resideo SM120 Safety Valve 2.5 Bar Instruction Manual
- June 13, 2024
- resideo
Table of Contents
resideo SM120 Safety Valve 2.5 Bar
Product Information
- Product Name: Braukmann SM120
- Medium: Water
- Connection Sizes: R 1/2 to R11/4
- Operating Temperatures: Flow temperature
- Specifications: Capacity: 50 – 300 kW
- Options: For options, visit homecomfort.resideo.com/europe
Product Usage Instructions
- Thoroughly flush the pipework.
- Install the membrane safety valve. The discharge opening is marked by an arrow on the valve body.
- Guide the outlet of the discharge line into a drain or container that can accept the total content of the system.
- If there is a risk of the discharge line becoming clogged or freezing, interrupt the discharge line using a funnel. The discharge line of the funnel must have twice the cross-section of the safety valve intake.
Safety Guidelines
- Follow the installation instructions.
- Use the appliance
- according to its intended use
- in good condition
- with due regard to safety and risk of danger.
- Note that the appliance is exclusively for use in the applications detailed in these installation instructions (see 2 Technical Data). Any other use will not be considered to comply with requirements and would invalidate the warranty.
- Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
- Immediately rectify any malfunctions which may influence safety.
Technical Data
Media
Medium:| Water
Connections/Sizes
Connection sizes:| R 1/2″ to R11/4″
Operating temperatures
Flow temperature:| max. 120 °C (248 °F)
Specifications
Capacity:| 50 – 300 kW
The valve size is determined by the size of the inlet
connection.
Closed heating or solar systems. Not suitable for water
storageheaters.
Options
For Options visit homecomfort.resideo.com/europe
Assembly
Installation Guidelines
- Safety valve must be installed in the cold water supply pipework before the water heater
- The installation must be carried out so that:
- There are no shut-off valves or fittings, narrowing of the pipework or strainers between the water heater and the safety valve
- Good access is provided for service and maintenance
- That the safety valve is positioned above the heat generator
- That between the safety valve and heat exchanger a max. 1 m long straight connection line with the size of the inlet diameter is installed
- The safety valve must be mounted so that in its installed condition no external forces act on it
- The discharge line must be performed to the size of the safety valve outlet diameter and may not have more than 2 elbows and or be longer than 2 m
- The discharge line must be installed with an incline
Assembly instructions
CAUTION!
The safety valve may not be overheated through welding and soldering work on
the system. Install the safety valve only after these tasks are completed.
-
Thoroughly flush pipework
-
Install the membrane safety valve
• Tighten the connections with max. 18 Nm when joining. Cracks may form in the material when tighten to strongly which may cause leaks in the system.
• Installation in horizontal pipe with safety cap pointing up
• Note flow direction
• Install without tension or bending stresses -
Install discharge line
- CAUTION! Risk of scalding through hot liquid escaping from the discharge opening. Route discharge line so that neither personal injuries nor property damage can be caused by discharged fluid. The discharge opening is marked by an arrow on the valve body
-
Guide the outlet of the discharge line into a drain or container which can accept the total content of the system. If there is a risk that the discharge line becomes clogged or can freeze, interrupt the discharge line, e.g. by a funnel. The discharge line of the funnel must have twice the cross-section of the safety valve intake
Start-up
- Mount a warning sign readily visible near the discharge line or on the safety valve with the following text:
- CAUTION! While heating, water must escape from the discharge line for safety reasons. Do not close!
- Make sure that all water connections are tight
- We recommend flushing the supply line before commissioning the plant
Maintenance
In order to comply with EN 806-5, water fixtures must be inspected and serviced on an annual basis. As all maintenance work must be carried out by an installation company, it is recommended that a servicing contract should be taken out.
Inspection
CAUTION!
- Risk of scalding through hot liquid escaping from the discharge opening.
- Function check by verifying the response: While the system is operating, briefly open the safety valve by turning the cap. After closing the cap the valve must close again the backed up water drain completely.
Maintenance CAUTION!
- Risk of scalding through hot liquid escaping from the discharge opening.
- If a malfunction is detected, a repair can be attempted by opening and closing the cap several times. A replacement is necessary if this action is not successful.
Disposal
Observe the local requirements regarding correct waste recycling/disposal!
CONTACT
- Manufactured for and on behalf of Pittway Sàrl, Z.A., La Pièce 4,
- 1180 Rolle, Switzerland
- by its authorised representative
- Ademco 1 GmbH
- For more information
- homecomfort.resideo.com/europe
- Ademco 1 GmbH, Hardhofweg 40,
- 74821 MOSBACH, GERMANY
- Phone: +49 6261 810
- Fax: +49 6261 81309
- © 2020 Resideo Technologies, Inc. All rights reserved.
- Subject to change. MU1H-1324GE23 R0420_PL-01