OXBOX JMM4A0A18S21SAA Series Wall Mount Air Handler Installation Guide
- June 13, 2024
- Oxbox
Table of Contents
OXBOX JMM4A0A18S21SAA Series Wall Mount Air Handler
Product Information
The JMM4A series wall mount air handler is a versatile unit designed for installation in a closet, utility room, alcove, or as a wall-mounted unit. It is suitable for air conditioning applications and can be equipped with field installed electric resistance heaters. The unit meets current federal OSHA Guidelinesfor safety.
Important: This Document is customer property and is to remain with this unit.
Note: The small air handlers have been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280 or theequivalent. They are suitable for mobile home use.
California Proposition 65 requires warnings for products sold in California that contain or produce any of over 600 listed chemicalsknown to the State of California to cause cancer or birth defects. This air handler contains fiberglass insulation, which producesrespirable particles known to cause cancer.
Product Usage Instructions
Before installing or servicing the air handler, ensure compliance with national, state, and local codes.
Safety Precautions:
- Individuals with adequate backgrounds of electrical andmechanical experience should handle repairs.
- Disconnect all electrical power, including remote disconnects,before installation or servicing.
- Follow proper lockout/tagout procedures to prevent inadvertent energization.
- Take necessary precautions when working with live electricalcomponents.
- Avoid storing corrosive or combustible materials near theunit.
- Ensure proper grounding as per local and state electrical coderequirements.
Installation:
- Install the air handler in a closet, utility room, alcove, or as a wall-mounted unit.
- Follow the National Electric Code, NFPA No. 90A and 90B, and any other local codes or utilities requirements.
Optional Electric Resistance Heaters:
- If desired, field install electric resistance heaters according to the manufacturer’s instructions.
Mobile Home Use:
- The small air handlers are suitable for use in mobile homes.
California Proposition 65 Warning:
- This air handler contains fiberglass insulation, which producesrespirable particles known to cause cancer.
For further assistance or information, refer to the complete user manual or contact customer support.
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL
CODES
Important: This Document is customer property and is to remain with this
unit. The JMM4A series wall mount air handler is designed for installation in
a closet, utility room, alcove and can be wall mounted. These versatile units
are applicable to air conditioning applications. Field installed electric
resistance heaters are available.
Features
Standard Features
-
All aluminum coil.
-
Factory installed piston style refrigerant control-
Field installed TXV kits available. -
Blower and coil slide out easily for maintenance.
-
Factory-sealed cabinet certified to achieve 2% or
less air leakage rate at 1.0 inch water column. -
Front or bottom return air.
-
Painted finish on galvanized steel.
-
Sturdy polycarbonate drain pans.
- Air handler has factory installed drain pan and
is shipped for upflow applications only.
- Air handler has factory installed drain pan and
-
208/230 VAC operation.
-
Stud or wall mount installation.
-
Fully insulated cabinet.
-
3/4” NPT primary and secondary drains.
-
AHRI certified and ETL listed.
Optional Accessories
Safety Information
WARNING
SAFETY HAZARD! This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
WARNING
HAZARDOUS VOLTAGE!
Disconnect all electrical power, including remote disconnects before
installing or servicing. Follow proper lockout/tagoutprocedures to ensure the
power can not be inadvertently energized. Failure to disconnect power before
servicing couldresult in death or serious injury.
WARNING
LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
WARNING
EXPLOSION HAZARD!
Do not store corrosive or combustible materials, gasoline, or other flammable
vapors or liquids near the unit. Failure to follow this warning could result
in property damage, serious personal injury, or death.
WARNING
ELECTRICAL HAZARD!
Grounding Required! Follow proper local and state electrical code on
requirements for grounding. Failure to follow thiswarning could result in
property damage, serious personal injury, or death.
WARNING
HAZARDOUS VAPORS! Do not install an air handler with a non-ducted return in the same closet, alcove, or utility room as a fossil fuel device. Hazardous vapors can be distributed throughout the conditioned space and equipment damage can result.
Important: These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for thepurchaser’s purposes, the matter should be referred to your installing dealer or local distributor.Important: Installation of this unit shall be made in accordance with the National Electric Code, NFPA No. 90A and 90B, and any other local codes or utilities requirements.
Note: The small air handlers have been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent. “SUITABLE FOR MOBILE HOME USE.”
WARNING
PROPOSITION 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to State of California to cause cancer. All manufacturer products meet current federal OSHAGuidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards. California’s Proposition 65 requires warnings for products sold inCalifornia that contain or produce any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural vapor. All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market. You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air-conditioning equipment, or found in natural vapor used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers.
- Glass Wool (Fiberglass) Insulation
- Carbon Monoxide (CO)
- Formaldehyde
- Benzene
More details are available at the websites for OSHA (Occupational Safety and Health Administration), at www.osha.gov and the State of California’s OEHHA (Office of Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products present safety and health risks, when improperly used, handled and maintained
CAUTION
CORROSION HAZARD! To prevent shortening its service life, the air handler
should not be used during the finishing phases of construction. The low return
air temperatures can lead to the formation of condensate. Condensate in the
presence of chlorides and fluorides from paint, varnish, stains, adhesives,
cleaning compounds, and cement creates a corrosive condition which may cause
rapid deterioration of the cabinet and internal components.
CAUTION
SAFETY HAZARD! Sharp Edge Hazard. Be careful of sharp edges on equipment or
any cuts made on sheet metal while installing or servicing. Personal injury
may result.
WARNING
Make sure the blower motor support is tight (3-motor mount bolts) then check
to see if wheel is secured to motor shaft before operating unit
Installation Instructions
Unpacking
Carefully unpack the unit and inspect the contents for damage. If any damage is found at the time of delivery, proper notification and claims should be made with the carrier. Check the rating plate to assure model number and voltage. Furthermore, check that kits match with what was ordered. The manufacturer should be notified within 5 days of any discrepancy or parts shortage
Location
The small air handler should be centrally located and may be installed in a closet, alcove, utility room, or basement. Minimumclearances must be met. The air handler comes standard with two different options formounting, wall mount or frame mount. Both mounting options requirethe unit to be level from side to side and from front to back in order toallow condensate to properly drain from the unit. Failure to do this will result in condensate leaking out from the unit, potentially causing structural damage to the surrounding support structures, dry wall, carpet, etc. Also, both mounting structures require the ability to accommodate a minimum of 150 lb load. Failure to do this will cause damage to the support structure and potentially damage the unit.
WALL MOUNT
The air handler comes standard with an upper and lower wall mount bracket. Reference Figure 3-1 for more detail.
- Remove lower wall mounting bracket from the back of the unit by removing one screw which attaches the bracket to the air handle r. Note: Discard the screw after you have removed the wall mounting bracket.
- Install bracket on the wall by using 3 wood screws (not provided). Make sure the bracket is level in order to provided proper drainage from the unit. Note: Do not attach the wall mounting bracket into unsupported dry wall. Make sure that the wood screws are going into a structure that can suppport a minimum load of 150 lb.
- Lift the air handler above the wall mounting bracket and attach the unit to the installed bracket. Reference Figure 3-1.
- Install the additional bottom plate for extra support for this type mounting (see figure 3-1).
Note: The additional plate is shipped in the bottom of the shipping carton (only for 30/36k unit).
FRAME MOUNT
The air handler comes with 8 clearance holes (4 on each side). These holes are
used to mount the air handler inside of a frame structure (see Figure 3-2).
When mounting in this fashion, make sure that the wood screws are mounted from
within the air handler and not outside of the unit. Install the screws from
outside the unit, and avoid damaging the coil. If the frame does not provide
support in the front of the unit and additional support is needed, open up the
tabs and fix the unit to the frame or other support structure with screws
(only for 30K/36K). Select a solid and level site to ensure proper
installation of the frame mount. Verify that there is suf ficient space for
installation and maintenance.(See Figure. 3-3)
IMPORTANT: The (8) wood screws are not provided with the unit. #12 x 1 ½˝
wood screws are recommended. When the unit is installed on a wood frame, the
screws should be used to fix the unit to the studs. If they are not used, the
unit may fall down or cause other damage. See Figure 3-2 for frame mount
installation.
Duct Work
Field ductwork must comply with the National Fire Protection Association NFPA
90A, NFPA 90B and any applicable local ordinance.
WARNING
Do not, under any circumstances, connect return ductwork to any other heat producing device such as fireplace insert, stove, etc. Unauthorized use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury or property damage.
Sheet metal ductwork run in unconditioned spaces must be insulated and covered with a vapor barrier. Fibrous ductwork may be used if constructed and installed in accordance with SMACNA Construction Standard on Fibrous Glass Ducts. Ductwork must comply with National Fire Protection Association as tested by U/L Standard 181 for Class I Air Ducts. Check local codes for requirements on ductwork and insulation.
- Duct system must be designed within the range of external static pressure the unit is designed to operate against. It is important that the system airflow be adequate. Make sure supply and return ductwork, grills, special filters, accessories, etc. are accounted for in total resistance. See airflow performance tables in this manual.
- Design the duct system in accordance with “ACCA” Manual “D” Design for Residential Winter and Summer Air Conditioning and Equipment Selection. Latest editions are available from: “ACCA” Air Conditioning Contractors of America, 1513 16th Street, N.W., Washington, D.C. 20036. If duct system incorporates flexible air duct, be sure pressure drop information (straight length plus all turns) shown in “ACCA” Manual “D” is accounted for in system.
- Supply plenum is attached to the 3/4” duct flanges supplied with the unit.
- IMPORTANT: If an elbow is included in the plenum close to the unit, it must not be smaller than the dimensions of the supply duct flange on the unit.
- IMPORTANT: If connected to the blower casing, the front flange on the return duct must not be screwed into the area where the power wiring is located. Drills or sharp screw points can damage insulation on wires located inside unit.
- Secure the supply and return ductwork to the unit flanges, using proper fasteners for the type of duct used and tape the duct-to-unit joint as required to prevent air leaks.
Condensate Drain
The unit is supplied with primary and auxiliary condensate drains that have
3/4” NPT connections. Both drains must be trapped outside the unit and piped
in accordance with applicable materials and building codes. Do not reduce the
drain line size less than the connection size on the drain pan. Condensate
should be piped to an open drain or to the outside. All drains must pitch
downward away from the unit a minimum of 1/4” per foot of line to ensure
proper drainage. Insulate the primary drain line to prevent sweating where dew
point temperatures may be met. (Insulation is optional depending on climate
and application needs.)
Important: If cleanout Tee is used, standpipe must be sealed/capped.
DIFFERENT AIR SUPPLY
Bottom Return Conversion: Divert the return air from the factory standard
front return to a bottom return.Remove the cross brace when converting cabinet
to bottom return.
Refrigerant Piping
Refrigerant pipe connections are located on the top of the unit. Refrigerant
piping external to the unit shall be sized in accordance with the instructions
of the outdoor equipment. When units are recessed mounted in the wall, make
certain that piping connections are pressure tested prior to the wall being
closed. While brazing, be sure to protect the cabinet and grommets from heat
damage. Metering Device
All units are shipped and installed with throttle designed for air
conditioning operation. Pressures equalize after shut down. Some outdoor
models may require a start assist kit. See outdoor unit for more information.
Blower
This unit is supplied with a multi-speed PSC motor with a direct drive blower
wheel which can obtain various air flows. The unit is shipped with factory set
cooling and heating speed taps. Airflow performance tables are available for
additional speed taps. Disconnect all power to the unit before making any
adjustments to the motor speed taps. Be sure to check the air flow and the
temperature drop across the evaporator coil to ensure sufficient air flow.
Wiring
Field wiring must comply with the National Electric Code (C.E.C. in Canada)
and any applicable local ordinance.
WARNING
Disconnect all power to unit before installing or servicing. More than one disconnect switch may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death.
POWER WIRING
It is important that proper electrical power is available for connection to
the unit model being installed. See the unit nameplate, wiring diagram and
electrical data in the installation instructions.
- If required, install a branch circuit disconnect of adequate size, located within sight of, and readily accessible to the unit.
- IMPORTANT: After the Electric Heater is installed, units are equipped with one 30-60 amp. circuit breaker. These breaker(s) protect the internal wiring in the event of a short circuit and serve as a disconnect. Circuit breakers installed within the unit do not provide over-current protection of the supply wiring and therefore may be sized larger than the branch circuit protection.
- Supply circuit power wiring must be 75°C minimum copper conductors only. See Electrical Data in this section for ampacity, wire size and circuit protector requirements. Supply circuit protective devices may be either fuses or “HACR” type circuit breakers.
- Power wiring may be connected to either the right or left side. Two 7/8” dia. concentric knockouts are provided for connection of power wiring to unit.
- Power wiring is connected to the power terminal block in unit electric cabinet.
CONTROL WIRING
IMPORTANT: Class 2 low voltage control wiring should not be run in
conduit with main power wiring and must be separated from power wiring, unless
class 1 wire of proper voltage rating is used.
- Low voltage control wiring should be 18 Awg. color-coded. For lengths longer than 100 ft., 16 Awg. wire should be used.
- Low voltage control connections are made to low voltage pigtails extending from top of air handler (see Figure 1). Connections for control wiring are made with wire nuts. Control wiring knockouts (7/8˝) are also provided on the right and left side of the unit for side connec-tion.
- See wiring diagrams attached to indoor and outdoor sections to be connected.
- Make sure, after installation, separation of control wiring and power wiring has been maintained.
GROUNDING
WARNING
The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death.
- Grounding may be accomplished when installed in accordance with electrical codes by bonding the metal conduit to the unit cabinet or by attaching ground wire(s) to ground lug(s) provided in the unit wiring compartment.
- Ground lug(s) are located close to wire entrance on left side of unit (upflow). Lug(s) may be moved to marked locations near wire entrance on right side of unit (upflow) if alternate location is more convenient.
- Use of multiple supply circuits require grounding of each circuit to lug(s) provided in unit.
Air Filter
An air filter must be installed before air enters the evaporator coil in order
to protect the coil, blower, and other internal parts from excessive dirt and
dust A filter must be installed. Consult the filter manufacturer for proper
sizing and maximum velocity requirements.
Filter Sizes
MODEL | FILTER SIZE IN [mm] |
---|---|
18/24 | 16Χ20[406Χ508] |
30/36 | 20Χ20[508Χ508] |
Thermostat
Select a thermostat that is commonly used with HP or AC single stage
heating/cooling with electric heat. The thermostat will energize the fan on a
demand for heating or cooling.
Install the thermostat on an inside wall, away from drafts, lights or other
heat sources in a location that has sufficient air circulation from other
rooms being controlled by the thermostat. The thermostat should be mounted 4
to 5 feet above the floor.
Sequence of Operation
Cooling (cooling only)
When the thermostat calls for cooling, the circuit from R to G is completed.
The blower motor is energized directly by the 24VAC signal from the
thermostat.
The circuit from R to Y is also completed, energizing the compressor contactor
of the outdoor unit. The contactor will close and start the compressor and
condenser fan motor.
Heating (electric heat only)
Note: The thermostat must be setup to bring the blower on when the
electric heat is energized.
When the thermostat calls for heating, the circuit from R to G is completed
and the blower motor is energized directly by the 24VAC signal from the
thermostat. The circuit from R to W is completed energizing the heating
contactor(s).
Operational And Checkout Procedures
To obtain proper performance, all units must be operated and charge
adjustments made in accordance with procedures found in the Service Facts
document of the outdoor unit.
After installation has been completed, it is recommended that the entire
system be checked against the following list:
- Be sure unit suspension (if used) is secure and there are no tools or loose debris in, around or on top of the unit.
- Properly insulate suction lines and fittings.
- Properly secure and isolate all refrigerant lines.
- Verify that all electrical connections are tight.
- Check all duct outlets; they must be open and unrestricted.
- Check drain lines and be sure all joints are tight.
- Be sure the return air filter is installed.
- Operate complete system in each mode to verify proper performance. Verify operation of supplementary electric heater.
This air handler comes with a factory-installed piston metering device. A TXV
may be required to achieve minimum efficiency ratings or for long refrigerant
line set applications. Reference AHRI for system combination ratings.
Charge the system by superheat when using a piston. Reference the outdoor unit
installation guide to charge the system by subcooling when using a TXV.
Table 1 Superheat Charging Chart
Outdoor Temp(oF) | Indoor Temperature(oF) Dry Bulb/Wet Bulb |
---|---|
95/79 | 90/75 |
Superheat (°F)
115| 23| 16| 7| 5| 5| 5
110| 24| 17| 9| 5| 5| 5
105| 26| 19| 11| 6| 5| 5
100| 27| 21| 13| 7| 5| 5
95| 29| 23| 16| 8| 5| 5
90| 30| 25| 18| 12| 6| 5
85| 32| 26| 20| 16| 9| 5
80| 34| 28| 22| 17| 11| 5
75| 35| 30| 24| 19| 13| 6
70| 37| 32| 26| 21| 16| 10
65| 38| 34| 29| 24| 19| 13
60| 40| 36| 31| 27| 22| 17
55| 41| 37| 33| 29| 25| 21
Note: Chart is based on 400 CFM/Ton indoor airflow and 50% relative humidity. If indoor relative humidity is above 70% or below 20%. use indoor wet bulb temperature only. Airflow range is 375 to 425 CFM/Ton.
Maintenance
The system air filter(s) should be inspected, cleaned or replaced at least monthly. Make certain that the access panels are replaced and secured properly before placing the unit back in operation. This product is designed for dependable service; however, periodic maintenance should be scheduled and conducted by trained professional service personnel. This service should be conducted at least annually, and should include testing and inspection of electrical and refrigerant components. The heat transfer surface should be cleaned. The blower motor is permanently lubricated for normal operating conditions.
Wiring
SCHEMATIC DIAGRAM
SEE RATING PLATE FOR VOLTS&HERTZ
CAUTION: NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE
ATTENTION: NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND
NOTES:
- Use copper wire(75 min), to be wired in accordance with N.E.C. and local codes.
- If any of the original wire as supplied must be replaced,use the same or equivalent type wire.
- Remove the red lead from 240V terminal and then connect the red lead to 208V terminal on the transformer for 208 volts.
- Factory default fan speed is medium; FM red wire connected to FR #4. For HI speed connect FM black wire to FR #4. For LOW speed connect FM blue wire to FR #4 and FM red wire to FR #6. Always connect the unused FM wire to the dummy terminal CN3.
- TDB has a 90-100s off delay when G is de-energized.
- ConnectRto R,G to G, etc. See outdoor or indoor instructions for details.
- Cooling controls wiring not used with electric heaters,
- N.E.C., class2,24volts.
Section 5. – Heater Pressure Drop Table – Use For All TMM4B Wall Mount Air Handler Models
NUMBER OF RACKS |
---|
MODEL
| AIRFLOW CFM| 1| 2| 3
AIR PRESSURE DROP – INCHES W.G.
JMM4A0B30,36
| 1400| 0.06| 0.08| 0.08
1300| 0.06| 0.08| 0.08
1200| 0.06| 0.08| 0.08
1100| 0.06| 0.08| 0.08
1000| 0.06| 0.08| 0.08
900| 0.04| 0.06| 0.06
800| 0.04| 0.06| 0.06
700| 0.04| 0.06| 0.06
JMM4A0A18, 24
| 900| 0.04| 0.06| 0.06
800| 0.04| 0.06| 0.06
700| 0.04| 0.06| 0.06
600| 0.04| 0.06| 0.06
500| 0.04| 0.06| 0.06
HEATER RACKS
HEATER MODEL| NO. OF RACKS
BAYHTRJ505BRKA| 1
BAYHTRJ508BRKA| 2
BAYHTRJ510BRKA*| 3
Accessory Heater Usage
NUMBER OF RACKS | SIZES USED WITH | kW | INTERNAL CIRCUIT PROTECTION |
---|---|---|---|
1 | 18-36 | 5 | Circuit Breaker |
2 | 18-36 | 7.5 | Circuit Breaker |
3 | 18-36 | 10 | Circuit Breaker |
Minimum CFM
MODEL | NUMBER OF RACKS |
---|---|
1 | 2 |
JMM4A0A18 21SAA | 450 |
JMM4A0A24 21SAA | 450 |
JMM4A0B30 21SAA | 700 |
JMM4A0B36 31SAA | 700 |
Section 6. Performance and Electrical Data (WALL-MOUNT AIR HANDLERS ARE SUITABLE FOR MOBILE HOME APPLICATIONS)
Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size. External static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation.
PSC-Airflow Performance (Standard CFM)
MODEL
JMM4A
| BLOW ER SPEEDS| EXTERNAL STATIC PRESSURE (in.w.c.)
---|---|---
0| 0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7|
0.8
18
| High| 813| 775| 731| 692| 653| 609| 560| 501| 424
Med| 695| 656| 620| 581| 540| 498| 440| 380| –
Low| 603| 562| 525| 485| 443| 393| –| –| –
24
| High| 947| 895| 847| 799| 753| 704| 655| 592| 530
Med| 845| 801| 759| 716| 675| 626| 573| 510| –
Low| 676| 640| 602| 563| 523| 499| –| –| –
30
| High| 1367| 1312| 1252| 1192| 1131| 1063| 990| 908| 821
Med| 1211| 1165| 1114| 1065| 1016| 960| 899| 833| 748
Low| 992| 952| 912| 873| 828| 782| 728| 656| 627
36
| High| 1397| 1345| 1290| 1263| 1196| 1116| 1051| 980| 907
Med| 1298| 1252| 1198| 1147| 1094| 1037| 976| 910| 842
Low| 1149| 1105| 1056| 1008| 960| 909| 856| 791| 726
- Shaded boxes represent airflow outside the required 300-450 cfm/ton.
NOTES:
- Airflow based upon dry coil at 230V with no electric heat and factory—approved filter.
- Airflow is equivalent for front or bottom return configurations.
The air distribution system has the greatest effect on airflow. The duct system is totally controlled by the contractor. For this reason, the contractor should use only industry-recognized procedures. Duct design and construction should be carefully done. System performance can be lowered dramatically through bad planning or workmanship. Air supply diffusers must be selected and located carefully. They must be sized and positioned to deliver air along the perimeter of the space. If they are too small for their intended airflow, they become noisy. If they are not located properly, they cause drafts. Air grilles must be properly sized to carry air back to the blower.If they are too small, they also cause noise. The installers should balance the air distribution system to ensure proper quiet airflow to all rooms in the home. This ensures a comfortable living space.
Dimensional Data
UNIT DIMENSIONS
MODEL SIZE
| __Dimensions inch (mm| )| | UNIT WEIGHT
/SHIPPING WEIGHT (LBS.(kg))
---|---|---|---|---
UNIT HEIGHT
“H” IN.(mm)
| UNIT WIDTH
“W” IN.(mm)
| UNIT WIDTH
“W1” IN.(mm)
| UNIT LENGTH
“D” IN.(mm)
| UNIT LENGTH
“D1” IN.(mm)
18| 36-1/2 (928)| 20-1/2 (521)| 17-2/5 (442)| 15 (381)| 9-1/2 (242)| 88/101|
(40)/(46)
24| 36-1/2 (928)| 20-1/2 (521)| 17-2/5 (442)| 15 (381)| 9-1/2 (242)| 88/101|
(40)/(46)
30| 39-1/2 (1004)| 22 (559)| 18-4/5 (478)| 19 (483)| 9-1/2 (242)| 106/124.4|
(48)/(56.4)
36| 39-1/2 (1004)| 22 (559)| 18-4/5 (478)| 19 (483)| 9-1/2 (242)| 106/124.4|
(48)/(56.4)
UNIT BACK DIMENSIONS
DIMENSION DATA
Model number
| Dimension inch [mm]
---|---
A| B| C
JMM4A0A18S21SAA| 24-9/10″ [150]| 10-1/8″[61]| 119-1/20″ [717]
JMM4A0A24S21SAA| 24-9/10″ [150]| 10-1/8″[61]| 119-1/20″ [717]
JMM4A0B30S21SAA| 24-9/10″ [150]| 10-1/8″[61]| 132″ [795]
JMM4A0B36S31SAA| 24-9/10″ [150]| 10-1/8″[61]| 132″ [795]
- Twenty ThreeC,LLC
- 800 Beaty Street, Davidson NC,28036
- www.oxboxhvac.com
- For more information contact your local dealer (distributor)
Since the manufacturer has a policy of continuous product and product data
improvement, it reserves the right to change the design and specification
without notice.