Altronix T2RM78SQ Mercury Networked Rack Kits Installation Guide

June 13, 2024
Altronix

Altronix T2RM78SQ Mercury Networked Rack Kits

Product Information

The Altronix/Mercury Networked Rack Kits are pre-assembled kits designed for access and power integration. The kits include the Trove2R enclosure with the TM2R Altronix/Mercury backplane, as well as various components depending on the model. The two available models are:

  1. T2RM78SQ: 8 Door Kit with Fused Outputs
  2. T2RM78SDQ: 8 Door Kit with PTC Outputs

These kits are fully assembled and include power supply/charger, networked access power controller, voltage regulator, and power distribution modules. All components are UL Listed sub-assemblies.

Product Usage Instructions

Before installing the Trove2R enclosure into a rack tower, ensure that the wiring methods comply with the National Electrical Code and local codes. These products are for indoor use only and must be installed within protected premises.

  1. Assemble and install the Z Bracket Wire Management Accessory (refer to Z Bracket Installation on page 3).
  2. Remove the backplane from the enclosure before installing it into the rack cabinet. Do not discard the hardware.
  3. To mount the included cUL Listed tamper switch (Tane Model 3/8 ASH FM WH or equivalent), turn the enclosure upside down and locate the mounting holes on the back of the drawer (refer to Fig. 1 on page 2).
  4. Insert the tamper switch flying leads into the center knockout of the three (3) holes from outside of the drawer with the button facing outwards. Make sure the tamper switch is inserted properly, then secure it.

For more detailed installation information, please refer to the corresponding Sub-Assembly Installation Guides included with the Trove kits.

Models Include

  • T2RM78SQ
    8 Door Kit with Fused Outputs
    Fully assembled kit includes:

    • Trove2R enclosure with TM2R Altronix/Mercury backplane
    • One (1) AL1024UXB2 – Power Supply/Charger
    • One (1) LINQ8ACM – Dual Input Networked Fused Access Power Controller
    • One (1) VR6 – Voltage Regulator
    • One (1) PDS8 – Dual Input Fused Power Distribution Module
  • T2RM78SDQ
    8 Door Kit with PTC Outputs
    Fully assembled kit includes:

    • Trove2R enclosure with TM2R Altronix/Mercury backplane
    • One (1) AL1024UXB2 – Power Supply/Charger
    • One (1) LINQ8ACMCB – Dual Input Networked PTC Access Power Controller
    • One (1) VR6 – Voltage Regulator
    • One (1) PDS8CB – Dual Input PTC Power Distribution Module

All components of these Trove kits are UL Listed sub-assemblies. Please refer to the included corresponding Sub-Assembly Installation Guides for further information.

Overview

Altronix Trove Mercury rack kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/charger and sub-assemblies. All kits accommodate a variety of Mercury modules for up to eight doors in a single enclosure.

Configuration Chart:

Altronix Model Number| 115VAC 60Hz

Input Current (A)

| Power Supply Board Input Fuse Rating| Power Supply Board Battery Fuse Rating| Nominal DC
Output Voltage Range (VDC)| Maximum Supply Current for Main and Aux. Outputs on Power Supply board and LINQ8ACM(CB) Access Power Controller’s outputs| Fail-Safe/Fail-Secure or Dry Form “C” Outputs| Current Per LINQ8ACM (CB) Output (A)| LINQ8ACM(CB) Board Input Fuse (PTC) Rating| LINQ8ACM(CB) Board Output Fuse (PTC) Rating| PDS8(CB) Board Input Fuse (PTC) Rating| PDS8(CB) Board Output Fuse (PTC) Rating
---|---|---|---|---|---|---|---|---|---|---|---
T2RM78SQ| 4.2| 5A/ 250V| 15A/ 32V| 20.17- 26.4| 24VDC @ 9.2A| 8| 2.5| 15A/ 32V| 3A/ 32V| 10A/ 32V| 3A/ 32V
T2RM78SDQ| 2.0| 9A| 2.5A| 9A| 2.5A

Hardware:Altronix-T2RM78SQ-Mercury-Networked-Rack-Kits-
\(1\)

Installation

Installing Trove2R into Rack Tower:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. These products are for indoor use only and must be installed within the protected premises.
Note: First assemble and Install Z Bracket Wire Management Accesory (refer to Z Bracket Installation)

  1. Remove backplane from enclosure prior to installing into rack cabinet (do not discard hardware).
  2. In order to mount included cUL Listed tamper switch (Tane Model 3/8 ASH FM WH or equivalent), turn the enclosure upside down and locate mounting holes (Fig. 1). Insert the tamper switch flying leads into the center knockout of the three (3) holes from outside of the drawer with the button facing outwards, make sure tamper switch is inserted properly then secure it with the two (2) screws (supplied). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm signal open the rack drawer.
  3. Slide the rack enclosure into an open 2U location in the four post rack cabinet.
  4. Utilizing proper fasteners attach front ears to the rack rails .
  5. Attach the rear of the adjustable slides to the rear rails of the rack cabinet with the proper fasteners.
  6. Secure the rack cover (Fig. 2a) and rack drawer (Fig. 2b) to earth ground.Altronix-T2RM78SQ-Mercury-Networked-Rack-Kits- \(3\)
  7. Ensure that all internal cofigurations (voltage selection, switch settings, etc.) are completed before mounting backplane back into Trove rack enclosure.

Bracket Installation for Trove2R:
Altronix Trove2R enclosure includes Z Bracket, a convenient and reliable wire management accessory.

  1. Carefully unpack Z Bracket. Do not discard included hardware (Fig. 3).
  2. Attach arms to each other using bolts and lock nuts (Fig. 4a).Altronix-T2RM78SQ-Mercury-Networked-Rack-Kits- \(6\)
  3. Attach the hinge brackets to the ends of arms using bolts and nuts, positioning them as shown on (Fig. 4b).
  4. Make sure that all nuts are tightened.
  5. Attach the hinge bracket on each end of Z Bracket, then attache the Z Bracket to the adjustable slide using bolts and lock nuts (included) (Fig. 5, 5a).Altronix-T2RM78SQ-Mercury-Networked-Rack-Kits- \(7\)
  6. Attach the hinge bracket on the shorter side of Z Bracket to the rear of the rack enclosure using bolts (included).

T2RM78S(D)Q: Configuration of Mercury Boards:

  1. Fasten spacers onto metal pems configuration (A), (B) or (C) of backplane depending on the access controller (Fig. 6).Altronix-T2RM78SQ-Mercury-Networked-Rack-Kits- \(8\)
  2. Position access controller module over corresponding spacers and fasten screws into spacers (Fig. 6a).
  3. Mount backplane to enclosure with hardware.

Mercury Access Controller Position Chart for the Following Models:

Altronix/Mercury Pem Mounting
LP1502, LP4502, MR52, MR16IN, MR16OUT A
LP2500, MUX8 B
Genetec Cloudlink C

Dimensions

Trove2R Enclosure Dimensions (H x W x D approximate):
3.375” x 19.0” x 33.25” (85.8mm x 482.6mm x 844.6mm). Shown with Z Bracket attached

Altronix-T2RM78SQ-Mercury-Networked-Rack-Kits- \(10\)

All registered trademarks are property of their respective owners. More than just power.™

  • Installing Company: __
  • Service Rep. Name: ___
  • Address: __
  • Phone #: __

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA
phone: 718-567-8181
fax: 718-567-9056
website: www.altronix.com
e-mail: info@altronix.com | Lifetime Warranty

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Altronix User Manuals

Related Manuals