Optimea OPC-A01-160HP Portable Air Conditioner User Manual
- June 13, 2024
- Optimea
Table of Contents
Instruction manual
Portable air conditioner
OPC-A01-160HP
Thank you for choosing our product.
Read this user manual before using this innovative Air Conditioner and keep it
safe for future reference. If you lose this User Guide, please contact your
reseller, or send an e-mail to:
info@optimea-france.fr to obtain the
electronic version
The refrigerant used in mobile air conditioners is the environment friendly
hydrocarbon R290.
Compared to the alternative refrigerant, the R290 is an ozone-free refrigerant
with little effect on environment.
Read the instructions before using and repairing.
The drawings provided in this manual may not be consistent with physical
objects. Refer to the physical objects.
Attention Matters
Safety warnings :
- Do not use any methods to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
- The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)
- Do not pierce or burn.
- Be aware that refrigerants may not contain an odour.
- Appliance shall be i nstalled, operated and stored in a room with a floor area larger than 15m2.
- Keep any required ventilation openings clear of obstruction;
- Servicing shall be performed only as recommended by the manufacturer.
- The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
- Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with an industry recognized assessment specification.
- Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
- All working procedure that affects safety means shall only be carried by professional persons.
Notes:
- The air conditioning is only suitable for indoor use, and is not suitable for other applications.
- Follow local grid interconnection rules while installing the air conditioning and ensure that it is properly grounded. If you have any question on electrical installation, follow the instructions of the manufacturer, and if necessary, ask a professional electrician to install it.
- Place the appliance in a flat and dry place and keep a distance of above 50cm between the unit and the surrounding objects or walls.
- After the air conditioning is installed, ensure that the power plug is intact and firmly plugged into the mains power outlet, and place mains power cable orderly to prevent someone from being tripped or pulling out the plug.
- Do not put any object into the air inlet and outlet of the air conditioning. Keep the air inlet and outlet free from obstructions.
- When drainage pipes are installed, ensure that the drainage pipes are properly connected, and are not distorted or bent.
- While adjusting the upper and lower wind-guide strips of the air outlet, pluck it with hands gently to avoid damaging wind-guide strips.
- When moving the appliance, make sure that it is in an upright position. Le climatiseur est destiné à un usage domestique et ne convient pas à d’éventuelles autres utilisations.
- The unit should stay away from gasoline, flammable gas, stoves and other heat sources.
- Don’t disassemble, overhaul and modify the appliance arbitrarily, otherwise it will cause a unit malfunction or even bring harm to persons and properties. To avoid danger, if a failure occurs, ask the manufacturer or professionals to repair it.
- Do not install and use the appliance in the bathroom or other humid environments.
- Do not pull the plug to turn off the appliance.
- Do not place cups or other objects on the body to prevent water or other liquids from spilling into the air conditioning.
- Do not use insecticide sprays or other flammable substances near the appliance.
- Do not wipe or wash the appliance with chemical solvents such as gasoline and alcohol. When you need to clean the appliance, you must disconnect the mains power supply, and clean it with a half-wet soft cloth. If the appliance is really dirty, scrub with a mild detergent.
- The appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and maintenance shall not be made by children without supervision. If the mains power cable is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard. The appliance shall be installed in accordance with national wiring regulations.
- Do not operate the appliance in a wet room such as a bathroom or laundry room.
Transportation, marking and storage for units
-
Transport of equipment containing flammable refrigerants Compliance with the transport regulations
-
Marking of equipment using signs Compliance with local regulations
-
Disposal of equipment using flammable refrigerants Compliance with national regulations
-
Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer’s instructions. -
Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage
to the equipment inside the package will not cause a leak of the refrigerant
charge.
The maximum number of pieces of equipment permitted to be stored together will
be determined by local regulations.
Features and Components
-
Features
(1) Brand new design, compact structure, clean lines, simple and generous shape.
(2) Air conditioning, dehumidification, ventilation and continuous drainage functions.
(3) The external interface is designed in height to facilitate assembly and ensure smooth circulation in the heating tube.
(4) Control panel LED screens, modern and stylish, high-end remote control, all for ease of use.
(5) Air filtration capacity.
(6) Timer function.
(7) Safety function that automatically restarts the compressor after three minutes, as well as many other safety functions.
Product operating range is 7°C to 35°C (inside room)
Temperature setting range is 16°C to 31° -
Components
-
Adjustable slide bar
-
Slide bai connector
-
Exhaust hose
-
Exhaust pipe joint
-
Remote control
Compliance
OPTIMEA OPC-A01-160HP complies with European directives:
- 2014/35/EU – Low Voltage (LVD)
- 2014/30/EU Electromagnetic Compatibility (EMC)
Electrical waste should not be disposed of with household waste. Please find out about recycling opportunities near you. Contact local authorities or your dealer for recycling advice. Do not dispose of these products with municipal household waste. Please sort this waste for proper treatment if necessary. The batteries used to operate the remote control contain materials that are hazardous to the environment. End-of-life batteries must be removed from the remote control and disposed of or recycled in an environmentally responsible manner.
Control Setting
- Control panel operation instructions
a) Operation interface
- Swing Key
- Timer Key
- Fan Key
- Up Key
- Display Window
- Down Key
- Mode Key
- Sleep Mode Key
- Power Key
1. SWING Key: The SWING function only works after turning on the unit, you
can turn the swing on or off.
2. TIMER Key: When the unit is on, press the key to close timing; When the
unit is off, press the key to open timing.
Press the key, when the timing symbol flashes, press up and down key to select
the required timing value.
Timing values can be set in 1-24 hours and the timing value is adjusted up or
down by one hour.
3. FAN SPEED Key: In cooling, heating and fan mode, press this key to select
low, medium, high speed. This function is not available in SLEEP mode and
DEHUMIDIFYING mode.
4. UP Key: Under timer mode, press this key to adjust the time upwards.
Under cooling and heating mode, press this key to adjust the temperature
higher.
This function is not available under FAN mode and DEHUMIDIFYING mode.
5. Display Window
6. DOWN Key: Under timer mode, press this key to adjust the timer downwards.
Under cooling and heating mode, press this key to adjust the temperature
lower. This function is not available under FAN mode and DEHUMIDIFYING mode.
7. Mode Key: When the unit is on, press this key to switch between cooling
dry fan heating mode.
8. Sleep Mode: When the power is on and in cooling mode (or heating mode),
press ‘SLEEP’ button to start the sleep mode. Under sleep mode, the FAN speed
is set to LOW speed and not adjustable.
The SLEEP mode can be canceled by pressing the button.
When sleeping mode turns on , under cooling/heating mode, one hour later,
setting temperature will go up/ go down 1ºC, the second one hour later,
setting temperature will go up/ go down another 1ºC, and then keep the same.
Under the sleep mode, display will be turned off after 10 seconds.
Sleeping mode is invalid under dehumidifying and fan mode.
Power Key: Press this key to turn on and turn off the unit.
Noted:
MEMORY FUNCTION: The appliance maintains its settings during a power failure.
b) Operation instructions of remote control
The air conditioner can be controlled with the remote control. Two AAA-
batteries are required to use the remote control.
POWER : Press the POWER button to turn the unit on and off.
MODE : Press the MODE button to switch between cooling, dry, fan, heating
modes.
UP : Press the UP button to increase the desired temperature and set the
duration of the timer.
DOWN : Press the DOWN button to reduce the desired temperature and set the
duration of the timer.
FAN : Press the FAN button to cycle between low, medium and high fan speeds.
TIMER : Press the TIMER button to set the duration of the power on or power
off tim er.
SWING : Press the swing button to change the orientation of the louver to
direct the air
TEMPE RATURE UNIT : Press to switch between displaying the temperature in
Celsius and Fahrenheit.
SLEEP MODE : Press to turn on the sleep mode. The unit will work with energy
saving logic and the lowest fan speed.
Protection function
-
Frost Protection Function:
In cooling mode, if the temperature of the exhaust pipe is too low, the unit will automatically enter protection status; if the temperature of the exhaust pipe rises to a certain temperature, it can automatically revert to normal operation. -
Overflow Protection Function:
When water in the water pan exceeds the warning level, the unit will automatically sound an alarm, and the “FULL” indicator light will flash. At this point, you need to move the drainage pipe connecting the unit or the water outlet to sewer or other drainage area to empty the water (details see Drainage Instructions at the end of this chapter). After the water is emptied, the unit will automatically return to the standby. -
Automatic Defrosting (heating models have this function):
The unit has an automatic defrosting function. Defrosting can be achieved through four – way valve reversing. -
Protection Function of the Compressor
To increase the service life of the compressor, it has a 3-minute delay booting protection function after the compressor is turned off.
Installation and adjustment
-
Installation
Warning: before using the unit, keep it upright for at least two hours.
The unit can be easily moved in the room. In the moving process, ensure that the unit is in the upright position and should be placed on a flat surface. Do not install and use the unit in the bathroom or other humid environments. Install the heat pipe assembly as shown in Fig.1
Figure 1
1 take out the outer connector assembly and the exhaust pipe assembly, and remove the plastic bags;
2 insert the heat pipe assembly (the end of the exhaust joint) into the back panel vent slot (push to the left) and complete the assembly (as shown in figure 1). -
Installation of window sealing accessories
There are two options to seal the window for better exhaust of hot air
Window plate for sliding windows
Half open the window and mount the window sealing plate assembly to the window (as shown in Fig.2 and Fig.3).Components can be placed in horizontal and vertical direction. Pull various components of the window sealing plate assembly open, adjust their opening distance to bring both ends of the assembly into contact with the window frame, and fix various components of the assembly.1.2 Install the window sealing plate assembly
Notes: 1) The flat end of the exhaust pipe joints must be snapped into place.
- The pipe cannot be distorted nor has substantial turning (greater than 45 °). Keep the ventilation of the exhaust pipe unblocked.
Move the unit with installed heat pipe and fittings before the window, and the distance between the body and walls or other objects shall be least 50 cm (as shown in Fig.4).
Elongate the exhaust pipe and snap the flat end of the exhaust pipe joints
into the hole of the window sealing plate assembly (as shown in Fig.5 and
Fig.6).
Notes
- The flat end of the exhaust pipe joints must be snapped into place.
- The pipe cannot be distorted nor has substantial turning (greater than 45 °). Keep theventilation of the exhaust pipe unblocked.
Important Notice:
The length of the exhaust hose shall be 280~1,500mm, and this length is based
on the specifications of the unit. Do not use extension tubes or replace it
with other different hoses, or this may cause a malfunction. Exhaust host must
be unblocked; otherwise it may cause overheating.
Drainage Instructions
This unit has two drainage methods: manual drainage and continuous drainage.
-
Manual drainage
When the unit stops after the water is full, turn off the unit power and unplug the power plug.
Notes Move the unit carefully, so as not to spill the water in the water pan at the bottom of the body.
Place the water container below the side water outlet behind the body.
Unplug the water plug, the water will automatically flow into the water container.
Notes
Keep the drainage cover and the water plug properly.
During drainage, the body can be tilted slightly backwards.
If the water container cannot hold all the water, before the water container is full, insert the water outlet with the water plug as soon as possible to prevent water from flowing to the floor or the carpet.
When the water is discharged, insert the water plug, and tighten the drainage cover -
Continuous drainage (Optional)
(only applicable to dehumidifying & heating mode), as shown in figure: Unplug the water plug.
Set the drainage pipe into the water outlet.
Connect the drainage pipe to the bucket.
Maintenance
Cleaning: before cleaning and maintenance, turn off the unit and unplug the plug.
-
Clean the surface
Clean with surface of unit with a wet soft cloth. Don’t use chemicals, such as benzene, alcohol, gasoline, etc; otherwise, the surface of the unit will be damaged or even the whole unit will be damaged. -
Clean the filter screen
If the filter screen is clogged with dust, and the effectiveness of the unit is reduced, be sure to clean the filter screen once every two weeks. -
Clean the upper filter screen frame.
Unscrew one screw fixed by EVA filter net and back shell with screwdriver, and take out EVA filter net.
Put the EVA filter screen into warm water with neutral detergent (about 40 / 104 ) and dry it in the shade after rinsing clean.
Unit Storage
- Unscrew the drainage cover, unplug the water plug, and discharge the water in the water pan into other water containers or directly tilt the body to discharge the water into other containers.
- Turn on the unit, adjust it to low-wind ventilation mode, and maintain this state until the drainage pipe becomes dry, so as to keep the inside of the body in a dry state and prevent it from mildewing.
- Turn off the unit, unplug the power plug, and wrap the mains power cable around the wrapping post; install the water plug and the drainage cover.
- Remove the exhaust pipe and keep it properly.
- Cover the unit with a plastic bag. Store the unit in a dry place, keep it out of the reach of children, and take dust control measures.
- Remove batteries from the remote control and keep them properly.
Note: Ensure that the body is placed in a dry place and keep all components properly.
Troubleshooting
- Information on servicing
1) Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
- Work procedure
Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapour being present while the work is being performed. - General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material. - Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe. - Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area. - No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed. - Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. - Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance.
The following checks shall be applied to installations using flammable refrigerants:
• The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
•The ventilation unit and outlets are operating adequately and are not obstructed;
• If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
• Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
• Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded. - Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include:
• That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
• That there no live electrical components and wiring are exposed while charging, recovering or pur- ging the system;
• That there is continuity of earth bonding.
- Repairs to sealed components
- During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
- Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a way that
the level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is
mounted securely. Ensure that seals or sealing materials have not degraded
such that they no longer serve the purpose of preventing the ingress of
flammable atmospheres. Replacement parts shall be in accordance with the
manufacturer’s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
-
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak. -
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. -
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. -
Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant- free area.)
Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed/ extinguished.
If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process. -
Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose-conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:
• Remove refrigerant;
• Purge the circuit with inert gas;
• Evacuate;
• Purge again with inert gas;
• Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times.
Compressed air or oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill ntil the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum.
This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.
This operation is absolutely vital if brazing operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available. -
Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
• Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
• Cylinders shall be kept upright.
• Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already).
• Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site. -
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
All personal protective equipment is available and being used correctly;
The recovery process is supervised at all times by a competent person;
Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery unit and operate in accordance with manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cyli- nders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. -
Labeling
Equipment shall be labeled stating that it has been decommissioned and emptied of refrigerant.
The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. -
Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. Special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working o rder. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery unit, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant.
The evacuation process shall be carried out prior to returning the compressor to the suppliers.
Only electric heating to the compressor body shall be employed to accelerate this process.
When oil is drained from a system, it shall be carried out safely.
Fuse parameters of the unit
Type: 5ET or 932 or 5H Voltage: 250V Current: 3.15 A
a) Storage of the device:
-
Unscrew the drain plug and remove the rubber plug, then empty the water into a container.
You can tilt the device slightly for this purpose. -
Turn the machine on, set it to the slow ventilation mode and let it run until the drain pipe is dry, so that the inside of the machine body remains dry and free of mould.
-
Turn off the machine, unplug the power outlet and wrap the power cord around the power pole; replace it with rubber and the drain plug.
-
Remove the heat drain and store it carefully.
-
Cover the air conditioner with a plastic bag. Place the air conditioning in a dry place, keep it out of the reach of children and make sure it is not in a dusty environment.
-
Remove the batteries from the remote control and store them carefully.
Note: Make sure the appliance is placed in a dry place and carefully store all machine components.
Repair
Do not repair or disassemble the air conditioning by yourself. Unqualified repair will lead to failure of the warranty card, and may cause damage to users or their properties.
Problems | Reasons | Solutions |
---|---|---|
The air conditioning does not work. | There is no electricity. | Turn it on |
after connecting it to a socket with electricity.
The “Full” indicator will flash.| Discharge the water inside.
The ambient temperature is too low or too high| Recommend to use the unit in a
temperature of 7-35▢ (44-95 ▢ ).
In cooling mode. the room temperature is lower than the set temperature; in
heating mode. the room temperature is higher than the set temperature.| Change
the set temperature
In dehumidification mode, the ambient
temperature is low.
| The unit is placed in a room with an ambient temperature of greater than 17
▢ (62 ▢)
).
The cooling effect is not good| There is direct sunlight at the product.| Pull
the Curtain.
---|---|---
Doors or windows are open. there are a lot of people: or in cooling mode.
there are other sources of heat.| Close doors and windows, move away from the
heat source or add new air conditioner
The filter is dirty.| Clean or replace the filter screen.
The air inlet or outlet is blocked.| Clear obstructions.
Big Noise| The air conditioning is not placed on a flat surface.| Put the unit
on a flat and hard place (to reduce noise).
compressor does not work.| Overheat protection starts.| Wait for 3 minutes
until the temperature is lowered. and then restart the unit.
The remote control does not work.| The distance between the unit
and the
remote control is too far.
| Let the remote control get close to the unit.
and make sure that the remote controldirectly
faces to the direction of the remote-control
receiver.
The remote control is not aligned with the direction of the remote-control
receiver
Batteries are dead.| Replace batteries.
Displays ‘E2’.| The pipe temperature sensor is abnormal.| Please contact
professional service technician or after-sales service
provider.
Displays ‘El| The room temperature sensor is abnormal_| Please contact
professional service technician or after-sales service
provider.
Note: If problems not listed in the table occur or the above recommended solutions are not effective, please contact professional service technician or after-sales service provider.
Addendum
Schematic diagram for air conditioning
The specific technical parameters of the unit shall be subject to the
nameplate on the appliance
This symbol on the product or in the instructions means that your electrical and electronic equipment should be disposed at the end of its life separately from your household waste. There are separate collection systems for recycling in the EU. For more information, please see contact the local authority or your retailer where you purchased the product.
OPTIMEA
Optimea reserves the right to make any changes to the characteristics of its
products without notice. In compliance with Article L.122-4 of the
intellectual property code, any representation or reproduction not expressly
authorized is illegal.
Installation and use instructions OPC-A01-160HP – Édition : december 2021.
OPTIMEA SAS au capital de 145 000€ – Nanterre B 492 729 132- CODE NAF 2825Z –
TVA FR 43492729132 16 rue moulin des bruyères 92400 COURBEVOIE
www.optimea-france.fr
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>