BAXI Gas Fired Wall Mounted Condensing Combination Boiler Instruction Manual

June 13, 2024
BAXI

BAXI Gas Fired Wall Mounted Condensing Combination Boiler Instruction Manual
BAXI Gas Fired Wall Mounted Condensing Combination
Boiler

Gas Fired Wall Mounted Condensing Combination Boiler

Please keep these instructions in a safe place.
If you move house, please hand them over to the next occupier.

The Benchmark Scheme

Baxi Heating UK Ltd is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimise safety, efficiency and performance.

Benchmark is managed and promoted by the Heating and Hotwater Industry Council. For more information visit www.centralheating.co.uk

Product Overawe

Quick Reference Guide

Key to Controls

Product Overawe

Standby – Reset – Esc

Boiler Information View

Increase CH Temperature Button

Decrease CH Temperature Button

Increase DHW Temperature Button

Decrease DHW Temperature Button

Summer / Winter / Only Heating Mode Button

Summer – DHW only request mode

Winter – DHW & CH request mode

Only Heating – Only CH request mode

NOTE: When altering any settings it is necessary that the buttons are FIRMLY pressed for several seconds.

Display Description

Display Description

DHW and CH OFF (frost protection still enabled)

Indicate errors that prevent burner from starting

Error – Not resettable by user

Water pressure too low

Indicates a resettable error

Indicates navigation in programming mode (parameter)

Indicates navigation in programming mode

Generic error

Burner lit

DHW request

Heating mode

Units for temperature

Units for pressure

Service due

Troubleshooting

Boiler not working

Boiler Working
Boiler Working
Troubleshooting

*To display the water pressure press 6 times. ‘05’ will alternate with the system pressure.

(NOTE: When the pump is running the gauge under the boiler may show a slightly differnt reading to the display)

If you don’t know what you need to do to get the boiler to light, or need help with the system and controls, contact your installer as soon as possible

Temperature / Care of the Boiler

To increase or decrease the boiler temperature

  1. Press the ( ) to increase the CH temperature.
  2. Press the ( ) to decrease the CH temperature.

NOTE: An NTC device is positioned in the heat exchanger which shuts down the appliance if the boiler temperature exceeds 100°C. Press the ( ) button to re- establish normal operating conditions.
Operating Conditions

Summer – Winter – Only Heating Mode

  1. Press ( ) button until the required mode appears:-
    Summer – DHW only request mode
    Winter – DHW & CH request mode
    Only Heating – Only CH request mode

  2. See 3.1 or 3.2 to set the required temperature.

Cleaning the Outercase

The painted panels should be wiped with a damp cloth and then dried completely. DO NOT USE ABRASIVE CLEANING AGENTS.

Boiler Frost Protection

  1. The boiler incorporates an integral frost protection feature that will operate in both CH & DHW modes, and also when in standby ( displayed).
  2. If the boiler temperature falls below 5° C, then the boiler will operate until the water temperature has been raised.
  3. Further protection may be required for the system. Consult your installer for details.

Information Display

The table opposite shows information that can be displayed by pressing the button.

The button can be pressed so that the display shows the following information:-

  1. press – ‘00’ alternates with Sub-Code (only when fault on boiler) or ‘000’
  2. presses – ‘01’ alternates with CH Temperature
  3. presses – ‘02’ alternates with Outside Temperature (where Sensor fitted)
  4. presses – ‘03’ alternates with DHW Temperature
  5. presses – ‘04’ alternates with DHW Temperature
  6. presses – ‘05’ alternates with System Water Pressure
  7. presses – ‘06’ alternates with Return Temperature
  8. presses – ‘04’ alternates with Flue Temperature
  9. presses – ‘05’ alternates with Heat Exchanger Temperature

Repressuring System & ‘Service Due

Central Heating System Pressure

  1. The normal operating water pressure is between 1 and 2.5 bar (Fig. 1). If the pressure exceeds 3 bar the safety pressure valve will operate and a fault is indicated (E117 displayed). Contact your installer.
    System Pressure

  2. It may be necessary to depressurize the system occasionally (as Fig. 2 or E118 displayed). A filling device (the filling loop) will be fitted on the system. This will be on the boiler itself, or on pipework near to the boiler.
    Displayed

  3. If you are unsure of its position, or cannot identify it, consult the installer who fitted the boiler.

  4. The filling loop consists of two taps and a separate copper pipe with connection fittings.

  5. Only when repressurising should the copper pipe be connected between the two taps. Ensure that the nuts on the pipe ends are tightened onto the taps.

  6. Fully open one of the taps first, and then while watching the pressure gauge, carefully open the second tap.

  7. The system pressure is shown at all times on the gauge under the boiler and can be viewed on the display when there is power to the boiler.

  8. To display the water pressure press 6 times. ‘05’ will alternate with the system pressure. (NOTE: When the pump is running the gauge under the boiler may show a slightly differnt reading to the display)

  9. When the needle on the gauge or figures on the display indicate 1 or more turn both taps off.

  10. Disconnect the copper pipe from the taps (a small amount of water may be present) and remove it. Keep the pipe in a safe place for future use.

‘Service Due’ Message ‘Sd’ will show for three seconds, alternating with the boiler temperature
Service Due

‘Service Due’ Message

  1. After 11 months operation the ‘Service Due’ message will be shown on the boiler display.
  2. Please contact your Installer, Annual Service Provider or ‘heateam’ – The Service Division of Baxi to arrange your Annual Service. You can contact ‘heateam’ on telephone number 08448 711 545 or visit www.heateam.co.uk

Clearances

For your Safety

  1. This appliance must have been installed in accordance with the manufacturer’s instructions and the regulations in force.

  2. Any modification that may interfere with the normal operation of the appliance without express written permission from the manufacturer or his agent could invalidate the appliance warranty. In GB this could also infringe the Gas Safety (Installation and Use) Regulations
    Heating Industry definition meaning England, Scotland, Wales, Northern Ireland, Isle of Man and the Channel Isles

  3. Your boiler must not be operated without the casing correctly fitted.

  4. Do not interfere with any sealed components on this boiler.

  5. Take note of any warning labels on your boiler.

  6. Your boiler should have the following minimum clearances for Safety and Maintenance (Figs. 3 & 4):-
    Product Dimensions

    Product Dimensions****

    • Top – 175mm
    • Bottom – 150mm*
    • Left side – 5mm
    • Right Side – 5mm
    • Front – 5mm (In Operation)
    • 450mm (For Servicing)
      *This is MINIMUM recommended dimension. Greater clearance will aid installation and maintenance.
  7. If your boiler is installed in a compartment, do not use it for storage purposes. Do not obstruct any purpose provided ventilation openings.

  8. Flammable materials must not be stored in close proximity to your boiler.

  9. Avoid skin contact when your boiler is in operation, as some surfaces may get hot e.g. pipework.

  10. Ensure that the flue terminal, outside the house, does not become damaged or obstructed, particularly by foliage.

  11. It is important that the condensate drain system is not blocked, modified or damaged in any way as this would affect the operation of your boiler. Your installer should have insulated any exposed pipework

Error Codes

List of Error Code

Error Codes

  1. The display shows two types of signals: and . In both cases the display shows symbol and the numeric value of the error (see the “error table” below).
  2. The spanner cannot be reset by the user. Please contact your Installer, Annual Service Provider or ‘heateam’ – The Service Division of Baxi to arrange your Annual Service. You can contact ‘heateam’ on telephone number 08448 711 545 or visit www.heateam.co.uk
  3. Fault errors can be reset by pressing the button

WARNING: If an error code (is different from the ones described below) appears on the display or a certain fault appears frequently, contact the authorized ‘heat am’.

Table Of Error Codes

  • 09 :Gas Valve Connection Cable
  • 15 :Gas Valve Fault
  • 20 :Central Heating NTC Fault
  • 28 :Flue NTC Fault
  • 40 :Central Heating Return NTC Fault
  • 55 :Calibration Required
  • 109 :Pre-circulation Fault
  • 110 :Safety Thermostat Operated
  • 117 :Primary System Water Pressure Too High
  • 118 :Primary System Water Pressure Too Low
  • 125 :Circulation Fault (Primary)
  • 128 :Flame Failure
  • 130 :Flue NTC Operated
  • 133 :Interruption Of Gas Supply or Flame Failure
  • 134 :Elapsed Time – Gas Valve Open Without Gas
  • 135 :Interruption Of Gas Supply (Internal Error)
  • 154 :Flow/Return Sensor Temperature Test
  • 160 :Fan or Fan Wiring Fault
  • 270 :Circulation Fault (Dry Fire)
  • 321 :Hot Water NTC Fault
  • 384 :False Flame

Legislation

Installation, Commissioning, Service & Repair

  1. This appliance must be installed in accordance with the manufacturer’s instructions and the regulations in force. Read the instructions fully before installing or using the appliance.
  2. In GB, this must be carried out by a competent person as stated in the Gas Safety (Installation & Use) Regulations.
  3. Definition of competence: A person who works for a Gas Safe registered company and holding current certificates in the relevant ACS modules, is deemed competent.
  4. In IE (Eire), this must be carried out by a competent person as stated in I.S. 813 “Domestic Gas Installations”.

Lifting – This product should be lifted and handled by two people. Stooping should be avoided and protective equipment worn where necessary. Carrying & lifting equipment should be used as required, e.g. when installing in a loft space.

All Gas Safe registered engineers carry an ID card with their licence number and a photograph. You can check your engineer is registered by telephoning 0800 408 5500 or online at www.gassaferegister.co.uk

The boiler meets the requirements of Statutory Instrument
“The Boiler (Efficiency) Regulations 1993 No 3083” and is deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water boilers fired with liquid or gaseous fuels:-

Type test for purpose of Regulation 5 certified by:
Notified Body 0085.

Product/Production certified by:
Notified Body 0086.
Ref: 86-BL-647

For GB/IE only

Benchmark Commissioning Checklist

  1. Please ensure that the installer has fully completed the Benchmark Checklist on the inside back pages of the installation instructions supplied with the product and that you have signed it to say that you have received a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist as a means of complying with the appropriate Building Regulations (England and Wales).
  2. All installations must be notified to Local Area Building Control either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer who should, on receipt, write  the Notification Number on the Benchmark Checklist.
  3. This product should be serviced regularly to optimise its safety, efficiency and performance. The service engineer should complete the relevant Service Record on the Benchmark Checklist after each service.
  4. The completed Benchmark Checklist may be required in the event of any warranty work

Emergency

Warning !

If you smell gas

  • Do not operate light switches
  • Do not operate any electrical equipment
  • Do not use a telephone in the hazardous area
  • Extinguish any naked flame and do not smoke
  • Open windows and doors in the hazardous area
  • Turn off the gas supply at the meter
  • Warn any other occupants and vacate the premises
  • Telephone the National Gas Emergency Service on:- 0800 111 999

Faulty boiler
If it is known or suspected that a fault exists on the boiler, it must not be used until the fault has been corrected by a competent person.

In an Emergency

  1. If a water or gas leak occurs or is suspected, the boiler can be isolated at the inlet valves by turning their taps through 90° (1 /4 turn) downwards
  2. Please contact your Installer, Annual Service Provider or ‘heateam’ – The Service Division of Baxi to arrange your Annual Service. You can contact ‘heateam’ on telephone number 08448 711 545 or visit www.heateam.co.uk as soon as possible.

In an Emergency 

Please complete the boxes below

Serial Number
Serial Number

Date of Installation
Date of Installation

Installer Details (name, address and contact number(s))
Installer Details
Instructions

All descriptions and illustrations provided in this leaflet have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet. All goods are sold subject to our standard Conditions of Sale which are available on request.

BAXI
A Trading Division of Baxi Heating UK Ltd (3879156)
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 0844 871 1525 Technical Enquiries 0844 871 1555
Website www.baxi.co.uk e&oe

Warranty & Service

Standard Warranty Terms & Conditions
To activate your second year free warranty you must register your boiler with heateam the service division of Baxi Heating UK Ltd either by completing and returning the registration card or calling our telephone registration line on 0800 013 7989.

It is also a requirement of the warranty that the boiler has an annual service (every 12 months) in accordance with the installation and servicing instructions, performed by a Gas Safe registered engineer.

If you would like heateam to carry this out please call on 0844 871 1525.

Our promise to you
If you experience a fault with your new boiler, we aim to provide a safe and high quality repair service supported by our dedicated national network of highly skilled engineers. If your installer can’t resolve the problem for you, we will do everything we can to get an engineer out to you as quickly as possible.

Nothing in this warranty will affect your statutory consumer rights.

What you need to do if you experience a problem with your heating system or the operation of the boiler
You should always contact your installer first, because the cause of the fault may not be related to the boiler. If your installer confirms that the fault is with the boiler and he/she can’t repair it, our friendly customer service team is on hand to help. Simply call our service division heateam on 0844 871 1525 to book an engineer visit or for any general advice that you may need. Our contact centre is open Monday to Friday 8am – 6pm, weekends and Bank Holidays 8.30am – 2pm, excluding Christmas Day and New Years Day.

When calling heateam it would be helpful if you could have the following information to hand:-

  1. Boiler serial number (see opposite).
  2. Boiler make and model number.
  3. Your installer name and address details.
  4. Proof of purchase (if you do not have the boiler serial number).

What this warranty covers
Free of charge repair or replacement of components found to be of faulty manufacture.

Free of charge replacement of the complete unit provided always that the failure is related to a manufacturing fault that cannot be repaired or is uneconomic to repair.

What this warranty does not cover
Repairs to boilers which haven’t been installed and commissioned properly, and as set out in the installation instructions (this includes the need to flush the system effectively and add a suitable corrosion inhibitor).

Any damage caused by hard water scale deposits and/or aggressive water resulting from corrosion.

Any other defects or failures, either in the connected heating system or outside of the boiler itself.

Faults caused by inadequate supply of electricity, gas or water to the property. Installations within commercial settings for which this boiler was not designed.

Reimbursement of any third party repair or replacement costs that we haven’t been told about or agreed with you in advance.

Compensation for consequential losses (e.g. loss of earnings, business losses, stress and inconvenience) arising from a production breakdown, including repair delays caused by factors outside our reasonable control.

After Sales Service 0844 871 1525

© Baxi Heating UK Ltd 2012

Comp No. 720633506 (2/12)

© Baxi Heating UK Ltd 2012 All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means, or stored in any retrieval system of any nature (including in any database), in each case whether electronic, mechanical, recording or otherwise, without the prior written permission of the copyright owner, except for permitted fair dealing under Copyrights, Designs and Patents Act 1988.

Applications for the copyright owner’s permission to reproduce or make other use of any part of this publication should be made, giving details of the proposed use, to the following address:

The Company Secretary, Baxi Heating UK Limited,

Brooks House, Coventry Road, Warwick. CV34 4LL

Full acknowledgement of author and source must be given.

WARNING: Any person who does any unauthorised act in relation to a copyright work may be liable to criminal prosecution and civil claims for damages

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals