Honeywell Home T10 Smart Home Thermostat Instructions
- June 14, 2024
- Honeywell Home
Table of Contents
Honeywell Home T10 Smart Home Thermostat
Product Information
Specifications
- Model Numbers:
- YTHM1004R3000: Kit with T10+ Thermostat, EIM, Wireless Indoor Sensor, & Wired Discharge and Return Sensors
- YTHM1004R3001: Kit with T10+ Thermostat, EIM, Wireless Indoor Sensor, wireless outdoor sensor, and wired Discharge and Return Sensors
Product Usage Instructions
Dry Contact Alerts
A Dry Contact device such as a wet switch can be connected to the S1, S2, S3,
or S4 terminals at the Equipment Interface Module. When the dry contact device
detects a problem, the thermostat displays an alert on the home screen along
with the dealer information.
Notifications
- Water Leak Alert: When the dry contact device detects a water leak, the thermostat alerts the user.
- System Shutdown Alert: A problem with the system was detected and it has been shut down. Contact your dealer for service.
- Full Drain Pan Alert: When the dry contact device detects that the condensation drain pan is full, the thermostat provides an alert to the user.
- Dirty Filter Alert: When the dry contact device detects a dirty air filter (pressure drop across the filter), and the thermostat alerts the user to replace the filter.
- Service Needed Alert: When the dry contact device detects an issue that requires service, the thermostat provides an alert to the user.
- Fan Failure Alert: The Fan Failure Alert protects the equipment when there is no airflow. When the dry contact device (for example, sail switch) detects no airflow for 5 minutes after a call for forced air heat, cool, or fan, the thermostat alerts the user that the system was shut down due to a lack of airflow.
- Custom Alert: Allows the dealer to enter a custom alert to be displayed when a dry contact device is\ activated. For example, a float switch can detect when your sump pump is not working.
Dry Contact Setup Example
- Select the Dry Contacts in the System
- Enable specific alerts such as Full Drain Pan Alert or Dirty Filter Alert
- Configure follow-up settings for each alert, such as shutting off the system or just sending an alert message
Frequently Asked Questions (FAQ)
-
Q: How do I connect a Dry Contact device to the T10+ with EIM?
A: Connect the Dry Contact device to one of the S1, S2, S3, or S4 terminals at the Equipment Interface Module. -
Q: What happens when a water leak is detected?
A: The thermostat alerts the user about the water leak. -
Q: Can I configure the T10+ to control a humidifier when a water leak alert is active?
A: Yes, there is a follow-up setting that allows you to choose whether to shut off the humidifier or just send an alert message. -
Q: What should I do if the system is shut down due to a problem?
A: Contact your dealer for service. -
Q: How does the Full Drain Pan Alert work?
A: When the dry contact device detects that the condensation drain pan is full, the thermostat provides an alert to the user. You can choose to configure the follow-up setting to either shut off the system or just send an alert message. -
Q: How does the Dirty Filter Alert work?
A: When the dry contact device detects a dirty air filter (pressure drop across the filter), the thermostat alerts the user to replace the filter. -
Q: What happens when a critical problem is detected with the system?
A: The thermostat alerts the user that the system is shut down. The system will not call for heating, cooling, fan, or IAQ equipment until the dry contact is deactivated or the feature is no longer configured at the thermostat. -
Q: What is a Fan Failure Alert?
A: The Fan Failure Alert protects the equipment when there is no airflow. If the dry contact device (e.g., sail switch) detects no airflow for 5 minutes after a call for forced air heat, cool, or fan, the thermostat alerts the user that the system was shut down due to a lack of airflow. The thermostat will call for the fan and lock out all other equipment until the dry contact device senses airflow again or the feature is no longer configured at the thermostat.
Applies to the following Model Numbers:
- YTHM1004R3000: Kit with T10+ Thermostat, EIM, Wireless Indoor Sensor, & Wired Discharge and Return Sensors
- YTHM1004R3001: Kit with T10+ Thermostat, EIM, Wireless Indoor Sensor, wireless outdoor sensor, & Wired Discharge and Return Sensors
Dry Contact Alerts
A Dry Contact device such as a wet switch can be connected to the S1, S2, S3, or S4 terminals at the Equipment Interface Module. When the dry contact device detects a problem, the thermostat displays an alert on the home screen along with the dealer information.
When the user presses the alert for more information, the notification screen is displayed, prompting them to contact their dealer.
The following dry contact alerts are available for the T10+ with EIM:
-
Full Drain Pan Alert
- When the dry contact device detects that the condensation drain pan is full, the thermostat provides an alert to the user.
- NOTE: When a full drain pan alert is selected, there is a follow-up setting asking if you want to shut off the system when this alert is active or just send the alert message.
-
Dirty Filter Alert
When the dry contact device detects a dirty air filter (pressure drop across the filter), the thermostat alerts the user to replace the filter. -
Dry Contact Setup Example
-
Water Leak Alert
- When the dry contact device detects a water leak, the thermostat alerts the user.
- NOTE: When a water leak alert is selected, and the T10+ is configured to control a humidifier there is a follow-up setting asking if you want to shut off the humidifier when this alert is active or just send the alert message.
-
System Shutdown Alert
When the dry contact device detects a critical problem with the system, the thermostat alerts the user that the system is shut down. When the dry contact device detects a problem with the system (for example, smoke detection), the thermostat will not call for heating, cooling, fan, or IAQ equipment until the dry contact is deactivated or the feature is no longer configured at the thermostat. -
Service Needed Alert
When the dry contact device detects an issue that requires service, the thermostat provides an alert to the user. -
Fan Failure Alert
The Fan Failure Alert protects the equipment when there is no airflow. When the dry contact device (for example, sail switch) detects no airflow for 5 minutes after a call for forced air heat, cool, or fan, the thermostat alerts the user that the system was shut down due to a lack of airflow. The thermostat will call for the fan and lock out all other equipment until the dry contact device senses air flow again or the feature is no longer configured at the thermostat. -
Custom Alert
Allows the dealer to enter a custom alert to be displayed when a dry contact device is activated. For example, a float switch can detect when your sump pump is not working.
Custom Alerts 1 through 4
Allows the dealer to enter a custom alert to be displayed when a dry contact device is activated. For example, a float switch can detect when your sump pump is not working.
When Custom Alert 1 through Custom Alert 4 is selected in ISU 6005, the T10+ asks you to name the alert and then gives options for additional settings related to the alert. These settings are:
-
Which set of S terminals on the EIM the dry contact alert is wired to (ISU 6190). There are four (4) sets of configurable S terminals on the EIM. If a set of S terminals is already configured for use by a different dry contact alert (or sensor), it will not be configurable.
-
Whether the switch wired to these terminals is normally open or closed (ISU 6200). The switch wired to the S terminals could either be open in normal (not alert) conditions or closed.
-
Enter the dry contact alert name (ISU 6210).
-
Whether there is an alert message displayed when the alert is active (ISU 6215). In most cases, the installer would want an alert message to appear on the T10+ if there was a dry contact alert active. However, the installer may be using the “alert” to do some other action (like running a ventilator when a sensor is reading high CO2). This may be a normal operation and they may not wish to show an alert.
-
Lock Out Heat or Lock Out Cool (ISUs 6230, 6340, 6440, 6540)
If the installer previously chose to lock out heat or cool on a custom dry contact alert condition, The T10+ will then ask if:- You want a delay before the lockout (ISU 6600 or 6620). For example, if someone was using a door sensor to lock out cooling, you wouldn’t want to short-cycle the cooling every time someone enters or exits. But if the door is left open for a certain length of time, you may wish to shut down the heat or cooling.
- If you still want a maximum temperature for cool (ISU 6610) or a minimum indoor temperature for heat (ISU 6630). Example: If someone had a heat lockout configured when the window was open, they left the window open, and the indoor temperature dropped to 40°F, you probably still want the heat to run because the danger of pipes freezing overrides the inefficient use of heating with a window open
-
Activate Fan (ISUs 6230, 6340, 6440, 6540)
If selected, this setting turns on the fan when the selected custom dry contact alert (custom dry contact 1 through 4) is active. -
Activate Custom U terminal (ISUs 6230, 6340, 6440, 6540)
If you choose to activate a custom U terminal during a custom alert, the T10+ will ask you to name the U terminals used. That way the T10+ equipment status menu can show what is being turned on or locked out. For example, you could wire a shut-off valve to the U contacts and the status would then show “Shut off valve energized” under the equipment status -
Humidifier Lockout (ISU 8095)
If the T10+ and EIM are set for a custom dry contact alert and to control a humidifier, you can choose to lock out the humidifier during a custom dry contact alert (the water leak alert option also offers this setting) -
Dehumidifier Lockout (ISU 9145)
If the T10+ and EIM are set for a custom dry contact alert and to control a dehumidifier, you can choose to lock out the dehumidifier during a custom dry contact alert. -
Turn On Ventilator (ISU 10065)
If the T10+ and EIM are set for a custom dry contact alert and to control a ventilator, you can choose to turn on the ventilator during a custom dry contact alert. -
Lockout Ventilator (ISU 10140)
If the T10+ and EIM are set for a custom dry contact alert and to control a ventilator, you can choose to lock out the ventilator during a custom dry contact alert
Installer Setup (ISU)
NOTES:
- For this file, only the dry contact ISU settings are shown. Full ISU settings are found in the product data sheets located at: https://customer.resideo.com/resources/Techlit/TechLitDocuments/33-00000s/33-00462.pdf.
- The firmware is occasionally updated over the air (OTA) from the factory. To ensure the latest firmware updates are installed, confirm the thermostat is connected to a stable WiFi connection. Some ISU settings may not be shown on models that don’t have the latest firmware.
ISU #| Heading| Question| Options| Contingent Previous Setting?| EIM
Needed?
| T10, T10+,
or Both
| Notes
---|---|---|---|---|---|---|---
6000| Dry Contact Alerts| Select dry contact alerts| Full Drain Pan Alert,
Dirty Filter Alert, Water Leak Alert, System Shutdown Alert, Service Needed
Alert, Fan Failure Alert.| | Yes| T10+| See dry contact alert for operation
details
6005| Dry Contact Alerts| Select dry contact alerts| Custom Alert 1, Custom
Alert 2, Custom Alert 3, Custom
Alert 4
| | Yes| T10+| See dry contact alert for operation details
6050| Dry Contacts| What terminals are wired to the full drain pan alert dry
contact?| None, EIM S1, EIM S2, EIM S3, EIM S4| 6000 has full drain pan
selected| Yes| T10+| See dry contact alert for operation details
6060| Dry Contacts| Full drain pan alert dry contact setup| Normally Open,
Normally Closed| Yes| T10+
6065| Dry Contacts| Full drain pan alert dry contact actions| System shutdown
(select or de-select)| Yes| T10+
6070| Dry Contacts| What terminals are wired to the Dirty filter alert dry
contact?| None, EIM S1, EIM S2, EIM S3, EIM S4| 6000 has dirty air filter
selected| Yes| T10+| See dry contact alert for operation details
6080| Dry Contacts| Dirty filter alert dry contact setup| Normally Open,
Normally Closed| Yes| T10+
6090| Dry Contacts| What terminals are wired to the water leak alert dry
contacts?| None, EIM S1, EIM S2, EIM S3, EIM S4| 6000 has water leak selected|
Yes| T10+| See dry contact alert for operation details
6100| Dry Contacts| Water leak alert dry contact setup| Normally Open,
Normally Closed| Yes| T10+
6110| Dry Contacts| What terminals are wired to the system shutdown alert dry
contact?| None, EIM S1, EIM S2, EIM S3, EIM S4| 6000 has system shutdown alert
selected| Yes| T10+| See dry contact alert for operation details
6120| Dry Contacts| System shutdown alert dry contact setup| Normally Open,
Normally Closed| Yes| T10+
6130| Dry Contacts| What terminals are wired to the service needed alert dry
contact?| None, EIM S1, EIM S2, EIM S3, EIM S4| 6000 has service needed alert
selected| Yes| T10+| See dry contact alert for operation details
6140| Dry Contacts| Service needed alert dry contact setup| Normally Open,
Normally Closed| Yes| T10+
6150| Dry Contacts| What terminals are wired to the fan failure alert dry
contact?| None, EIM S1, EIM S2, EIM S3, EIM S4| 6000 has fan failure alert
selected| Yes| T10+| See dry contact alert for operation details
6160| Dry Contacts| Fan failure alert dry contact setup| Normally Open,
Normally Closed| Yes| T10+
6190| Dry Contacts| What terminals are wired to the custom alert 1 dry
contact?| None, EIM S1, EIM S2, EIM S3, EIM S4| 6005 has custom
alert 1 selected
| Yes| T10+| See dry contact alert for operation details
6200| Dry Contacts| Custom alert 1 dry contact setup| Normally Open, Normally
Closed| Yes| T10+
6210| Dry Contacts| Custom alert 1 name| Type in the alert name| Yes| T10+
6215| Dry Contacts| Show custom alert 1 message| Yes, No| Yes| T10+| Will an
alert message be shown on display when alert 1 is active?
6220| Dry Contacts| Custom alert 1 message| Type in the message displayed when
this alert is active| 6215 is set to Yes| Yes| T10+| See dry contact alert for
operation details
6230| Dry Contacts| Custom alert 1 actions| Lockout Heat, Lockout Cool,
Activate Fan, Activate Custom U Terminal| 6005 has custom
alert 1 selected
| Yes| T10+
6240| Dry Contacts| What terminals are wired to Custom U contact?| EIM U1, EIM
U2, EIM U3| 6230 has Custom U terminal selected| Yes| T10+| When the switch
wired to S1 for dry contact alert activates, the Custom U contacts will change
state to activate or shut off whatever is wired to those terminals.
---|---|---|---|---|---|---|---
6250| Dry Contacts| Custom U dry contact name| Type in the name of what the
Custom U dry contact is controlling| Yes| T10+
6260| Dry Contacts| Custom U dry contact setup| Normally Open, Normally
Closed| Yes| T10+
6300 –
6340
| These are duplicate settings to 6200-6260, but for dry contact alert 2 (if selected)| 6005 has custom
alert 2 selected
| Yes| T10+|
6400-
6440
| These are duplicate settings to 6200-6260, but for dry contact alert 3 (if selected)| 6005 has custom
alert 3 selected
| Yes| T10+|
6500 –
6540
| These are duplicate settings to 6200-6260, but for dry contact alert 4 (if selected)| 6005 has custom
alert 4 selected
| Yes| T10+|
6600| Dry Contacts| Cool Lockout Delay Time| Off, 5-60 minutes in 5 minute
increments| 6230, 6340, 6440,
or 6540 set to lock out cool
| Yes| T10+| See dry contact alert section for operation details
6610| Dry Contacts| Cool lockout maximum indoor temperature| None, 80°F –
99°F| Yes| T10+
6620| Dry Contacts| Heat Lockout Delay Time| Off, 5-60 minutes in 5 minute
increments| 6230, 6340, 6440,
or 6540 set to lock out heat
| Yes| T10+| See dry contact alert section for operation details
6630| Dry Contacts| Heat lockout minimum indoor temperature| None, 40°F –
60°F| Yes| T10+
6640| Dry Contacts| Custom U Contact Minimum Off Time| Off, 1-5 minutes| 6240
set to U1, U2, or U3.| Yes| T10+|
8095| Humidification| Humidifier Lockout Dry Contacts| Full drain pan, water
leak, Custom Alert 1 – 4 (options
depend on 6000 or 6005 settings)
| 8000 = steam, bypass or fan powered.
6000 = full drain pan, water leak. 6005 = custom dry contact alert
| Yes| T10+| This will lock out the humidifier when the associated dry
contact alert is active
9145| Dehumidification| Dehumidifier Lockout Dry Contact| Custom Alert 1 – 4
(options depend on 6005 settings)| ISU 6005 is set for a custom dry contact
alert| Yes| T10+| If enabled, the dehumidifier will lock out whenever the
selected dry contact alert is active
10065| Ventilation| Turn on ventilation dry contacts| Custom Alert 1 – 4
(options depend on 6005 settings)| ISU 6005 is set for a custom dry contact
alert & ISU 10145 is not selected for the same custom alert.| Yes| T10+| If
enabled, the ventilator will come on whenever the selected dry contact alert
is active
10145| Ventilation| Ventilation lockout dry contacts| Custom Alert 1 – 4
(options depend on 6005 settings)| ISU 6005 is set for a custom dry contact
alert & ISU 10065 isn’t selected for the same custom alert.| Yes| T10+| If
enabled, the ventilator will be locked out whenever the selected dry contact
alert is active.
Setting Custom Dry Contact Alerts for the T10+ with EIM
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
33-00646-01 K.K. 03-23 | Printed in United States.
© 2023 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell
International, Inc. This product is manufactured by Resideo Technologies, Inc.
and its affiliates. www.resideo.com.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>