GREISINGER GIA 010 N Universal Display for Transmitter Instruction Manual

June 13, 2024
GREISINGER

GREISINGER GIA 010 N Universal Display for Transmitter

GREISINGER-GIA-010-N-Universal-Display-for-Transmitter-FIG-
\(2\)

Product Information

  • The GIA 0420 N and GIA 010 N are microprocessor controlled display devices designed for universal use with measuring transducers. They have a 4-digit LCD display with a maximum display area ranging from -1999 to +9999 digits. The devices also feature a switching output (NPN-output) which can be configured as a 2-point controller or min/max alarm, with the state of the output displayed on the LCD.
  • The GIA 0420 N is designed for connection to measuring transducers with a 4 to 20 mA output, while the GIA 010 N is designed for connection to measuring transducers with a 0 – 10 V output. The devices can be programmed using buttons located at the rear side, allowing for adjustment of the operating range and other parameters without the need for additional accessories. All programmable parameters are saved in an EEProm and will remain there for at least 10 years in case of a power failure.
  • The devices are equipped with a self-diagnosis system that continuously monitors essential parts for perfect functioning, ensuring maximum operational reliability. Prior to delivery, the devices are tested and calibrated, but it is recommended to configure the device for your specific application before use.

Product Usage Instructions

  1. Read the operating manual carefully to familiarize yourself with the device’s operation.
  2. Make sure to configure the device for your specific application before use. Refer to the chapter on configuration in the manual.
  3. Connect the GIA 0420 N or GIA 010 N to the appropriate measuring transducer according to its output signal (4-20mA or 0-10V).
  4. If using the GIA 0420 N, ensure that no auxiliary supply is needed as it is powered by the measuring current.
  5. Use the buttons located at the rear side of the device to input parameters and limit values as required.
  6. To adjust the operating range, enter the maximum and minimum measuring range limits, as well as the decimal point position.
  7. Take note that all programmable parameters are saved in an EEProm and will remain there for at least 10 years in case of a power failure.
  8. Ensure that the device is properly calibrated for accurate measurements.
  9. Keep the operating manual within reach for reference and consultation when needed.

Adhere to the general safety advice provided in the manual to ensure trouble- free operation and reliability of the device. Follow the standard safety measures and special safety advises given in the manual when using the device.

Designated Use

  • The GIA 0420 N and GIA 010 N are microprocessor controlled display devices.
  • The different design types of the device have an input for: – standard signal 4 – 20 mA (GIA 0420 N) – standard signal 0 – 10 V (GIA 010 N)
  • The measuring value is displayed on a 4-digit LCD display with max. display area ranging from -1999 to +9999 digits.
  • The device additional features a switching output (NPN-output) which can be configured as 2-point controller or min-/max alarm. The state of the output is displayed with an arrow at the LCD.
  • The GIA 0420 … is designed for the connection of any measuring transducers (with a 4 to 20 mA output). This design type doesn’t need an auxiliary supply as it is supplied by the measuring current.
  • The GIA 010 … is designed for the connection of any measuring transducers (with a 0 – 10 V output).
  • The parameters and limit values can be input by buttons accessible at the rear side. The operating range of the display device can be directly adjusted to the transmitter without any additional accesso-ries by simply entering the maximum and minimum measuring range limits as well as the decimal point position. All programmable parameters of the device are saved in an EEProm. In case of a current failure they will remain there for at least 10 years.
  • The device is equipped with a self-diagnosis system continuously monitoring the essential parts of the device for their perfect functioning. Both the self-diagnosis and the measuring sensor monitoring for values exceeding or falling below permissible limits ensure maximum operational reliability of the device.
  • Prior to delivery the device will be tested and completely calibrated. However, prior to you starting your operation make sure to configurate the device for your application. Please also refer to chapter “Configuration”.

General Note

Read this document carefully and get used to the operation of the device before you use it. Keep this document within reach for consulting in case of doubt

Safety Requirements

General safety advices
This device has been designed and tested in accordance with the safety regulations for electronic devices. However, its trouble-free operation and reliability cannot be guaranteed unless the standard safety measures and special safety advises given in this manual will be adhered to when using the device.

  1. Trouble-free operation and reliability of the device can only be guaranteed if the device is not subjected to any other climatic conditions than those stated under “Specification”.

  2. Standard regulations for operation and safety for electrical, light and heavy current equipment have to be ob-served, with particular attention having to be paid to national safety regulations (e.g. VDE 0100).

  3. When connecting the device to other devices (e.g. PC) the interconnection has to be designed most thoroughly as internal connections in third-party devices (e.g. connection GND with protective earth) may lead to undesired volt-age potentials.

  4. If there is a risk whatsoever involved in running it, the device has to be switched off immediately and to be marked accordingly to avoid re-starting.
    Operator safety may be a risk if:

  5. there is visible damage to the device.

  6. the device is not working as specified.

  7. the device has been stored under unsuitable conditions for a longer time.
    In case of doubt, please return device to manufacturer for repair or maintenance.

  8. The buttons at the rear side are necessary for the configuration of the device. The device is ESD sensitive at this area!! The configuration must be done considering adequate ESD safety measures!

  9. Warning: Do not use these products as safety or emergency stop devices or in any other application where failure of the product could result in personal injury or material damage. Failure to comply with these instructions could result in death or serious injury and material damage.

  10. This device must not be used at potentially explosive areas! The usage of this device at potentially explosive areas increases danger of deflagration, explosion or fire due to sparking.

  11. This device is not constructed for use in medical applications.

  12. This device must not be run with a defective or damaged power supply unit. Danger to life due to electrical shock! 3.2 Skilled Personnel
    Are persons familiar with installation, commissioning and operation of the product and have professional qualification relating to their job.

For example:

  • Training or instruction resp. Qualification to switch on or off, isolate, ground and mark electric circuits and devices or systems.
  • Training or instruction according to the state.
  • First-aid training.

Disposal Notes

The device must not be disposed in the unsorted municipal waste! Send the device directly to us (sufficiently stamped), if it should be disposed.). We will dispose the device appropriate and environmentally sound

Electric connection

The GIA … N is connected via screw-type/plug-in terminals on the rear side.
General Note : Screw-type/plug-in terminals have to be mounted while they are still loose and plug them in only afterwards. Soldering lands may be damaged in case of improper assembly of already plugged terminals.
Please use applicable screwdriver and do not forcibly tighten the screws.

Supply voltage

  • GIA 0420 N device takes power from measuring current
  • GIA 010 N 12 … 28 V or according device declaration

Electric connection and commissioning of the device must be carried out by trained and skilled personnel. Wrong connection may lead to the destruction of the display device, in which case we cannot assume any warranty! ! Mind for the GIA 0420 … the maximum input current rating of 40mA under any circumstances !

Terminal assignmentGREISINGER-GIA-010-N-Universal-Display-for-
Transmitter-FIG- \(3\)

connection number GIA 0420 N GIA 010 N
1 signal + supply +
2 signal – supply -, GND
3 (inexistent) signal +
4 switching output + switching output +
5 switching output – switching output –

Connection example for optionally switching output
Please note : The max. permitted voltage and switching current of the switching output must not be exceeded (even not for a short time).

Example assignment for switching output (i.e. switching of relays )GREISINGER-GIA-010-N-Universal-Display-for-Transmitter-FIG-
\(4\)

Configuration

Note : The device can be ESD sensitive at the area of the buttons. The configuration must be done considering adequate ESD safety measures!

Please note: measuring current should be at least 4 mA during configuration of a GIA 0420 N!

Follow these instructions to configure the device:

  • Press button 2 for 2 seconds during actual value display, „dP“ is displayed.
  • Set parameter value with button 2 and button 3.
  • Save the set with button 1, the parameter name is displayed again.
  • Proceed to the next parameter with button 1, the name of that parameter is dis- played.

If there is no key pressed within 60 seconds the configuration is cancelled. The settings already entered are lost.

Parameter Value Description
Button 1 Button 2 and 3
DP Position of decimal point
—- Max. display range: -1999 … 9999
—.- Max. display range: -199,9 … 999,9
–.– Max. display range: -19,99 … 99,99
-.— Max. display range: -1,999 … 9,999
D,.LO Lower display range limit (display low)
-1999 … 9999 This value is displayed for input signal = 4mA.
D,.X, Upper display range limit (display high)
-1999 … 9999 This value is displayed for input signal = 20mA.
L, (Measuring range) limit
OFF deactivated:

Exceeding of the measuring range limit is tolerable as long as value is within measuring range (p.r.t. note).

ON.ER| active, (display error):

The measuring range limit is exactly bounded by the input signal.

When exceeding or short falling the input signal the device will display an error message.

ON.RG| active, (display measuring range limit):

The measuring range limit is exactly bounded by the input signal.

When exceeding or short-falling the input signal the device will display the se- lected lower/upper display value.

e.g. humidity: when shortfalling or exceeding, the device will display 0% or 100%.

_ _Note:_ When exceeding the measuring range, the device will always display an error message (.Err.1. or .Err.2.) independent of the current limit settings ._

The measuring range is from approx 3,7 and 20,8 mA respective 10.5 V (a falling below 0V will not detected) .

FILT| Filter
OFF| Filter deactivated
0. 1 2.0| Filter active:    Prevents “jumping” of the last digit and filters short noise pulses.

Higher numbers imply stronger filtering

Attention: this causes higher response times of the switching functions!

OVTP Output function
NO No output, device used as display
2P 2-point-controller
AL.F 1 Min- / max- alarm, together

Depending on the selected output function further parameters have to be adjusted. The configuration menu automatically skips parameters not needed for the selected output function. The following diagram shows which parameters are successively displayed for each output function. A description of the single parameters follows afterward

Parameter Value Description
Button 1 Button 2 and 3

1.ON

only at outP = 2P

| Switch-on point of output 1

D,.LO … D,.X,

| Value at which output 1 should be switched on.

Value has to be between upper and lower measuring range limit set at the be- ginning of the configuration menu.

1.OFF

only at outP = 2P

| Switch-off point of output 1

D,.LO … D,.X,

| Value at which output 1 should be switched off.

Value has to be between upper and lower measuring range limit set at the beginning of the configuration menu.

1.DEL

only at outP = 2P

| Delay of switching function of output 1
0.0 … 999.9| The set value is the time [in seconds] the device waits at least after switching- off output 1 to switch it on again.
1.ERR

only at outP = 2P

| Preferred position of output 1
ON, OFF|

If an error occurs, the device switches output 1 to “active” (on) or “inactive” (off)

AL.X,

only at outP = AL.F 1

| Max-alarm point

AL.LO … D,.X,

| Value, at which max-alarm should be triggered.

Value has to be between upper and lower measuring range limit set at the be- ginning of the configuration menu.

AL.LO

only at outP = AL.F 1

| Min-alarm point

D,.LO … AL.X,

| Value, at which min-alarm should be triggered.

Value has to be between upper and lower measuring range limit set at the be- ginning of the configuration menu.

A.DEL

only at outP = AL.F 1

| Alarm delay
0 … 9999| The set value is the alarm delay in seconds.

The alarm case has to last for the set time to trigger the alarm.

After having set and confirmed the last point (depending on the selected output function) the configuration is done.
Press button 1 one more time after the input of the last parameter to close the configuration menu. The devices restarts (segment test).

Selection of switching and alarm points

Note : The device can be ESD-sensitive at the area of the buttons. The configuration must be done considering adequate ESD safety measures!
Note : All relevant switching and alarm points can be set at this menu. (Preferred output position and delay of the output can only be set at the configuration menu)
Depending on the selected output function different parameters have to be adjusted. The configuration menu automatically skips parameters not needed for the selected output function.
Note : The menu cannot be called if output function is set off. Follow these instructions to adjust switching and alarm points: ****

  • Press button 1 for 2 seconds during the actual value display, „1.on“ or „AL.Hi“ is displayed.
  • Set parameter value with button 2 and button 3.
  • Save the set with button 1, the parameter name is displayed again.
  • Proceed to the next parameter with button 1, the name of that parameter is displayed.

If there is no key pressed within 60 seconds the configuration is cancelled. The settings already entered are lost.

Parameter Value Description
Button 1 Button 2 and 3

1.ON

only at outP = 2P

| Switch-on point of output 1
__

D,.LO … D,.X,

| Value at which output 1 should be switched on.

Value has to be between upper and lower measuring range limit set at the be- ginning of the configuration menu.

1.OFF

only at outP = 2P

| Switch-off point of output 1
__

D,.LO … D,.X,

| Value at which output 1 should be switched off.

Value has to be between upper and lower measuring range limit set at the be- ginning of the configuration menu.

AL.X,

only at outP = AL.F 1

| Max-alarm point
__

AL.LO … D,.X,

| Value, at which max-alarm should be triggered.

Value has to be between upper and lower measuring range limit set at the be- ginning of the configuration menu.

AL.LO

only at outP = AL.F 1

| Min-alarm point
__

D,.LO … AL.X,

| Value, at which min-alarm should be triggered.

Value has to be between upper and lower measuring range limit set at the be- ginning of the configuration menu.

A.DEL

only at outP = AL.F 1

| Alarm delay
0 … 9999| The set value is the alarm delay in seconds.

The alarm case has to last for the set time to trigger the alarm.

After having set and confirmed the last point (depending on the selected output function) the configuration is done. Press button 1 one more time after the input of the last parameter to close the configuration menu. The devices re-starts (segment test).

Offset and slope adjustment

Note : The device can be ESD-sensitive at the area of the buttons. The configuration must be done considering adequate ESD safety measures!
The offset and slope-adjustment function can be used for compensating the tolerance of the used sensor, resp. for vernier adjustment of the used transducer/transmitter.

Follow these instructions to run the offset and slope adjustment of the device:

  • Press button 3 for 2 seconds during the actual value display, and „OFFS“ is displayed.
  • Set parameter value with button 2 and button 3.
  • Save the set with button 1, the parameter name is displayed again.
  • Proceed to the next parameter with button 1, the name of that parameter is displayed.
    Parameter| Value| Description
    ---|---|---
    Button 1| Buttons 2 and 3|
    OFFS| Offset
    -5.00 … 5.00| The offset in digit

The set offset value is subtracted from measured value.

SCAL| Scale

-5.00 … 5.00

| The scale in %.

The displayed value is calculated according to the following formula:

Display = (measured value – offset – di.Lo) * (1 + slope adjustment [% / 100] ) + di.Lo

Example for offset and slope adjustment:

Connection of pressure transmitter.
The device displays without offset and slope adjustment: at 0 bar = 0.08, at 20 bar = 20.02

From this calculated:| offset:

slope:

| 0.08

20.02 – 0.08 = 19.94

---|---|---
difference :| 0.06| (= ideal slope – actual slope = 20.00 – 19.94)
Therefore this values should be set:| offset =| 0.08
scale =| 0.30| (= difference / actual slope = 0.06 / 19.94 = 0.0030 = 0.30% )

From this calculated: offset: 0.08 slope: 20.02 – 0.08 = 19.94 difference: 0.06 (= ideal slope – actual slope = 20.00 – 19.94)
Therefore this values should be set: offset = 0.08 scale = 0.30 (= difference / actual slope = 0.06 / 19.94 = 0.0030 = 0.30% )

Min -/max max- value memory

The device features a minimum/maximum-value storage. In this storage, the highest and lowest performance data is saved.

  • Calling of the minimum value:
    Press button 3 shortly: the device will display “Lo“ briefly, after that the min-value is displayed for about 2 sec.

  • Calling of the maximum value:
    Press button 2 shortly: the device will display “Hi“ briefly, after that, the max-value is displayed for about 2 sec.

  • Erasing of the min/max values:
    Press buttons 2 and 3 for 2 sec.: The device will display “CLr“ briefly, after that the min/max values are set to the current displayed value.

Error Codes

When detecting an operating state that is not permissible, the device will display an error code. The following error codes are defined:

Err.1:| Exceeding of measuring range

Indicates that the valid measuring range of the device has been exceeded. Possible causes:                  – Input signal to high

–  Sensor shorted (at 0(4)-20mA)

Remedies:                            – The error message will be reset if the input signal is within the limits.

–  Check transmitter and device configuration (e.g. input signal).

---|---
Err.2:| Values below the measuring range

Indicates that the values are below the valid measuring range of the device. Possible causes:                  – Input signal is to low or negative

–  Current below 4mA

–  Sensor broken (at 4-20mA)

Remedies:                            – The error message will be reset if the input signal is within the limits.

–  Check transmitter and device configuration (e.g. input signal).

Err.3:| Display range has been exceeded

Indicates that the valid display range (9999 digit) of the device has been exceeded. Possible causes:                  – Incorrect scale

Remedies:                            – The error message will be reset if the display value is below 9999.

Err.4:| Values below display range

Indicates that display value is below the valid display range of the device (-1999 digit). Possible causes:                  – Incorrect scale

Remedies:                            – The error message will be reset if the display value is above -1999.

Err.7:| System error

The device features an integrated self-diagnostic function that checks essential parts of the device permanently. When detecting a failure, the error message Err.7 will be displayed.

Possible causes:                  – Actual temperature is below/above the valid temperature range

–  Device defective

Remedies:                            – Stay within valid temperature range

–  Exchange the defective device.

Er.11:| Value could not be calculated

Indicates a measuring value, needed for calculation of the display value, is faulty or out of range. Possible causes:                  – Incorrect scale

Remedies:                            – Check settings and input signal

Specifications


Input signal:

| GIA 0420 …

4 … 20 mA (2-wire)

| GIA 010 …

0 … 10 V (3-wire)

---|---|---
Voltage load:| 3.0 – 3.5 V (typ.)|
Input resistance:| | approx. 100 kOhm
max. permissible input:| 25 mA (40mA short time)| 15 V
Supply voltage:| | 12 – 28 V
Supply current:| from current loop| < 10 mA

GREISINGER-GIA-010-N-Universal-Display-for-Transmitter-FIG-
\(8\) GREISINGER-GIA-010-N
-Universal-Display-for-Transmitter-FIG- \(9\)