netvox R718PA5 Wireless NO2 Sensor User Manual

June 13, 2024
netvox

netvox Logo Model: R718PA5
Wireless NO2 Sensor
R718PA5
User Manual 

Copyright© Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.

Introduction

R718PA5 is a Class A device based on the LoRaWAN™ protocol of Netvox and is compatible with LoRaWAN protocol. R718PA5 can be connected with an NO2 sensor (RS485), and report the NO2 concentration collected by the device to the corresponding gateway. The device is compatible with LoRaWAN protocol.
LoRa Wireless Technology:
LoRa is a wireless communication technology dedicated to long distance and low power consumption. Compared with other communication methods, LoRa spread spectrum modulation method greatly increases to expand the communication distance. Widely used in long-distance, low-data wireless communications. For example, automatic meter reading, building automation equipment, wireless security systems, industrial monitoring. Main features include small size, low power consumption, transmission distance, anti-interference ability and so on.
LoRaWAN:
LoRaWAN uses LoRa technology to define end-to-end standard specifications to ensure interoperability between devices and gateways from different manufacturers.

Appearance

Main Feature

  • Adopt SX1276 wireless communication module
  • 12V DC power supply
  • NO2 sensor detection
  • The base is attached with a magnet that can be attached to a ferromagnetic material object
  • Main body IP Rating: IP65 / IP67 (Optional)
  • Compatible with LoRaWAN™ Class A
  • Frequency hopping spread spectrum technology
  • Configuring parameters and reading data via the third-party software platforms, and set alarms via SMS text and email (optional)
  • Applicable to the third-party platforms: Actility/ ThingPark/ TTN/ MyDevices/ Cayenn

Set Up Instruction

On/Off

Power On DC12V adapter
Turn On DC12V power supply, the green indicator flashing once means turn on

successfully.
Turn Off (Restore to factory sett| Press and hold the function key for 5 seconds, and the green indicator flashes 20 times
Power Off| Remove DC12V adapter
Note| 1. On/off interval is suggested to be about 10 seconds to avoid the interference of capacitor inductance and other energy storage components
2. The first five seconds after power on, the device will be in engineering test mode

Network Joining

Never Join the Network| Turn on the device to search the network
The green indicator keeps on for 5 seconds: success
The green indicator remains off: fail
---|---
Had Joined the Network (Not restore to the factory setting)| Turn on the device to search the previous network
The green indicator keeps on for 5 seconds: success
The green indicator remains off: fail
Fail to Join the Network| Suggest to check the device verification information on the gateway or consult your platform server provider

Function Key

Press and Hold for 5 Seconds| Restore to the factory setting / turn off
The green indicator flashes 20 times: success
The green indicator remains off: fail
---|---
Press once| The device is in the network: the green indicator flashes once and the device sends a data report
The device is not in the network: the green indicator remains off+

Data Report

After power on, the device will immediately send a version packet report, and then send another report with the data of NO2 concentration after 20 seconds.
The device sends data according to the default configuration before any other configuring.
Default setting
MaxTime: 180s (3min)
MinTime: The MinTime configuration is not available, but it needs to be set greater than 0 because of the software limitation.
Note:

  1. Report interval is based on the factory default.
  2. R718PA5 reports the NO2 concentration value.
  3. The device reported data parsing please refer to Netvox LoRaWAN Application Command document and Netvox Lora
    Command Resolver http://www.netvox.com.cn:8888/cmddoc

5.1 Example of ReportDataCmd
FPort:0x06

Bytes 1 1 1 Var(Fix=8 Bytes)
Version DeviceType ReportType NetvoxPayLoadData

Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType– 1 byte – Device Type of Device The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType – 1 byte –the presentation of the NetvoxPayLoadData,according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)

Device Device Type ReportType NetvoxPayLoadData
R7 I SPA Series 0x57 0x06 Battery
(1 Byte, unit:0.1V) NO2
(2Bytes,O.Ippm) SO2
(2Bytes,O.Ippm) H2S
(2Bytes ,O.Ippm) Reserved

(1Byte,fixed Ox00)

Uplink:015706000032FFFFFFFF00
1 st byte (01): Version
2 nd byte (57): DeviceType 0x57 - R718PA Series
3rd byte (06): ReportType
4th byte (00): DC power supply
5th6 th byte (0032): NO2 – 5ppm, 0032(HEX)=50(DEC),50*0.1ppm=5.0ppm
7th8th byte (FFFF): SO2
9th 10th byte (FFFF): H2S
11 th byte (00): Reserved
5.2 Example of ConfigureCmd
FPort:0x07

Bytes 1 1 Var (Fix =9 Bytes)
CmdID DeviceType NetvoxPayLoadData

CmdID– 1 byte
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)

Description| Device| Cmd ID| Device Type| NetvoxPayLoad Data
---|---|---|---|---
Config ReportReq| R7 18PA Series| Ox01| 0x57| MinTirne (2bytes Unit: s)| MaxTime (2bytes Unit: s)| Reserved (5Bytes, Fixed Ox00)
Config ReportRsp| 0x81| Status (OxOtsuccess)| Reserved (8Bytes, Fixed Ox00)
ReadConfig ReportReq| 0x02| Reserved (9Bytes, Fixed Ox00)
ReadConfig ReportRsp| 0x82| MinTime (2bytes Unit: s)| MaxTime (2bytes Unit: s)| Reserved (SBytes, Fixed Ox00)

  1. Configure R718PA5 device parameter MaxTime = 1min
    (The MinTime configuration is useless, but it needs to be set greater than 0 because of the software limitation.)
    Downlink: 0157000A003C0000000000
    Device Return:
    8157000000000000000000 (configuration success)
    8157010000000000000000 (configuration failure)

  2. Read R718PA5 device parameter
    Downlink: 0257000000000000000000
    Device Return:
    8257000A003C0000000000 (device current parameter)

Installation

  1. R718PA5 has the built-in magnet (as the figure below) which can be attached to the surface of an iron object duri installation, which is convenient and quick. In order to make the installation firmer, please use screws (purchased separately) to fix the device to the wall or othe surface (as Figure below).
    NO2 Sensor is fixed by screws that needs two screws (purchased separately) in the middle.
    Note:
    Do not install the device in a metal shielded box or in an environment surrounded by other electrical equipment to avoid affecting the wireless transmission of the device.

  2. R718PA5 regularly reports data that is NO2 concentration according to MaxTime.
    The default Max Time is 3 min.
    Note:
    MaxTime can be modified by the downlink command,but it is recommended not to set the interval too short.

R718PA5 can be applied to the scene of detecting the
NO2 concentration.
Example:

  • Underground parking lot
  • Environmental protection monitoring

netvox R718PA5 Wireless NO2 Sensor - Housing

Important Maintenance Instruction

Kindly pay attention to the following in order to achieve the best maintenance of the product:

  • Keep the device dry. Rain, moisture, or any liquid, might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.
  • Do not use or store the device in dusty or dirty environment. It might damage its detachable parts and electronic components.
  • Do not store the device under excessive heat condition. High temperature can shorten the life of electronic devices, destroy batteries, and deform or melt some plastic parts.
  • Do not store the device in places that are too cold. Otherwise, when the temperature rises to normal temperature, moisture will form inside, which will destroy the board.
  • Do not throw, knock or shake the device. Rough handling of equipment can destroy internal circuit boards and delicate structures.
  • Do not clean the device with strong chemicals, detergents or strong detergents.
  • Do not apply the device with paint. Smudges might block in the device and affect the operation.
  • Do not throw the battery into the fire, or the battery will explode. Damaged batteries may also explode.

All of the above applies to your device, battery and accessories. If any device is not working properly, please take it to the nearest authorized service facility for repair.netvox Logo

References