Altronix VertiLine24 Series VertiLine24D CCTV Rack Mount Power Supplies Installation Guide
- June 4, 2024
- Altronix
Table of Contents
More than just power.™
VertiLine24 Series
CCTV Rack Mount Power Supplies
Installation Guide
Models Include:
VertiLine24
– 24VAC or 28VAC @ 10A
– Twenty-four (24) fuse-protected outputs| VertiLine24D
– 24VAC or 28VAC @ 10A
– Twenty-four (24) PTC-protected outputs
---|---
VertiLine246
– 24VAC or 28VAC @ 14A
– Twenty-four (24) fuse-protected outputs| VertiLine246D
– 24VAC or 28VAC @ 14A
– Twenty-four (24) PTC-protected outputs
Rev. 031808
Installing Company:
Service Rep. Name: ____
Address: ____
Phone #: ____
Overview:
Altronix VertiLine CCTV Rack Mount Power Supplies provide 24 power outputs in a space-saving 1U EIA 19” rack mount chassis which may be rack, wall, or shelf mounted. The units feature individually selectable 24VAC and/or 28VAC power outputs with surge suppression. VertiLine CCTV Rack Mount Power Supplies are also available in eight (8) and sixteen (16) output models with various power ratings.
Specifications:
Input:
- Selectable 115VAC, 60Hz or 240VAC, 50/60Hz input.
Output:
- Twenty-four (24) individually selectable 24VAC or 28VAC power outputs with OFF position.
- Twenty-four (24) external blade fuse or PTC-protected outputs.
- Surge suppression.
Features:
- Twenty-four (24) power LED indicators.
Features (cont’d):
- Removable terminal blocks with locking screw flange.
- Illuminated master power disconnect circuit breaker with manual reset.
- IEC 320 – 3-wire grounded line cord (detachable).
Mechanical:
- Units can be rack, wall or shelf mounted.
- Modular 1U standard EIA 19” rack mount chassis
- Enclosure Dimensions (H x W x D approx.):
1.625” x 19.125” x 8.5”
(41.3mm x 486mm x 216mm).
Twenty-four (24) Output Rack Mount Configuration Reference Chart:
Altronix Model Number| Output Voltage (VAC)| Total Output Current (Power)|
Number of Outputs| Output Protection| Class 2 Rated Power- Limited Output
Protection| Current (max. per output)| Fuse Rating| Main Fuse Rating| 115VAC
60Hz
Input Current| 230VAC 50/60Hz
Input Current| Agency Listings| UL Listings and File Numbers
---|---|---|---|---|---|---|---|---|---|---|---|---
VertiLine24| 24VAC or
28VAC| 10A| 24| Fused| –| 3A| 3A| 10A| 3A| 1.6A| ****
| ****
UL Listed for Commercial CCTV
Equipment (UL 2044).
VertiLine24D| 24VAC or
28VAC| 10A| 24| –| PTC| 2.5A| –
VertiLine246| 24VAC or
28VAC| 14A| 24| Fused| –| 3A| 3A| 15A| 4A| 2.5A
VertiLine246D| 24VAC or
28VAC| 14A| 24| –| PTC| 2.5A| –
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes.
Installation Instructions:
-
Set the input voltage selector switch located on the left side of the VertiLine unit (facing the front panel) for 115VAC or 230VAC operation (Fig. 1c, pg. 4).
-
Attach mounting brackets to VertiLine unit for rack or wall mount installation (Figs. 4-5, pg. 7).
Affix rubber pads to VertiLine for shelf installation (Fig. 6, pg. 7). -
Secure the unit in a rack, mount the unit to a wall, or place the unit on a shelf as desired (the unit should be spaced at least 3” from any video monitors). When installing the unit in a rack, allow for one-half of a U spacing above the unit for ventilation.
-
Plug the grounded AC line cord (included) into the IEC 320 connector of the VertiLine unit (Fig. 1g, pg. 4).
Insert the plug end of the line cord into a grounded AC receptacle. -
Set the illuminated master power disconnect circuit breaker to the (ON) position (Fig. 3, pg. 6).
-
Select 24VAC or 28VAC power output for cameras 1-24 with the corresponding voltage adjustment switches (Fig. 1b, pg. 4).
-
Measure output voltage before connecting cameras. This helps avoid potential damage.
All terminals with common suffixes (P) “1P, 2P …” are the same polarity. -
Set illuminated master power disconnect circuit breaker to the (OFF) position (Fig. 3, pg. 6).
-
Connect the power outputs of terminals marked [1P & 1N] to the power inputs of camera 1 (Fig. 2, pg. 5).
Repeat this step for each additional camera (Outputs 2-24). After the wiring is completed, insert the terminal block into the corresponding connector and secure it by tightening the screws. -
Upon completion of the wiring, set the illuminated master power disconnect circuit breaker to the ON (RESET) position (Fig. 3, pg. 6).
-
The power LEDs (Green) on the faceplate for Outputs 1-24 will illuminate when AC power is present
(Fig. 1a, pg. 4). If any of these LEDs are off, a loss of AC power output may be due to a blown fuse or a tripped PTC caused by a short circuit or overload condition. If all of the LEDs are OFF, there may be a complete loss of supply power to the VertiLine unit or the illuminated master power disconnect circuit breaker is in the OFF position, or the main fuse 1-12 or 13-24 is blown (Fig. 1d, pg. 4).*
To restore the power output for VertiLine24 or VertiLine246:
- Switch the corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).
- Eliminate the trouble condition.
- Replace the corresponding automotive blade fuse.*
- Switch the output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
To restore the power output for VertiLine24D or VertiLine246D:
- Switch the corresponding output voltage switch to the OFF position (Fig. 1b, pg. 4).
- Eliminate the trouble condition.
- Allow 1 minute for PTC to cool off.
- Switch the output voltage switch to the 24VAC or 28VAC position as desired (Fig. 1b, pg. 4).
*Note: Replace fuses with the same type and rating:
Output fuses are rated @ 3A for all models.
Main fuse ratings:
10A for VertiLine24 and VertiLine24D.
15A for VertiLine246 and VertiLine246D.
Automotive Blade Fuse
Typical Hookup:
The lightning flash with an arrowhead symbol within an equilateral
triangle is intended to alert the user to the presence of an insulated
DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to
alert the user to the presence of important operating and maintenance
(servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open the enclosure.
There are no user-serviceable parts inside.
Refer servicing to qualified service personnel.
1U EIA 19” Rack Mount Chassis
Mechanical Drawing & Dimensions (H x W x D):
1.625” x 19.125” x 8.5” (41.3mm x 486mm x 216mm)
Power Switch With Built-In Circuit Breaker:
OFF position – Switch not illuminated. Outputs are not powered.
RESET (ON) position – Switch illuminated. Outputs powered.
Circuit breaker tripped – Switch not illuminated.
Power LEDs on the faceplate are not illuminated. Outputs are not powered.
To reset the circuit breaker set the power switch to the ON (RESET) position
(Fig. 3, pg. 6).
Mounting Options:
Rack Mount Installation
- Remove factory-installed screws from both sides of the rack chassis (Fig. 4a).
- Install mounting brackets (A) on the left and right side of the rack chassis using the two (2) flat head screws (B) (included) (Fig. 4b).
- Place the unit into desired EIA 19” rack position and secure it with mounting screws (not included) (Fig. 4c).
Wall Mount Installation
- Install mounting brackets (A) on the left and right side of the rack chassis using two (2) flat head screws (B) (included) (Fig. 5a).
- Place unit at the desired location and secure with mounting screws (not included) (Fig. 5b).
Caution: It is necessary to make sure mounting screws are securely fastened to a beam when installing.
Shelf Installation
- Position and affix rubber pads (C) (included) at each corner on the bottom of the unit (Fig. 6).
- Place the unit in the desired location.
Mounting Hardware (Included):
| A Two (2) mounting brackets
---|---
| B Six (6) flat head screws for mounting brackets.
| C Four (4) rubber pads.
Notes:
Altronix is not responsible for any typographical errors.