RENO-B4 Single Channel Loop Detectors Instruction Manual
- June 13, 2024
- RENO
Table of Contents
RENO-B4 Single Channel Loop Detectors
Product Information
- Product Name : Model B Series Single Channel Loop Detectors
- Manufacturer: Reno A&E
- Address : 4655 Aircenter Circle Reno, NV 89502-5948 USA
- Telephone : 775-826-2020
- Fax : 775-826-9191
- Website : www.renoae.com
- Email : contact@renoae.com
Product Usage Instructions
- Before applying power, verify the source voltage.
- The model designation indicates the input power required, output configuration, sensitivity boost configuration, and Fail-Safe/Fail-Secure configuration for the detector.
- If the model has a rear mounted, 11-pin, Amphenol style connector, it is fitted with models B-3, B-4, and B-8. If it has a rear mounted, 10-pin, MS style connector, it is fitted with models B-1, B-5, and B-35.
- The detector is factory configured for either Fail-Safe or Fail-Secure operation (see unit side label).
- The output state of each output relay in either Fail-Safe or Fail-Secure mode is listed in the table below.
Relay | Fail-Safe | Fail-Secure |
---|---|---|
A | Power Failure Call | Power Failure No Call |
B | Loop Failure Call | Loop Failure No Call |
- The detector has one green (PWR) LED and two red (DET and FAIL) LEDs to indicate power status, output state, and/or loop failure conditions.
- The frequency LEDs provide an indication of the current detector operating frequency.
- There are two front panel pushbutton switches
- RESET: Press to reset the detector.
- The internal DIP switches have the following functions
- Sensitivity : Set the sensitivity according to the table under the Sensitivity section.
- Two Second Delay : Activate a two-second timing delay.
- Sensitivity Boost : Enable sensitivity boost (only for models with SB).
- Exit Pulse Relay B : Set pulse mode for Relay B.
- Limited Presence : Set limited presence mode for Relay B.
- Entry Pulse Relay B : Set pulse mode for Relay B with no delay.
- True PresenceTM Presence Mode Relay B : Set True PresenceTM presence mode for Relay B.
Note: The default settings are specified in the table.
- After changing the frequency setting, press the front panel RESET pushbutton to reset the detector.
Please refer to the complete user manual for detailed installation and operating instructions.
MODEL B SERIES
SINGLE CHANNEL LOOP DETECTORS
INSTALLATION AND OPERATING INSTRUCTIONS
General
Please verify source voltage before applying power. The model designation
indicates the input power required, output configuration, sensitivity boost
configuration, and Fail-Safe / Fail-Secure configuration for the detector as
follows.
NOTE: Models B-3, B-4 and B-8 are fitted with a rear mounted, 11-pin, Amphenol style connector. Models B-1, B-5, and B-35 are fitted with a rear mounted, 10-pin, MS style connector.
The detector is factory configured for either Fail-Safe or Fail-Secure operation (see unit side label). The output state of each output relay in either Fail-Safe or Fail-Secure mode is listed in the table below.
Relay A| Power Failure
Call
| Fail-Safe| Loop Failure
Call
| Fail-Secure
---|---|---|---|---
Power Failure
No Call
| Loop Failure
No Call
B| No Call| No Call| No Call| No Call
Indicators and Controls
Power / Detect / Fail LEDs
The detector has one green and two red LED indicators that are used to provide
an indication of the detector’s power status, output state, and/or loop
failure conditions. The table below lists the various indications and their
meanings.
Status| PWR (Power) LED| DET (Detect) LED| FAIL
LED
---|---|---|---
Off| No power or low power| Output(s) Off| Loop OK
On| Normal power to detector| Output(s) On| Open Loop
Flash| N/A| 4 Hz (50% duty cycle)
Two second timing delay activated
| 1 Hz (50% duty cycle) Shorted Loop
1 Hz (5% duty cycle)
Waiting for release of FREQ pushbutton to enter diagnostics mode (See Failed Loop Diagnostics)
NOTE: If the supply voltage drops below 75% of the nominal level, the PWR LED will turn off, providing a visual indication of low supply voltage. Model B detectors will operate with supply voltage as low as 70% of nominal supply voltage.
Frequency LEDs
The four red LED indicators provide an indication of the current detector
operating frequency.
Front Panel Pushbutton Switches
Two momentary contact, pushbutton switches are used to control the following.
RESET – Push the front panel mounted pushbutton labeled RESET to reset the
detector. FREQ – In situations where loop geometry forces loops to be located
in close proximity to one another, it may be necessary to select different
frequencies for each loop to avoid loop interference, commonly known as
crosstalk. The front panel mounted pushbutton labeled FREQ can be used to
configure the detector to operate at one of four (4) frequencies corresponding
to Low, Medium / Low, Medium / High, and High. Press the FREQ pushbutton to
toggle through and select one of the four frequency settings.
NOTE: After changing the frequency setting, the detector must be reset by pressing the front panel RESET pushbutton.
Internal DIP Switches
Switch | ON | OFF | Factory Default |
---|---|---|---|
1 | Sensitivity |
(See Table under Sensitivity Section)
| OFF
2| ON
3| ON
4| Two Second Delay| No Delay| OFF
5| Sensitivity Boost| No Boost| OFF *
6| Exit Pulse Relay B| Entry Pulse Relay B| OFF
7| Limited Presence| True PresenceTM| OFF
8| Pulse Mode Relay B| Presence Mode Relay B| ON **
- Sensitivity Boost (SB) models have DIP switch 5 set to the ON position. ** Dual Presence (DP) models have DIP switch 8 set to the OFF position.
Sensitivity (DIP Switches 1, 2, and 3)
DIP switches 1, 2, and 3 select one of the eight (8) sensitivity levels
available as shown in the table below. 0 is the lowest setting, 3 is normal,
and 7 is the highest setting. Use the lowest sensitivity setting that will
consistently detect the smallest vehicle that must be detected. Do not use a
sensitivity level higher than necessary.
Switch| | Sensitivity|
---|---|---|---
| 0| | 1| | 2| | 3 *| | 4| | 5| | 6| |
7|
1*| OFF| OFF| OFF| OFF | ON| ON| ON| ON
2*| OFF| OFF| ON| ON | OFF| OFF| ON| ON
3| OFF| ON| OFF| ON *| OFF| ON| OFF| ON
-
- Factory default setting.
Output Delay (DIP Switch 4)
A two second delay of Outputs A and B can be activated by setting DIP
switch 4 to the ON position. Output delay is the time the detector outputs are
delayed after a vehicle first enters the loop detection zone. If the two
second Output Delay feature is activated, the output relays will only be
turned on after two seconds have passed with a vehicle continuously present in
the loop detection zone. If the vehicle leaves the loop detection zone during
the two second delay interval, detection is aborted and the next vehicle to
enter the loop detection zone will initiate a new full two second delay
interval. The detector provides an indication that a vehicle is being detected
but that the outputs are being delayed, by flashing the front panel DET LED at
a four Hz rate with a 50% duty cycle. The factory default setting is OFF (no
Output Delay).
Sensitivity Boost (DIP Switch 5)
DIP switch 5 can be turned ON to increase sensitivity during the detect period
without changing the sensitivity during the no detect period. The boost
feature has the effect of temporarily increasing the sensitivity setting by up
to two levels. When a vehicle enters the loop detection zone, the detector
automatically boosts the sensitivity level. As soon as no vehicle is detected,
the detector immediately returns to the original sensitivity level. This
feature is particularly useful in preventing dropouts during the passage of
high bed vehicles. The factory default setting is OFF (no Sensitivity Boost)
unless sensitivity boost (SB) operation is specified, in which case the
factory default setting is ON (Sensitivity Boost).
Relay B Pulse Mode (DIP Switch 6)
Relay B is the pulse output. Its pulse output mode is controlled by DIP switch
6. Relay B can be configured to output a single 250 millisecond pulse when a
vehicle enters the loop detection zone (Pulse-on-Entry) or when a vehicle
leaves the loop detection zone (Pulse-on-Exit). Pulse-on-Entry is selected
when DIP switch 6 is OFF. Pulse-on-Exit is selected when DIP switch 6 is ON.
DIP switch 6 has no effect on Relay A (the presence output). The factory
default setting is OFF (Pulse-on-Entry).
NOTE: The setting of this DIP switch has no effect on the output mode of Relay B if DIP switch 8 is set to the OFF position (Presence Mode Relay B). For additional details, refer to the Relay B Output Mode section on page 3.
Presence Hold Time (DIP Switch 7)
Output A always functions as a presence output. DIP switch 7 can be used to
select one of two presence hold times; Limited Presence or True PresenceTM.
Both modes provide a Call output when a vehicle is present in the loop
detection zone. True PresenceTM is selected when DIP switch 3 is OFF. If DIP
switch 3 is ON, Limited Presence is selected. Limited Presence will typically
hold the Call output for about one to three hours. True PresenceTM will hold
the Call as long as the vehicle is present in the loop detection zone provided
that power is not interrupted or the detector is not reset. True PresenceTM
time applies only for normal size automobiles and trucks and for normal size
loops (approximately 12 ft2 to 120 ft2). The factory default setting is OFF
(True PresenceTM Mode).
Relay B Output Mode (DIP Switch 8)
Relay B has two modes of operation; Pulse or Presence. Its output mode is
controlled by DIP switch 8. When set to operate in Pulse Mode (DIP switch 8
ON), Relay B outputs a 250 millisecond pulse when a vehicle enters the loop
detection zone or when a vehicle leaves the loop detection zone. (See the
Relay B Pulse Mode section on page 2 for details.) When set to operate in
Presence Mode (DIP switch 8 OFF), the output of Relay B is the same as that of
Relay A. (See the Presence Hold Time section above for details.) The factory
default setting is ON (Pulse Mode Relay B) unless dual presence (DP) operation
is specified, in which case the factory default setting is OFF (Presence Mode
Relay B).
Call Memory
When power is removed for two seconds or less, the detector automatically
remembers if a vehicle was present and a Call was in effect. When power is
restored, the detector will continue to output a Call until the vehicle leaves
the loop detection zone (loss of power or power dips of two seconds or less
will not bring a gate arm down onto cars as they wait at the gate).
Failed Loop Diagnostics
The FAIL LED provides an indication of whether or not the loop is currently
within tolerance. If the loop is out of tolerance, the FAIL LED indicates
whether the loop is shorted (one Hz flash rate) or open (steady ON). If and
when the loop returns to within tolerance, the FAIL LED will turn off to
indicate that the loop fault condition has been corrected and that the loop is
once again within tolerance.
The Model B detector automatically stores the last loop failure type in non-
volatile memory. To determine the type of loop failure that has last occurred,
press and hold the FREQ pushbutton for at least three seconds. When the FAIL
LED begins flashing at one Hz rate with a 5% duty cycle, release the FREQ
pushbutton. The detector will then display the last loop failure type detected
(if any). This indication will be displayed one time for about fifteen seconds
unless terminated by pressing the RESET or FREQ pushbutton. The non-volatile
memory used to store the last loop failure type is automatically cleared each
time it is interrogated.
Pin Connections
Models B-3, B-4, and B-8 (Reno A&E Wiring Harness Model 802-4)
Pin | Wire Color | Function |
---|---|---|
1 | Black | AC Line / DC + |
2 | White | AC Neutral / DC Common |
3 | Orange | Relay B, Normally Open (N.O.) |
4 | Green | No Connection |
5 | Yellow | Relay A, Common |
6 | Blue | Relay A, Normally Open (N.O.) |
7 | Gray | Loop |
8 | Brown | Loop |
9 | Red | Relay B, Common |
10 | Violet or Black / White | Relay A, Normally Closed (N.C.) |
11 | White / Green or Red / White | Relay B, Normally Closed (N.C.) |
Models B-1, B-5, and B-35 (Reno A &E Wiring Harness Model 801-4)
Pin | Wire Color | Function |
---|---|---|
A | White | AC Neutral / DC Common |
B | Brown | Relay A, Normally Open (N.O.) |
C | Black | AC Line / DC + |
D | Red | Loop |
E | Orange | Loop |
F | Yellow | Relay A, Common |
G | Blue | Relay A, Normally Closed (N.C.) |
H | Green | Chassis Ground |
I | Violet | Relay B, Common |
J | Gray | Relay B, Normally Open (N.O.) |
NOTE: All pin connections listed above are with power applied, loop(s) connected, and no vehicle detected.
Warnings
Separately, for each loop, a twisted pair should be created consisting of only
two (2) loop wires running the entire distance from the loop to the detector
(including runs through all wiring harnesses) at a minimum of six (6) complete
twists per foot. For trouble free operation, it is highly recommended that all
connections (including crimped connectors) be soldered.
Loop Installation
The vehicle detection characteristics of an inductive loop detector are
greatly influenced by the loop size and proximity to moving metal objects such
as gates. Vehicles such as small motorcycles and high bed trucks can be
reliably detected if the proper size loop is selected. If the loop is placed
too close to a moving metal gate, the detector may detect the gate. The
diagram below is intended as a reference for the dimensions that will
influence the detection characteristics.
General Rules SLIDE GATE
- The detection height of a loop is 2/3 the shortest leg (A or B) of the loop.
- Example: Short leg = 6 feet, Detection Height = 2/3 x 6 feet = 4 feet.
A = | 6 ft | 9 ft | 12 ft | 15 ft | 18 ft | 21 ft |
---|---|---|---|---|---|---|
C = | 3 ft | 4 ft | 4.5 ft | 5 ft | 5.5 ft | 6 ft |
As the length of leg A is increased, distance C must also increase.
For reliable detection of small motorcycles, legs A and B should not exceed 6
feet.
Loop Installation – Saw Cut Type
- Mark the loop layout on the pavement. Remove sharp inside corners that can damage the loop wire insulation.
- Set the saw to cut to a depth (typically 2″ to 2.5″) that ensures a minimum of 1″ from the top of the wire to pavement surface. The saw cut width should be larger than the wire diameter to avoid damage to the wire insulation when placed in the saw slot. Cut the loop and feeder slots. Remove all debris from the saw slot with compressed air. Check that the bottom of the slot is smooth.
- It is highly recommended that a continuous length of wire be used to form the loop and feeder to the detector. Loop wire is typically 14, 16, 18, or 20 AWG with cross-linked polyethylene insulation. Use a wood stick or roller to insert the wire to the bottom of the saw slot (do not use sharp objects). Wrap the wire in the loop saw slot until the desired number of turns is reached. Each turn of wire must lay flat on top of the previous turn.
- The wire must be twisted together a minimum of 6 twists per foot from the end of the saw slot to the detector.
- The wire must be held firmly in the slot with 1″ pieces of backer rod every 1 to 2 feet. This prevents the wire from floating when the loop sealant is applied.
- Apply the sealant. The sealant selected should have good adhering properties with contraction and expansion characteristics similar to those of the pavement material.
LOOP PERIMETER | NUMBER OF TURNS |
---|---|
10 feet – 13 feet | 5 |
14 feet – 26 feet | 4 |
27 feet – 45 feet | 3 |
46 feet – 100 feet | 2 |
100 feet and up | 1 |
- Recommended Loop Wire: Reno A&E LW-120 for 1/8″ slots Reno A&E LW-116-S for 1/4″ slots
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>