Presentation of Conventional panel IRON 02/04

The conventional fire detection and fire alarm control panel IRON02/04 from COFEM represents all the knowledge of 50 years experiences in the fire detection market.
This control panel has two models so, it can be adapted to the needs of each installation: IRON02 (2 zones) and IRON04 (4 zones).

Main Technical features:

  • Control panel with 2 or 4 zones for using conventional detectors and MPC (manual call point).
  • Up to 32 devices (detectors + MPCs) per zone.
  • 2 monitored general sounder output, delayable from 0 to 7 minutes, and protected by a fuse.
  • 1 immediate alarm output through a dry NO/NC contact (Normally Open/Normally Closed).
  • 1 immediate fault output through a dry NO/NC contact (Normally Open/Normally Closed).
  • One 30V/DC monitored auxiliary outputs protected by a fuse for external power supply as sounders, relay units, etc.
  • It has a test mode for quickly and easy checking of detectors and manual call points.
  • It allows configuration of the Open line, alarm detector and alarm manual call point thresholds for adjusting to operation with other detectors.
  • Metal box with front bolted door, 10 predrilled holes of 28mm to connect wire with panel and area for two 2A batteries.
  • Certified according to standard EN 54-2 and EN 54-4.
  • Dimensions: 248 x 240 x 105 mm.
  • IP code IP30.

Control Panel

Indications LEDs, control keys and actions.

Here, you can see indicators LEDs and buttons that you have in your IRON02/04 control panel Cofem.
Control panel LEDs are the same for both references. The only difference is the number of zones LEDs.

Indications LEDs

Indications LEDs

Indicator leds are described:

LEDS LED color DESCRIPTION
ALARM Red

detector.
► Fixed
Test Mode| | Amber| Zone or zones in Test Mode.
► Fixed ⇒ At least a zone in test mode.
DISABLE| | Amber| Zone or zones disable.
► Fixed ⇒ At least a zone disable.
GENERAL FAULT| | Amber| System Fault
► Fixed
SUPPLY FAULT| | Amber| General power supply Fault.
► Fixed ⇒ Fault 110~230VAC input, 30V and Sounders output.
► Blinking ⇒ Without batteries.
SYSTEM FAULT| | Amber| CPU fault
► Fixed ⇒ Control panel is not operating.
SOUNDER FAULT| | Amber| General Sounder output condition.
► Fixed ⇒ Open line.
► Blinking ⇒ Short-circui
COM| | |
KEYBOARD ACCESS| | Amber| Access level to keyboard´s control panel
► Off ⇒ Level 1.
► Fixed ⇒ Level 2. Activate by microswitch permanently
► Blinking ⇒ Level 2. Activate by keys during 30 seconds.
POWER SUPPLY| | Green| System operating through 110~230 V/AC power supply.
► Fixed
BATTERY| | Green| System operating under batteries.
► Fixed
ACT SOUNDER| | Amber| ► Fixed ⇒ General sounder relays on. Panel is working without delay in general sounder relays.
►Blinking ⇒ General sounder relays delay activated.
SILENCE SOUNDER| | Amber| ► Fixed ⇒ General outputs sounders permanently stopped.
► Blinking ⇒ General outputs sounders stopped until new zone alarm.
ALARM
Fault / Test /Disable| | Red| Alarm zone
► Fixed ⇒ Alarm activated by MPC.
► Blinking ⇒ Alarm activated by detector.
| Amber| Test/Fault/Disable zone.
► Fixed ⇒ Disable zone.
► Blinking ⇒ Short-circuit fault / Open line fault / Test Mode.
SLEEPING MODE| | Amber| ► Blinking ⇒ Battery, General fault and Power supply fault.
Panel is in hibernation when it does not have power Supply
110/220V and batteries are under 21V.

Control keys and actions

a) How to stop buzzer.

Control keys and actions| Stop buzzer

Stop acoustic sound (buzzer) because of an alarm or fault.
►  1 pressing ⇒ switches off the sounder noise. In the event of a new incident, the buzzer will activate automatically.

---|---

b) How to stop sounders

| Activate control panel access

⇒ Pressing at the same time: Zone 1 and Zone 4.

---|---
Control keys and actions| Stop General sounder outputs.

►  1 pressing ⇒ Disactivate General sounder outputs relays.

c) How to activate sounders

| Activate control panel access

⇒ Pressing at the same time: Zone 1 and Zone 4.

---|---
Control keys and actions| Active General sounder outputs:

►  1 pressing ⇒ General sounder output relays are activated.

d) How to do a control panel reset

| Activate control panel access

⇒ Pressing at the same time: Zone 1 and Zone 4.

---|---
Control keys and actions| ►  Press constantly Þ Resets control panel.

World map

Customer Support

Commercial +34 935 862 690 comercial@cofem.com
Commercial cofem@cofem.com

FABRICANTE DE PRODUCTOS CONTRA INCENDIOS– FIRE PROTECTION MANUFACTURER FABRICANTSDE PRODUITS CONTRE INCENDIES
C/ Compositor Wagner, 8 – P.I. Can Jardí – 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 – cofem@cofem.comwww.cofem.com

cofem Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals