Dimplex LA 35TUR+ Reversible Air-to-Water Heat Pump
Please Read
Immediately
Important Information
ATTENTION!
For devices with a refrigerant quantity of 6 kg or more, the refrigerating
circuit must be checked for leaks each year in compliance with regulation (EC)
No. 842/2006.
ATTENTION!
The device is not suitable for operation with a frequency converter.
ATTENTION!
When transporting the heat pump, ensure that it is not tilted more than 45°
(in any direction)
ATTENTION!
The transport securing device is to be removed prior to commissioning.
ATTENTION!
Do not restrict or block up the area around the air inlet or outlet.
ATTENTION!
Ensure that there is a clockwise rotating field: With incorrect wiring the
starting of the heat pump is prevented. A corresponding warning is indicated
on the display of the heat pump manager (adjust wiring).
ATTENTION!
Never use cleaning agents containing sand, soda, acid or chloride as these can
damage the surfaces.
ATTENTION!
We recommend the installation of a suitable corrosion protection system to
prevent the formation of deposits (e.g. rust) in the condenser of the heat
pump.
ATTENTION!
Before opening the device, ensure that all circuits are isolated from the
power supply.
ATTENTION!
Any work on the heat pump may only be performed by authorised and qualified
after-sales service technicians.
Intended Use
This device is only intended for use as specified by the manufacturer. Any other use beyond that intended by the manufacturer is prohibited. This requires the user to abide by the manufacturers product information. Please refrain from tampering with or altering the device
Legal Regulations and Directives
The construction and design of the heat pump complies with all relevant EU
directives, DIN/VDE regulations (see CE declaration of conformity).
When connecting the heat pump to the power supply, the relevant VDE, EN and
IEC standards are to be adhered to. Any further connection requirements
stipulated by the network operator must also be observed.
When connecting the heating and/or cooling system, all applicable regulations
must be adhered to.
Persons, especially children, who are not capable of operating the device
safely due to their physical, sensory or mental abilities or due to their
inexperience or lack of knowledge, must not operate this device without
supervision or instruction by the person in charge.
Children must be supervised to ensure that they do not play with the device.
ATTENTION!
For devices with a refrigerant quantity of 6 kg or more, the refrigerating
circuit must be checked for leaks each year in compliance with regulation (EC)
No. 842/2006.
More information can be found in the chapter Maintenance / Cleaning.
Energy-Efficient Use of the Heat Pump
With the purchase of this heat pump you are helping to protect the
environment. A prerequisite for energy-efficient operation is the correct
design of the heat source system and heating system.
It is particularly important for the efficiency of a heat pump to keep the
temperature difference between heating water and heat source as small as
possible. For this reason, it is advisable to design the heat source and
heating system very carefully. A temperature difference of approx. one Kelvin
increases the power consumption by around 2.5%. When designing the heating
system, it should be borne in mind that special consumers such as e.g.
domestic hot water preparation should also be taken into consideration and
dimensioned for low temperatures. Underfloor heating systems (panel heating)
are optimally suited for heat pump use on account of the low flow temperatures
(30 °C to 40 °C).
It is important to ensure that the heat exchangers are not contaminated during
operation because this increases the temperature difference, in turn reducing
the COP.
Correct adjustment of the heat pump manager is also important for energy-
efficient use of the heat pump. Further information can be found in the
operating instructions of the heat pump manager.
Purpose of the Heat Pump
Application
The brine-to-water heat pump is to be used exclusively for the heating and
cooling of heating water. It can be used in new or already-existing heating
systems.
The heat pump is suitable for mono energy and bivalent operation down to an
external temperature of -25 °C.
Proper defrosting of the evaporator is guaranteed by maintaining a heating
water return flow temperature of more than 18 °C during continuous operation.
The heat pump is not designed for the increased heat consumption required when
a building is being dried out. For this reason, the additional heat
consumption should be met using special devices provided by the customer. If a
building is to be dried out in autumn or winter, we recommend installing an
additional electric heating element (available as an accessory).
In cooling operation, the heat pump is suitable for air temperatures ranging
from +10°C to + 45°C.
It can be used for silent and dynamic cooling. The minimum water temperature
is +7°C.
ATTENTION!
The device is not suitable for operation with a frequency converter.
Operating Principle
Heating
Surrounding air is drawn in by the fan and fed through the evaporator (heat
exchanger). The evaporator cools the air, i.e. it extracts heat from it. This
extracted heat is then transferred to the working medium (refrigerant) in the
evaporator.
The heat is brought to a higher temperature level by increasing its pressure
with the aid of the electrically driven compressors. It is then transferred to
the heating water via the liquefier (heat exchanger).
Water for domestic use and swimming pool water can be prepared simultaneously
or separately via the additional heat exchanger.
Electrical energy is used to raise the temperature of the heat in the
environment to a higher level. As the energy extracted from the air is
transferred to the heating water, this type of device is called an air-to-
water heat pump.
The air-to-water heat pump consists of the main components evaporator, fan and
expansion valve, as well as the low-noise compressors, the liquefier and the
electrical control system.
At low ambient temperatures, humidity accumulates on the evaporator in the
form of frost, reducing the transfer of heat. The evaporator is defrosted
automatically by the heat pump as required. Steam may be emitted from the air
outlet depending on the atmospheric conditions.
Cooling
The functions of the evaporator and the liquefier are reversed in the
“Cooling” operating mode.
The heating water transfers its heat to the refrigerant via the liquefier,
which is now functioning as an evaporator. The refrigerant is brought to a
higher temperature level using the compressor.
Heat is transferred to the surrounding air via the liquefier (which, in
heating operation, functions as an evaporator).
The waste heat can also be used for hot water preparation, swimming pool or
bathroom heating, via the additional heat exchanger.
Scope of supply
Basic Device
The heat pump is of compact design and is supplied complete with the
components listed below.
The refrigerant circuit is “hermetically sealed”. It contains the Kyoto
protocol-approved refrigerant R417A with a GWP value of 1950. It is CFC-free,
does not deplete ozone and is non-flammable.
- Evaporator
- Liquefier
- Ventilator
- Switch box
- Compressor 1
- Compressor 2
- Filter dryer
- Expansion valve
- Collector
- Hot water liquefier
Switch box
The switch box is located in the heat pump. It can be swung out after removing
the lower front cover and loosening the fastening screw located in the upper
left-hand corner.
The switch box contains the supply connection terminals as well the power
contactors and the soft starter unit.
The plug connectors for the control line are located on the switch box panel
near the pivotal point.
Heat pump manager
Use the heat pump manager for reversible heat pumps included in the scope of
supply to operate the reversible air-to-water heat pump.
The heat pump manager is a convenient electronic regulation and control
device. It controls and monitors the entire heating and cooling system on the
basis of the external temperature, including domestic hot water preparation
and safety systems.
The external temperature sensor, including fixing accessories, is included in
the scope of supply of the manager and must be installed by the customer.
The enclosed operating instructions describe the function and use of the heat
pump manager.
Accessories
Electrical connection line
4.1 Electrical connection line The electrical connection line is an accessory required for the functioning of the system. It connects the heat pump to the heat pump manager and it is available in various lengths.
External four-way reversing valve
The external four-way reversing valve (Y12) enables optimized heating and
cooling operation of the reversible air-to-water heat pump. The reversal of
the flow direction ensures an optimum flow through the heat exchanger in the
heat pump in heating operation as well as in the opposite direction in cooling
operation. The electrical actuator required for the automatic switching is
controlled by the heat pump manager. (max. permissible switching current 2A).
If the external four-way reversing valve is not used, the heat outputs and the
COPs are reduced as specified in the device information. With heating-only
operation without an external four-way valve, the hydraulic connection should
be carried out such that the heat exchanger is loaded in the opposite
direction (observe note in section 7.2 “Connection on heating side”).
The external four-way reversing valve with a set time of max. 30 seconds,
which is available as special accessory, ensures switching of the water flow
over the complete range of operating temperatures without any mixing losses.
Provision of a dirt trap with a mesh size of 0.6 mm is recommended at a
suitable location.
The hydraulic and electrical circuit diagrams in the Appendix show the basic
design. Detailed installation instructions are provided with the four-way
reversing valve.
Transport
ATTENTION!
When transporting the heat pump, ensure that it is not tilted more than 45°
(in any direction).
Use a wooden pallet for transporting the heat pump to the final installation
location. The basic device can be transported either with a lift truck or a
crane. The transport eyebolts must be removed after crane transport and the
sheet metal openings closed with the closing plugs supplied.
After the transport, the transport securing device is to be removed on either
side at the bottom of the unit.
ATTENTION!
The transport securing device is to be removed prior to commissioning.
Set-up
General
The device should always be installed on a permanently smooth, even and
horizontal surface. The entire frame should lie directly on the ground to
ensure a good soundproof seal and to prevent the water-bearing components from
becoming too cold. If this is not the case, additional insulation measures may
be necessary.
Furthermore, the heat pump should be set up so that the air outlet direction
of the ventilator is perpendicular to the main wind direction to allow
unrestricted defrosting of the evaporator. It must be possible to carry out
maintenance work without hindrance.
This is ensured when observing the distances to solid walls as shown in the
figure.
The specified dimensions are only valid for stand-alone installation.
ATTENTION!
Do not restrict or block up the area around the air inlet or outlet.
Condensed Water Pipe
Condensed water that forms during operation must be drained off frost-free. To ensure proper drainage, the heat pump must be mounted horizontally. The condensed water pipe must have a minimum diameter of 50 mm and should be fed frost-free into a sewer. Condensed water should not be discharged directly into clearing tanks and cesspits because the aggressive vapours could destroy the evaporator.
Installation
General
The following connections need to be established on the heat pump:
- Heating system flow and return flow
- Hot water circuit flow and return flow
- Condensate outflow
- Control line to the heat pump manager
- Power supply
Connection on heating side
The heating system connections on the heat pump have a 1 1/2″ external thread.
Route the connection hoses out of the device in a downwards direction. Use a
spanner to firmly grip the transitions when connecting the heat pump.
Before connecting the heating water system to the heat pump, the heating
system must be flushed to remove any impurities, residue from sealants, etc.
Any accumulation of deposits in the liquefier could cause the heat pump to
completely break down.
Once the heat pump has been connected to the heating system, it must be
filled, de-aerated and pressure-tested. We recommend water treatment according
to VDI 2035. Use of the optionally available four-way reversing valve is
recommended. A detailed installation description can be found in the
instructions included in the scope of supply of the valve.
The following is true for heating-only operation of the heat pump:
If the heat pump is used for heating purposes only, the hydraulic connections
at the liquefier can be connected the opposite way round. In this case, the
attached device label can be ignored.
Connection [A] is connected to the heating flow; connection [B] is connected
to the heating return flow.
Important: The notes/settings in the instructions of the heat pump
manager must always be observed and carried out accordingly; not doing so will
lead to malfunctions.
With this type of operation, cooling operation is not possible. The system can
only be operated in heating mode. The performance ratings are valid as
specified in the device information.
Minimum heating water flow
The minimum heating water flow through the heat pump must be assured in all
operating states of the heating system. This can be accomplished, for example,
by installing a differential pressure less manifold.
Antifreeze
A method of manual drainage (see illustration) should be provided for heat
pumps which are exposed to frost. The antifreeze function of the heat pump
manager is active whenever the manager and the heat circulating pump are ready
for operation. If the heat pump is taken out of service or in the event of a
power failure, the system has to be drained. The heating circuit should be
operated with a suitable antifreeze if heat pump systems are implemented in
buildings where a power failure cannot be detected (holiday homes).
Electrical Connection
A standard four-core cable is used for connecting the heat pump to the power
supply.
The cable must be provided by the customer. The conductor cross section is
selected in accordance with the power consumption of the heat pump (see
Appendix Device Information) and the applicable VDE (EN) and VNB regulations.
An all-pole disconnecting device with a contact gap of at least 3 mm (e.g.
utility blocking contactor or power contactor) as well as a 3-pole circuit
breaker with common tripping for all external conductors must be installed in
the power supply (tripping current in compliance with the Device Information).
When connecting, ensure that the incoming supply has a clockwise rotating
field.
Phase sequence: L1, L2, L3.
ATTENTION!
Ensure that there is a clockwise rotating field: With incorrect wiring the
starting of the heat pump is prevented. A corresponding warning is indicated
on the display of the heat pump manager (adjust wiring).
The control voltage is supplied via the heat pump manager.
The heat pump manager has a 230 V AC-50 Hz power supply and is connected in
compliance with its own operating instructions (16 A fuse).
The control lines (not included in the scope of supply) have rectangular plug
connectors on both ends. One end is connected to the heat pump manager, and
the other end is connected to the switch box in the heat pump. The plug
connections to the heat pump are located on the bottom of the switch box.
Two separate lines are used as control lines. One of the lines is designed for
the 230 V control voltage level, the other for the signal and/or extra-low
voltage level.
More detailed information can be found in the operating instructions of the
heat pump manager.
For detailed information, see circuit diagrams in the Appendix.
Start-Up
General
To ensure that start-up is performed correctly, it should only be carried out
by an after-sales service technician authorised by the manufacturer. This may
be a condition for extending the guarantee (see Warranty Service).
Start-up should be carried out in heating operation.
Preparation
8.2 Preparation
The following items need to be checked prior to start-up:
- The heat pump must be fully connected, as described in Chapter 7.
- All valves that could impair the proper flow of the heating water in the heating circuit must be open.
- The air intake and air outlet paths must be clear.
- The fan must turn in the direction indicated by the arrow.
- The settings of the heat pump manager must be adapted to the heating system in accordance with the manager’s operating instructions.
- Ensure the condensate outflow functions properly
Procedure
The heat pump is started up via the heat pump manager. Adjustments should be
made in compliance with the instructions.
Any faults occurring during operation are also displayed on the heat pump
manager, and can be corrected as described in the operating instructions of
the heat pump manager.
At hot water temperatures under 7° C, start-up is not possible.
The water in the buffer tank must be heated to a minimum of 18 °C with the
second heat generator.
To ensure a problem-free start-up, the following procedure is to be
implemented:
- Close all consumer circuits.
- Ensure that the heat pump has the correct water flow rate.
- Use the manager to select the automatic operating mode.
- In the special functions menu, start the “Start-up“ program.
- Wait until a return flow temperature of at least 25 °C has been reached.
- Now slowly reopen the heating circuit valves in succession so that the heating water flow is constantly raised by slightly opening the respective heating circuit. The heating water temperature in the buffer tank must not be allowed to drop below 20 °C during this process. This ensures that the heat pump can be defrosted at any time.
- When all heating circuits are fully opened and a return flow temperature of at least 18° C is maintained, set a minimum volume flow quantity on the overflow valve (where present)and on the heat circulating pump.
Maintenance / Cleaning
Maintenance
To protect the paintwork, avoid leaning anything against the device or putting objects on the device. External heat pump parts can be wiped with a damp cloth and domestic cleaner.
ATTENTION!
Never use cleaning agents containing sand, soda, acid or chloride as these can
damage the surfaces.
To prevent faults due to sediment in the heat exchanger of the heat pump, ensure that the heat exchanger in the heating system can not be contaminated. In the event that operating malfunctions due to contamination still occur, the system should be cleaned as described below.
Cleaning the Heating System
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust), particularly if steel components are used. These products enter the heating system via the valves, the circulating pumps and/or plastic pipes. It is therefore essential – in particular with respect to the piping of underfloor heating systems – that only diffusion- proof materials are used.
ATTENTION!
We recommend the installation of a suitable corrosion protection system to
prevent the formation of deposits (e.g. rust) in the condenser of the heat
pump.
Residue from lubricants and sealants may also contaminate the heating water.
In the case of severe contamination leading to a reduction in the performance
of the liquefier in the heat pump, the system must be cleaned by a heating
technician.
According to current information, we recommend using a 5% phosphoric acid
solution for cleaning purposes. However, if cleaning needs to be performed
more frequently, a 5% formic acid solution should be used.
In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction opposite to the
normal flow direction.
To prevent acidic cleaning agents from entering the heating system circuit, we
recommend connecting the flushing device directly to the flow and return flow
of the liquefier of the heat pump.
It is important that the system be thoroughly flushed using appropriate
neutralizing agents to prevent damage caused by cleaning agent residue
remaining in the system.
Acids must be used with great care and all relevant regulations of the
employers’ liability insurance associations must be adhered to.
If in doubt, contact the manufacturer of the chemicals!
Cleaning the Air System
Evaporator, ventilator and condensate outflow should be cleaned of contamination (leaves, twigs, etc.) before each new heating period.
ATTENTION!
Before opening the device, ensure that all circuits are isolated from the
power supply.
To prevent the evaporator and the condensate tray from being damaged, do not
use hard or sharp objects for cleaning.
Under extreme weather conditions (e.g. snow drifts), ice may form on the air
intake and air outlet grids. If this happens, the ice must be removed in the
vicinity of the air intake and air outlet grids to ensure that the minimum air
flow is maintained.
To ensure proper drainage from the condensate tray, it must be regularly
inspected and cleaned, if necessary.
All panelling can be removed to allow accessing the inside of the device. Note
that the upper covers can only be removed after the lower covers have been
taken off.
The two sash fasteners must be opened for this purpose. The cover must then be
slightly tilted forward and lifted off toward the top.
The lateral and rear panels are hooked into the cover panel.
Loosen the two screws for dismantling and unhook the panels by pulling them
back.
The cover panels on the ventilator side can be dismantled after the two upper lateral side panels have been removed. Loosen the screws for this purpose, slide the panel slightly to the right or left and then lift it off towards the front.
Maintenance
Refrigerating circuits with a minimum refrigerant quantity of 3kg, or
“hermetically sealed” refrigerating circuits with a minimum refrigerant
quantity of 6 kg must be tested for leaks yearly by the operator according to
regulation (EC) No. 842/2006.
The leak test is to be documented and archived for a minimum of 5 years. The
test is to be carried out by certified personnel only according to regulation
(EC) No. 1516/2007. The attached table can be used as a basis for the
documentation.
Faults / Trouble Shooting
This heat pump is a quality product and designed for trouble-free and
maintenance-free operation. In the event that a fault should occur, it will be
indicated on the heat pump manager display.
Simply consult the Faults and Trouble-Shooting page in the operating
instructions of the heat pump manager. If you cannot correct the fault
yourself, please contact your after-sales service technician.
ATTENTION!
Any work on the heat pump may only be performed by authorised and qualified
after-sales service technicians.
Decommissioning / Disposal
Before removing the heat pump, disconnect it from the power source and close all valves. Observe all environmentally-relevant requirements regarding the recovery, recycling and disposal of materials and components in accordance with all applicable standards. Particular attention should be paid to the proper disposal of refrigerants and refrigeration oils.
Device information
1 Type and order code | LA 35TUR+ |
---|---|
2 Design | |
2.1 Model | Reversible with additional heat exchanger |
2.2 Controller | External |
2.3 Thermal heat metering | Integrated |
2.4 Installation location / degree of protection according to EN
60529| Outdoor / IP24
2.5 Antifreeze condensate tray / heating water| Heated / yes1
2.6 Performance levels| 2
3 Operating limits|
3.1 Heating water flow / return flow| °C| | up to 652 ± 2 /
from 18
Cooling water flow| °C| | +7 to +20
Air (heating)| °C| | -25 to +40
Air (cooling)| °C| | +10 to +45
4 Performance ratings 3 / flow rate|
4.1 Heating water flow rate / internal pressure differential
A7/W35/50| m³/h / Pa| | 5.2 / 2900
A7/W45/38| m³/h / Pa| | 3.5 / 1400
A7/W55/45| m³/h / Pa| | 2.44 / 700
4.2 Heat output / COP 5 6 7| EN 255| EN 14511
at A-7 / W35| kW / —| 8| 17.8 / 2.9| 17.6 / 2.8
| kW / —| 9| 10.1 / 3.0| 9.9 / 2.9
at A2 / W35| kW / —| 8| 24,2 / 4,0| 23,6 / 3,7
| kW / —| 9| 14.0 / 4.3| 13.6 / 4.0
at A7 / W35| kW / —| 8| | 30.2 / 4.5
| kW / —| 9| | 17.3 / 4.8
at A7 / W55| kW / —| 8| | 27.1 / 2.8
| kW / —| 9| | 15.4 / 3.1
at A10 / W35| kW / —| 8| 33.4 / 5.1| 32.6 / 4.9
| kW / —| 9| 18.3 / 5.3| 17.5 / 5.1
4.3 Cooling water flow rate / internal pressure differential| m³/h
/ Pa| | 5.2 10 / 2900
4.4 Cooling capacity / COP 11 at A27 / W9| kW/– –|
8| 27.3 / 3.6
at A27 / W7| kW / —| 9| 15.0 / 4.2
at A27 / W18| kW / —| 8| 32.0 / 3.9
| kW / —| 9| 19.1 / 4.9
at A35 / W9| kW/– –| 8| 24.9 / 2.8
at A35 / W7| kW / —| 9| 13.6 / 3.3
at A35 / W18| kW / —| 8| 29.7 / 3.1
| kW / —| 9| 17.6 / 4.0
4.5 Sound power level energy / sound optimized| dB(A)| | up
to 72 / up to 70
4.6 Sound pressure level at a distance of 10 m (air outlet side)
12|
dB(A)
| | Up to 43
4.7 Flow rate of additional heat exchanger / internal pressure
differential|
m³/h / Pa
| | 2.5 / 9400
4.8 Air flow (controlling range) 3| m³/h| | 5000 – 15000
5 Dimensions, connections and weight|
---|---
5.1 Device dimensions without connections H x W x L mm| 2100 x 1735
x 980 (750)
5.2 Device connections for heating system Inch| 1 1/2” internal
thread
5.3 Device connections for additional heat exchanger (waste heat
recovery) Inches| 1 1/4″ external thread
5.4 Weight of the transportable unit(s) incl. packaging kg|
595
5.5 Refrigerant; total filling weight type / kg| R417A / 22.0
5.6 Lubricant; total filling quantity type / litres| Polyol ester
(POE) / 4.1
6 Electrical connection|
6.1 Nominal voltage; fuse protection
V / A| 400 / 25
6.2 Starting current with soft starter
A| 30
6.3 Nominal power consumption A2 W35/
max. consumption 5 8 kW
| 6.4 / 12.4
6.4 Nominal current A2 W35 / cos f 8 A / —| 11.5 / 0.8
6.5 Max. power consumption of compressor protection (per ompressor)
W| 70; thermostatically controlled
7 Complies with the European safety regulations| 13
8 Additional model features|
Type of defrosting (according to need)| Reverse circulation
-
The heat circulating pump and the heat pump controller must always be ready for operation.
-
For air temperatures between -25 °C and 0 °C, flow temperature increasing from 50 °C to 65 °C.
-
The fan speed is regulated according to need. It is freely adjustable and enables energy-optimized operation.
-
Minimum heating water flow
-
This data indicates the size and capacity of the system according to EN 14511 (5K at A7) and/or EN 255 (10K at A2) without weather-proof protective cover. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, defrosting capacity, bivalence point and regulation, should also be taken into consideration. The specified values have the following meaning, e.g. A7 / W35: external air temperature 7 °C and heating water flow temperature 35 °C.
-
The specified coefficients of performance are also achieved in parallel hot water preparation via additional heat exchangers.
-
In order to obtain the values specified, the optionally available hydraulic 4-way reversing valve (external) must be used.
Without the reversing valve, the heat output is reduced by approximately 10%, the COPs by approximately 12%. -
2-compressor operating mode
-
1-compressor operating mode
-
Minimum cooling water flow
-
Considerably higher COPs are achieved by means of cooling operation and waste heat recovery using additional heat exchangers.
-
The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35 °C.
-
See CE declaration of conformity