The HP will display an error code if it is unable to function normally.
Error codes are indicated by a red LED on the control panel. The control panel is visible via a small window at the right side of the heat pump and it can be accessed by removing the heat pump top cover (4 screws).

Sanden GAU A45HPC Heat Pump - heat pump top cover

After a component is replaced or the inspection is completed, cycle power to the unit several times to confirm the error does not re-occur.
Below is the list of the error codes. If the corrective action does not solve the error problem, a malfunction of the PCB valve is highly likely.

Error code Reason for the error Corrective action
H9 HP ambient (outdoor) temperature thermistor error – Check the thermistor

connectors on the main PCB or control PCB in the heat pump unit for any disconnection, fall-off, wire breakage or short circuit.
– Measure resistance of the thermistor indicated by the error code. G12
HC| HP water outlet (outgoing) temperature thermistor error
J3| HP discharge temperature thermistor error
J5| HP suction temperature thermistor error
J6| HP defrost temperature thermistor error
J8| HP water inlet (return) temperature thermistor error
H7| Tank temperature thermistor error| – Check the thermistor cable on the terminal block in the heat pump unit for any disconnection, fall-off, wire breakage or short circuit.
– Measure resistance of the thermistor indicated by the error code.
E6| Compressor booting error| – Check the compressor connector.
– Replace the main PCB or heat pump.
H6| Compressor revolution error| – Check the supply voltage.
– Measure resistance of each thermistor.
– Measure resistance of coil of expansion valve to check open or short circuit.  – Replace the PCB or heat pump.
U0| Refrigerant leakage error| – Measure resistance of each thermistor.
– Measure resistance of coil of expansion valve to check open or short circuit.
– Replace the main PCB or heat pump.
E1| Main PCB error| – Replace the main PCB.
E2
L7| Control PCB error| – Replace the control PCB.
F5| Communication error between main PCB to control PCB| – Check the communication connector on the main PCB and control PCB.
– Replace the main PCB or control PCB.
E8| High inlet current error| – Check the installation location.
– Check the supply voltage.
– Replace the main PCB or heat pump.
H8| Current error| – Replace the main PCB.
L4| High temperature of module error| – Check the installation location.
– Remove foreign objects from the evaporator coil (e.g. fallen leaves, grass, snow).
– Check the fan motor is not flowing by dirt.
– Replace the main PCB or fan motor.
L5| High outlet current error| – Measure resistance of the discharged thermistor.
– Measure resistance of coil of expansion valve to check open or short circuit.
– Replace the main PCB or heat pump.
P4| Module temperature thermistor error| – Replace the main PCB.
U2| High voltage error| – Check the supply voltage.
HJ| Water circuit error| – Check the inlet water valve.
– Check for any piping bend, blockage, kink or frozen.
– Measure resistance of each thermistor.
– Measure resistance of coil of expansion valve to check open or short circuit.
– Replace the main PCB or heat pump.
EC| High water outlet error| – Check the water circuit is not flowing by air, dirt or scaling.
– If the water circulation pump is not working, replace the pump.
– Measure resistance of water outlet (outgoing) thermistor.
– Replace the main PCB.
E9| Water circulation pump error| – Check the water is full in the tank.
– If the water circulation pump is not working, replace the pump.
– Check the revolution of pump by controller.  If the revolution is low, replace the pump.
– Replace the main PCB.
E7| Fan motor locked| – Remove foreign objects around the fan motor.
– Check the fan motor connectors on the main PCB.
– Replace the main PCB.
F3| Discharged temperature error| – Measure resistance of the discharged thermistor.
– Replace the main PCB or heat pump.