HILTI CFS-W P Firestop Power Wrap Instruction Manual

June 4, 2024
HILTI

HILTI logo FIRESTOP
POWER WRAP
CFS-W P
Technical Manual
European Technical Assessment
ETA-20/0989
Instruction Manual
HILTI CFS W P Firestop Power Wrap
-

CFS-W P FIRESTOP POWER WRAP

The all-rounder for combustible pipes and insulation in coated board

HILTI CFS W P Firestop Power Wrap - POWER WRAP

Applications

  • Passive fire protection of wastewater, roof drainage, potable water, and refrigeration pipes in board applications
  • Firestopping wastewater and roof drainage pipes in drywall, aerated concrete, masonry, and concrete
  • Heating, cooling, and freshwater pipes in the shaft wall

Advantages

  • Approved for a comprehensive range of combustible pipe and insulation materials in coated board applications
  • Endless solution: one firestop product for all common combustible pipes and types of pipe insulation
  • Cost-effective installation: one-person installation with no need for hooks, anchors, or drilling
  • Code-compliant: all pipes tested with end configurations meeting code requirements for the application

Technical Data

Dimensions (L × W × H) 10000 × 50 × 2 mm
Storage and transportation temperature range –5 to 50 °C
Complementary products CFS-S ACR
Order designation Package contents Length Sales pack quantity Item number
CFS-W P Firestop power wrap 1 × CFS-W P Firestop power wrap 10 m 1 pc

2133384
CFS-W P Hook| 20 × CFS-W P Hook| | 20 pc| 2133385

INSTRUCTIONS FOR USE

RIGID / FLEXIBLE WALL APPLICATION
ETA-20/0989

www.hilti.group
http://fsselector.hilti.com

RIGID FLOOR APPLICATION
ETA-20/0989

HILTI CFS W P Firestop Power Wrap - 2

https://qrco.de/bby6C5

WALL APPLICATION IN COATED BOARD
ETA 11 / 0429

HILTI CFS W P Firestop Power Wrap - 3HILTI CFS W
P Firestop Power Wrap - 4https://qrco.de/bby6C5

HILTI CFS W P Firestop Power Wrap - 5

Layers| | | |
---|---|---|---|---
0| –| 4 mm| 9 mm
(mm)| L (mm)| L (mm)| L (mm)
2| 32| ? 250| 300| 360
40| ? 300| ?. 360| 410
50| ? 370|
?. 420| 470
56| ?410| ? 460| 520
3| 63| ? 690| ? 770| 820
75| ? 810| ? 880| 950
4| 82| 1200| 1300| 1400
90| ?. 1300| ?. 1400| 1500
110| 1530| 1650| 1750
125| 1730| 1830| 1960
6| 135| 2850| 3000| 3150
140| 2960| 3120| 3300
160| 3330| 3520| 3650
| Layers| | | | |
---|---|---|---|---|---|---
Ø| AF1| AF2| AF3| AF4
(mm)| L (mm)| L (mm)| L (mm)| L (mm)
2| 32| ≥ 400| ≥ 420| ≥ 460| ≥ 500
40| ≥ 420| ≥ 470| ≥ 530| ≥ 580
50| ≥ 490| ≥ 540| ≥ 590| ≥ 640
56| ≥ 520| ≥ 590| ≥ 620| ≥ 690
4| 63| ≥ 1180| ≥ 1290| ≥ 1370| ≥ 1500
75| ≥ 1390| ≥ 1500| ≥ 1600| ≥ 1720
5| 90| ≥ 1940| ≥ 2110| ≥ 2210| ≥ 2360
110| ≥ 2290| ≥ 2570| ≥ 2570| ≥ 2730

HILTI CFS W P Firestop Power Wrap - 6

GENERAL INFORMATION

HILTI CFS W P Firestop Power Wrap - 7

Partition| Shaft Wall| Flexible Wall| Rigid Wall| Rigid Floor
Base Material Thickness (tE)| 3 × 15 mm| ≥ 100 mm| ≥ 100 mm| ≥ 150 mm
Annular Gap| 0–15 mm| | 0–15 mm|
Gap Filler| CFS-S ACR| CFS-S ACR or gypsum plaster| CFS-S ACR or mortar
Penetrant| Standard and nonstandard Aluminium composite pipes,
plastic conduits| Plastic pipes (PE,PP, PVC, ABS)

MAIN APPROVED APPLICATIONS

| | |
---|---|---|---
Application| Pipe material| Pipe Ø mm| Shaft wall| Flexible wall| Rigid wall| Rigid floor
Waste Water & Roof Drainage
| PE, PE-HD (EN1519-1,
EN12666-1, EN12201-2)| 32 to 110
(32 to 160)| –| EI 90 U/U (EI 90U/C)
ABS (EN1455-1)| –| EI 90 U/U (EI 90 U/C)
SAN+PVC (EN1565-1)| –| EI 90 U/U (EI 90 U/C)
PVC-U (EN1329-1, EN 1453-1,
EN1452-1, EN1566-1,
EN ISO 15493, EN 1452)| –| EI 90 U/U (EI 90 U/C)
PE (EN ISO 15494, DIN 8074)| –| EI 90 U/U (EI 90 U/C)
PE-S2 Geberit® dB20| –| EI 90 U/U (EI 90 U/C)
PP Non-regulated| –| EI 90 U/U (EI 90 U/C)
PE, PE-HD (EN1519-1, EN12666-1, EN12201-2) with Elastomeric insulation| 32 to 110| –| EI 90 U/U
ABS (EN1455-1) with Elastomeric insulation| –| EI 90 U/U
SAN+PVC (EN1565-1) with Elastomeric insulation| –| EI 90 U/U

Heating & Cooling, Freshwater

| AI Composite*| 14–32| EI 90 U/C| –| –
---|---|---|---|---|---

  • Al Composite: Geberit® Mepla, Uponor Uni Pipes Plus®, Ke Kelit® Kelox Multilayer pipe®, Rehau® Rautitan Stabi®, TECEFlex®, Rehau® Rautitan Flex Roth Alu-Laserplus®,®, Viega Sanfix Fosta®

Application| Pipe material| Pipe Ø mm| Coated board in
flexible/ rigid wall| Coated board in
rigid floor
---|---|---|---|---
Wastewater| PE/PE-HD (EN 1519-1,
EN12555-1,EN12201-2),
Geberit®  Silent dB20| 32 to 110
(32 to 160)| EI 90 U/U (EI 90 U/C)
PVC (EN1452-1, EN1329-1,
EN1453-1, EN1566-1, EN
ISO1452-2, EN ISO 15493,
DIN8061/8062)
PP non-regulated*
Industry| PE (EN15494, DIN8074/8075)| EI 90 U/C
PVC (EN1452-1, EN1329-1,
EN1453-1, EN1566-1, EN
ISO1452-2, EN ISO 15493,
DIN8061/8062)
Roof drainage| PE/PE-HD (EN 1519-1,
EN12555-1,EN12201-2) with
Elastomeric insulation| 32 to 110| EI 90 U/U
Potable water & Cooling| Composite pipes** with elastomeric insulation| 16 to 75| EI 90 U/C
Copper pipe with combustible insulation| 10 to 42| EI 90 C/U
Steel pipe with combustible insulation| 10 to 219

  • PP non-regulated: Coes ® BLUE POWER, Coes ® PhoNo Fire, Geberit ® Silent PP, Ke Kelit ® PhonEx ® AS, Marley ® Silent, Ostendorf ® Skolan ®, Pipelife ® Master3, Poloplast ® Polo-KAL 3S ®, Poloplast ® NG ®, Poloplast ® Polo-KAL XS ®, Rehau ® Raupiano ® Plus, Valsir ® Silere ®, Valsir ® Triplus ®, Wavin ® AS ®, Wavin SciTech
    ** Composite pipes: Rehau ® ® Rautitan stabil, Geberit ® Mepla, Ke Kelit ® Kelox, Uponor MLC

Excerpt of ETA documents. Check the exact field of application for each pipe (type, diameter, pipe wall thickness) in the ETA-20/0989 and ETA 11/0429 document

OTHER APPROVED APPLICATIONS

Multiple penetrations of Al. composite pipes

EI90 U/C

See ETA-20/0989 for details of approved pipes

CHARACTERISTICS OF CFS-W P

Characteristics| Assessment of characteristics| Norm, standard, test
---|---|---
Health and the environment
Dangerous substances| Hilti Firestop wrap CFS-W P” was tested for SVOC and VOC according to
EAD 350454-00-1104, clause 2.2.5.1, in accordance with EN 16516 with a
loading factor of 0.007m²/m³. Release scenarios IA1 and IA2 have been tested.
The concentration of SVOC after 3 days and after 28 days was <0.005mg/m³.
The concentration of the total emission of VOC after 3 days and after 28 days was, as well, <0.005mg/m³.| Material safety data sheet
Durability and serviceability| Category Y2 (Product intended for use at a temperature below 0 °C, but with no exposure to rain or UV| EAD 350454-00-1104
Reaction to fire| Class E| EN 13501-1