R718PA5 is a Class A device based on the LoRaWAN™ protocol of Netvox and is
compatible with LoRaWAN protocol. R718PA5 can be connected with an NO2 sensor
(RS485), and report the NO2 concentration collected by the device to the
corresponding gateway. The device is compatible with LoRaWAN protocol.
LoRa Wireless Technology:
LoRa is a wireless communication technology dedicated to long distance and low
power consumption. Compared with other communication methods, LoRa spread
spectrum modulation method greatly increases to expand the communication
distance. Widely used in long-distance, low-data wireless communications. For
example, automatic meter reading, building automation equipment, wireless
security systems, industrial monitoring. Main features include small size, low
power consumption, transmission distance, anti-interference ability and so on.
LoRaWAN:
LoRaWAN uses LoRa technology to define end-to-end standard specifications to
ensure interoperability between devices and gateways from different
manufacturers.
Appearance
Main Feature
- Adopt SX1276 wireless communication module
- 12V DC power supply
- NO2 sensor detection
- The base is attached with a magnet that can be attached to a ferromagnetic material object
- Main body IP Rating: IP65 / IP67 (Optional)
- Compatible with LoRaWAN™ Class A
- Frequency hopping spread spectrum technology
- Configuring parameters and reading data via the third-party software platforms, and set alarms via SMS text and email (optional)
- Applicable to the third-party platforms: Actility/ ThingPark/ TTN/ MyDevices/ Cayenn
Set Up Instruction
On/Off
Power On | DC12V adapter |
---|---|
Turn On | DC12V power supply, the green indicator flashing once means turn on |
successfully.
Turn Off (Restore to factory sett| Press and hold the function key for 5
seconds, and the green indicator flashes 20 times
Power Off| Remove DC12V adapter
Note| 1. On/off interval is suggested to be about 10 seconds to avoid the
interference of capacitor inductance and other energy storage components
2. The first five seconds after power on, the device will be in engineering
test mode
Network Joining
Never Join the Network| Turn on the device to search the network
The green indicator keeps on for 5 seconds: success
The green indicator remains off: fail
---|---
Had Joined the Network (Not restore to the factory setting)| Turn on the
device to search the previous network
The green indicator keeps on for 5 seconds: success
The green indicator remains off: fail
Fail to Join the Network| Suggest to check the device verification information
on the gateway or consult your platform server provider
Function Key
Press and Hold for 5 Seconds| Restore to the factory setting / turn off
The green indicator flashes 20 times: success
The green indicator remains off: fail
---|---
Press once| The device is in the network: the green indicator flashes once and
the device sends a data report
The device is not in the network: the green indicator remains off+
Data Report
After power on, the device will immediately send a version packet report, and
then send another report with the data of NO2 concentration after 20 seconds.
The device sends data according to the default configuration before any other
configuring.
Default setting
MaxTime: 180s (3min)
MinTime: The MinTime configuration is not available, but it needs to be set
greater than 0 because of the software limitation.
Note:
- Report interval is based on the factory default.
- R718PA5 reports the NO2 concentration value.
- The device reported data parsing please refer to Netvox LoRaWAN Application Command document and Netvox Lora
Command Resolver http://www.netvox.com.cn:8888/cmddoc
5.1 Example of ReportDataCmd
FPort:0x06
Bytes | 1 | 1 | 1 | Var(Fix=8 Bytes) |
---|---|---|---|---|
Version | DeviceType | ReportType | NetvoxPayLoadData |
Version– 1 byte –0x01——the Version of NetvoxLoRaWAN Application Command
Version
DeviceType– 1 byte – Device Type of Device The devicetype is listed in Netvox
LoRaWAN Application Devicetype doc
ReportType – 1 byte –the presentation of the NetvoxPayLoadData,according the
devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
Device | Device Type | ReportType | NetvoxPayLoadData |
---|---|---|---|
R7 I SPA Series | 0x57 | 0x06 | Battery |
(1 Byte, unit:0.1V) | NO2 | ||
(2Bytes,O.Ippm) | SO2 | ||
(2Bytes,O.Ippm) | H2S | ||
(2Bytes ,O.Ippm) | Reserved |
(1Byte,fixed Ox00)
Uplink:015706000032FFFFFFFF00
1 st byte (01): Version
2 nd byte (57): DeviceType 0x57 - R718PA Series
3rd byte (06): ReportType
4th byte (00): DC power supply
5th6 th byte (0032): NO2 – 5ppm, 0032(HEX)=50(DEC),50*0.1ppm=5.0ppm
7th8th byte (FFFF): SO2
9th 10th byte (FFFF): H2S
11 th byte (00): Reserved
5.2 Example of ConfigureCmd
FPort:0x07
Bytes | 1 | 1 | Var (Fix =9 Bytes) |
---|---|---|---|
CmdID | DeviceType | NetvoxPayLoadData |
CmdID– 1 byte
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)
Description| Device| Cmd ID| Device Type| NetvoxPayLoad
Data
---|---|---|---|---
Config ReportReq| R7 18PA Series| Ox01| 0x57| MinTirne (2bytes Unit: s)|
MaxTime (2bytes Unit: s)| Reserved (5Bytes, Fixed Ox00)
Config ReportRsp| 0x81| Status (OxOtsuccess)| Reserved (8Bytes, Fixed Ox00)
ReadConfig ReportReq| 0x02| Reserved (9Bytes, Fixed Ox00)
ReadConfig ReportRsp| 0x82| MinTime (2bytes Unit: s)| MaxTime (2bytes Unit:
s)| Reserved (SBytes, Fixed Ox00)
-
Configure R718PA5 device parameter MaxTime = 1min
(The MinTime configuration is useless, but it needs to be set greater than 0 because of the software limitation.)
Downlink: 0157000A003C0000000000
Device Return:
8157000000000000000000 (configuration success)
8157010000000000000000 (configuration failure) -
Read R718PA5 device parameter
Downlink: 0257000000000000000000
Device Return:
8257000A003C0000000000 (device current parameter)
Installation
-
R718PA5 has the built-in magnet (as the figure below) which can be attached to the surface of an iron object duri installation, which is convenient and quick. In order to make the installation firmer, please use screws (purchased separately) to fix the device to the wall or othe surface (as Figure below).
NO2 Sensor is fixed by screws that needs two screws (purchased separately) in the middle.
Note:
Do not install the device in a metal shielded box or in an environment surrounded by other electrical equipment to avoid affecting the wireless transmission of the device. -
R718PA5 regularly reports data that is NO2 concentration according to MaxTime.
The default Max Time is 3 min.
Note:
MaxTime can be modified by the downlink command,but it is recommended not to set the interval too short.
R718PA5 can be applied to the scene of detecting the
NO2 concentration.
Example:
- Underground parking lot
- Environmental protection monitoring
Important Maintenance Instruction
Kindly pay attention to the following in order to achieve the best maintenance of the product:
- Keep the device dry. Rain, moisture, or any liquid, might contain minerals and thus corrode electronic circuits. If the device gets wet, please dry it completely.
- Do not use or store the device in dusty or dirty environment. It might damage its detachable parts and electronic components.
- Do not store the device under excessive heat condition. High temperature can shorten the life of electronic devices, destroy batteries, and deform or melt some plastic parts.
- Do not store the device in places that are too cold. Otherwise, when the temperature rises to normal temperature, moisture will form inside, which will destroy the board.
- Do not throw, knock or shake the device. Rough handling of equipment can destroy internal circuit boards and delicate structures.
- Do not clean the device with strong chemicals, detergents or strong detergents.
- Do not apply the device with paint. Smudges might block in the device and affect the operation.
- Do not throw the battery into the fire, or the battery will explode. Damaged batteries may also explode.
All of the above applies to your device, battery and accessories. If any device is not working properly, please take it to the nearest authorized service facility for repair.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>