AFWFilters Covers Air Injection Systems with Fleck Installation Guide
- June 7, 2024
- AFWFilters
Table of Contents
AFWFilters Covers Air Injection Systems with Fleck
Installation Instructions for Air Injection Systems with Fleck 5600 and
5600SXT
Covers air injection silver, gold, and platinum filter systems.
THANK YOU
Thank you for purchasing a new Air Injection System from Oceanic Water
Systems. We appreciate the opportunity you have given us to provide you with
better water. We are committed to providing the best customer experience
possible and have provided these installation instructions to make things as
simple as possible. If you have read through these entire instructions and FAQ
section and still have questions feel free to contact us for further help. Our
office hours are Monday-Friday 10:00 AM – 4:00 PM PST, and you can call us at
661-575-0033. You can also use the
contact us link above to connect you to one of our technical experts.
BEFORE YOU BEGIN
- BASIC PLUMBING SKILLS ARE REQUIRED FOR INSTALLATION. IF YOU ARE UNSURE OF YOUR ABILITIES TO INSTALL THE SYSTEM USING THESE INSTRUCTIONS PLEASE HIRE A QUALIFIED PLUMBER.
- READ THROUGH YOUR PARTS LIST AND VERIFY ALL COMPONENTS ARE ACCOUNTED FOR AND IN GOOD CONDITION BEFORE SCHEDULING A PLUMBER.
- PLEASE READ THROUGH THE ENTIRE INSTRUCTION MANUAL CAREFULLY. IF HIRING A PLUMBER ENSURE THEY HAVE A COPY BEFORE THEY START.
- MOST COMMON QUESTIONS ARE ANSWERED IN THE INSTRUCTIONS OR FAQ SECTION. IF YOU HAVE READ BOTH OF THOSE AND STILL HAVE QUESTIONS YOU MAY CONTACT US FOR FURTHER HELP.
- PLUMBING RELATED QUESTIONS NEED TO BE DIRECTED TO A LOCALLY QUALIFIED PLUMBER. WE ARE NOT PLUMBERS AND ANY PLUMBING QUESTIONS WE RECEIVE WILL NOT BE ANSWERED.
SYSTEM REQUIREMENTS
Your chosen installation location and water supply must meet ALL of the following requirements:
- 20-90 PSI (1.38-6.20BAR)
- 34-110°F (1.1-43.3°C)
- System must be protected from freezing
- Firm level surface AFTER the pressure tank
- 3-prong, 120V outlet within 5 ft. (1.5 m) of the control head with constant power. GFCI outlet is recommended. Use of an extension cord is NOT recommended. • A 1.5 inch standpipe, sump pit, or outside drain.
Please note : The drain line is pressurized and can be ran vertically if necessary.
VERIFY SYSTEM INVENTORY
Use the following table to help verify the parts that are included with your
system and verify that they are all accounted for. Inspect all parts for
damage and report any damage immediately. Damage claims must be made within 30
days of delivery to be eligible for replacement.
Polyglass Tank
A tall slender tank 44–65 inches in height with an opening on the top. Larger
tanks may have a gray threaded adapter to reduce tank opening to match control
head. Please Note: If you have the Vortech tank upgrade, the Vortech tank
replaces the standard tank, so a system with the Vortech tank upgrade will
still have only one polyglass tank.
Note for loaded systems: Tanks that are shipped loaded may arrive on their side or even upside down. The tanks are closed and the media will return to the bottom once place in the correct position. Any mixing of tank contents will correct itself after being placed in service.
Riser/Distributor Tube
A tall pipe that runs from the bottom of the tank to the control valve. If
your tank is loaded (empty tanks only weigh 20-30 pounds) DO NOT pull the
riser tube out of the tank. One end has a basket (basket design varies) and it
usually ships inside the tank. Please Note: On systems with the Vortech tank
there is no basket as the pipe is connected to the bottom tank plate and is
not removable. (Tank cutaway shown)
Control Head
Screws on top of the tank and controls the water flow and backwashing cycles.
Digital SXT has LCD panel. The mechanical has control knobs.
Please note: Some SXT systems may have labels referring to the older SE model
number. This is an internal designation and does NOT indicate that you
received an SE controller. This image will show the differences for easy
reference.
Bypass Valve
Depending on your order your system will have either a single piece stainless
steel bypass or a two part plastic bypass with yoke connection. This is what
connects to your control head and provides standard fitting connections to
hook up to your plumbing.
Drain Fitting
Fitting(s) that connect the control head to the drain line. Please Note:
Drain line is not included. Depending on the system ordered there are
multiple options, and the pictures shown are common examples but actual
fitting may vary.
Before you start plumbing
PRE-INSTALLATION PREPARATION
Money-saving tip: If hiring a plumber to do the installation you can save some money by preparing the tank ahead of time. This cuts down on the time the plumber has to spend and doing so is simple enough that most people can accomplish it in less than an hour.
Verify riser tube position
NOTE REGARDING LOADED TANKS: Systems that arrive loaded will have the
riser tube in place and attempting to remove it will require the tank to be
emptied and refilled. DO NOT try to remove the riser tube from a loaded tank.
The riser tube sits in an indentation centered in the bottom of the tank. With
the riser tube properly positioned, ensure that it is within 1/3 inch (8 mm)
above or below the lip of the tank. If it is not contact us for help
correcting the problem.
If your system came loaded – Start Here
1. ATTACH THE CONTROL HEAD
1. Lubricate the O-rings DO NOT use Vaseline
The tank O-ring——seals the control valve to the tank, and the pilot O-ring——seals around the riser tube. Verify they are present and free from nicks or kinks. Use a silicone lubricant or vegetable oil to both O-rings. DO NOT use petroleum based lubricants! Please note that the pilot O-ring is up inside the control head and you will usually have to reach up inside to feel it. It is very secure inside the head and almost impossible for it to come out. It is also a good idea to verify that the riser tube fits snugly into the pilot hole and that the O-ring seals around it.
Inspect and install dispersal basket
Air Injection Systems will have a top dispersal basket— used to facilitate the oxidation process. The larger end will be towards the bottom of the tank, with the cone pointing up. Push it down the riser tube until the top is about 1 inch (25 mm) below the bottom of the tank threads.
Screw on control head hand tight only
DO NOT apply anything (pipe dope, plumbers paste, Teflon tape, etc.) to the
threads on the control head or the resin tank!
Ensure the riser tube slips inside the pilot opening in the bottom of the head. Screw the head down onto the resin tank until solid contact is made between the tank and O-ring, then tighten about another 1/4–1/3 of a turn and STOP. Do not over tighten the control head as this can cause damage. Once properly tightened down check to ensure the tank and control head meet evenly all the way around.
1. SETUP CONTROL HEAD
1. Plug control head in
Plug the control head into a qualifying outlet as stated in the requirements section. Please Note: The control head can be plugged in and operated without water, this will not damage the control head. Once plugged in, verify the system is receiving power and ensure the outlet is not on a switch that might get turned off. On digital valves the display should light up and start flashing a time, on mechanical valves you may hear a quiet hum of the motor or you may have to wait to see if the time dial keeps track of time. Please note: The service icon (the icon that looks like a faucet) indicates that the system is IN SERVICE, that is the system is running and working. It DOES NOT indicate the system needs serviced.
DIGITAL CONTROLLER – Initial valve setup
For initial programming enter master programming by setting the clock to 12:01 pm. To set the time of day press and hold the up OR down arrow until the service icon is replaced with the programming icon. Use the up and down arrows to set the time of day (PM is indicated in the upper right corner of the screen). Hold the arrow button to advance quickly through the time. Once the time is set, press the extra cycle button to save the setting. Once the parameter display is gone, press and hold the up AND down arrow buttons together for 5-10 seconds until the programming icon appears and [DF] is shown in the parameter code. Once each setting has been entered, use the extra cycle button to advance to the next setting. Please Note: Most of these settings will be left alone.
Depending on your system some settings may not be shown, and some settings may be different than shown here. Do not change any settings unless specifically instructed to do so by these instructions or one of our techs.
E n s u r e the time is set to 12:01pm, hold BOTH up and down arrows until programming icon appears
| R e qu i r e d| This setting is required and
should be changed if it does not match
V a r iabl e| This setting will vary depending on the
system and application. Use these instructions to set appropr
P L E A SE NOTE:| Any setting on your system that is
not specifically highlighted below will be left at default. This is a list of
all pos will NOT be shown on your system and are included for informational
purposes only.
C od e| P a ra meter| Op t ions|
D e s c r iption
DF| ****
Display Format
| G A L| Volume is displayed in gallons and time in a 12-hour
AM/PM format – T hese instructions are based on the GAL setting
Ltr| Volume is displayed in liters and time in 24-hour format
VT| Valve Type| d F 1 b
– OR – AIO
| Downflow single backwash – used on air injection systems that require the
air draw. Some systems show an AIO option, but if that is not available use
the dF1b setting
Fltr| Filter – used for basic backwashing systems that do not need the air
draw
dF2b| Downflow double backwash – similar to the dF1b but with 2 backwashes.
Not commonly used.
UFbd| Upflow brine first – not commonly used.
UFtr| Uplow filter – not commonly used.
Othr| Other – not commonly used
CT| Control Type| FI| Metered (Flow) Immediate – counts down from the
programmed gallon capacity and begins a backwash immediately after reaching 0.
Only used on dual tank water softeners.
Fd| Metered (Flow) Delayed – counts down from the programmed gallon capacity
and when 0 is reached queues a backwash cycle for the set regeneration time.
Only used on water softeners.
Tc| Time Clock – will begin a backwash cycle at the set regeneration
time after the set number of days has passed. Common setting on all
backwashing systems except water softeners to ensure consistent cleaning of
the media.
| | dAY| Day of the Week – will begin a backwash cycle on the set day(s) at
the set regeneration time. More consistent Time Clock setting is recommended
in most situations.
---|---|---|---
NT| Number of Tanks| 1| For systems with only 1 media tank (all systems except
dual tank softeners).
2| For systems with 2 media tanks (dual tank softeners only).
UT| Indicates current tank in service| U1| Tank 1 is in service
U2| Tank 2 is in service (dual tank softeners only).
C| Capacity| 1-999.9 (x1000)| System capacity, in grains. Metered softeners
only.
H| Hardness| 1-199| Hardness of the water, in grains. Metered softeners only.
RS| Reserve Selection| SF| Percentage safety factor – this uses a percentage
of the capacity for a reserve. Softener systems only.
rc| Fixed reserve capacity – uses a set volume for a reserve. Softener systems
only.
SF|
Saftey Factor
| 0-50%| Only applies to softeners with RS set to SF
RC| Reserve Capacity| 1-(half of calculated capacity)| Fixed reserve capacity,
softeners only. It is commonly set to the average number of gallons used in a
day. If you are unsure of your actual usage, a good rule of thumb is to set it
to the number of people in the house times 75. Example, if there are 4 people
in the house, you would set it to 300 gallons (4×75).
DO| Day Override| 3| This setting will start the backwash cycle after
the set number of days. Typically set to 3 or less to ensure the media gets
lifted and cleaned off regularly. This ensures effective filtration and long
media life.If you have very dirty water or use large volumes of water you will
want to set this to 1 or 2. For Filox media: Filox media used in Platinum
systems requires backwashing at minimum every 2 days, with every night
recommended for best results.
RT| Regen Time| 12 : 0 0| This sets the time that the
backwash cycle will start. This process can take up to 2 hours depending on
system size and configuration, so schedule it when water will not be used. It
is common to set to run when everyone is asleep or out of the house, and
ensure it does not conflict with any other systems you may have.
BW| Backwash| 10| This sets the length of the backwash portion of the cycle.
During this cycle water flows through the system in reverse to lift the media
and rinse off accumulated contaminants, with a strong flow of water going out
the drain line. Reducing this cycle can lead to reduced media life and
premature system failure. For very dirty water longer times may be needed.
BD
-OR- AD
| Brine Draw
-OR-
Air Draw
| 60| This sets the length of the brine draw portion of the cycle. Air
injection systems may show AD, but BD functions the same way. During this
cycle a slow flow of water will go down the drain as the air pocket is created
in the tank.
RR| Rapid Rinse| 1| The rapid rinse cycle runs water through the tank in the
normal direction to get rid of excess air and settle the media for normal
operation. During this cycle there will be a steady flow of water down the
drain.
---|---|---|---
BF| Brine Fill| 0| ****
This sets the length of the brine fill portion of the cycle. On air injection systems this will be set to OFF.
D1- D7
| Day of the Week Setting| ****
OFF
| ****
Set to On or OFF for each dayof the week. Only applies to systems with Control Type dAY, not typically used.
CD
| ****
Current Day
| ****
1-7
| ****
Used to set the current day. Only applies to systems with Control Type dAY, not typically used.
FM| Flow Meter Type (metered systems only)| P0.7| 3/4″ Paddle Wheel Meter
Gen| Generic or Other Meter
P2.0| 2″ Paddle Wheel Meter
t1.5| 1.5″ Turbine Meter
P1.5| 1.5″ Paddle Wheel Meter
t1.2| 1.2″ Turbine Meter
t1.0| 1″ Turbine Meter
P1.0| 1″ Paddle Wheel Meter
t0.7| 3/4″ Turbine Meter
K| Meter Pulse Setting| 0.1-999.9| Pulses per gallon. Only applies to systems
with FM set to Gen, not typically used.
Pressing the extra cycle button after the final setting will save your
changes. If no buttons are pressed for 60 seconds while in programming mode
the changes will be cancelled.
I f you accidentally change a setting that does not have a recommended
or variable value: Please do a hard reset as outlined in the resets section to
return all values to default. You can then go back through the programming to
set it up according to the chart above.
Once you have finished programming use the arrows to set the current time of day. Once the time is set the display should then show the service icon, with the data display flashing between the current time of day and days remaining until the next backwash. Once it reaches 0 the system will queue a backwash for the set time. A flashing service icon indicates that a backwash is queued. A manual backwash can be queued by pressing the extra cycle button. An immediate backwash can be initiated by holding the extra cycle button for about 5 seconds. The service icon indicates that the system is “In Service” and functioning correctly, it does NOT mean that the system needs service.
After initial setup the master programming should not need to be used again unless a system reset is performed. Even in the event of a power outage all settings are retained. If your water use or water quality changes you can use the user programming to make common changes to the programming as lined out below
Ensure the time is NOT set to 12:01pm, hold BOTH up and down arrows until programming icon appears
Please refer to the master programming chart for proper values each setting.
Code| Parameter| Options| Description
DO| Day Override| 3| This setting will start the backwash cycle after the set
number of days.
RT| Regen Time| 2:00| This sets the time that the backwash cycle will start.
CD| Current Day| 1-7| Sets the current day (day of week systems only)
Pressing the extra cycle button after the final setting will save your
changes. If no buttons are pressed for 60 seconds while in programming mode
the changes will be cancelled.
SXT User Programming Chart
DIGITAL Controller – Resets
If your controller is showing odd behavior such as erratic display, no display, or showing an error code, the first step is to try and reset it. Start with the soft reset, and if that does not solve the problem move on to the master reset. If the problem persists contact one of our technicians.
Reset | Directions | Effect |
---|---|---|
Soft Reset | Hold Extra Cycle and Down buttons for 25 seconds | This will reset |
all parameters to the system default values, but leaves the days since the
last backwash intact. This is a good place to start if you feel you may have
changed a default setting. After resetting proceed through the master
programming section.
Hard Reset| Hold Extra Cycle button while plugging the unit in| This will
reset all parameters in the system. This is typically reserved for erratic
behavior that a soft reset does not resolve. After resetting proceed through
the master programming section.
Plumbing the system in
PLUMBING GUIDELINES
Before you continue Many homeowners install their own water systems with basic plumbing skills; if you are not comfortable with projects like this, please hire a professional plumber. Make sure to check local plumbing codes and follow any codes that apply. These instructions offer basic plumbing tips and can not cover every situation. They are intended as a supplement and should not replace local plumbing codes or actual plumbing experience.
Drain Line Connection
Please note: Drain water comes out under line pressure, so it can be run
vertically to connect to an overhead drain pipe.
Never make a direct connection into a waste water drain. A physical air gap of at least 3 inches (76 mm) between the end of the drain line and the wastewater level in the drain pipe should be used to avoid contamination of the line. An additional gap of 3/4 inch (19 mm) between the drain pipe and drain line is recommended to prevent any problems in the case of a pipe overflow. Using a simple P-trap as shown——is ideal as well, but a stand pipe with a diameter of at least 1.5 inches (38 mm) is adequate. As the water coming out is under pressure, make sure to secure the drain line so that it does not move and create a mess.
Do not tie multiple systems into a single drain line.
If hooking up multiple systems, each system needs a separate, independent
drain line to ensure proper operation and prevent damage. Systems can all be
run to the same standpipe/sump/outside drain, but the drain line from each
system needs to be separate.
Do not use additional fittings on the drain line.
Avoid installing any additional fittings (check valves, ball/gate valves,
etc.) as this can prevent proper backwash and cause premature system failure.
Inlet/Outlet Connections
Do not overtighten the screws. The bypass valve will have some up and down movement, this is normal. The clips simply hold the connection fittings together and the screws only need tightened enough to keep the clips in place. Further tightening will not stop leaks and tightening too much can damage the system, which will not be covered under warranty.
Verify flow direction. Untreated water will enter the system on the side marked with an arrow pointing toward the front of the control head (on both the bypass valve and the control head itself). The inlet side will have a check valve and water will flow through it into the tank, the side shown——will be facing you. (some models will have an arrow on the check valve itself, and the arrow should point toward the head). Treated water will exit the system on the side marked with an arrow pointing away from the front of the control head (on both the bypass valve and the control head itself).
Correct inlet/outlet connections are vital. Improper flow direction will prevent proper operation and can damage your system and your plumbing. The direction of flow can not be changed. Turning the bypass upside down will not change the direction of the water flow.
It is recommended to keep the bypass in the service position when making plumbing connections and turn it to bypass when first turning the water back on. shows the bypass position. In bypass position the handles will be turned 90-degrees and be perpendicular to the inlet and outlet fittings.
When soldering do not solder directly to the included connection or close to the control control head. First solder a short (min 3-inch [7.6-cm]) piece of copper pipe onto the adapters, away from the valve, before connecting the adapter to the bypass or yoke fitting.
For threaded connections, do NOT tighten the adapters into fittings while they are connected to the control head. Disconnect the bypass or yoke fitting, and connect the adapter using a high quality thread sealant (pipe joint compound or Teflon/PTFE tape), and replace.
When installed the bypass valve can move up and down, this is normal.
PLACE SYSTEM IN SERVICE
Once all plumbing is done and plumbing connections have been checked for leaks you can place the system in service.
Open bypass valve slowly
If you have more than one system, enure the other systems are bypassed to
prevent any possible problems. Open a faucet that is near the system, a
laundry sink or outside faucet (if it will be treated by the system) is ideal,
this will allow the air to bleed out of the system. Slowly open up the bypass
valve just to the point of allowing water to enter the system at a trickle,
and leave it like that until the tank is full of water. If you prefilled the
system it should only take a minute or two. Once the tank is full, slowly open
the bypass valve the rest of the way. Allow water to run out of the faucet for
15-20 minutes to ensure all the air is worked out of the tank and off of the ,
then close the faucet.
Check for leaks
Check the system for any leaks, paying attention to the seal between the tank and control head as well as the connections between the bypass valve and control head. Open a nearby faucet and check to ensure there is no leaks that show up when water is running.
Flush the system
Open a nearby faucet. The water may be discolored at first, this is normal.
Let water run out of the faucet for at least 10 minutes, or until any
discoloration clears up. Depending on the system this may be almost immediate,
or it may take a couple of hours. Once the water is cleared up a manual
backwash should be run.
Initiate manual backwash
It is a good idea to allow the system to run through a manual cycle. On
mechanical valves, turn the main knob until it clicks into the first position.
On digital systems, hold the extra cycle button for 5-10 second until the
backwash starts.
Verify proper operation
Watch the system as it steps through each cycle, make sure it moves to each
position, that water is not leaking from any other fittings, and that water is
flowing down the drain line.
Frequently Asked Questions
INVENTORY AND SETUP
What is the proper order to arrange multiple systems?
If you are installing more than one tank system the typical order for
installation is: sediment filter > pH filter > iron filter > carbon filter >
water softener > arsenic filter Whole house cartridge systems are typically
installed after any tank systems, the Scale Sentry system after the cartridge
system(s), and any UV systems will be last.
Do I need a prefilter?
In most cases a prefilter is not necessary. Since the system cleans itself
most particulate in the water will be trapped and rinsed off by the backwash
cycle, eliminating the need for a sediment prefilter.
My polyglass tank arrived and sits crooked, what do I do?
The black boot on the bottom of the tank may get knocked out of alignment
during shipment. If your tank is a bit tilted, simply pick the tank up 2–3
inches (5–8 cm) off the floor and drop it gently but firmly down, favoring the
side that needs to be adjusted to make the tank stand straight.
After installing the bypass it still moves up and down, is that normal?
Yes. The bypass seals with O-ring and even when tightened down some movement
will occur, without leaking. The system requires this movement to allow for
pressure changes in the system. Do not overtighten the bypass valve. As long
as the screws are snug enough to keep the bypass from coming apart further
tightening will just cause damage.
DRAIN LINE
Can I run my drain line to a sewer/septic?
Yes. These systems can be ran to your sewer or septic line and is typically
the recommended place to run the drain. Most concerns are related to the
amount of water going down the drain, and a properly designed septic/sewer
system will not have a problem handling it.
Can my drain line be ran vertically?
Yes. Water from the drain comes out under pressure and can be ran vertically
if needed.
DIGITAL DISPLAY
Why does my display flashing between the time of day and a number?
This is normal, with the number displayed indicating the number of days until
the next backwash.
What does the faucet icon mean?
That is the service icon, meaning the system is in service. It does NOT mean
the system needs service. If it is flashing then a backwash is queued for the
next set time.
What does the water drop icon mean?
That is the flow icon. Only used on metered softeners, it indicates water is
flowing through the system.
What does the circled exclamation icon mean?
That indicates an error. Match the number on your display with the number on
the error chart below for troubleshooting tips.
Error Code | Error Type | Cause | Solution |
---|---|---|---|
0 | Cam Sense Error | Piston took more than 6 minutes to advance | Unplug the |
system, disconnect the piston from the motor/gear, and verify that the piston
moves freely inside the valve; if it does not replacement of the seal and
spacers and possibly the piston is required. After reconnecting the piston,
inspect the control head for any broken, worn, or disconnected parts, and
replace or reconnect any that are found. Perform a hard reset. After verifying
programming run the system through a backwash and watch the motor to ensure
that it is moving the piston, if it is not the motor needs to be replaced. If
error still occurs contact us for support.
1| Cycle Step Error| Unexpected cycle input| Unplug the system and check to
ensure all electrical connections and cam switches are secure. Plug the unit
back in and check the master programming and ensure valve type and system type
are correct for your system. Initiate a manual regeneration and verify it
progresses through the steps correctly. If error reoccurs, contact us for
support.
2| Regen Failure| More than 99 days since last backwash (7 on day of the week
setups)| Perform a manual backwash to reset the error. Check your settings to
ensure the system is setup to backwash automatically. Check the meter to
ensure it is not stuck and that the gallons remaining is counting down.
3| Memory Error| Circuit board memory failure| Perform a hard reset and go
through the master programming to update the settings. If error occurs again
contact us for support
---|---|---|---
UD| Upper Drive Sync| Piston is syncing| Common when changing programming or
if system loses power. System will automatically recover from this state.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>