117517V Uraproof Service Relation Instructions

June 14, 2024
Ura

117517V Uraproof Service Relation

117517V-Uraproof-Service-Relation-product

Product Information

Specifications

  • Product Name: Relations Pro
  • Model Numbers: 117 517V, 117 518V, 117 519V, 117 527V, 117 528V, 117 529V, 117 537V, 117 539V, 117 547V, 117 549V, 117 559V
  • IP Rating: IP66
  • Impact Resistance Rating: IK10

Installation

To install the Relations Pro product, follow these steps:

  1. Measure and mark a spot where you want to install the product.
  2. Make sure the installation area is clean and free from any obstructions.
  3. Position the product on the marked spot and secure it using the appropriate mounting hardware.

Note: The product dimensions are as follows:

  • Width: 223 mm
  • Height: 150 mm
  • Depth: 118 mm

Raccordement

To connect the Relations Pro product, follow these steps:

  1. Prepare a 12 mm power supply connection.
  2. Use the LE14217AA power supply for the connection.

Fonctionnement

To operate the Relations Pro product, follow these steps:

  1. Make sure the product is properly connected and powered on.
  2. The “Bloc OK” indicator LED should be green and blinking.
  3. If the battery needs replacement, replace it with a new one.
  4. If the block needs replacement, replace it with a new one.

Remplacement des batteries

To replace the batteries in the Relations Pro product, follow these steps:
Note : The battery specifications are as follows:

  • Battery Type: 111 914 Ni-MH
  • Voltage: 1.2V
  • Capacity: 1.1 Ah

For model numbers 117 517V, 117 518V, 117 519V, 117 537V, and 117 539V:

  1. Remove the old batteries from the product.
  2. Insert new batteries of type 111 914 Ni-MH into the product.

For model numbers 117 527V, 117 528V, and 117 529V:

  1. Remove the old batteries from the product.
  2. Insert new batteries of type 111 921 Ni-MH into the product.

Note : Use only Ura brand accessories for replacement.

FAQ

  • Q: Can I use non-Ura brand accessories for battery replacement?
    A: No, it is recommended to use only Ura brand accessories for battery replacement to ensure compatibility and optimal performance.

  • Q: What is the IP rating of the Relations Pro product?
    A: The Relations Pro product has an IP66 rating, which means it is protected against dust and powerful water jets.

  • Q: What is the impact resistance rating of the Relations Pro product?
    A: The Relations Pro product has an IK10 rating, which means it is highly resistant to impact.

Installation

117517V-Uraproof-Service-Relation-fig-
\(1\)

Connection

IEC 61347-2-7/A2 : 2021
Maximum outage duration (TRM): 18 days

Note:

  • BAES+BAEH blocks must be connected to a remote control ref. 140 012, 140 130 or 140 131.
  • The connected SATI blocks must be associated to remote controls 140 130 or 140131 for operation in connected mode.
  • For addressable blocks, an addressing procedure, installation and commissioning is described in the technical sheet available on the website www.ura.fr.

Functioning

  • When powering up, check that the white LEDs are on standby (low luminous flux) and that the green SATI LED is on.
    Note : During the first 28 hours of charging the green SATI LED flashes.

  • In the event of a power failure, the green SATI LED turns off and the white LEDs light up more brightly (with variation in luminous flux for BAES+DBR). When power returns, the unit automatically returns to standby (green SATI LED on). The block continuously monitors the status of its security components and automatically performs the following tests:

  • Weekly : emergency switch and test of light sources for 15 seconds.

  • Quarterly : emergency switch, a test of light sources, and battery life (1 hour for BAES and 5 hours for BAEH).

Meaning of the test results by the signaling LEDs:

Green SATI LED on steady| SATI green LED flashing| Yellow LED on steady and green LED off| Yellow LED flashing and green LED off
---|---|---|---
OK Block| Block in charge| Replace the battery| Replace the block

Battery replacement

Battery replacement:
Important: The batteries must be replaced when the autonomous unit no longer meets its rated operating time.
Carry out the intervention only after the interruption of the power supply

Ref. battery Features Name Product references

111 914

| ****

Ni-MH 1,2V – 1,1 Ah

| 1| 117 517V, 117 518V, 117 519V, 117 537V, 117 539V
2| 117 559V, 117 547V, 117 549V
111 921| Ni-MH 6V – 1,1 Ah| 1| 117 527V, 117 528V, 117 529V

Safety information

  • The safety electrical source (battery) is not a user-accessible component and must only be replaced by a qualified person.
  • The light source of this luminaire is not replaceable.
  • When the light source reaches the end of its life, the entire luminaire must be replaced.

For Ambiance blocks:
Luminaires bearing this label should be placed so as to avoid staring at the light for an extended period of time at a short distance.

This product must be installed in accordance with the installation rules and preferences by a qualified electrician. Improper installation and/or incorrect use may result in risk of electric shock or fire. Before carrying out the installation, read the instructions and take into account the specific installation location of the product.
Do not open, disassemble, alter or modify the device unless specifically indicated in the instructions. All Ura products must only be opened and repaired by personnel trained and authorized by Ura. Any unauthorized opening or repair voids all responsibilities, replacement rights, and warranties.
Use only Ura brand accessories.

service
Relations Pr o
0810008989
Fax : 0810110110
E-mail : www.ura.fr

References