CROUSE HINDS IF 1378 Corrosion Protection Kit Instruction Manual

June 13, 2024
CROUSE-HINDS

CROUSE HINDS IF 1378 Corrosion Protection Kit

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

APPLICATIONS

TMC-K Series Cold Shrink™ Corrosion Protection Kits are designed to provide a quick and easy method for protecting TMC and TMCX Series Terminator® Cable Fittings from the corrosive influences of wet and salt-fog installation environments.
A TMC-K Cold Shrink™ Corrosion Protection Assembly is an open-ended tubular rubber sleeve ,…,hich is factory expanded and assembled onto a removable core. The core is removed after the assembly has been positioned for installation over a Terminator® Cable Fitting.
TMC-K Cold Shrink™ Assemblies are made from EPDM rubber material that contains no chlorides or sulfurs. They conform to the moisture seal requirements of ANSI Standard C119.1.
TMC-K Series Corrosion Protection Kits are assigned according to the following table:

TMC-K Kit

Catalog No.

| TMC Fitting Catalog No.| TMCX Fitting Catalog No.
---|---|---
__

TMC- K1

| __

TMC165

| __

TMCX165

TMC- 1 <2| TMC285| TMCX285
TMC- K3| TMC3112| TMCX3112
TMC- K4| TMC4140| TMCX4140
TMC- K5| TMC5161| TMCX5161
TMC- K6| TMC6206| TMCX6206
TMC- K7| TMC7247| TMCX7247
TMC- K8| TMC8302| TMCX8302
TMC- K9| TMC9352| TMCX9352
TMC-K10| TMC10402| TMCX10402

METHODS:
Mastic material, provided in each TMC-K Kit, is meant to fill and seal the NPT thread area of each Terminator® Cable Fitting prior to Cold Shrink™ Assembly installation. The mastic is provided in two forms:

  • TMC-K1 through TMC-K6 . . . Mastic Strips
  • TMC-K7 through TMC-K10 . . Mastic Roll

TMC-K1, TMC-K2 & TMC-K3:

  • Two Cold Shrink™ Assemblies are provided in these kits.
  • The smaller of these (less than three inches long) serves as an adapter to increase the diameter range of the protective outer sleeve assembly.

INSTALLATION

  1. Position Cold Shrink™ Assembly (Figure 2) over cable jacket. Direct loose core pull tab onto cable first as shown.
    NOTE (TMC-K1, TMC-K2 & TMC-K3 Kits):
    Position smaller Cold Shrink™ Assembly over the cable last as shown ® (Figure 2).

  2. Install TMC or TMCX Terminator® Cable Fitting according to instructions provided. See typical example @ (Figure 2).

  3. Use mastic seal strips {or roll) from kit to fill gap over NPT threads of fitting © (Figure 3).
    Remove white release liners before wrapping. Build mastic level to flats of fitting hex nut. Mastic material may be folded to ease wrapping.

  4. TMC-K1, TMC-K2, TMC-K3 Only: Position Cold
    Shrink™ Adapter Assembly as shown ® (Figure 4).
    Install by unwinding loose core pull tab in a counter-clockwise direction around cable.

  5. Position Cold Shrink™ Corrosion Protection Assembly ® (Figure 5) over Terminator® Cable Fitting. Install by unwinding loose core pull tab in a counter-clockwise direction around cable. Rubber corrosion protection sleeve should make contact with enclosure wall during installation.

NOTE: Plastic core is recyclable

All statements, technical information and recommendations contained herein are based on information ahd tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds

‘Terms and Conditions of Sale”, and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.

Cold Shrink™ is a Trademark of 3M

Cooper Industries Inc.
Crouse Hinds Division
PO Box 4999, Syracuse, New York 13221 • U.S.A
Copyright 1997, Cooper Industries Inc.