EG4 6000EX-48 Inverter Charger User Manual
- June 15, 2024
- Eg4
Table of Contents
6000EX-48 Inverter Charger
User Manual
6000EX-48 Inverter Charger
ABOUT THIS MANUAL
Purpose
This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installation and operation this manual for future reference.
Scope
This manual provides safety and installation guidelines as well as information
on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating
instructions. Read and keep this manual for future reference. Before
installing or using the unit, read all instructions and cautionary markings on
the unit, the batteries, and all appropriate sections of the manual.
CAUTION- Do not disassemble the unit. Take it to a qualified service
center when service or repair is required. Incorrect re-assembly may result in
a risk of electric shock or fire. To reduce risk of electric shock, shutdown
and disconnect all wiring before attempting any maintenance or cleaning.
Turning off the unit alone will not reduce the risk of shock or injury.
CAUTION – Only qualified personnel can install this equipment.
NEVER charge a battery below specified minimum temperature; refer to the
battery data sheet. Wire size is critical for safe operation, and optimal
performance of the equipment. Refer to a accredited sizing resource or cable
manufacturer specifications to meet inverter/ charge requirements.
Use caution when working with metal tools on or around all systems and
batteries. Risk of electrical arcs and/or short circuiting of equipment can
lead to severe injury and damage. Strictly follow installation procedure when
connecting and disconnecting AC or DC terminals. Refer to INSTALLATION section
of the manual for details. The is not a guarantee of battery protection. Size
and install the correct for the batteries if not included with the product.
GROUNDING -This inverter/charger should be connected to a permanent
grounded wiring system. The grounding system must meet the Authority Having
Jurisdiction (AHJ) requirements in your area.
NEVER short AC output and DC inputs. Do NOT connect to the grid with a shorted
DC input. Warning!! Only qualified service person are able to service this
device. If errors still persist after following troubleshooting table, please
contact your retailer for further assistance.
WARNING: Because this inverter is non-isolated, only three types of PV
modules are acceptable: Monocrystalline, Polycrystalline with class A-rated,
and CIGS modules. To avoid any malfunction, do not connect any PV modules with
possible current leakage to the inverter. For example, grounded PV modules
will cause current leakage to the inverter. When using CIGS modules, please be
sure NOT to ground.
CAUTION: DC breakers and surge protection on PV lines recommended.
Without breakers the equipment is at higher risk of damage from sources such
as surges and lighting strikes.
SPECIFICATIONS
MODEL | 6KW |
---|---|
RATED OUPUT POWER | 6000W |
PV INPUT (DC)
Max. PV Power| 7500W
Max. Input voltage (Maximum PV open voltage)| 500 VDC
Max Ouput DC Power MPPT range| 277 VDC~480 VDC
Working MPP range| 120 VDC~480 VDC
Max. DC Input current / Tołal array amps| 27A
Number of MPP Trackers| 1
GRID-TIE OPERATION (lnFernaFional Use Only)
GRID OUTPUT (AC)
Nominal Output Voltage| 110-120VAC (L-N) / 220-240VAC (L1-L2)
Feed-in Grid Voltage Range| 93.5~126.5 VAC For 110 Vac model 102~138 VAC For
120 Vac model
Feed-in Grid Frequency Range| 57 Hz ~63 Hz
Nominal Output Current| 27.3A (for 110VAC)
25A (for 120VAC)
Power Factor Range| >0.99
Maximum Conversion Efficiency (DC/AC)| 95%
OFF-GRID, HYBRID OPERATION
GRID INPUT
Acceptable Input Voltage Range| 65 – 140 VAC (Appliances) or 95 – 140 VAC
(UPS)
Frequency Range| 50 Hz/60 Hz (Auto sensing)
Rating of AC Transfer Relay| 40A
BATTERY MODE OUTPUT (AC)
Nominal Output Voltage| 110-120VAC (L-N) / 220-240VAC (L1-L2)
Output Waveform| Pure Sine Wave
Efficiency (DC to AC)| 93%
BATTERY & CHARGER
Nominal DC Voltage| 48 VDC
Maximum Charging Current (from Grid)| 120A
Maximum Charging Current (from PV)| 120A
Maximum Total Charging Current| 120A
GENERAL
Dimension, H X W X D| 23-3/8” x 14-3/8” x 5-1/2” (593.6 x 365 x 138.4 mm)
Net Weight| 79 lbs. (35 kgs)
INTERFACE
Parallel| Yes, Up to 9
Communication| RS232/Dry-Contact/Wi-Fi
ENVIRONMENT
Humidity| 0 ~ 90% RH (No condensing)
Operating Temperature| 14°F to 122°F (-10°C to 50°C)
INTRODUCTION
This is a residential self-consumption multi-function inverter, combining the functions of an inverter, solar charge controller, and battery charger to offer uninterrupted power system in a single package. The comprehensive LCD display offers user-configurable and easily-accessible button operations such as battery charging current, AC or solar charging priority, and acceptable input voltage based on different applications.
Depending on different power situations, this hybrid inverter is designed to
manage power from PV modules (solar panels), battery bank, and the utility or
generator AC input. When MPP input voltage of PV modules is within acceptable
range (see specification for the details), this inverter is able to charge the
battery.
NOTE: Never connect the positive or negative poles of the solar equipment
to ground.
NOTE: This inverter is only compatible with 240V Split-phase grid or
generator input. The voltage between Line 1 and Line 2 is equal to Line 1 to
Neutral plus Line 2 to Neutral. The equipment does not support single-phase or
three-phase input or output.
Product Overview
NOTE: For parallel installation and operation, refer to the commissioning guide and connection diagrams.
- LCD display
- Status indicator
- . Charging indicator
- Fault indicator
- Function buttons
- Power on/off switch
- AC input connectors
- AC output connectors (Load connection)
- PV connections
- Battery connections
- RS-232 communication port
- Remote LCD panel communication port
- Parallel communication port (only for use in parallel setups)
- Current sharing port (only for parallel model)
- Dry contact
- USB communication port
- LED indicators for USB function setting / Output source priority timer / Charger source priority setting
- BMS communication port (RS-485)
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure nothing inside the
package is damaged. Check to ensure the following items are included with each
inverter:
Preparation
To prepare for the wiring step of installation, remove the bottom cover as
shown below. Mounting the Unit
Consider the following points before selecting a location for installation:
- Avoid mounting the inverter on combustible construction materials. Masonry or fire-resistant surfaces for mounting are recommended.
- Mount on a solid surface or appropriate strut/frame.
- Install this inverter at the operator’s eye level in order to allow the LCD display to be read at all times.
- The ambient temperature should be between 14°F(-10°C) and 122°F(50°C) to ensure optimal operation.
- Install the inverter vertically and follow local AHJ requirements for equipment clearances.
- Ensure enough clearance based on the diagram above for proper cooling/ventilation.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACES ONLY.
Mounting the Inverter
Install the unit using all three screw holes. Use #8 (M4) or #10 (M5)
screws. Battery Connection
CAUTION: For safe operation and regulation compliance, it is required to
install a separate DC over-current protector or disconnect device between
battery and inverter. It may not be required to have a disconnect device in
some applications, however, you are required to have over-current protection
installed. Please refer to typical amperage in the below table for required
fuse or breaker size.
WARNING! All wiring must be performed by electrically trained personnel
WARNING! It’s critically important for system safety and efficient
operation to use appropriate cable sizes for battery connections. To reduce
risk of injury, please use the proper recommended cable and terminal sizes
below. Recommended battery cable and terminal size:
Model| Typical Amperage| Minimum Battery Capacity|
Wire Size| Ring Terminal| Torque Value
---|---|---|---|---|---
Min size| Dimensions
D (mm)| L (mm)
6KW| 137A| 300AH| 2AWG| 2AWG/ 38mm2| M10 13mm nut| 39| ~ (2-3 Nm)
Please follow below steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the nuts are tightened with a torque of 17-27 in-lbs/ 2-3 Nm. Make sure polarity at both the battery and the inverter/ charger is correctly connected and ring terminals are tightly screwed to the battery terminals.
WARNING: Shock Hazard
Installation must be performed carefully; arc and shock hazards are present.
CAUTION! Do not place anything between the flat part of the inverter
terminal and the ring terminal. Mixed materials, gaps, and loose connections
can all lead to overheating.
CAUTION! Do not apply anti-oxidant substance on the terminals before
terminals are connected.
CAUTION! Before connecting the DC circuit, ensure proper polarity of the
system. Ensure the positive (+) terminal of the inverter is properly connected
to the battery, and disconnect/fusing or breaker, as well as the polarity of
the negative (-) connections.
AC Input/Output Connection
CAUTION! Before connecting to AC input power source, install a separate
AC breaker (40A max) between inverter and AC input power source. Ensure the
input breaker and conductor ratings match. Installation of a breaker on the AC
input is required for OCP and means of disconnect. Check with your AHJ and
ensure correct system design for regulatory compliance.
CAUTION! There are two sets of terminal blocks, one for input and the
other for output. While the terminals are marked “IN” and “OUT”, double check
to ensure wires throughout the system are connected and phased correctly. Use
fine stranded 90C rated wiring of the correct type based on code requirements.
WARNING! All wiring must be performed by qualified personnel. Follow the
requirements of your local AHJ.
WARNING! For all AC wiring, proper sizing is required. Refer to the wire
type and ampacity calculations required by the specific design, site, and
local regulatory requirements. To reduce risk of injury and damage to
equipment, please use the minimum recommended cable size as below. Suggested
minimum cable requirement for AC wiring:
Model | Gauge | Terminal Torque Value |
---|---|---|
6KW | 10 AWG | ~10-14 in-lbs (1.2-1.6 Nm) |
Please follow the below steps to implement AC input/output connection:
-
Before making AC input/output connection, disconnect all DC sources of energy.
-
Remove ~7/16” (10mm) of insulation from all eight wires (L1, N, L2, G).
-
Insert AC input wires according to labeling on the terminal blocks and tighten the terminal screws. Be sure to connect the grounding conductor ( ) first.
→ Ground (Green or Green with Yellow stripe)
L1 → Line (Black)
L2 → Line (Red)
N → Neutral (White or Gray)
Note: Cord grips, conduit, or other approved methods of securing wires must be used.
Note: Wire colors may vary. WARNING:
Ensure all AC power sources and loads are disconnected before wiring the unit. -
Insert the AC output wires according to labeling on the terminal block and tighten terminal screws. Be sure to connect the grounding conductor ( ) first.
→ Ground (Green or Green with a Yellow stripe)
L1 → Line 1 (Black)
L2 → Line 2 (Red)
N → Neutral (White or Gray)
Note: Cord grips or other approved methods of securing wires must be used.
Note: Wire colors may vary. -
Make sure the wires are securely connected, and use required cord grips or conduit.
CAUTION: Important
Connect AC wire to correct terminals. If either Line 1 or 2 are reversed with
Ground/Neutral it will cause a short-circuit and damage the equipment and
loads connected to the system.
CAUTION: Appliances with heavy start and run demands, such as air
conditioners, require special consideration. For many air conditioners for
example, at least 2~3 minutes to restart might be required to allow enough
time to balance refrigerant gases. If a power outage occurs and recovers in a
short time, it may cause damage to the connected appliances. To prevent
damage, please check with the manufacturer of the appliance to see if it is
equipped with a time-delay function or soft-start feature before installation.
Overload of the inverter/charger may trigger a fault leading to a sudden loss
of AC output power, which may cause damage to appliances with
motors/compressors.
PV Connection
CAUTION: Before connecting to PV modules/strings, install separate DC
circuit breakers or a means of disconnect paired with properly sized fuses
between inverter and PV modules/strings. DO NOT work with or connect live PV
conductors to the unit EVER. Ensure all exposed conductors are safely
disconnected from the power source.
NOTE: Use 600V/30A rated circuit breakers. DC rated breakers must be
used. The over voltage category of the PV input is II. Please Follow the steps
below to complete PV connections.
WARNING! All wiring must be performed by qualified personnel.
WARNING: Making connections with live a PV source will damage the
inverter!
WARNING! It’s very important for system safety and efficient operation to
use appropriate cables for PV module connection. To reduce risk of injury, use
the proper recommended cable size below.
CAUTION: It is required to use a PV surge protection device. Damage to
the inverter can occur from surges such as lighting or short circuits.
Model | Typical Amperage | Cable Size | Torque |
---|---|---|---|
6KW | 27A | 10AWG | ~17-21 in-lbs (-2.0-2.4Nm) |
PV Module Selection:
- Open Circuit Voltage (Voc) of the PV modules/strings must not exceed the unit’s maximum rating. Voc must be calculated including the environmental impacts, such as temperature in accordance to the module manufacturer’s data sheet and reliable weather data for the installation location.
- Voltage at Maximum Power (Vmp) of PV strings must be higher than the start-up voltage of the inverter.
WARNING: Exceeding the maximum input voltage will destroy the unit!
Solar Charging Mode
INVERTER MODEL| 6KW
Max. PV Array Open Circuit Voltage| 500 Vdc
PV Array MPPT Voltage Range| 120-480Vdc
MPP Number| 1
Follow the below steps to complete PV connection:
- Remove 10 mm (3/8in) of insulation from positive and negative conductors.
- Check for correct polarity of connections at the PV inputs at the disconnect, with the disconnecting means off to ensure the exposed output in not live. Connect the positive pole (+) of the PV source to the positive pole (+) of PV input terminal. Connect the negative pole (-) of the PV source to the negative pole (-) of the PV input terminal. Tighten the terminals.
Final Assembly
After connecting all wiring, please put the bottom cover back by screwing four screws as shown below.
Communication Connection
Serial Connection
Please use the supplied communication cable to connect to inverter and PC.
Insert the bundled CD into a computer and follow the on-screen instructions to
install the monitoring software. For the detailed software operation
instructions, please check the user manual of the software stored on the CD.
Wi-Fi Connection
Wi-Fi module can enable wireless communication between off-grid inverters and
the cloud monitoring platform. Users have complete remote monitoring and
control capacity for inverters when combining the WiFi module with the
SolarPower APP, available for both iOSand Android based device. All data
loggers and parameters are saved in the cloud. Refer to Appendix IV for
detailed operation. Dry Contact Signal
There is one dry contact (3A/250VAC) available on the rear panel. It could be
used to deliver a signal to an external device when battery voltage reaches a
warning level.
Unit Status | Condition | Dry contact port: |
---|---|---|
NC & C | NO & C | |
Power Off | Unit is off and no output is powered. | Close |
Power On | Output is powered from Utility. | Close |
Output is powered from Battery or Solar. | Program 01 set as SUB | Battery |
voltage < Low DC warning voltage | Open | Close |
Battery voltage > Setting value in Program 21 or battery charging reaches
floating stage| Close| Open
Program 01 is set as SBU| Battery voltage < Setting value in Program 20| Open|
Close
Battery voltage > Setting value in Program 21 or battery charging reaches
floating stage| Close| Open
OPERATION
Power ON/OFF After completing installation of the unit, the next step
is powering on for setup. Start by pressing the On/Off switch (located on
display unit) to power on the system.
Operation and Display Panel
Refer to the diagram and table below for details on the operation and display
panel. There are three indicators, four function keys, and an LCD display.
LED
Indicators
LED Indicator | Messages |
---|---|
Setting LED1 | Green |
Setting LED2 | Green |
Setting LED3 | Green |
**Status Indicator** | **** |
utility in Line mode.
Flashing| Output is powered by battery or PV in battery mode.
CHG| Green| Solid On| Battery is fully charged
Flashing| Battery is charging.
FAULT| Red| Solid On| Fault mode
Flashing| Warning mode
Function Keys
Function Key | Description |
---|
| ESC| Exit the setting/go back
| Reserved| Reserved
| Reserved| Reserved
| Up| Scroll to previous selection
| Down| Scroll to next selection
| Enter| To confirm/enter the selection in setting mode
LCD Display Icons
Icon | Function |
---|
Input source information
| Indicates AC input information is being displayed
| Indicates PV1 input information is being displayed (PV2 not used)
Left digital display information
| Indicates input voltage, input frequency, battery voltage, PV voltage,
charger current
Middle digital display information
| **** Indicates the setting when cycling through options.
| Indicates the warning and fault codes.
Warning: Flashing with warning code
Fault: display with fault code
Right digital display information
| Displays the output voltage, output frequency, load percent, load VA, load
W, PV charger power, DC discharging current based on current unit being
displayed and cycled through.
Battery information
| Displays battery state of charge (SOC) by ranges from 0-24%, 25-49%, 50-74%,
and 75-100% per bar, and charging status.
Load information
| Indicates output overload.
| Indicates the load level by 0-24%, 25-49%, 50-74%, and 75-100%.
0%~24%| 25%~49%| 50%~74%| 75%~100%
|
| ****|
Mode operation information
| Indicates connection to an AC input source.
| **** Indicates connection of the PV array.
| Indicates solar is being used to charge the battery bank.
| Indicates the DC/AC inversion is working.
Mute operation
| Alarm is disabled. Warning: Will not signal a fault when disabled!
LCD Setting
After pressing and holding ENTER button for 3 seconds, the unit will enter
setting mode. Press “UP” or “DOWN” buttons to select setting programs. Then,
press the “ENTER” button to confirm the selection or the ESC button to exit.
Program | Description | Selectable option |
---|---|---|
00 | Exit setting menu | Escape |
01| Output source priority selection| SUB (Default)
| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, Utility energy
will supply power to the loads at the same time.
SBU| Solar energy provides power to the loads as first priority.
If solar energy is not sufficient to power all connected loads, battery energy
will supply power to the loads at the same time.
Utility provides power to the loads only when battery voltage drops to either
low-level warning voltage or the setting point in program 20, or if solar and
battery is not sufficient.
02| AC input voltage range| Appliances (Default setting)
| If selected, acceptable AC input voltage range will be set to 65-140VAC.
---|---|---|---
UPS| If selected, acceptable AC input voltage range will be set to 95-140VAC.
03| Output voltage| 110Vac| 120V (Default setting)
04
|
Output frequency
| 50Hz| 60Hz (Default setting)
05| Solar supply priority| Available power will charge battery first (default
setting)| Solar energy provides power to charge battery as first priority.
Power supplies the loads first| Solar energy provides power to the loads as
first priority.
06| Overload bypass: When enabled, the unit will transfer to line mode if
overload occurs in battery mode.| Bypass disabled| Bypass enable (default
setting)
07| Auto restart when overload occurs| Restart disable (default setting)|
Restart enabled
08| Auto restart when over temperature occurs| Restart disable (default
setting)| Restart enabled
09| Solar energy feed to grid configuration
WARNING: THIS SETTING IS NOT CERTIFIED FOR THE UNITED STATES,
ALWAYS GET SPECIFIC PERMISSION FROM YOUR UTILITY AND AHJ TO OPERATE THIS
MODE| Feed to grid disable (default setting)| Solar energy back-feed to
grid disable.
Feed to grid enable| Solar energy back-feed to grid enable.
10| Charger source priority: Configure battery charger source priority| If
this inverter/charger is working in Line, Standby or Fault mode, charger
source can be programmed as below:
---|---|---
Solar first| Solar energy will charge battery as first priority. Utility/AC
input will charge battery only when solar energy is not available.
Solar and Utility (default)| Solar energy and utility/AC input will charge
battery at the same time.
Solar only
**| Solar energy will be the only charger source, even when utility/AC
input power is available.
If this inverter/charger is working in Battery mode, only solar energy can
charge the battery. Solar energy will charge battery if it’s available and
sufficient.
11| Maximum charging current: To configure total charging current for solar
and utility chargers.
(Max charging current = utility/AC input charging current + solar charging
current)| 60A (default setting) 120A is needed for 7.5kW PV capacity
**| The setting range is from 10A to 120A. Each click is a 10A increment.
13| Maximum utility/AC input charging current| 30A (default setting)| The
setting range is from 10A to 120A. Each click is a 10A increment.
14| Battery type| AGM (default)| Flooded
User-Defined| If “User-Defined” is selected, battery charge voltage and low DC
cut-off voltage can be set up in program 17, 18 and 19.
EG4| If this is selected, programs 11, 17, 18 and 19 will be automatically set
up. Please contact the battery supplier for installation procedure.
| | LIb-protocol
| Select “ LIb” if using Lithium battery compatible to Lib protocol. If
selected, programs of 11, 17, 18 and 19 will be automatically set up. No need
for further setting.
---|---|---|---
3rd party Lithium battery| If selected, programs of 11, 17, 18 and 19 will be
automatically set up. Please contact the battery supplier for installation
procedure.
17| Bulk charging voltage (C.V voltage)| Default setting: 56.4V
If self-defined is selected in program 14, this program can be set up. Setting
range is from 48.0V to 64.0V. Each click is an increment of 0.1V.
18| Float charge voltage| Default setting: 54.0V
If self-defined is selected in program 14, this program can be set up. Setting
range is from 48.0V to 64.0V. Each click is an increment of 0.1V.
19| Low DC cut off battery voltage setting
| Default setting: 40.8V
If self-defined is selected in program 14, this program can be set up. Setting
range is from 40.8V to 48.0V. Each click is an increment of 0.1V. Low DC cut-
off voltage will be fixed to setting value no matter what percentage of load
is
20| Bypass loads to grid when grid is present.
| connected. default setting: 46V| Setting range is from 44V to 51V and each
click is an increment of 1V. In EG4 Mode you will see a percentage instead
21| Set point for transfer back to off-grid operation if system is bypassed
based on 20| Battery fully charged| The setting range is from 48V to 58V, Each
click is an increment of 1V.
In EG4 Mode you will see a percentage instead
Default setting: 54V
22| Auto return to default display screen| Return to default display screen
(default)
| If selected, no matter how users switch display screen, it will
automatically return to default display screen (Input voltage /output voltage)
after no button is pressed for 1 minute.
---|---|---|---
Stay at latest screen
| If selected, the display screen will stay at latest screen user selects
(good for keeping your favorite view up)
23| Backlight control| Backlight on (default)
| Backlight off
24| Alarm control| Alarm on (default setting)
| Alarm off
25| Beeps while primary power source is interrupted/faults| Alarm on (default
setting)
| Alarm off
26| AC coupling (may require firmware update not available at release date of
this model)| Enable| Disable
27| Record Fault codes (this is best to enable)| Record enabled (default)
| Record disable
28| AC output mode *This setting is only available when the inverter is in
standby mode (Switch off).| Single: When selected, the unit is used in
standalone operation.
| Parallel: When selected, Parallel stacking of up to 9 units is enabled
29| Reset PV energy storage kwh history| Not reset (default setting)
| Reset
30| Scheduled Start charging time for AC charger| 00:00 (default setting)
The setting range of starting time for the AC charger is from 00:00 to 23:00,
each click is 1 hour.
---|---|---
31| Scheduled Stop charging time for AC charger| 00:00 (default setting)The
setting range of stop charging time for AC charger is from 00:00 to 23:00,
each click is 1 hour.
32| Scheduled time for AC output on| 00:00 (default setting) The setting range
of scheduled time for AC output on is from 00:00 to 23:00, each click is 1
hour.
33| Scheduled time for AC output off| 00:00 (default setting) The setting
range of scheduled time for AC output off is from 00:00 to 23:00, each click
is 1 hour.
95| Current time setting – Minute| For minute setting, the range is from 00
to 59.
96| Current time setting – Hour| For hour setting, the range is from 00 to
23.
97| Current time setting– Day| For day setting, the range is from 00 to 31.
98| Current time setting– Month| For month setting, the range is from 01 to
12.
99| Current time setting – Year| For year setting, the range is from 16 to
99.
Display Setting
The LCD display information is cycled through by pressing “UP” or “DOWN” keys.
The selectable information is switched as below order: input voltage, input
frequency, PV voltage, charging current, battery voltage, output voltage,
output frequency, load percentage, load in watts, load in VA, load in watts,
DC discharging current, main board firmware version and SCC firmware version.
Select item | LCD display |
---|---|
Input 1 voltage and output 1 voltage (Default display screen) | Input 1 |
Voltage=120V, output 1 voltage=120V
Input 2 voltage and output 2 voltage (Default display screen)| Input 2
Voltage=120V, output 2 voltage=120V
Input 1 frequency and output 1 frequency| Input 1 frequency=60.0Hz, output 1
frequency=60.0Hz
Input 2 frequency and output 2 frequency| Input 2 frequency=60.0Hz, output 2
frequency=60.0Hz
---|---
Battery voltage and output 1 voltage| Battery Voltage=48.0V, output 1
voltage=120V
Battery voltage and output 2 voltage| Battery Voltage=48.0V, output 2
voltage=120V
Battery voltage and load 1 percentage| Battery Voltage=48.0V, load 1
percentage = 68%
Battery voltage and load 2 percentage| Battery Voltage=48.0V, load 2
percentage = 68%
---|---
Battery voltage and load 1 in VA| Battery Voltage=48.0V, load 1 in
VA=1.08kVA
Battery voltage and load 2 in VA| Battery Voltage=48.0V, load 2 in
VA=1.08kVA
Battery voltage and load 1 in watts| Battery Voltage=48.0V, load 1 in
Watt=1.88kW
Battery voltage and load 2 in watts| Battery Voltage=48.0V, load 2 in
Watt=1.88kW
---|---
PV1 voltage and PV power| PV1 Voltage=360V, PV power=1.58kW
Charger current and DC discharging current| Charging current=30A, discharging
current=0A
PV energy generated today| Daily production example = 6.3kWh
PV energy generated this month| Monthly energy example = 358kWh
---|---
PV energy generated this year| Yearly energy example = 8.32MWh
Lifetime PV energy generated| Total energy example = 13.9MWh
Date| Date example Nov 28, 2016.
Time (24HR format)| Time example 13:20.
---|---
Main CPU version checking.| Main CPU version 00001.00
Secondary CPU version checking.| Secondary CPU version 00020.21
Operating Mode Description
Operating mode | Behaviors | LCD display |
---|
** Standby mode
Note:* Standby mode: The inverter is not turned on yet but at this time,
the inverter can charge battery without AC output.
| No output power, solar or utility charger available| The battery is
charging using utility/AC input power.
The battery is charging using PV energy.
The battery is charged using utility/AC input and PV energy.
| | Battery is charged by PV energy and feed PV energy to grid.
---|---|---
The battery is not charging.
Line mode| Output power from utility. Charger available| Utility
charges battery and provides power to load.
Utility and battery power provide power to load.
Line mode| ****
**** Output power from utility. Charger available
| PV energy, battery power and utility provide power to load.
Output power from utility. Charger available| PV energy and utility charge
battery, and utility provides power to load.
PV energy charges battery, utility and PV energy provide power to the
load.
PV energy is charging the battery, PV energy provides power to the load and
feeds remaining energy to the grid.
Battery mode| Output power from battery or PV| PV energy and the
battery are supplying power to the loads.
---|---|---
PV energy is charging the battery and providing power to the loads.
The battery is providing power to the loads.
Only PV mode| Output power from PV| PV energy is providing power
to the loads.
Fault mode
Note:
*Fault mode: Errors are caused by inside circuit error or external reasons
such as over temperature, output short circuited and so on.| **** No output,
no charging.| The battery is not charging.
Parallel Function
- Introduction
This inverter can be used in parallel in only split phase systems. A maximum of nine units can parallel together. The supported maximum output power is 54kW/54KVA.
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Note: Use a 40A 2 Pole AC breaker for only 1 unit and install one breaker for the AC input in each inverter.
Recommended Battery Capacity**** Inverters in parallel| 2| 3| 4| 5| 6| 7| 8| 9
---|---|---|---|---|---|---|---|---
Battery Capacity (48V)| 500AH| 700AH| 1000AH| 1200AH| 1400AH| 1700AH| 1900AH| 2100AH - Parallel Operation
Two inverters in parallel:
Warning: Current sharing cables must be connected properly based on the below diagrams. Current sharing cables are shown in green, dashed lines. Improper connections and setup of these cables will result in damage.
Power Connection
Three inverters in parallel:
Power Connection Communication Connection Four inverters in parallel:
Power Connection Communication Connection Five inverters in parallel:
Power Connection Communication Connection Six inverters in parallel:
Power Connection Communication Connections Seven inverters in parallel:
Power Connection Communication Connection
Eight inverters in parallel:
Power Connection Communication Connection
Nine inverters in parallel:
Power Connection Communication Connection
LCD Setting and Display
Setting Program:
Program | Description | Selectable option |
---|---|---|
**** 28 | AC output mode | |
*This setting is only available when the inverter is in standby mode (Switch off). | Single: | |
When selected, the unit is used in single operation. | ||
Parallel: | When selected, this inverter is operated in parallel system. The |
maximum number of parallel units is 9.
Parallel system fault codes:
Fault Code | Fault Event | Icon on |
---|---|---|
60 | Power feedback protection | |
71 | Firmware version inconsistent | |
72 | Current sharing fault | |
80 | CAN fault | |
81 | Host loss | |
82 | Synchronization loss | |
83 | Battery voltage detected different | |
84 | AC input voltage and frequency detected different | |
85 | AC output current unbalance |
BMS Communication Install – EG4-LL
Introduction
When connecting to an EG4-LL battery use the supplied RJ45 battery
communication cable. Please check withyour dealer or installer for details.
This custom-made RJ45 communication cable delivers information and signal
between lithium battery and the inverter. The information is listed below:
- Re-configure charging voltage, charging current an d battery discharge cut-off voltage according to the lithium battery parameters as .
- Starting and stopping of charging is based on the batteries State Of Charge (SOC).
Pin Assignment for BMS Communication Port
PIN | Definition |
---|---|
PIN 1 | RS232TX |
PIN 2 | RS232RX |
PIN 3 | RS485B |
PIN 4 | NC |
PIN 5 | RS485A |
PIN 6 | CANH |
PIN 7 | CANL |
PIN 8 | GND |
Battery Communication Install – EG4-LL Cont.
Using the 1ft RS485 cable, interconnect the batteries as illustrated in the
diagram below. Battery Communication Install –
LiFePower4
Using the 1ft RS485 cable, interconnect the batteries as illustrated in the
diagram below.
Settings for EG4 Lithium Batteries- Master/Slave
-
Dip Switch: There are 4 Dip Switches which set different baud rates and battery group addresses. If switch position is turned to the “OFF” position, it means “0”. If switch position is turned to the “ON” position, it means “1”.
EG4-LL Battery
Dip 1, 2, and 3 are in the “ON” positionon = down
Dip 4 is in the “OFF” position off = up
The 1-3 “ON” & 4 “OFF” configuration is to indicate Master battery status and is reserved for communications with the 5inverter.
A Max of 16 batteries can communicate in a single battery bank using different dipswitch addresses. EG4-LifePower4 Battery
Dip 1, 2, 3, and 4 are in the “OFF” position *off = down
The ALL “OFF” position is to indicate the Master battery status and is reserved for communications with the inverter
A Max of 16 batteries can communicate in a single battery bank. Please Note: If you change the dipswitches, you must power cycle the batteries for the BMS to recognize the new dipswitch address. -
Installation
Step 1. Use the RS485 cable to connect inverter and Lithium battery as Fig 1.
Step 2. Switch on the battery breaker/s.
Step 3.Turn on the inverter.
Step 4.Select battery type as “EG4” in LCD program 5 for the Master inverter.
For other paralleled inverters, you must set to “USE”.
If communication between the inverter and battery is successful, the battery
icon on LCD display will flash
For EG4-LL ensure the red power switch is set to “ON” as well as the breaker.
Even with the EG4 batteries having built-in breakers, a minimum 150A in line
breaker is required, and a 200A in line breaker is recommended.
Refer to each battery manual for setting master and follower battery address
settings.
Battery Based Commissioning REQUIRED PROCEDURE
Note: Systems must be commissioned while connected to a battery bank. PV or
AC input only based commissioning is not recommended or supported.
NOTE: This guide is to be used after the physical installation of the
system is complete.
NOTE: For best use case, ensure that all settings are programmed per
user/site specific requirements.Single Unit Systems:
Step 1 – Ensure all inverter connections are correct, and all input and output
breakers of the system are off.x
Step 2 – Turn on the system’s DC breaker (between inverter and batteries if
equipped), master battery breaker and/or power button, and then power on the
inverter by depressing the power button (in that exact order).
Step 3 – After the startup countdown, hold the enter “ ” button for 3 seconds
to access the settings menu.
Step 4 – Use the down arrow to go to program setting 28 (AC output mode).
Note: If the inverter is already set to “SIG”, press escape to return to main
screen, power on the rest of the batteries and skip to Step 10.
Step 5 – Depress/release the power button to go into standby mode.
Step 6 – Press the enter button, then use the up and down buttons to set the
inverter to “SIG.” Press the enter button (to save the setting) and then press
escape to return to the main screen.
Step 7 – Depress the power button to exit standby mode.
Step 8 – Turn off battery breakers and inverter to power down the system to
ensure settings implementation.
Step 9 – Turn on the system’s DC breaker (between inverter and batteries if
equipped), all battery breakers and/or power buttons, and power on the
inverter. (in that exact order)
Step 10 – Switch on all AC in breakers.
Step 11 – Ensure PV voltage meets specifications on page 9. Turn on PV power.
Step 12 – Switch on all AC out breakers.
Multi-unit Systems:
Step 1 – Ensure all inverter connections are correct, and all input and
output breakers of the system are off.
Step 2 – Turn on the system’s DC breaker (between inverters and batteries if
equipped), master battery
breaker and/or power button, and then power on all inverters by depressing the
power buttons (in that exact order). Step 3 – After the startup countdown,
hold the enter “ ” button for 3 seconds to access the settings menu.
Step 4 – Use the down arrow to go to program setting 28 (AC output mode).
Step 5 – Depress/release the power button to go into standby mode.
Step 6 – Press the enter button, then use the up and down buttons to set the
inverter to “PAL.” Press the enter button (to save the setting) and then press
escape to return to the main screen.
Step 7 – Depress the power button to exit standby mode. Repeat steps 3-7 for
all inverters.
Step 8 – Turn off battery breakers and inverters to power down the system and
ensure settings implementation.
Step 9 – Turn on the system’s DC breaker (between inverters and batteries if
equipped), all battery breakers and/or power buttons, and then power on all
inverters by depressing the power buttons (in that exact order).
NOTE: Host and slave inverters will be randomly defined.
Step 10 – Switch on all AC in breakers.
Step 11 – Ensure PV voltage meets specifications on page 9. Turn on PV power.
Step 12 – Switch on all AC out breakers.
Troubleshooting
Warning Indicator
Warning Code | Warning Event | Icon flashing |
---|---|---|
01 | Fan locked | |
02 | Over temperature | |
03 | Battery over charged | |
04 | Low battery | |
07 | Overload |
10| Inverter power derating|
15| PV is weak|
19| Battery is not connected|
32| DSP remote command loss|
60| S disable charge/discharge|
61| BMS command loss| ****
62| BMS pack warning|
69| BMS stopped charge|
70| BMS force charge|
71| BMS stopped discharge|
Faults Reference Code
Fault Code | Fault Event | Icon on |
---|---|---|
01 | Fan is locked. | |
02 | Over temperature | |
03 | Battery voltage is too high. | |
04 | Battery voltage is too low. | |
05 | Output is short circuited. | |
06 | Output voltage is abnormal. | |
07 | Overload time out. | |
08 | Bus voltage is too high. | |
09 | Bus soft start failure. | |
10 | PV current is over. | |
11 | PV voltage is over. | |
12 | Charge current is over. | |
51 | Over current or surge | |
52 | Bus voltage is too low. | |
53 | Inverter soft start failure. | |
55 | Over DC offset in AC output | |
56 | Battery is not connected. | |
57 | Current sensor failure. | |
58 | Output voltage is too low. |
General Trouble Shooting
Problem| LCD/LED/Buzzer| Explanation / Possible cause| What
to do
---|---|---|---
Unit shuts down automatically
during startup process.| LCD/LEDs and buzzer will be active for 3 seconds and
then complete off.| The battery voltage is too low (<1.91V/Cell)|
1. Re-charge battery.
2. Replace battery.
No response after power on.| No indication.| 1. The battery
voltage is far too low. (<1.4V/Cell)
2. Battery polarity is connected reversed.| 1. Check if batteries and the
wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Utility/AC input is available, but the unit only pulls energy from the
batteries when in utility/AC input as priority source.| Input voltage is
displayed as 0 on the LCD and green LED is flashing.| Input protector is
tripped| Check if AC breaker is tripped and AC wiring is connected well.
Green LED is flashing.| Insufficient quality of AC power. (Utility
or Generator)| 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range
setting is correct. (UPSàAppliance)
Green LED is flashing.| You have set “Solar First” as the priority of output
source.| Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.|
LCD display and LEDs are flashing| Battery is disconnected.|
Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.| ****
Fault code 07
| Overload error. The inverter is overload 110% and time is up.| Reduce the connected load by switching off some equipment.
Fault code 05
| ****
Output short circuited.
| Check if wiring is connected well and remove abnormal load.
Temperature of internal converter component is over 248°F (120°C).| Check
whether the air flow of the unit is blocked or whether the ambient temperature
is too high.
Fault code 02| Internal temperature of inverter component is over 212°F
(100°C).
Fault code 03| Battery is over-charged.| Return to repair center.
The battery voltage is too high.| Check if spec and quantity of
batteries meet requirements.
Fault code 01| Fan fault| Replace the fan.
Fault code 06/58| Output abnormal (Inverter voltage below than 190Vac or
is higher than 260Vac)| 1. Reduce the connected load.
2. Return to repair center
Fault code 08/09/53/57| Internal components failed.| Return to repair center.
Fault code 10| Surge| Restart the unit, if the error happens again,
please return to repair center.
Fault code 12| DC/DC over current or surge.
Fault code 51| Over current or surge.
Fault code 52| Bus voltage is too low.
Fault code 55| Output voltage is unbalanced.
**** Fault code 56| Battery is not connected well or fuse is burnt.| If the
battery is connected well, please return to repair center.
Fault code 11| Solar input voltage is more than 500V.| Reduce solar input
below 500V in all temperatures
Parallel Systems Trouble Shooting
Situation | **Solution** |
---|---|
Fault Code | Fault Event Description |
60
| ****
Current feedback into the inverter is detected.
| 1. Restart the inverter.
2. Check if L1/L2/N cables are phased properly in all inverters.
3. For parallel system in split phase, make sure the red/black current
sharing cables are connected well (with screws) to all inverters.
4. If the problem remains, please contact your installer.
71| The firmware version of each inverter is not the same.| 1.
Update all inverter firmware to the same version.
2. Check the version of each inverter via LCD settings and make sure the CPU
versions are th same. If not, please contact your installer/retailer to
provide the firmware to update.
3. After updating, if the problem still remains, please contact your
installer.
72
| The output current of each inverter is
different.
| 1. Check if sharing cables are connected properly and restart the inverter.
2. If the problem remains, please contact your installer.
80| CAN data loss| 1. Check if communication cables are connected well and
restart the inverter.
2. If the problem remains, please contact your retailer installer.
81| Host data loss
82| Synchronization data loss
83| **** The battery voltage of each inverter is not the same.| 1.
Make sure all inverters share same the same battery bank
2. Remove all loads and disconnect AC input and PV input. Then, check battery
voltage of all inverters. If the values from all inverters are close, please
check if all battery cables are the same length and same material type.
Otherwise, please contact your installer/retailer to provide SOP to calibrate
battery voltage of each inverter.
3.If the problem still remains, please contact your retailer or installer.
84| AC input voltage and frequency are different.| 1. Check the
utility wiring conncetion and restart the inverter.
2. Make sure utility starts up at same time. If there are breakers installed
between utility and inverters, please be sure all AC input breakers can be
powered on at one time . A main breaker or disconnect is required
3. If the problem remains, please contact your installer.
85| AC output current unbalance| 1. Restart the inverter.
2. Remove some excessive loads and re-check load information from LCD of
inverters. If the values are different, please check if AC input and output
cables are in the same length and material type.
3. If the problem remains, please contact your installer.
Wi-Fi Operation Guide in Remote Panel
- Introduction
The Wi-Fi module can enable wireless communication between off-grid inverters and the cloud monitoring platform. Users have complete and remote monitoring and control experience for inverters when combining the Wi-Fi module with the SolarPower APP, available for both iOS and Android based device. All data loggers and parameters are saved in the the cloud.
• The major functions of this APP:
• Delivers device status during normal operation.
• Allows to configure device settings after installation.
• Notifies users when a warning or alarm occurs.
• Allows users to query inverter history data.![EG4 6000EX-48 Inverter Charger
-
Remote Panel](https://manuals.plus/wp-content/uploads/2023/11/EG4-6000EX-48 -Inverter-Charger-Remote-Panel.jpg)
- Solar Power App
2.1. Download and install APP
- Solar Power App
Operating system requirementt for your smarts phone::
iOS system supports iOS 9.0 and above
Android system supports Android 5.0 and above
Please scan the following QR code with your smart phone and download Solar
Power App.
https://play.google.com/store/apps/details?id=wifiapp.volfw.solarpower https://apps.apple.com/us/app/id1491698936
Or you may find “Solar Power” app from the Apple® Store or “Solar Power Wi-Fi” in Google® Play Store.
Initial Setup
Step 1: Registration at first time
After the installation, please tap the shortcut icon to access this APP on
your mobile screen. In the screen, tap “Register” to access “User
Registration” page. Fill in all required information and scan the remote box
PN by tapping icon. Or you can simply enter PN directly. Then, tap “Register”
button.Then, a “Registration success” window will pop up. Tap “Go now” to
continue setting local Wi-Fi network connection. Step 2: Local Wi-Fi Module
Configuration
Now, you are in “Wi-Fi Config” page. There are detailed setup procedure listed
in “How to connect?” section and you may follow it to connect Wi-Fi. Enter the “Settings
Wi-Fi” and select connected Wi-Fi name. The connected Wi-Fi name is the same
as your Wi-Fi PN number and enter default password “12345678”.Then, return to Solar Power APP and tap “ ” button when Wi-Fi
module is connected successfully.
Step 3: Wi-Fi Network settings Tap icon to select your local Wi-Fi router name
(to access the internet) and enter password. ![EG4 6000EX-48 Inverter Charger
- enter password](https://manuals.plus/wp-
content/uploads/2023/11/EG4-6000EX-48-Inverter-Charger-enter-password.jpg)Step
4: Tap “Confirm” to complete the Wi-Fi configuration between the Wi-Fi module
and the Internet. If the connection fails, please
repeat Step 2 and 3. Diagnose Function
If the module is not monitoring properly, please tap “ ” on the top right corner of the screen for further details. It will show repair suggestions. Please follow it to fix the problem. Then, repeat the steps in the chapter 4.2 to re-set network setting. After all setting, tap “Rediagnosis” to re-connect again. Login and APP Main Function
After finishing the registration and local Wi-Fi configuration, enter registered name and password to login. Note: Select “Remember Me” for your login convenience afterwards. Overview
After login is successful, you can access the “Overview” page to have an overview of your monitoring devices, including overall operation situation and energy information for current power and daily power as below diagram. Devices
Tap the icon (located on the bottom) to enter Device List page. You can review all devices here by adding or deleting Wi-Fi Module in this page. Tap icon on the top right corner and manually enter part number to add device. This part number label is pasted on the bottom of remote LCD panel. After entering part number, tap “Confirm” to add this device in the Device list.For more information about Device List, please refer to the section 2.4.
User Information
In ME page, users can modify “My information”, including User’s Photo , Account security ,Modify password , Clear cache ,and Log-out , shown as below diagrams. 2.2. Device List
In Device List page, you can pull down to refresh the device information and then tap any device you want to check up for its real-time status and related information as well as to change parameter settings. Please refer to the parameter setting list. Device Mode
On the top of screen, there is a dynamic power flow chart to show live operation. It contains five icons to present PV power, inverter, load, utility and battery. Based on your inverter model status, there will be Standby Mode , Line Mode , Battery Mode . Standby Mode Inverter will not power the load until “ON” switch is pressed. Qualified utility or PV source can charge battery in standby mode. Line Mode Inverter will power the load from the utility with or without PV charging. Qualified utility or PV source can charge battery. Battery Mode
Inverter will power the load from the batter with or without PV charging. Only PV source can charge battery.
Device Alarm and Name Modification
In this page, tap the icon on the top right corner to enter the device alarm page. Then, you can review alarm history and detailed information. Tap the icon on the top right corner, a blank input box will pop out. Then, you can edit the name for your device and tap “Confirm” to complete name modification. Device Information Data
Users can check up Basic Information , Product Information , Rated information , History , and Wi-Fi Module Information by swiping left. Basic Information displays basic information of the inverter, including AC voltage, AC frequency, PV input voltage, Battery voltage, Battery capacity, Charging current, Output voltage, Output frequency, Output apparent power, Output active power and Load percent. Please slide up to see more basic information.
Production Information displays Model type (Inverter type), Main CPU version and secondary CPU version.
Rated Information displays information of Nominal AC voltage, Nominal AC current, Rated battery voltage, Nominal output voltage, Nominal output frequency, Nominal output current, Nominal output apparent power and Nominal output active power. Please slide up to see more rated information.
History displays the record of unit information and setting timely.
Wi-Fi Module Information displays of Wi-Fi Module PN, status and firmware version.
Parameter Setting
This page is to activate some features and set up parameters for inverters. Please note that the listing in “Parameter Setting” page in the below diagram may differ from the models of each inverter. To highlight a few: Output Setting , Battery Parameter Setting , Enable/ Disable items , Restore to the defaults There are three ways to modify setting and they vary according to each parameter.
a) Listing options to change values by tapping one of it.
b) Use the Activate/Shut down function by clicking the “Enable” or “Disable” button.
c) Changing values by clicking arrows or entering the numbers directly in the column. Each function setting is saved by clicking the “Set” button.
Please refer to below parameter setting list for an overall description and note that the available parameters may vary depending on different models. Please always see the original product manual for detailed setting instructions.
Parameter setting list:
Item | Description |
---|---|
Output setting | Output source priority |
priority.
AC input range| Input voltage range selection
Output voltage| To set output voltage.
Output frequency| To set output frequency.
Battery parameter setting| Battery Type| Select connected battery type
Battery Cut-off Voltage| Set battery cut-off voltage
Bulk Charging Voltage| Set battery bulk charging voltage
Battery Float Voltage| Set battery floating charging voltage
Max Charging Current| To configure total charging current for solar and
utility chargers.
Max AC Charging Current| Set maximum utility charging current
Charging Source Priority| To configure charger source priority
Back To Grid Voltage| Set battery voltage to stop discharging when grid is
available
Back To Discharge Voltage| Set battery voltage to stop charging when
grid is available
Enable/Disable Functions| Overload Auto Restart| If disabled, the unit won’t
be restarted after overload occurs.
Overload Temperature Auto Restart| If disabled, the unit won’t be restarted
after over-temperature fault is solved.
Overload Bypass| If enabled, the unit will enter bypass mode when overload
occurs.
Beeps While Primary Source Interrupt| If enabled, buzzer will alarm when
primary source is abnormal.
Buzzer| If disabled, buzzer won’t be on when alarm/fault occurred.
Backlight| If disabled, LCD backlight will be off when panel button is not
operated for 1 minute.
LCD Screen Return To Default Display| If selected, no matter how users switch
display screen, it will automatically return to default display screen (Input
voltage /output voltage) after no button is pressed for 1 minute.
Fault Code| If enabled, fault code will be recorded in the inverter when any
fault
| Record| happens.
---|---|---
Solar Supply Priority| Set solar power as priority to charge the battery or to
power the load.
Reset PV Energy Storage| If clicked, PV energy storage data will be reset.
Start Time For Enable AC Charge Working| The setting range of start charging
time for AC charger is from 00:00 to 23:00. The increment of each click is 1
hour.
Ending Time For Enable AC Charge Working| The setting range of stop charging
time for AC charger is from 00:00 to 23:00. The increment of each click is 1
hour.
Scheduled Time For AC Output On| The setting range of scheduled time for AC
output on is from 00:00 to 23:00. The increment of each click is 1 hour.
Scheduled Time For AC Output Off| The setting range of scheduled time for AC
output off is from 00:00 to 23:00. The increment of each click is 1 hour.
Country Customized Regulations| **** Select inverter installed area to meet
local regulation.
Set Date Time| Set date time.
Restore to the default| This function is to restore all settings back to
default settings.
Version 1.2.0 January 2023 – I
information subject to change without notice.
Documents / Resources
| EG4
6000EX-48 Inverter
Charger
[pdf] User Manual
6000EX-48 Inverter Charger, 6000EX-48, Inverter Charger, Charger
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>