Altronix OLS20 Off-Line Power Supply Charger Installation Guide

June 4, 2024
Altronix

Altronix LOGO

OLS20
Off-Line Power Supply/Charger
Installation Guide

Overview:

Altronix OLS20 power supply/charger converts 115VAC 50/60Hz input into a 12VDC @ 1A or 24VDC @ 0.5A of continuous supply current (refer to specifications). This general-purpose power supply has a wide range of applications for access control and security system accessories that require additional power.

Specifications:

Input:

  • Input 115VAC 50/60Hz, 0.5A.

Output:

  • 12VDC or 24VDC selectable operation.
  • 0.5A continuous supply current @ 24VDC 1A continuous supply current @ 12VDC.
  • Filtered and electronically regulated outputs.
  • Short circuit and thermal overload protection.

Battery Backup:

  • Built-in charger for sealed lead acid or gel type batteries.
  • Specified at 25˚C ambient.

Battery Backup (cont’d):

  • Maximum charge current 0.3A.
  • Automatic switch over to stand-by battery when AC fails.

Additional Features:

  • AC input and DC output LED indicators.
  • Operating temperature: – 20ºC to 50ºC.
  • Includes battery leads.

Board Dimensions (W x L x H approx.): 3” x 2.5” x 1” (76.2mm x 63.5mm x 25.4mm).

Voltage Output Selection Table:

Output VDC Switch Position Max. Load DC
12VDC SW 1 – ON 1.2A
24VDC SW1 – OFF 0.5A

Installation Instructions:

OLS20 should be installed in accordance with the National Electrical Code and all applicable Local Regulations.

  1. Mount the OLS20 in the desired location/enclosure (mounting hardware included).

  2. Set the OLS20 to the desired DC output voltage via SW1 (refer to Voltage Output Selection Table).

  3. Connect AC power to connector #1 (Fig. 1) (black & white flying leads) and ground (green flying lead) Use 18 AWG or larger for all power connections (Battery, AC input).
    Keep power-limited wiring separate from non-power-limited wiring (115VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
    CAUTION: Do not touch exposed metal parts.
    Shut branch circuit power before installing or servicing equipment.
    There are no user-serviceable parts inside. Refer installation and servicing to qualified service personnel.

  4. Measure output voltage before connecting devices. This helps avoiding potential damage.

  5. Connect devices to be powered to the terminals marked [– DC +] (Fig. 1).

  6. When the use of stand-by batteries is desired, they must be lead acid or gel type.
    Connect battery to the terminals marked [– BAT +] (Fig. 1).
    Use two (2) 12VDC batteries connected in series for 24VDC operation.
    Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

For continuous protection against fire replace fuse with the same type and rating 5mm – 20mm, 250V, 2A.

LED Diagnostics:

Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. The stand-by battery is supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend Function/Description
L, G, N Connect 115VAC to these terminals: Black to Hot, White to Neutral,

Green to ground.
– DC +| 12VDC @ 1.0A continuous supply current. 24VDC @ 0.5A continuous supply current.
– BAT +| Stand-by battery connections. Maximum charge rate 0.3A.

Altronix OLS20 Off Line Power Supply Charger

Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
website: www.altronix.com 
e-mail: info@altronix.com