OIM Px – 413 PID Digital Temperature Controller User Manual
- June 13, 2024
- OIM
Table of Contents
USER’S OPERATING MANUAL FOR PID DIGITAL TEMPERATURE CONTROLLER
(Model: Px – 413 / 713)
SPECIFICATIONS
- DISPLAY TYPE
: 3 Digit 7 segment LED (Bright White)
Model No. | Px – 413 | Px – 713 |
---|---|---|
Display height (PV) | 0.56″ | 0.80″ |
-
STATUS LED’S
: OUT : Control Output Status -
INPUT
Sensor input| : TC: J, K & RTD Pt-100
---|---
Range| : Refer below Table.
A0/00 LT-| d0/001.| d2t78 – 9t7 L-| 000SV – 66-| (012I)00 kid
---|---|---|---|---
d0/001.| d0666 – ZE| 00666 – 0| 0/1 (N)1V–I0
d0/001.| d0666 – ZE| 0009/ – 0| 0/1 (r)mad
Aoeirmov| d0/30 uoRniosed| jo Joi a6ueN| 00 Joi a6ueu| adAi Josuas
Sampling Time| : 125 msec.
---|---
Resolution| : 1°C / °F
CJC for TC| : Built in automatic
LWC for Pt-100| : Built in up to 18E max
Digital Filter| : 1 to 10 Sec. -
RELAY OUTPUT
Contact Type| : N/O, N/C, COM
---|---
Contact Rating| : 5A @ 250VAC or 30 VDC
Life Expectancy| : > 5,00,000 operations
Isolation| : Inherent -
SSR DRIVE OUTPUT
Drive Capacity| : 12V @ 30mA.
---|---
Isolation| : Non-Isolated. -
FUNCTION
Output 1| : Main Control output (Selectable)
- Relay
- SSR
---|---
- ENVIRONMENTAL
Operating Range| : 0 ~50°C, 5~90% Rh
---|---
Storage Humidity| : 95% Rh (Non-condensing) - POWER SUPPLY
Supply Voltage| : 90~270VAC, 50/60Hz.
---|---
Consumption| : 4W Maximum. - PHYSICAL
Housing| : ABS Plastic
---|---
INSTALLATION GUIDELINES
- Prepare the cut-out with proper dimension as shown in figure.
- Remove clamp from Controller.
- Push the Timer through panel cut-out and secure the Controller in its place by tightening the side clamp.
SAFETY INSTRUCTION
MECHANICAL
- Ambient temperature and relative humidity surrounding the Controller must not exceed the maximum specified limits.
- The Controller in its installed state must be protected against excessive electrostatic or electromagnetic interferences.
ELECTRICAL
- The Controller must be wired as per wiring diagram & it must comply with local electrical regulation.
- The Electrical noise generated by switching inductive loads might create momentary Fluctuation in display, latch up, data loss or permanent damage to the instrument. To reduce this use snubber circuit across the load.
TERMINAL CONNECTIONS:
OVER ALL DIMENSIONS & PANEL CUT OUT (IN MM)
PROGRAMMING
USER LIST : To access the user list Press & Release SET key once.
Parameter | Display | Range | Description |
---|---|---|---|
Control Set Point | LSPL – HSPL | User can change the SP value using UP/ DOWN |
and SHIFT keys. Holding the key will change the value at a faster rate. Press SET key to store the desired value.
CONTROL LIST : To enter in this mode press SET & DOWN key simultaneously for 3 sec.
Parameter | Display | Range | Description | Default |
---|
Lock
Code| | 1 – 9999| Set this parameter to 15 (Default LOCK CODE) to access
Control List. User has a choice to set different Lock Code via USER LOCK CODE
in Config. List.| 15
Propor tional Band| | 0.5
to
99.9°C| This parameter will be prompted only if selected control action is
PID. It sets bandwidth over which the output power is adjusted depending upon
the error (SV-PV). The value of this parameter is automatically set by Auto
tune function.| 5.0°C
Integral Time| | 0
to
9999 Sec.| This parameter will be prompted only if selected control action is
PID. It sets the time taken by PID algorithm to remove steady state error.
Value of this parameter is automatically set by Auto Tune function. If set to
‘0’, this function will be disabled.| 240
Derivative
Time| | 0
to
300 Sec.| This parameter will be prompted only if selected control action is
PID. It defines how strongly the Controller will react to the rate of change
of PV. Value of this parameter is automatically set by Auto Tune function. If
set to ‘0’, this function will be disabled.| 60
Cycle Time| | 0.5
0.User to
99.9 Sec.| This parameter will be prompted only if selected control action is
PID.
can set this value based on process being controlled & type of Output being
selected. For Relay 0/P, cycle time should be more 12sec & for SSR 0/P, cycle
time should be less than lOsec.| 16.0 Sec.
Output Power Limit| | 0%
to
100 %| This parameter will be prompted only if selected control action is PID.
This parameter will decide the maximum output power in % applied to the load.|
100%
Output
Off| | 1 to 10| This parameter will be prompted only if selected control
action is PID. With this parameter 0/P will be Completely OFF after the Set
Point + Offset Value. If Disable, 0/P will act Depending upon the PID Value
after Set Point achieved.| Disable
Tune
Offset| | 50 %
to
100 %| This parameter will be prompted only if selected control action is PID.
This parameter allows the User to carry out Auto Tuning function below the set
point. (If Tune offset is 50 % tuning will be carried out at 50 % of the set
point and if 100 % tuning will be carried out at 100% of the set point.)| 100%
Control
Hys.| | 1 to 25°C| This parameter will be prompted only if selected control
action is ON-OFF. It sets the dead band between ON & OFF switching of the
Output. Larger value of hysterisis minimize the number of ON-OFF operation of
load.This increases life of actuators like contactors but also produces large
errors (between PV & SV).| 2°C
Delay| | 0
to
500 Sec.| This parameter will be prompted only if selected control action is
ON-OFF. It sets the main output restart time where 0/P once turned OFF will
turn ON only after restart time, regardless difference between PV & SP in Heat
or Cool mode. If set to ‘0’, 0/P will be switched without delay. Also, Delay
will be applicable in case of every power ON.| 0 Sec.
CONFIGURATION LIST :
- To enter in this mode, Press and hold SET & UP key simultaneously for 3 sec.
- Press UP or DOWN key to scroll between parameter options.
- Press SET key to store the current parameter & move on to the next parameter.
Parameter | Display | Description | Default |
---|---|---|---|
Lock Code | Set this parameter to 15 (Default LOCK CODE) to access Config. |
List.
User has a choice to set different Lock Code between 1 to 9999 via USER LOCK
CODE in Config. List.| 15
Input Type| | This parameter value is set acco ding to the type of sensor
(Thermocouple or RTD input) connected to the controller s input terminals.|
Sensor Type| Range for °C| Range for °F| Resolution °C/°F| Accuracy
Fe-k(J) T/C| 0 — 760°C| 32 — 999°F| 1°C/°F| ±1°C/°F
Cr-AL(K) T/C| 0 — 999°C| 32 — 999°F| 1°C/°F
Pt-100(RTD)| -99 — 450°C| -146 — 842°F| 1°C/°F
Temp Type| | °C : If selected, the instrument will display the temperature in
°C.| °C
°F : If selected, the instrument will display the temperature in °F.|
Lower
LiSmit| | Sets the minimum limit for set point adjustment. It can be set from
minimum specified range of selected sensor to HSPL value.
0 C| °
Higher
SP
Limit| | Sets the maximum limit for set point adjustment. It can be set from
LSPL value to maximum specified range of selected sensor.| °
400 400°C
Process Value Offset| | Function of this parameter is to add/subtract a
constant value to the measured PV to obtain final PV for control applications.
This parameter value can be altered :
(i) To compensate for known thermal gradient.
(ii)To match the display values with another recorder or indicator measuring
the same PV.| 0°C
Input
Filter| | The controller is equipped with an adaptive digital filter which is
used to filter out any extraneous pulses on the PV. The filtered PV Value is
used for all PV dependent functions. If the PV signal is fluctuating due to
noise, increase the filter time constant value.|
Control Mode| | User can select between PID or ON-OFF action algorithm to be
adopted for output.| PID
Control Logic
For
Output| | This parameter will be prompted only if selected control mode is ON-
OFF. User can select heating logic in which OP1 will remain ON till PV < SR
(PV increases when output is ON.)| Heat
This parameter will appear only if selected control mode is ON-OFF. User can
select cooling logic in which OP1 will remain ON till PV > SR (PV decreases
when output is ON.)|
Output
Type| | User has to set this parameter very carefully in accordance with the
output used. (Separate terminal for RELAY & SSR, Refer electrical installation
)
Select Relay if LOAD is connected via contactor. Whenever user selects Relay,
Cycle time will automatically get set to 16 sec.| Relay
Select SSR if LOAD is connected via SSR (DC voltage pulses). Whenever user
selects SSR, Cycle time will automatically get set to 1sec. User can modify
cycle time via control list.|
Overshoot
Control
Point| | This parameter will be prompted only if selected control action is
PID. Setting this parameter on higher side will proportionally slows down the
rate of rise of PV to minimize overshoot (this may cause delay to reach SP).
Disabling or Setting this parameter on lower side will proportionally increase
the rate of rise of PV ( which may cause overshoot). Disable this option if
delay is not required to reach SP.
(This may cause overshoot w.r.t. SP)| . Disable
Auto
Tune| | This parameter will be prompted only if selected control action is
PID.
If Enabled, this parameter will be prompted if user press Shift key for 3Sec.|
If Disabled, this parameter will not be prompted if user press Shift key for
3Sec.| Enable
Set
Point| | If Enabled, User can View & edit the Set point (SP1) in USER list.|
Enable
---|---|---|---
If disabled, User can not View or edit Set Point (SP1) in USER list.
User Lock Code| | Default USER LOCK CODE is 15 to access Control &
Configuration List.
User has a choice to set its own USER LOCK CODE between 1 to 9999, this is to
prevent unauthorized access of Control & Configuration List.| 15
AUTO TUNING MODE: To enter in this mode, Press & hold SHIFT key for minimum 3 sec in Run Mode.
Parameter | Display | Description | Default |
---|
Auto
Tuning
Mode| | This function will be executed only if selected control action is PID.
Auto-tuning function is enabled by setting this parameter to ‘YES’. The
decimal of LSB flashes till Auto tuning function is in progress. During Auto-
tuning, Controller learns the process characteristics by itself & calculates
required P, I & D values. User can cancel or abort this feature by setting
this parameter to ‘NO’.| No
USER GUIDE:
ON-OFF ACTION: In this mode, Output (Relay/SSR) remains ON till actual temperature reaches to the set point value. On reaching SP, Output turns OFF & remains OFF till actual temperature drops down (in Heat logic) or raises (in Cool logic) equal to hysterisis set by User. (As shown in Fig : 3.1 & 3.2)
AUTO TUNING MODE: In this mode, Controller learns the process characteristics by itself and calculates the required P,I & D values. It can be performed at any time after power ON but, it is best to start it when the process is at Ambient temperature in order to minimize overshoot & undershoot. Auto tuning is applied in case of :
- Initial set up for a new process.
- Substantial change in SP from previous auto tuning value.
- Control accuracy is not satisfactory.
If the control performance by using auto-tuning is still unsatisfactory, User can apply the further adjustments of P,I & D values as shown below
Adjust | Symptom | Solution |
---|---|---|
Proportional Band | Slow Response | Decrease PB |
Over Shoot or Oscillations | Increase PB | |
Integral Time | Slow Response | Decrease Int |
Instability or Oscillation | Increase Int | |
Derivative Time | Slow Response or Oscillation | Decrease Dt |
High Over Shoot | Increase Dt |
Mfgd by: Innovative Instruments & Controls LLP
338, New Sonal Link Service Industrial Premises Co-op Society Ltd,
Building No.2, Link Road, Malad (W), Mumbai – 400064.
Tel: 022-66939916/17/18;
E-mail: sales@itherm.co.in
Website:
www.itherm.co.inhttps://www.youtube.com/channel/UCzWGtv0HuHUgZR4KKRyKG1w/videos
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>