hold the “HOT” or “COLD” button to
9. adjust the time more quickly.
NOTICE: The time is displayed in twenty-four hour clock time. For example, 11:00 is 11:00 a.m. and 23:00 is 11:00 p.m.

Press the “PUMP” button when the desired time flashes on the display.

The following steps will set the temperature drop that must occur before the recirculation pump will activate.

Temperature drop below set temp. at which °F -10 -15 -20* -25 -30 -35 -40

11. pump turns on

°C -6 -8 -11 -14 -17 -19 -22

*The value has been preset at the factory. (Default)

Press the “HOT” button or the “COLD” button to select the temperature at which the pump will activate.

Press the “PUMP” button on the controller to save your settings.

54 Page

Owner’s Guide Normal Operation

Operation

Controllers

Built-in controller

Remote controller

The following steps will set the temperature drop that must occur before the recirculation pump will turn off.

Temperature drop below set temp. at which °F -5* -10 -15 -20 -25 -30 -35

13. pump turns off

°C -3 -6 -8 -11 -14 -17 -19

*Preset at the factory. (Default)

Press the “HOT” button or the “COLD” button to select the temperature at which the pump will turn off.

Press the “PUMP” button on the controller to save your settings.

  1. When the controller is on, the current time and set

temperature in the display turns on.

OR

When the controller is off, the display turns off.

– Selecting a pump timer-

Operation

Press the “PUMP” button on the controller to set the

mode. (The options are shown in step 3.) This operation is available regardless of the ON/OFF status of the

controller.

Controllers

Built-in controller

Remote controller

The current status of the PUMP TIMER will flash for 10
2. seconds. During this time, you can change the mode.
Otherwise, the mode will remain unchanged.

Press the “PUMP” button on the controller in order to change the option. The order of the option is as follows.

NO PUMP TIMER activated

Only PUMP TIMER 1 activated

Only PUMP TIMER 2 activated

PUMP TIMERS 1 & 2 activated

Press the “INFO” button on the controller in order to save your setting.

55 Page

Owner’s Guide Normal Operation

-Display example-
The display on the controller indicates which PUMP TIMER is set by displaying a number below the time: 1, 2, or 12. (12 indicates PUMP TIMER 1 and PUMP TIMER 2.)
The arrow to the right of ON or OFF indicates the current status of the PUMP TIMER(s). If the current time falls within the time range set for a PUMP TIMER, the arrow will point toward ON. (The timer is ON.)
If the current time falls outside the time range set for a PUMP TIMER, the arrow will point toward OFF. (The timer is OFF.)
See below for examples of each scenario. In each scenario below, PUMP TIMER 1 is set to activate at 6:00 AM (6:00) and deactivate at 9:00 AM (9:00). PUMP TIMER 2 is set to activate at 6:00 PM (18:00) and deactivate at 9:00 PM (21:00).

Examples
The display shows that PUMP TIMER 1 is in operation. The current time falls within the time range that is set for for PUMP TIMER 1.
1. Current time: 8:00 AM (8:00) Set temperature of output water: 120 °F PUMP TIMER 1: SET PUMP TIMER 2: OFF
The display shows that PUMP TIMER 1 is NOT in operation. The current time falls outside the time range that is set for for PUMP TIMER 1.
2. Current time: 10:00 AM (10:00) Set temperature of output water: 120 °F PUMP TIMER 1: SET PUMP TIMER 2: OFF
The display shows that PUMP TIMER 2 is in operation. The current time falls within the time range that is set for for PUMP TIMER 2.
3. Current time: 8:00 PM (20:00) Set temperature of output water: 120 °F PUMP TIMER 1: OFF PUMP TIMER 2: SET
The display shows that PUMP TIMER 2 is NOT in operation. The current time falls outside the time range that is set for for PUMP TIMER 2.
4. Current time: 10:00 PM (22:00) Set temperature of output water: 120 °F PUMP TIMER 1: OFF PUMP TIMER 2: SET
The display shows that PUMP TIMER 1 and PUMP TIMER 2 are set, and one of them is in operation. In this example, PUMP TIMER 1 is running because it is set to activate between 6:00 AM
5. and 9:00 AM. (See above.)Current time: 7:00 AM (7:00) Set temperature of output water: 120 °F PUMP TIMER 1: SET PUMP TIMER 2: SET
The display shows that PUMP TIMER 1 and PUMP TIMER 2 are set, and none of them is in operation. The current time falls outside the time ranges that are set for for
6. PUMP TIMER 1 and PUMP TIMER 2. Current time: 10:00 AM (10:00) Set temperature of output water: 120 °F PUMP TIMER 1: SET PUMP TIMER 2: SET

Controllers

Built-in controller

Remote controller

56 Page

Owner’s Guide Normal Operation

-Pump operation test-
The following procedure will operate the pump. This is useful to verify that the pump is operating properly and to check the water flow rate.

Operation

Controllers

Built-in controller

Remote controller

Press the ON/OFF button on the controller so the STAND BY LED turns off.

Press and hold “INFO.” and “PUMP” simultaneously
2. for at least 3 seconds, then the integrated pump
starts operation for 5 minutes.
A segment of the zero (on the right) is lit as follows in clockwise order during forced pump operation.
3.

The pump will stop operation automatically after five

minutes.

OR

Press the “ON/OFF” button to stop pump operation

test.

-On-Demand Pump Operation-
The On-Demand pump operation complies with California’s Title 24. This operation runs the pump and fires the water heater each time the “PUMP” button on the heater’s built-in controller or optional remote controller is pushed. The pump runs until water temperature at the return thermistor inside the water heater reaches 102°F (38.9°C) or the water temperature at the thermistor rises 10°F (5.6°C) above the initial temperature of the water. The pump will automatically stop after 5 minutes if still in operation. Number 5 DIP switch of the lower bank needs to be changed to “ON” position in the operation. Note: The pump timer is not available when the No. 5 DIP switch of the lower bank is set to “ON”.

Operation

Controllers

Built-in controller

Remote controller

Press the “PUMP” button to start pump operation and fire the water heater.

“P” and the set temperature are indicated (on the right) during On-demand pump operation.

The pump will stop automatically in five minutes and
3. the current set temperature and time will be
displayed on the screen.
57 Page

Owner’s Guide Normal Operation

·
· WARNING
·

For On-demand pump operation, adjust only the No. 5 DIP switch in the LOWER bank of DIP switches. (See below.) DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.

Set DIP switch shown in the table below. On-demand pump operation

Lower bank of DIP switches

ON 1234 5678
ON 1234 5678

Lower bank of
DIP switches

No. 5 : OFF DEFAULT

No. 5 : ON

58 Page

Owner’s Guide Normal Operation

ADDITIONAL FEATURES
-Information mode-
You can get some information about the water heater condition by pressing the “INFO” button. For more information, follow the procedures below:

Operation

Controllers

Built-in controller

Remote controller

Press the “INFO” button on the controller to enter the information mode.

Press the “INFO” button to display the inlet water temperature.

Inlet water temperature (EX.: 60 °F)

Press the “INFO” button again to display the outlet water temperature.

Outlet water temperature (EX.: 120 °F)

Press the “INFO” button again to display the water flow.

Water flow (EX.: 3.5 GPM)

5. Press the “INFO” button to exit the information mode.

-Unit conversion mode-
Units of measure can be changed from Imperial

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

John Wood User Manuals

Related Manuals