BAPI-Stat “Quantum Slim” Wireless Temperature or
Temp/Humidity Sensor
Installation & Operations
rev. 08/16/23 49524_Wireless_BLE_Quantum_Slim_Temp_Hum
Overview and Identification
- Built in or remote temperature sensor
- User adjustable settings via receiver or WAM
- Onboard memory to store readings when ommunication is interrupted
- Transmits to a digital Gateway or a wireless-to-analog Receiver
The
BAPI-Stat “Quantum Slim” Wireless Sensor measures the temperature or
Temp/Humidity and transmits the data via Bluetooth Low Energy to a receiver or
gateway.
The units are perfect for monitoring the temperature inside refrigerator and
freezer cases. The sensor body mounts on the outside of freezers and can be
mounted either inside or outside of refrigerators. It is available with an
internal sensor or an external probe or thermobuffer.
The external cable fits between the door seal or through a hole without
affecting appliance efficiency.
Adjustable Settings
BAPI’s wireless devices have several settings that can be can be field
adjusted to suit the needs of the installation. All settings are configured by
either BAPI’s cloud based Wireless Asset Monitoring (WAM) or the receiver.
(See the WAM or receiver instructions documents available on the BAPI website
for more information on adjusting the settings.)
Sample Rate/Interval – The time between when the sensor wakes up and
takes a reading. The available values are 10 sec, 30 sec, 1 min, 3 min or 5
min with the gateway, or 30 sec, 1 min, 3 min or 5 min with the receiver.
Transmit Rate/Interval – The time between when the sensor transmits the
readings to the gateway or receiver. The available values are 30 sec, 1, 2, 3,
4, 5, 10, 15, 20 or 30 minutes, or 1, 6 or 12 hours with the gateway, or 1, 5,
10 or 30 minutes with the receiver.
Delta Temperature – The change in temperature between sample intervals
that will cause the sensor to override the transmit interval and immediately
transmit the changed temperature. The available values are 0.1, 0.2, 0.3, 0.4,
0.5, 1, 2, 3, 4, 5 °F or °C with the gateway, and 1 or 3 °F or °C with the
receiver.
Delta Humidity – The change humidity between sample intervals that will
cause the sensor to override the transmit interval and immediately transmit
the changed humidity. The available values are 0.5, 1, 2, 3, 4 or 5 %RH with
the gateway, and 3 or 5 %RH with the receiver.
Temperature Min/Max – The maximum or minumum temperature that will cause
the sensor to override the transmit interval and immediately transmit a
reading to the gateway. (Only available when using a gateway.)
Temperature Offset – Adjusts the temperature value being transmitted to
match that of a calibrated reference device. The available values are ±0.1,
0.2, 0.5, 1, 2, 3, 4 or 5 °F or °C. (Only available when using a gateway.)
Humidity Offset – Adjusts the humidity value being transmitted to match
that of a calibrated reference device. The available values are ±0.5, 1, 2, 3
or 5 %RH. (Only available when using a gateway.)
Associated Receiver or Gateway
RECEIVER (Wireless-to-Analog)
The wireless receiver from BAPI receives the data from one or more wireless
sensors. The data is then transferred to the analog output modules and
converted to an analog voltage or resistance. The receiver supports up to 32
sensors and up to 127 different analog output modules. GATEWAY
The wireless gateway receives the data from one or more wireless sensors.
The gateway then provides the data to the cloud via MQTT. The gateway also
sends a confirmation signal to eachsensor upon a successful reception of data.
The gateway supports up to 32 sensors.
Please see BAPI’s Wireless Quick Start Guide, or the gateway or receiver
instructions available on the BAPI website (www.bapihvac.com/gateway-quick-
start) to establish communication between the sensors and the gateway or
receiver.
Initial Activation
For convenience, BAPI recommends pairing the sensor to the intended receiver
or gateway prior to mounting either device. Both devices need to be powered-on
to pair. See the receiver or gateway installation manual for instructions on
pairing the sensor.
The unit
comes with a pre-installed battery. To activate the unit, remove the base
plate and pull out the battery insulator tab as shown in Fig. 1. Press the
Service button and the Service LED should flash once to confirm power. If the
sensor will not be commissioned for more than a couple of days, BAPI
recommends reinstalling the battery insulator tabs to conserve battery life.
Drywall Mounting
-
Place the base plate vertically against the wall where you want to mount the sensor and mark the two mounting holes.
-
Drill two 3/16” (4.8mm) holes in the center of each marked mounting hole. Insert a drywall anchor into each hole.
-
Secure the base to the drywall anchors using the #6 x 1” (25mm) mounting screws provided.
-
Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover by backing out the lock-down screw using a 1/16” (1.6mm) Allen wrench until it is flush with the bottom of the cover.
Probe or Thermobuffer Mounting
Mount the External Probe using a Flexible Probe Bracket (Fig. 3) or use the clip or screw hole on the Hanging Bracket Sensor (Fig. 4)
Operation
Power the unit as described in “Initial Activation” section. Follow the gateway or receiver instructions for pairing the unit and changing the adjustable settings. (The instructions are available on the BAPI website.)
Wireless Sensor Reset
Sensors remain paired to the gateway or receiver and output modules when power is interrupted or the batteries are removed. To break the bonds between them, the sensors need to be reset. To do this, press and hold the “Service Button” on the sensor for about 30 seconds. During those 30 seconds, the green LED will be off for about 5 seconds, then flash slowly, then begin flashing rapidly. When the rapid flashing stops, the reset is complete. The sensor can now be paired to a new receiver or gateway. To re-pair to the same receiver or gateway, you must reset the receiver or gateway. Output modules that were previously paired to the sensor do not need to be re-paired.
Onboard Memory
Sensor retains up to 16,000 readings should the communication become interrupted. The sensor only stores readings from missed transmissions and only when the sensor is paired to a gateway. Once communication is re- established with the gateway, the stored readings are transmitted and then erased from the sensor. The current reading and nine previous readings are sent at each transmit interval until the sensor is caught up. Temporarily shortening the transmit interval will allow the sensor to more quickly clear any stored readings.
Battery Replacement
-
Remove the cover from the base plate by turning in the cover lockdown screw with a 1/16” (1.6mm) Allen wrench until the cover can be removed.
-
Remove the used battery from its holder and discard in an environmentally safe manner. Replace with a new battery in the correct orientation (Fig 6).
-
Attach Cover by latching it to the top of the base, rotating the cover down and snapping into place. Secure the cover by backing out the lock-down screw using a 1/16” (1.6mm) Allen wrench until it is flush with the bottom of the cover.
Battery Specs : One 3.6V Lithium batteries: (#14505, 14500 or equivalent)
Diagnostics
Possible Problems:
Sensor is not communicating with the gateway or receiver, or the transmitted
values are incorrect.
Possible Solutions:
Make sure the sensor is within range of the gateway or receiver.
Verify that the green LED on the sensor circuit board flashes when the
“Service” button is pressed, indicating a transmission. If it does not flash,
replace the battery.
Verify that the sensor is properly paired to the gateway or receiver and
analog output modules as described in the gateway or receiver instructions
available on the BAPI website. Re-pair them if needed. If necessary, perform
the “Wireless Sensor Reset” procedure on page 3.
Specifications
Battery Power: One included 3.6V 14505, 14500 or equiv. lithium battery
(Note: Standard AA batteries are not compatible)
Wire Power: 9 to 30 VDC or 24 VAC, halfwave rectified
Sensor Accuracy:
Temp: ±1.25°F (0.7°C) from 32 to 158°F (0 to 70°C)
Humidity: ±2%RH @ 77°F (25°C), 20 to 80%RH
Temperature Range: -4 to 221°F (-20 to 105°C)
Transmission Distance: Varies by application*
Environmental Operation Range:
Temp: -4 to 149°F (-20 to 65°C)
Humidity: 10 to 90% RH, non-condensing
Enclosure Material & Rating: ABS Plastic, UL94 V-0
Frequency: 2.4 GHz (Bluetooth Low Energy)
Receiver Sensitivity: -97 dBm
Ext. Probe Material: 304 Stainless Steel
1.75” (44mm) Bullet Probe with FEP Cable
1” (25mm) Thermobuffer with FEP Cable
User Adjustable Settings:
Delta T (Temp): 0.1°F/C to 5.0°F/C
Delta T (Humidity) : 0.1%RH to 5.0%RH
Transmit Inte r val: 30 sec to 12 hour
Sample Interval: 10 sec to 5 min
Temp Offset: ±0.1°F/C to ±5.0°F/C
Humidity Offset: ±0.1%RH to ±3.0%RH Onboard Memory: Sensor retains up to 16,000 readings should
the communication become interrupted. If using a Gateway, the data is re-
transmitted once communication is re-established.
Agency: RoHS
*In-building range is dependent on obstructions such as furniture and walls and the density of those materials. In wide open spaces, the distance may be greater; in dense spaces, the distance may be less.
**Actual battery life is dependent on the sensor’s adjustable settings and
environmental conditions.
BAPI-Stat “Quantum-Slim” Calculated Battery Life**
Transmit Interval | Sample Rate | Estimated Life (years) |
---|---|---|
30 sec | 30 sec | 0.58 |
1 min | 1 min | 1.04 |
3 min | 1 min | 2.03 |
5 min | 5 min | 3.02 |
10 min | 5 min | 4.01 |
Specifications subject to change without notice.