GLOBAL SOURCES 2453707 Ulta Freezer User Manual

June 14, 2024
global sources

GLOBAL SOURCES 2453707 Ulta Freezer

Specifications

  • Model: TM
  • Temperature: Low
  • Power Supply: Dedicated power supply marked on the product label
  • Voltage: Rated voltage (with specific requirements for higher voltage
  • Power Cord: ULT unit equipped with a standard three-prong power plug

Precautions for Safe Operation

Electric Shock Risk

  • Failure to observe WARNING signs could result in a hazard to personnel possibly resulting in serious injury or death.
  • Failure to observe CAUTION signs could result in injury to personnel and damage to the unit and associated property.

Grounding

  • Your ULT unit must be properly grounded in conformity with national and local electrical codes.
  • Dedicated power lines with individual breakers are highly recommended.
  • A loose plug in the socket may cause fire.
  • Never use gas lines, water mains, telephone lines, or lightning rods as the grounding device for your ULT unit. This type of improper grounding may cause electric shock or other danger.

Precautions for safe operation

Warning Failure to observe WARNING signs could result in a hazard to personnel possibly resulting in serious injury or death.
Caution Failure to observe CAUTION signs could result in injury to personnel and damage to the unit and associated property.

Actions or operations which are prohibited
Actions or operations which must be followed

  • When CO2/LN2 backup is activated, the location place must be well ventilated. Increased CO2 in the air may be harmful and even fatal. If the ventilation is poor, other methods should be considered in order to ensure safe working environments.
  • If there is a leakage of petroleum gas or other flammable gas, close the gas supply valve and open doors and windows to ventilate the air. Do not plug or unplug your freezer unit in order to avoid potential explosion or fire.
  • Only professional technicians or service personnel can install the unit.Failure to do so may cause electric shock or result in a fire hazard.
  • The freezer must be securely installed on a firm floor. On an uneven surface may result in the product tipping over thereby causing injury and damage.
  • Please use the dedicated power supply marked on the product label to avoid fire and electric shock.
  • If the voltage being used is 10% higher than the rated voltage, a regulator with a capacity of 4000 W or higher must be installed.
  • If the power cord needs to be extended, the cross-section of the extended cable must be no less than 14Awg and no longer than 9ft for products of 220V~240V/50Hz or 220V~/60Hz and no less than 12Awg and no longer than 3m for products of 115V~/60Hz to avoid fire or electric shock.
  • Your ULT unit is equipped with a standard three-prong power plug (grounded) complying with the standard three-prong socket (grounded) rated 10A .Your unit must be properly grounded in conformity with national and local electrical codes. Dedicated power lines with individual breakers are highly recommended. A loose plug in the socket may cause fire.
  • Never install your ULT in an outdoor area. If the unit is exposed to moisture, there is a danger of electric shock.
  • Your ULT must not be installed in a damp area or an area subjected to water spray, as may reduce the degree of insulation and thereby cause electrical leakage or electrical shock.
  • Never directly pour water into the unit. The water may cause electrical shock or short circuit.
  • Do not place heavy objects on top of the unit, as a falling object may cause injury.
  • Never use gas lines, water mains, telephone lines or lightning rods as the grounding device for you ULT unit. This type of improper grounding may cause electric shock or other danger.
  • When unplugging the power cord from the socket, please grip the plug itself and pull it out. Manufacturer should provide test data on Plug Pullout passing.
  • Should there be any Malfunction in the equipment, power off the unit and unplug the power cord from the power supply. Continued operation in an abnormal condition may result in electric shock and fire.
  • User must not dismantle, repair or modify the equipment. Such operations may result in fire or personal injury.
  • Before any repair and maintenance of the freezer, please disconnect the power to avoid electric shock or injury to personnel.
  • When repairing and maintaining your freezer, take precautions to work in a well-ventilated area.
  • If the unit is not to be in use for a long period of time, make sure the power cord is unplugged.
  • The freezer needs to be disposed by specialized personnel.
  • Do not use any unapproved electrical components with the freezer.

Technical data

Model

| Ambient temperature

(℃)

| Electric protection type|

Temperature range(℃)

| Rated voltage

(V)

| Rated frequency

(Hz)

---|---|---|---|---|---
2453707| 1/1| I| -40~-86| 120| 60

Model

| Effective volume

(Cu. Ft)

| Input power

(W)

| Power consumption

(KW/24H)

| Weight

(Kg)

|

External dimension WxDxH(inch)

---|---|---|---|---|---
2453707| 3.5| 680| 5.5| 108| 30x26x32

Packing List

Name                                                                 Quantity| 2453707
---|---
Warranty Card/Installation and Commissioning Manual| 1/1
User manual/Position Installation Methods| 1/1
Plastic bag| 1
Ice scraper| 1
Key| 4
Position limiter| 2

Accessary Packing List

Specification

Name ULT Freezer
Model 2453707

External dimension

WxDxH(inch)

|

30x26x32

Enclosure / inner wall| Pure-polyester coated steel plate
Outer door| Pure-polyester coated steel plate
Inner door| Stainless steel
Shelf| Stainless steel
Test hole| 1
Thermal insulation| VIP + polyarethane foam
Compressor| Hermetically sealed
Evaporator| Copper tube
Condenser| Micro-channel type
Refrigerant| R600a R1150 R50
Temperature controller| Microprocesser controller
Temperature display| Digital display
Noise| 46.8dB(A)
Temperature sensor| Platinum resistor (Pt100)

Alarm device

| High/low temperature alarm, sensor fault alarm, power failure alarm, dirty condenser filter alarm, ambient temperature alarm, low battery alarm and door open alarm
Remote alarm terminal battery| Maximam load: DC 30V, 2A Rechargeable battery, DC12V, automatic charging
Foaming Cabinet| HFO-1233zde
USB| Standard
Software version| V2

  • Never store flammable, explosive or volatile materials in the unit, nor use any flammable spray near the unit, as this may cause an explosion or fire.

  • Never store corrosive chemicals with acid or alkaline properties in the unit, as this can lead to damage to internal components of the unit.

  • Do not use any glass containers with the unit. These containers may crack at low temperatures and cause injury.

  • Do not climb on top of the unit or place any object on it. Falling equipment may cause injury or property damage.

  • Do not use any hard objects such as nails and wires in opening or gaps such as air ventilation ports. Accidental contact between a hard object and a moving part may result in electric shock or injury.

  • After restarting your unit from a power outage or shutdown, ensure that all setting are correct. Accidental changes in settings may damage the stored products.

  • In the event of a power outage and recovery, wait for at least 5 minutes before turning the unit on again to avoid damage to compressors and refrigeration system.

  • The air filter for the condenser should be cleaned regularly according to the manual
    instruction. A dirty filter could cause a malfunction or the freezer temperature to rise.

  • During any repair operations, gloves should be worn to prevent getting injured by sharp edges or corners.

  • Do not use bare hands to directly handle any stored products always use cryogenic gloves. The cold temperature of products and the interior walls may cause frostbites.

  • Do not tilt the unit more than 45 degrees when moving it.

  • Do not attempt to use the handle to lift or move the unit to avoid damaging the freezer or injuring personnel.

  • We recommend the unit be installed and maintained by a professional to avoid any electrical hazard. The replacement of any spare parts(battery) shall be conduct by service technicians .

  • Keep all ventilation clear of obstruction.

  • Do not use mechanical devices or other means to accelerate the defrosting process, other than those recommended by the manufacturer.

  • Do not damage the refrigerant circuit.

  • Disposal of the equipment and refrigerant according to national and local ordinances when pursuing.

  • The instructions for split-systems that use a flammable refrigerant shall include the substance of the following warning:

  • In order to reduce flammability hazards the installation of this equipment shall only be carried out by a suitably qualified person.

Product Features

This product can be used by clinical, pharmaceutical, scientific research, quarantine departments, etc. for the preservation of articles under low temperature.

  1. Temperature control
    Temperature is controlled by computer and numerically displayed and regulated in units of 1°C; temperature range: -40°C to -86°C.

  2. Safety system

  3. Various malfunction alarms (high temperature alarm, power failure alarm, probe failure alarm, hot condenser alarm, high ambient temperature alarm, doors open alarm, low battery alarm).

  4. Two types of alarms (Buzzer sounding alarm, Flashing light alarm).

  5. Protective functions (password protection, power up delay protection).

  6. All independent components are safely grounded.

  7.  Refrigeration system

  8. Optimized auto-cascade refrigeration technology and compressor, ensuring stronger refrigeration capacity.

  9. High-performance insulation layer, ensuring excellent thermal insulation effect.

  10. Unique multi-layer door sealing structure and anti-condensation heating technology, effectively reducing frosting.

  11. Scope of application: applies to the preservation of articles by clinical, pharmaceutical,scientific research, quarantine departments, etc. under low temperature.

  12. 31.8 inch cabinet, placeable under the laboratory bench, saving the storage space.

  13. Ergonomic design

  14. LED display screen, showing temperature inside the box, ambient temperature and input voltage, settable high/low temperature alarm and temperature inside the box, having fault warning function.

  15. Adjustable shelf design, convenient for storage of articles.

  16. Safety door lock to prevent opening at will.

  17. Wide climate zone design, suitable for the environment ranging from 10°C to 32°C.

  18. “Innovative” integration of lock and handle and compact caster design, ensuring flexibility and convenience.

  19. Intelligent condenser fan start and stop, saving energy effectively.

  20. Advanced and practical network and remote warning.

Not all models have all features mentioned above. For specific features, please refer to the specification table of each specific model. Due to the product improvement, images may not always be entirely representative of the actual products.

Circuit diagram

Refrigeration principle and circuit diagram

Refrigeration schematic diagram

Usage Precautions

  • When the unit operates normally, the unit frame at the front near the door may be slightly warm; This is normal because hot tubing is embedded there to prevent condensation from forming on the frame.
  • Before samples are loaded into the unit, make sure the unit temperature has reached the set point then load the samples into the freezer in batches. Load from the bottom of the unit to the top, one shelf at a time. Allow for enough time for internal temperature to stabilize between loading.
  • The temperature display indicates the temperature from the sensor location inside the unit chamber, which may vary from the temperature at the center of the freezer but will gradually reach the actual temperature of the freezer over time.
  • Two access ports are installed in the back wall of the unit which can be used as the pass-thru for thermocouple wires during testing and validation. Once all test wires are through the access port, make sure that the gap in the port is sealed properly with insulation materials. Failure to seal the access port may affect the operation of the unit. The port ring in the outer wall can also accumulate frost and ice.
  • When cleaning the unit, mild or neutral detergent solution should be used. Never use a hard wire brush, acid, gasoline, powder detergent, polishing powder, or hot water to clean the freezer, as these tools and materials can damage the paint coating and plastic components. Never use gasoline or solution with volatile chemicals to clean plastic or rubber parts.
  • After the freezer runs for some time, a layer of frost usually forms on the interior liner and inner doors. When this layer of frost becomes too thick, it can negatively impact the refrigeration performance of the unit. Energy consumption can increase.If the thickness reaches about 5 m/3/10in, use the supplied scraper to remove the frost.
  • Before removing the frost, temporarily transfer the stored samples to another freezer to prevent rising temperature from damaging the samples.
  • Behind the interior walls, there are many refrigeration lines. Do not use a knife, an ice pick, or a screwdriver to cut ice and frost. This may damage not only the liner but also the refrigeration tubes.
  • If the freezer is not in use for a period of time, turn off the power and backup battery.The power cord should be unplugged.

Electromagnetic compatibility requirements:

  • a) This machine complies with the emission and immunity requirements specified in EN 61326-1.
  • b) This machine is designed and tested as Class A equipment specified in CISPR. In domestic situations, this machine may cause radio interference and protective measures shall be taken.
  • c) It is recommended to evaluate the electromagnetic environment before using the machine.
  • d ) It is prohibited to use this machine near strong sources of radiation (such as unshielded video sources), otherwise it may interfere with normal operation of this machine.

Product Installation

Installation environment

  • Ambient temperature: 10°C to 32°C. The ideal temperature is 18°C to 25°C. If necessary, use an air- conditioning system to achieve the requires ambient condition.
  • Environment humidity: less than 80%RH. At an environment of 32°C, humidity should be less than 57%RH.
  • Avoid large amounts of dust.
  • Avoid mechanical swing or vibration.
  • Highest recommended elevation for safe usage: 2,000m above sea level.
  • Input voltage : rated voltage ± 10%.
  • The transient state is Category II facility(overvoltage category).
  • Pollution Degree: 2.

Caution

  • An ULT is sensitive to its operating environment. If a unit is not installed in the conditions mentioned above, it may not operate reliably.
  • The unit is intended for indoor use only.

Installation site
For the equipment to achieve optimal operating conditions, an intended installation location should satisfy the following requirements.

  • Do not install the unit in a confined space. The doorway should be large enough for the unit to freely be transferred in or out of the room if necessary.
  • The location for installation should be level.
  • Installation area should be well ventilated without direct sunlight.
  • The freezer unit cannot share the same power socket with other equipment. The power plug should be securely connected to the power socket.
  • The power cord for the freezer should not be twisted or pinched.
  • If the power cord needs to be extended, the cross-section of the extended cable must be no thinner than 2mm(14 gauge wire) and no longer than 3m(9.8ft).
  • Before using the freezer, check the voltage supply. A voltage stabilizer to deliver rated voltage ± 10% is recommended for areas in which the voltage is known to be unstable. The voltage stabilizer should be rated at least 4000W.
  • The freezer must be grounded.
  • If the power socket is connected with a ground terminal, make sure to inspect it for proper connection before using the equipment.

Trouble Shooting

info: Please take below chart as reference for some common malfunction.

Fault Troubleshooting solution

Start failure of the box

| Is the power connection correct and is the power switch in “ON” position?
Is the power voltage too low?
Check whether there is an input voltage externally.

Poor cooling

| Is ambient temperature too high?
Check whether the inner door is closed tightly. Is the outer door is closed? (Frost between the box and the door gasket may damage the sealing of the door)
Is the condenser filter screen clogged?
Is the temperature set correctly?
Is the freezer away from the direct sunlight?
Is the freezer close to the heat source?
Are the rubber cover and insulation material for test hole are installed and placed correctly?
Are a lot of high-temperature articles contained in the freezer for a short time?

Noise

| Is the installed on the solid and flat ground?
Does the enclosure contact with other articles?
Is the leveled by horizontal stand bar?

Storage shelf, storage case
If the unit is used to store small samples, storage racks and boxes provide more efficient use of internal space.

Warning

  • Do not ground the freezer through gas lines, water mains, telephone lines and lightning rods, as this may lead to electric shock.
  • After installation, the power plug must be easily accessible to unplug in case of an emergency. Nothing should block ventilation port of the freezer.

Preparation before use

  1. Remove packing materials and straps.
  2. Remove all packing materials and straps for transportation.
  3. Check the supplied accessories
  4. Check the items in the packing box according to the packing list. If they do not match each other,please contact manufacturer.
  5. Placement condition
  6. Reserve at least 30cm of clearance around the refrigeratorfor ventilation.
  7. Adjust Leveling legs
  8. Rotated the leveling legs clockwise to extend them out tolevel the unit to the floor and ensure that the unit does notmove while in use.
  9. Standing
  10. After adjusting and cleaning the unit, do not immediatelyconnect the power cord.Allow for a minimum of 24hrs priorto connecting the freezer to the power line. This always forinternal fluids and lubricants to be reset in proper  orientationprior to power up.
  11. For indoor use only- Never use in Wet conditions.

caution

  1. To handle the freezer before unpackaging, forklift may be used. If the forklift is used,it shall be inserted at the bottom of blocking from the front or back of the freezer tomove the freezer. Do not use compression forklift attachments.
  2. After unpackaging, to handle the freezer, it may be moved using the attachedwheels.
  3. During handling, do not tilt freezer more than 25°.
  4. Pease be careful to slip while pushing the Freezer.

Power on for the first time
When the unit is started for the first time, please follow the procedures below.

  1. while keeping the unit empty, plug in the power cord to dedicated power socket that meets all national and electrical requirements.
  2. If the unit has a backup cooling system (optional) turn off the backup system.
  3. Connect the freezer to the power supply, turn on the power switch located on the side of the freezer (as in the illustration on the right), and then turn on the battery switch.
  4. Set the unit to desired temperature: Do not load the unit with any samples. Power up the unit to let it run down to -60°C. Let it run at -60°C for 8 hours then lower it to -80°C. Observe the unit performance for 24 hours for normal cycling to ensure that it is working properly.

Optional components

CO2 and LN2 auxiliary cooling system
For installation and operation of the backup cooling system, please refer to the user’s manual provided with the system.

Caution Please purchase steel cylinders fitted with a siphon, The siphon can be used to siphon fluids that flow out from the bottom of the steel cylinders.

Warning

  • The location of any equipment using CO2/LN2 must be in a well ventilated area. Increased CO2 in the air may be harmful and even fatal. If the ventilation is poor, another method should be considered in order to ensure a safe working environment.
  • CO2/LN2 cylinders should be adequately secured. Unsecured tanks may present a safety risk.
  • The temperature of liquid CO2/LN2 is extremely low, which could cause frostbite. When replacing the cylinder, always wear appropriate personal protective equipment.

Recycle of Rechargeable Battery
When the battery reaches end of life, contact a local recycling organization to dispose of the battery.

Location of the battery
The battery is for the power outage alarm. It is located inside the control box on the right side of the unit.

  • Please highlight this text. Customer should not be replacing or accessing this compartment.

Removal of the battery

  1. Turn off the unit and unplug the power cord from the socket.
  2. Remove side panel by removing screws.
  3. Use a screwdriver to remove the 4 screws on the cover of the control box.
  4. Unplug the connecting terminals from battery.
  5. Remove the bracket that fastens the battery. Then remove the battery.
  6. Follow regulations to recycle or properly dispose of battery.
  7. When changing the battery, make sure that the brown wire connects to the positive pole of the battery and that the blue wire connects to the negative pole of the battery.
  8. The polarity must not be reversed. Incorrect polarity can damage the computer’s motherboard and prevent the battery from being charged.

info:

  • Your ULT unit should be cared for by trained personnel. Every 2 to 4 hours, the Unit’s working status should be inspected and recorded on a daily basis.Should there be a malfunction in the unit, the freezer temperature rises. If the problems cannot be corrected in a short time, please remove the stored samples, move them to another unit that meets the temperature requirements to avoid potential damage to samples.
  • Before putting samples in the freezer to be stored, first check that the freezer’s temperature is at the desired setpoint to prevent damage or loss.

It is not recommended to load excessive amounts of samples into the unit at one time. Overloading may result in inadequate performance. The freezer and the compressors can become overheated.
Samples must be loaded in batches, while gradually decreasing temperature setting. The process should be repeated until the final temperature is reached.

  • Do not use any unauthorized mechanical tools or other means to accelerate the defrosting process.
  • Do not damage the refrigeration circuit.
  • Do not use any unapproved electrical components in the freezer.

Operation after a Power Outage
Your ULT freezer control settings are stored in its memory system. Should there be power outage and recovery, the unit can resume its operation based on the previous settings.

Warning

  • In the event of a power outage and recovery, be sure to wait for at least 5 minutes before turning the unit on again to avoid damaging the compressors and refrigeration system.
  • If the unit is not in use for a long period of time, make sure the power cord is unplugged. Supplier needs to provide data on this- Power Cord insulation should according to UL standards based on appropriate voltage and wattage.

Refrigerator Components ● Control Panel

Refrigerator Components

Defrosting on the inner wall
Frost and ice can form between the door gasket and frame to form an air gap, which can decrease the refrigeration efficiency of the unit. Use the provided plastic scraper to remove excess frost.

To defrost the unit, follow procedure below:

  1. Turn off any backup refrigeration system if applicable.
  2. Remove the samples from the unit that need to be defrosted. Move them to another unit or a container for temporary storage.
  3. Turn off the power supply.
  4. Open the outer door and inner doors to let the unit thaw for a period of time.
  5. Use a dry cloth to soak up any water on the floor of the unit before restarting the unit.
  6. Load the samples back into the unit after it reaches the set temperature.
  7. Turn on the backup refrigeration system if present.

Caution:  Do not remove the frost by knife, screwdriver or other sharp tools.

Battery maintenance

  • During continuous power-on operation of the box, please detect the battery level every 15 days. If low battery level is detected, please make sure that the battery switch is in the “ON” position to make the battery charged. When charging the battery for one week continuously, re-test the battery level. Under normal circumstances, the battery should be sufficient at this time. If the battery level is still low, it is recommended to replace the rechargeable battery.
  • The battery is a kind of consumables and its service life is about 2 to 3 years. If the battery has been used for more than 3 years, it may fail to give an alarm in case of power failure.

Disposal of the freezer

Warning

  • If the box is left unused for a long time in an unsupervised area, make sure that no child can get access to it and the door is not completely closed.
  • Scrapping of the box shall be carried out by professional personnel. Be sure to dismantle the door to prevent suffocation, etc.
  • Disposal of discarded freezer shall be conducted by the relevant personnel. Dismantle the door to prevent occurrence of accidents such as suffocation.

Cleaning and Maintenance

Cleaning of components

Warning

  • To prevent electric shock or injury to operators, the AC power supply to the freezer must be disconnected completely prior to any repair and maintenance work is being performed.
  • During any repair maintenance work, it must be completed in a well-ventilated area to prevent inhalation of refrigerants.

Cleaning the freezer

  • Clean the unit once a month.
  • Use a dry cloth to wipe away loose dust inside and outside of the freezer. If the unit is dirty, use a clean cloth soaked with a neutral detergent solution.
  • Using a dry cloth to wipe away any residual detergent solution.
  • Do not pour water directly onto the exterior or into the interior of the unit. Water can damage the electrical insulation thereby causing a malfunction.
  • Compressors and other mechanical parts are hermetically sealed. They do nt need lubrication.
  • Clean frost and ice off the unit once a month. Also, clean the condenser filter once a month.

Clean the condenser filter
When the control panel shows an alarm signal for “Hot Condenser”, the alarm light flashes. The filter still be cleaned once a month. If the filter is clogged, it will affect the refrigeration efficiency and reduce the product’s lifespan.

To clean the filter, follow the procedure below:

  1. Remove the front grill cover.
  2. Pull out the filter screen.
  3. Use water to wash the filter screen away from the freezer.
  4. After the filter screen is dry, reinstall It back in its original position and close the cover.
  5. If the “Hot Condenser” light is on before cleaning, check the light to make sure that it shuts off after cleaning.
    If it does not shut off, please contact service personnel.

Control panel

Usage

Unlocking method

  1. Press “Up” or “Down” to “06”;
  2. Press and hold “Set” for 5 seconds to make “Lock” light off to enter unlock state and carry out various settings;
  3. Press “Set” to select “TS” temperature setting inside the box, “ALH” high-temperature alarm setting, and “ALL” low-temperature alarm setting in a circular manner;

“TS” method

  1. Under the unlock state, press “Set” to select the “TS” and make current set temperature inside the box flash;
  2. Press “Up” or “Down” to adjust the set temperature inside the box;
  3. After completion of modification, press “Set” to save set temperature inside the box and return to display TS;

“ALH” setting method

  1. Under the unlock state, press “Set” to select the “ALH” setting and make current set ALH value flash;

  2. Press “Up” or “Down” to adjust the set ALH value;
    The modification scope shall be set temperature inside the box. This Scope seems too narrow- given the much lower temperature this fridge is capable of.

  3. After completion of modification, press “Set” to save set ALH value and return to display ALH;
    If there is no key operation for 20 seconds, the set ALH value is not saved, and after function lock, the temperature inside the box is displayed.

“ALL” setting method

  1. Under the unlock state, press “Set” to select the “ALL” setting and make current set ALL value flash;

  2. Press “Up” or “Down” to adjust the set ALL value;
    The modification scope shall be -99°C ~ set temperature inside the box – 5°C;

  3. After completion of modification, press “Set” to save set ALL value and return to display ALL;
    If there is no key operation for 20 seconds, the set ALL value is not saved, and after function lock, the temperature inside the box is displayed.
    Remarks: ALH and ALL values are related to the TS values. If the temperature inside the box is changed, the difference of ALH and ALL values from temperature inside the box shall not change. If ALH and ALL values are changed, temperature inside the box shall not be changed.

Automatic alarm recovery time setting

  • When the unit is in alarm mode, you may press the “Silence” key to stop the buzzing of the alarm.( The remote alarm cannot be cancelled).
  • If the condition persists, the buzzer alarm will resume automatically after 30 minutes.

Remote alarm terminal

  • The remote alarm terminal is installed on the right side of the freezer’s motor compartment, and the alarm signal will be output by this terminal. The load capacity of the terminal is DC 30V, 2A.

Contact output:

  • The remote alarm terminal is installed on the right side of the freezer’s motor compartment, and the alarm signal will be output by this terminal. The load capacity of the terminal is DC 30V, 2A.

Contact output:

  • Standard RS485 port can be used to transmit freezer temperature data to customer’s software for monitoring.
Alarm Code Status Indication Buzzer

Low battery

|

E22

| Lead-acid battery: when the battery is connected, after the battery is charged for 24 hours, the battery voltage is less than

10.5V

|

Alarm light flickers

|

/

Lithium battery: when the battery is connected, after the battery is charged for 24 hours, the battery voltage is less than

9.0V

|

Alarm light flickers

|

/

Power failure alarm

|

E30

|

When the box is powered off

|

Alarm light and power indicator flash simultaneously

| The buzz alarm sounds once every 3 seconds; the display panel

does not display the temperature inside the box for 30 seconds; the normal display lasts for 5 seconds; the above-

mentioned displays occur

alternately; remote alarm output

Door opening alarm| E40| The door opening signal is detected for 5 minutes| Alarm light flickers| Buzzer alarm, remote alarm output
Dirty condenser fault|

E50

| When the condenser filter is blocked, or the condenser

temperature is too high due to the high ambient temperature

|

Alarm light flickers

|

Buzzer alarm

Caution

  • A flashing alarm cannot be cancelled unless the malfunction is eliminated. The buzzing alarm can be temporarily silenced for 30 minutes by pressing the “Silence” key . However, if the problem persists, the buzzer alarm will resume after 30 minutes.
  • When using the freezer, the battery switch must be turned on to charge the battery.
  • When there is a power outage, the battery sustains the temperature display. If the battery voltage is insufficient, the temperature display will turn off.
  • While the battery is still capable of providing power to display, the temperature display can be turned off by unplugging the power cord and turning off the battery control switch.

User parameter adjustment

  • Under the unlock state, press and hold “UP” for 5s to enfer the user parameter settings, and press “UP or “Down” to select 7 parameters including dA, T1, T2, P6, IC, PS1 and CL1. Press “Set” after selecting one parameter to modify this parameter;

  • dA: Door opening alarm delay, with default of 5min, adjustable from 1 to 30min;
    Press “Up” or “Down” key to modify the set value of door-opening alarm delay;

  • T1: The USB fetch cycle defaults to 6min, which is adjustable in 1 ~ 99min;
    Press “Up” or “Down” key to modify the set value of usb fetch cycle;

  • T2: USB time, Year (P1:10 to 99) / Month (P2:01 to 12)/Day (P3:01 to 31)/Hour (P4:00 to 23)/ Minute (P5:00 to 59);
    Press “UP or “Down” to modify the set usb time;

  • P6: USB derivative mode, with the default of 12, adjustable from 0 to 12;
    The data can be exported in different periods, the parameters 0 ~12 can be set, and the default value of 12 means the one year of data can be exported once; setting it to 0 means exporting all the data once, setting it to be 1 – 12 means respectively exporting the data of several months before the current time, such as the data of 2 months, 3 months… 12 months.
    Press “UP or “Down” to modify the set USB derivative mode value;

  • IC (optional): IC card registration password modification, with the default of 008, adjustable from 000 to 999;
    Press “UP or “Down” to modify the set IC card registration password.

  • Setting method: Press “Up” or “Down” key to increase or decrease the password value by 1. Press “UP” or “Down” for each 1s to increase or decrease by 1. When continuously increasing or decreasing by 10, press “UP”or “Down” to for each 1s to increase or decrease by 10.

  • PS1: unlock password, with the default of 06, adjustable from 01 to 99;
    Press “UP”or “Down” to modify the set unlock password value.

  • Setting method: Press “Up” or “Down” key to increase or decrease the password value by 1. Press “UP”or “Down” for each 1s to increase or decrease by 1. When continuously increasing or decreasing by 10, press “UP”or “Down” to for each 1s to increase or decrease by 10.

  • CL1: IC card logout, with the default of 0, adjustable from 0 to 1;
    Select CL1 for parameter list. Press “Set”, 000 flashes and it requires to enter the registration password. Enter the correct password and then press “Set” to execute the order. The CL1 flashes for 3 times and there is a buzz sound, which means that the logout is completed. In case of three times of entering wrong password, it will exit and lock, and re-display the temperature inside the freezer.

USB data export

  1. Plug in the USB disk to automatically export the temperature, alarm and event records of the machine. When the data export is started, the decimal point in the lower right corner of the right-most digital pipe on the display panel flashes. When the data export is completed, the decimal point is on without flashing.Unplug the USB disk and the decimal point is off.
  2. System storage space can meet 15 years of data storage.

Notice

  1. The “Set” key must be pressed for confirming the saving after each parameter value is set. In other cases, the modified value cannot be saved.
  2. In the above parameter setting process, press the “Buzzing cancel” to return the last layer of parameter/exit the parameter setting, or exit the parameter setting with 20s of no pressing.

Display and Alarms

Connect the power supply for the unit and switch the power switch to the “ON” position to enter into power-on state and make the display screen to show the temperature inside the box.
Working status prompt of the display panel:

  • “Locked” light on: all settings are locked to prevent misoperation;
  • “Run” light on: the refrigeration system is in operation;
  • “Power” light on : the box has been powered by the main power supply;
  • “Alarm” light on: the box has a fault alarm;

Functions of the buttons

  1. “Set ”: enter the unlock password to unlock the keyboard (long press for 5s) or confirm the settings;
  2. “Up” and “Down”: select parameters or increase / decrease parameter values, and can be cycled when used for selecting parameters or parameter values;
  3. Silence”: temporarily silence the buzz or return to the previous-level parameters / exit parameters setting to return to display the temperature inside the box;
  4. Inquiry”: when the display panel is locked, press this key to query the device alarm code, input voltage and the ambient temperature where the equipment is used. The digital pipe displays the corresponding fault code, voltage and ambient temperature for 2s and then restores to display the temperature inside the unit;
Alarm Code Status Indication Buzzer

High temperature

alarm

|

E00

| Displayed temperature ≥ set temperature for high-temperature

alarm, continuously for 1min

| Alarm light flashes and overtemperature

alarm light flashes

| Buzzer alarm, remote alarm output
Low

temperature alarm

|

E01

| Displayed temperature ≤ set

temperature for low-temperature alarm, continuously for 1min

| Alarm light flashes and

overtemperature alarm light flashes

| Buzzer alarm, remote alarm output
Too high ambient

temperature

|

E02

| Ambient temperature ≥ 35℃ , continuously for 30s|

Alarm light flickers

|

/

Main sensor fault| E10| In the case of main sensor fault| Alarm light flickers| Buzzer alarm
Fault of the ambient

temperature sensor

|

E11

|

In the case of ambient temperature sensor fault

|

Alarm light flickers

|

Buzzer alarm

Condenser sensor fault| E12| In the case of condenser fault| Alarm light flickers| Buzzer alarm
Battery disconnection|

E20

| Power switch turning off

or battery connection line loosening

|

Alarm light flickers

|

Buzzer alarm

Reversed

battery installation

|

E21

| Detect that the reversed battery installation signal is low level|

Alarm light flickers

|

Long buzzer sound alarm

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

global sources User Manuals

Related Manuals