TEKRON PTP Translator User Manual
- June 14, 2024
- Tekron
Table of Contents
TEKRON PTP Translator
PTP Translator
User Manual
Contents
- Introduction
- Product Overview
- LED Indicators
- Inputs and Outputs
Introduction
Welcome to the PTP Translator user manual! This document contains everything you need to know about the key features,hardware, and installation process of the PTP Translator.
Product Overview
The PTP Translator is a device that provides synchronization and translation capabilities. It allows synchronization of outputs to UTC time and features various inputs and outputs for flexible connectivity. The device can be configured over a LAN (Local Area Network) and supports NTP / SNTP License.
LED Indicators
The top of the PTP Translator features two LED indicators. The SYN LED shows the synchronization status of the unit, while the ALM LED shows the alarm status of the unit. Outputs are synchronized to UTC time only when the SYN LED is fully illuminated.
LED | Meaning |
---|---|
SYN LED | Off |
The PTP Translator has no power. | |
SYN LED | Slow Flash (1x flash per second) |
The PTP Translator is operating in the holdover state (holdover |
timer is running) or is operating in the tuning state (time server
is gaining synchronization).
SYN LED| Fast Flash (5x flashes per second)
| The PTP Translator is not synchronized (out of sync and not in
holdover).
SYN LED| On
| The PTP Translator is synchronized.
ALM LED| Meaning
---|---
ALM LED| Off
| The PTP Translator is operating normally and has no
alarms.
ALM LED| Fast Flash
| At least one alarm is active. Refer to the alarm window in the
Clock tab of the Configuration Tool to find the name of the active
alarm(s). Refer to the Alarm Specification table below for the
details on each alarm by name.
Alarm Name
No Sync
Holdover
Factory Reset Armed
ADMIN/ETH1 Address Fault
Sync Forced
Inputs and Outputs
The PTP Translator is equipped with various inputs and outputs for flexible connectivity.
ETH: Ethernet Port (ST Fiber / RJ-45)
PTP Translator units are fitted with either an RJ-45 10/100 Mbps Ethernet interface or an ST multi-mode Fiber 100BASE-FX Ethernet interface. The unit can be configured over the LAN (Local Area Network) and can be loaded with an NTP / SNTP License.
Next to the Ethernet connector are two LEDs: The green LNK LED (above), and the yellow ACT LED (below). The LNK LED will be on when the unit is connected to a valid Ethernet port whilst the ACT LED will be on/flashing when there is activity on either the transmit or receive pair on the Ethernet port.
TX: Fiber Output
This port is for fiber output.
TTL: TTL Output
This port is a programmable TTL level output that may be configured to
output in either inverted or non-inverted polarity.
ALM: Alarm Output
The alarm output is a type A (normally open) dry contact type.
Additionally, it is a high voltage isolated contact capable of switching up to
300 V at 100 mA.
Introduction
Welcome to the PTP Translator user manual! This document contains everything you need to know about the key features, hardware, and installation process of the PTP Translator.
Product Overview
The PTP Translator converts IEEE 1588-2008 (PTPv2) messages into legacy time
codes including IRIG-B, DCF77, user defined pulses and serial strings, as well
as NTP server messages. The PTP Translator also supports SNTP client.
The PTP Translator clips onto a standard DIN rail. Its rugged compact design
is suitable for noisy electrical environments, while built in electrical
isolation combined with strong push pull drives on outputs simplifying wiring
schemes and enhancing reliability. Refer to Figure 1.
LED Indicators
The top of the PTP Translator features two LED indicators. The SYN LED shows
synchronization status of the unit, while the ALM LED shows the alarm status
of the unit.
Outputs are synchronized to UTC time only when the SYN LED is fully
illuminated.
Table 1, Table 2 and Table 3 below provide information regarding the interpretation of the LEDs.
Table 1 – SYN LED Functionality
SYN LED | Meaning |
---|---|
Off | The PTP Translator has no power. |
Slow Flash (1x flash per
second)
| The PTP Translator is operating in the “holdover” state (holdover timer is
running) or is operating in the “tuning” state (time server is gaining
synchronization).
Fast Flash
(5x flashes per second)
|
The PTP Translator is not synchronized (out of sync and not in holdover).
On| The PTP Translator is synchronized.
Table 2 – ALM LED Functi0nality
ALM LED | Meaning |
---|---|
Off | The PTP Translator is operating normally and has no alarms. |
Fast Flash
| At least one alarm is active. Refer to the alarm window in the Clock tab of the Configuration Tool to find the name of the active alarm(s). Refer to the Alarm Specification table below for
the details on each alarm by name.
Table 3 – Alarm Specification
Alarm Name | Specification |
---|---|
No Sync | The PTP Translator is not synchronized to an external time source, or |
the holdover period has expired and/or the maximum inaccuracy threshold has
been reached.
Holdover| The PTP Translator has lost synchronization to an external time
source and is now in holdover.
Factory Reset Armed| This alarm is generated if the Forgotten Password Reset
(Factory Reset Process) is enabled
and has been initiated by the user.
ADMIN/ETH1
Address Fault
| This alarm comes up when the DHCP server is unavailable or when the IP address is assigned
to some other node in the network and cannot be assigned to the PTP Translator’s Ethernet port. Under such situations the Ethernet port defaults to a link local address.
Sync Forced| This alarm is generated when the “Never leave Sync (Test Mode)” option has been selected.
Inputs and Outputs
ETH: Ethernet Port (ST Fiber / RJ-45)
PTP Translator units are fitted with either an RJ-45 10/100 Mbps Ethernet
interface or an ST multi-mode Fiber 100BASE-FX Ethernet interface. The unit
can be configured over the LAN (Local Area Network) and can be loaded with an
NTP / SNTP License.
Next to the Ethernet connector are two LEDs: The green “LNK” LED (above), and
the yellow “ACT” LED (below). The LNK LED will be on when the unit is
connected to a valid Ethernet port whilst the ACT LED will be on/flashing when
there is activity on either the transmit or receive pair on the Ethernet port.
TX: Fiber Output
This port transmits an IRIG-B (B00x or B22x), programmable pulse or DCF77
signal over fiber, that may be configured to output in either inverted or non-
inverted polarity. The fiber transmitter is compatible with 50/125 μm,
62.5/125 μm and 100/140 μm multimode glass fiber.
TTL: TTL Output
The TTL output is a high drive, non-isolated TTL level driver which can be
configured using Tekron’s Configuration Tool. This port transmits an IRIG-B
(B00x or B22x), programmable pulse, or DCF77 signal using 0 – 5 Vdc TTL level
on pins “+” and “-” of the screw terminal connector. The default output is an
un-modulated IRIG-B signal (IRIG-B004 with C37.118.1 extensions). It can be
used as the master source signal to drive one or many slave devices. The
IRIG-B timing pulses (both leading and trailing edges) from this port is
typically to within 100 ns of UTC.
This port is a programmable TTL level output that may be configured to output in either inverted or non-inverted polarity:
- A configurable number of pulses per second, minute, hour, day with adjustable pulse-width and offset.
- IRIG-B time code (Un-modulated DCLS or Modified Manchester) with option C37.118.1 or AFNOR extensions.
- Simulated DCF77 receiver time code.
ALM: Alarm Output
The alarm output is a type “A” (normally open) dry contact type. Additionally,
it is a high voltage isolated contact capable of switching up to 300 V at 100
mA.
Note: The “Normally-Open” (NO) descriptor refers to the de-energized
state of the relay.
The PTP Translator operates with the alarm relays energized during normal
operation, and de-energized in the alarm state. It follows that, in the event
of all power to the PTP Translator being lost, the alarm relay defaults to the
“alarm” state (open contact). The “+” and “-” symbols are included for
reference purposes only, as the alarm contacts are not polarized.
The “ALM” output is a synchronization fail alarm. This alarm is active (contact open) when the unit is not synchronized and is not in the holdover state.
OPT: Optional Output
The PTP Translator has a slot for one IO card to allow a variety of user
interfaces. Each card is limited to one additional port with at least 3 kV
isolation from the rest of the system to avoid current loops. Refer to Table 5
for the list of orderable options.
Software
Configuration Tool
The PTP Translator can be configured via Ethernet. The configuration tool can
be downloaded from the Tekron Support website: www.support.tekon.com. By
default, the unit is shipped with DHCP enabled for automatic IP address
assignment, with a fall back to link local addressing (169.254.xxx.xxx) if no
DHCP server is present.
- Default Username: admin
- Default Password: Password
Note: The user is required to change the default password on first login.
Installation
Identification
Each PTP Translator unit is shipped with an identification label on the side
of the case. The label provides details of the optional output (if any) and
power supply fitted to the unit, and the unit’s serial number.
Check the identification label on the side of the unit to ensure that the
correct order code and voltage range has been supplied before proceeding with
the installation.
The label on the side of PTP Translator contains the voltage range: Do not
apply power outside of this range!
Location
The unit is intended for installation in restricted access areas. A restricted
access area can be accessed only using a lock and key or other means of
security. Installation is to be done by suitably qualified personnel.
Power Supply
DC power should be applied to the ‘+’ and ‘-‘ screw clamp terminals above the
“PWR” input. The DC polarity is not critical. As shown in Figure 2, the input
voltage range can be found on the side of the unit, above the power input
screw clamp terminals.
Note: The Power supply has polarity protection built in to prevent
damage.
The input voltage range is marked on the product label on the side of the
unit, and on a label above the “+’ and ‘-“ screw clamp terminals on the power
input. Do not apply voltage outside the range noted.
The label on the side of TTM 01-G indicates the type of output Option Card
fitted: Do not apply voltages to output only interfaces!
Hazardous Voltage
Up to 300 V may be present at the power input port “PWR”. Up to 275 V may be
present at the alarm relay port “ALM” (in Figure 3). These voltages are
supplied to the unit only, and not generated by the unit. However, the
installer must exercise care in wiring the screw clamps to ensure bare copper
is not accessible.
Earthing
The GND connection is located next to the power supply input terminals
(highlighted in Figure 3). This must be connected to earth for full protection
of the PTP Translator.
The unit must be safety earthed whenever it is powered on, using the earth
terminal as pictured in Figure 3. The cable cross section must be equal to or
greater than 0.2 mm2 (30 AWG).
Mounting the PTP Translator
The PTP Translator is designed to be mounted to a standard ‘Top Hat’ din rail
mount using the supplied clips on the base (See Figure 3). The clips can also
be used to screw mount the unit by extending them beyond the case edge.
Connecting the PTP Translator
The PTP Translator has a RJ-45/ 100Base FX connector and ST Fiber output on
the top, and a row of rising clamp screw terminals on the bottom. Any
connection not required may be left unterminated. The screw terminals are
designed for the following cables:
- 0.2 – 4.0mm² (30 – 12 AWG) solid cable
- 0.2 – 2.5mm² (30 – 14 AWG) stranded cable
The Fiber PTP Translator has a dual ST Fiber connector for the Ethernet and is labeled ETH on the case whereas the IRIG-B fiber out is simply labeled TX.
The connections from left to right along the bottom are:
- Optional output (OPT) ‘+’ and ‘-’
- Alarm (ALM) ‘+’ and ‘-’
- TTL ‘+’ and ‘-’
- Ground
- Power Supply Negative
- Power Supply Positive
If the optional output isn’t fitted, then the unused terminals are covered.
Factory Reset
The PTP Translator features the ability to reset to factory default settings
if the administrator password is forgotten, or if the time server is rendered
unreachable on the network due to incorrect settings, provided that physical
access to the unit is available.
This feature is disabled by default to maximize security and must be enabled
via the Tekron Configuration Tool before it can be used. When disabled, there
is no method to gain full access to the unit without the administrator
password, and if the administrator password is forgotten, the unit must be
returned to Tekron for reprogramming at the customer’s expense.
This feature may be permanently disabled by Tekron on request.
For further details on this feature, see the Configuration Tool Manual, which
can be downloaded from the Tekron website at
support.tekron.com
Factory Hardware Options
Power Supply Options
There are three different power supply options available for the PTP
Translator, detailed in Table 4. Low, medium, or high voltage power supplies
are available and feature similar maximum output ratings but different levels
of isolation.
Table 4 – PTP Translator Orderable Power Supply Modules
Power
Supply
| Input Voltage Ratings| Maximum Power Rating| Isolation
---|---|---|---
Low| 14 – 36 Vdc.| 4 W| 1.6 kV
Medium| 20 – 75 Vdc.| 4 W| 1.6 kV
High| 90 – 300 Vdc.| 4 W| 3.75 kV
Optional Output Cards
The PTP Translator has a slot for one I/O card, to allow a variety of user
interfaces. Each card is limited to one additional port with at least 3 kV
isolation from the rest of the system to avoid current loops.
Table 5 below shows the orderable options:
Table 5 – PTP Translator Orderable Interface Modules
Output Type | Features |
---|---|
None | No optional output. |
TTL | TTL (5 V, 150 mA) IRIG-B (B00x, B22x), DCF77 or user defined pulse |
output.
Serial| RS232 level (9 V, 10 mA) output supporting serial strings.
AM IRIG-B| Amplitude Modulated (AM) IRIG-B (B12x) signal, typically 8 V with
3:1 mark space ratio.
Output Impedance 120 Ω. Requires a 100 – 180 Ω terminator.
Isolation and Protection
The TTL output features an earthed, non-isolated driver and is designed for
connection within the same rack. Since it is the only output with an earth
reference, it is isolated from the power supply via the power supply isolation
and from all other IO by their isolation. All the other outputs are
galvanically isolated (including the optional TTL output card) from the
internal electronics and power supply.
The Alarm port has a UL and VDE approved 3.75 kV AC isolated contact and is
protected by a 600 V, 175 mA self-resetting fuse and a 350 V transient
suppressor diode.
The Copper Ethernet port provides 1.5 kV isolation and includes ESD
suppression on board.
All optional output cards feature at least 3 kV isolation from earth and have
ESD suppression suitable for the interface type.
The power supply isolation varies from 1.6 kV for the low and medium voltage
power supplies to 3 kV for the high voltage power supply. In addition, a
varistor protects the power supply against transverse voltages and transient
suppressor diodes protect the internal electronics from longitudinal events.
Appendix
PTP Translator Specifications
Physical Specifications
UL94-V0 polycarbonate flame retardant DIN rail enclosure with IP40 compliance (Ingress Protection rating).
Dimensions
| Width Depth
Height
| 72 mm
60 mm
90 mm
Weight| 0.15 kg
Input and Output Specifications
TTL| 5 V (4.5 V at 150 mA)| 2 Pin| < 100 ns to UTC
Fiber (λ = 820 nm)1| -19 dB optical power| ST| < 100 ns to UTC
Alarm| 275 Vac / 275 Vdc,
100 mA
| 2 Pin|
Ethernet (Copper)| | RJ-45|
Ethernet (Fiber)2| TX: -17 dB optical power
RX: -33 dB sensitivity
| Dual ST, ½ inch pitch|
Optional Output Specifications
TTL| 5 V (4.5 V at 150 mA)| 2 Pin| < 100 ns to UTC
Serial (String)| ± 9 V| 2 Pin| < 1 ms to UTC
AM IRIG-B (modulated)| 8 V| 2 Pin| < 2 µs to UTC
Environmental Specifications
Operating Temperature Range| -10 to +65° C
Electrical Specifications
Power Supply
| Low Voltage| 14 – 36 Vdc| 2 Pin + common earth
Medium Voltage| 20 – 75 Vdc| 2 Pin + common earth
High Voltage| 90 – 300 Vdc| 2 Pin + common earth
Power drain| 4 W max
- Fibre transmitter is compatible with 50/125 μm, 62.5/125 μm and 100/140 μm multimode glass fiber.
- Fibre Ethernet is compatible with 50/125 μm and 62.5/125 μm multimode glass fiber.
Serial Output String (Serial Output Option)
General Key to Fields
Fields between brackets (‘<’ and ‘>’) represent ASCII character codes. The
used codes are in Table 6 below:
Table 6 – ASCII character codes
Placeholder | HEX | Content |
---|---|---|
01 | ASCII Start of Header character | |
02 | ASCII Start of Text character | |
03 | ASCII End of Text character | |
07 | ASCII BEL character | |
0A | ASCII Line Feed character | |
0D | ASCII Carriage Return character | |
20 | ASCII Space character |
NGTS Time Code O/P
The NGTS time code is normally used in conjunction with a 10 ms pulse that
finishes precisely on the second. Timing Transmitted once per minute. Sent
during the last second before the minute rollover to which the data in the
string refers. Table 7 details the NGTS serial string format and fields.
Table 7 – NGTS String Time Code Format Fields
Timing| Transmitted once per minute. Sent during the last second before
the minute rollover to which the data in the string refers.
---|---
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition| TyyMMDDWhhmmx
Placeholder| Content
T| “T”
yy| Last two digits of the year: e.g., “21” = the year 2021
MM| Month: “00” = January … “12” = December
DD| Day of Month: 01…31
W| Day of week: “1”= Monday … “7”= Sunday
hh| Two-digit hour
mm| Two-digit minute
x| Time mode: ”0” = Local time, “1” = UTC time
Example: Interpretation:
T020422112340
IRIG J-17 Time Code O/P
Table 8 details the IRIG-J17 serial string format and fields.
Table 8 – IRIG-J17 String Time Code Format Fields
About | This code is compatible with IRIG Standard 212-00. |
---|---|
Timing | Transmitted once every second. The leading edge of the “start” |
bit of the first character
Default Comms| 9600 bps, 7-bit ASCII, odd parity
Definition|
Placeholder| Content
Example: Interpretation:
String-A Time Code O/P
Table 9 details the String A serial string format and fields.
Table 9 – String A Time Code Format Fields
About| This code is very similar in data content to the IRIG J-17 code but adds a two-character field
containing the year, and uses 8-bit ASCII, no parity data format.
---|---
Timing| Transmitted once every second. The leading edge of the “start”
bit of the first character
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
Placeholder| Content
Example: Interpretation:
String-B Time Code O/P
Table 10 details the String B serial string format and fields.
Table 10 – String B Time Code Format Fields
About| This code substitutes a “Quality” indicator byte for the year field, but otherwise is identical
in form, function, and timing to String-A.
---|---
Timing| Transmitted once every second. The leading edge of the “start”
bit of the first character
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
Placeholder| Content
Table 11 – String B Quality Character ‘Q’ Indicators
“Quality” Character (Q) | Content |
---|---|
HEX | ASCII |
20 | ‘ ’ (space) |
2E | ‘.’ (full stop) |
2A | ‘*’ |
23 | ‘#’ |
3F | ‘?’ |
Example: Interpretation:
String-C Time Code O/P
Table 12 details the String C serial string format and fields.
Table 12 – String C Time Code Format Fields
About| This code is effectively a combination of String-A and String B. It provides both year
information and a sync indicator field.
---|---
Timing| Transmitted once every second. The leading edge of the “start”
bit of the first character,
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
Example: Interpretation:
String-D Time Code O/P
String-D is IDENTICAL in content to String-B (in Table 10), but the second
mark is at the leading edge of the start-bit of the (
- Example: Interpretation:
-
112:12:34:36? day 112, time: 12:34:36, >100 μs sync error
String-E Time Code O/P
Table 13 details the String E serial string format and fields.
Table 13 – String-E Time Code Format Fields
About | This provides time, year information, and a sync indicator field. |
---|---|
Timing | The string is transmitted once every second, with the leading |
edge of the “start” bit of the
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
Placeholder| Content
YYYY| 4-digit current year
:| HEX 3A
ddd| Day of year: range “001” – “365”
:| HEX 3A
hh| hour: “00” – ”23”
:| HEX 3A
mm| minute: “00” – “59”
:| HEX 3A
ss| seconds: “00” – “59”
Q| Quality character, as defined in String B (refer to Table 11)
Example: Interpretation:
String-F Time Code O/P
Table 14 details the String F serial string format and fields.
Table 14 – String-F Time Code Format Fields
About| This string complies with the protocol required to drive Vorne
type Time Displays.
---|---
Timing| The string is transmitted once every second, with the leading
edge of the “start” bit of the
last
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
Placeholder| Content
String-G Time Code O/P
Table 15 details the String G serial string format and fields.
Table 15 – String-G Time Code Format Fields
About | This general time string is used predominantly in Europe. |
---|---|
Timing | The string is transmitted once every second, with the leading |
edge of the “start” bit of the
last
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
Placeholder| Content
Table 16 – String-G Clock Status Indicators
Clock Status
The s “Clock Status” is an ASCII character in the range 0-9, A-F representing
a single hex digit (nibble)
Bits| 3| 2| 1| 0|
| | | | 0| No announcement for time change
| | | | 1| Announcement for time change – active for an hour before
| | | 0| | Local Standard Time (LST)
| | | 1| | Daylight Saving Time (DST)
| 0| 0| | | Time/date invalid – clock is out of sync
| 0| 1| | | Hold-over mode – running on local Oscillator
| 1| 0| | | GPS / IRIGB controlled mode
| 1| 1| | | GPS / IRIGB controlled mode (high accuracy)
Table 17 – String-G Day of Week Indicators
Day of Week
The w “Day of Week” is an ASCII character in the range 1-7, 9, A-F
representing a single hex digit (nibble)
Bits| 3| 2| 1| 0|
| 0| | | | Local Time
| 1| | | | UTC time
| | 0| 0| 1| Monday
| | 0| 1| 0| Tuesday
| | 0| 1| 1| Wednesday
| | 1| 0| 0| Thursday
| | 1| 0| 1| Friday
| | 1| 1| 0| Saturday
| | 1| 1| 1| Sunday
Example: Interpretation:
String-H Time Code O/P
Table 18 details the String H serial string format and fields.
Table 18 – String-H Time Code Format Fields
About| This provides time and date information, and sync indicator
fields.
---|---
Timing| Transmitted once every second. The leading edge of the “Start”
bit of the first character
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
Placeholder| Content
otherwise
Example: Interpretation:
NMEA ZDA Time Code O/P
Table 19 details the NMEA ZDA serial string format and fields.
Table 19 – NMEA-ZDA Time Code Format Fields
About| This string is defined by the NMEA-0183 standard and transmitted
at 9600 bps.
---|---
Timing| Transmission is once every second. The leading edge of the
“start” bit of the “$” is exactly on
the second.
Default Comms| 9600 bps, 8-bit ASCII, no parity
Definition| $GPZDA,hhmmss.00,dd,MM,YYYY,s,xx,yyCC
Placeholder| Content
$GPZDA| ASCII “$GPZDA”
,| ASCII “,” (comma)
hh| UTC hour of day: “00” – “23”
mm| UTC minute of day: “00” – “60”
ss| UTC seconds: “00” – “59”
.00| ASCII “.00”
,| ASCII “,” (comma)
dd| UTC day of month: “01” – “31” depending on which month
,| ASCII “,” (comma)
MM| UTC month: “01” – “12”, “01” = January
,| ASCII “,” (comma)
YYYY| UTC year, 4 digits.
,| ASCII “,” (comma)
s| Local time zone offset sign (positive means local time leads UTC)
,| ASCII “,” (comma)
xx| Local time zone offset from UTC in hours
,| ASCII “,” (comma)
yy| Local time zone offset from UTC in minutes
CC| 2-digit hex representation of the result of XORing the 8 data bits of each
character between,
but not including the “$” and “*”. (00-FF)
Example: Interpretation:
$GPZDA,123456.0023042010+1200* UTC time is 12:34:56, 23 April 2010, the local
time offset is +12:00
NMEA RMC Time Code O/P
Table 20 details the NMEA ZDA serial string format and fields.
Table 20 – NMEA-RMC Time Code Format Fields
About| This string is defined by the NMEA-0183 standard and transmitted
at 9600 bps.
---|---
Timing| Transmission is once every second. The leading edge of the
“start” bit of the “$” is exactly on
the second.
Comms| 9600 bps, 8-bit ASCII, no parity
Definition|
$GPRMC,hhmmss.00,a,tttt.tttt,N,ggggg.gggg,W,0.0,0.0,ddmmyy,0.0,ECC
Placeholder| Content
$GPRMC| ASCII “$GPRMC”
,| ASCII “,” (comma)
hh| UTC hour of day: “00” – “23”
mm| UTC minute of day: “00” – “60”
ss| UTC seconds: “00” – “59”
.00| ASCII “.00”
,| ASCII “,” (comma)
a| Status: “A” = valid, “V” = invalid
,| ASCII “,” (comma)
tttt.tttt| Latitude (degrees, minutes): “00” – “89” degrees; “00.0000” –
“59.9999” minutes
,| ASCII “,” (comma)
N| Latitude (north/south): “N” = north, “S” = south
,| ASCII “,” (comma)
ggggg,gggg| Longitude (degrees, minutes): “000” – “180” degrees; “00.0000” –
“59.9999” minutes
,| ASCII “,” (comma)
W| Longitude (east/west): “E” = east, “W” = west
,| ASCII “,” (comma)
0.0| ASCII “0.0”
,| ASCII “,” (comma)
0.0| ASCII “0.0”
,| ASCII “,” (comma)
dd| UTC day of month
mm| UTC month
yy| 2-digit UTC year
,| ASCII “,” (comma)
0.0| ASCII “0.0”
,| ASCII “,” (comma)
E
CC| 2-digit hex representation of the result of XORing the 8 data bits of each
character between,
but not including the “$” and “*”.
Warranty
For terms and conditions of Tekron’s Warranty see the website http://tekron.com/about-tekron/warranty
WARNING
This product has been designed to comply with the limits for a Class A digital
device pursuant to Part 15 of FCC rules. These limits are designed to provide
reasonable protection against such interference when operating in a commercial
environment.
Notes
The information in this manual may change without notice. The manufacturer
assumes no responsibility for any errors that may appear in this manual.
Ethernet is a trademark of XEROX Corporation. Windows, Windows 95, Windows 98,
Windows 2000, Windows NT, Windows XP, Windows Vista, and Windows 7 are
trademarks of Microsoft™ Corp.
Copyright ©2014 Tekron International Ltd. All rights reserved. No part of the
contents of this document may be transmitted or reproduced in any form or by
any means without the written permission of Tekron International Ltd.
Published in New Zealand.
PTP Translator Manual / December 2021
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>