idOil Solar Powered Oil and Sand Separator Alarm Device User Guide
- June 12, 2024
- idOil
Table of Contents
idOil Solar Powered Oil and Sand Separator Alarm Device
Product Information
The Solar Powered Oil and Sand Separator Alarm Device is a product designed to
monitor and alert users of any issues related to oil and sand separation. It
is equipped with a local display and alarms to provide visual and audible
notifications. The device also features a browser-based user interface for
convenient access to settings and information.
This product is compliant with essential European standards, statutes, and
regulations. It has been manufactured by Labkotec Oy, a company with certified
ISO 9001 quality management system and ISO 14001 environmental management
system.
Product Usage Instructions
Before using the Solar Powered Oil and Sand Separator Alarm Device, it is
important to read the installation and user guide provided. Keep the manual
available for reference throughout the product’s lifespan and provide it to
any subsequent owners or users.
If any errors or discrepancies related to the manual are identified, please
report them before commissioning the device.
Markings and Symbols
The manual includes safety-related markings and symbols as well as
informative markings and symbols. Pay attention to these markings as they
highlight important information and user measures.
Conformity of the Product
The EU declaration of conformity and the technical specifications of the
product are included in the document. The product has been designed and
manufactured in accordance with essential European standards, statutes, and
regulations.
Limitation of Liability
Labkotec Oy, the manufacturer, reserves the right to change the operating
instructions due to continuous product development. It is important to follow
the instructions provided in the manual and adhere to directives, standards,
laws, and regulations regarding the installation location. Neglecting these
instructions may void any warranty and absolve the manufacturer from liability
for direct or indirect damage caused.
Safety and the Environment
The plant owner is responsible for the planning, installation,
commissioning, operation, maintenance, and disassembly of the device. Only
trained professionals should perform the installation and commissioning. It is
crucial to use the product in accordance with its intended purpose to ensure
the safety of operating personnel and the system.
Compliance with applicable laws and regulations related to usage or the intended purpose is necessary. The device has been approved for its intended purpose only. Failure to follow these instructions may void the warranty and release the manufacturer from any liability.
Installation and User Guide
EN
idOil® Solar
Solar Powered Oil and Sand Separator Alarm Device
DOC001599-EN-7 1/19/2022
Installation and User Guide | idOil Solar
DOC001599-EN-7
Installation and User Guide | idOil Solar
4/62
General information about the manual
This manual is an integral part of the product.
Please read the manual before using the product. Keep the manual available for
the entire duration of the product’s life span. Provide the manual to the next
owner or user of the product. Please report any errors or discrepancies
related to this manual before commissioning the device.
1.1 Markings and symbols
Safety-related markings and symbols
This marking warns of a possible hazard. Failing to observe the safety
instructions in question may result in injury or death. This marking warns of
a fault or hazardous situation. Failing to observe the safety instructions in
question may result in injury or device breakage. This marking warns of a
possible fault. Failing to observe the safety instructions in question may
result in device or system breakage or erroneous operation. This marking
emphasises an issue that requires special attention during installation and
when using the device in an explosive atmosphere.
Informative markings and symbols
This marking highlights essential information.
This marking refers to a user measure.
1.2 Conformity of the product
The EU declaration of conformity and the product’s technical specifications
are integral parts of this document.
All of our products have been designed and manufactured with due consideration
to the essential European standards, statutes and regulations.
Labkotec Oy has a certified ISO 9001 quality management system and ISO 14001
environmental management system.
1.3 Limitation of liability
Due to continuous product development, we reserve the right to change these
operating instructions.
The manufacturer cannot be held liable for direct or indirect damage caused by
neglecting the instructions provided in this manual or directives, standards,
laws and regulations regarding the installation location.
The copyrights to this manual are owned by Labkotec Oy.
DOC001599-EN-7
Installation and User Guide | idOil Solar
5/62
Safety and the environment
2.1 General safety instructions
The plant owner is responsible for the planning, installation, commissioning,
operation, maintenance and disassembly at the location.
Installation and commissioning of the device may be performed by a trained
professional only.
Protection of operating personnel and the system is not ensured if the product
is not used in accordance with its intended purpose.
Laws and regulations applicable to the usage or the intended purpose must be
observed. The device has been approved for the intended purpose of use only.
Neglecting these instructions will void any warranty and absolve the
manufacturer from any liability.
2.2 Intended use
The idOil alarm system is intended for monitoring liquid levels particularly
in oil and sand separators.
The system consists of a control unit and connected sensors that have been
installed in the oil or sand separator. The sensors can be placed in a zone 0
explosive atmosphere, but the control unit must be positioned in a safe area.
A more specific description of the product’s operation, installation and use
is provided later in this manual.
The device must be used in accordance with the instructions provided in this
document. Other use is counter to the product’s purpose of use. Labkotec
cannot be held liable for any damage caused by using the device in violation
of its purpose of use.
2.3 Transport and storage
Check the packaging and its content for any possible damage.
Ensure that you have received all the ordered products and that they are as
intended.
Keep the original package. Always store and transport the device in the
original packaging.
Store the device in a clean and dry space. Observe the permitted storage
temperatures. If the storage temperatures have not been presented separately,
the products must be stored in conditions that are within the operating
temperature range.
2.4 Installation and commissioning
If the temperature in the installation environment is expected to exceed
+40°C, the temperature tolerance of the supply voltage and relay connection
cable must be at least +80°C. Otherwise, any cable that meets the applicable
electrical regulations can be used as the supply voltage and relay connection
cable.
The internal temperature of the device can be 10°C higher than the ambient
temperature. This must be taken into account in the cabling of the device.
The idOil control unit must not be installed in potentially explosive areas,
but a sensor connected to it may be installed in potentially explosive
atmospheres of zones 0, 1 and 2. In potentially explosive area installations,
the national regulations and appropriate standards IEC/EN 60079-25
Intrinsically safe electrical systems “i” and/or IEC/EN 6007914 Explosive
atmospheres – Electrical installations design, selection and erection must all
be followed.
DOC001599-EN-7
Installation and User Guide | idOil Solar
6/62
If it is possible that static electricity can cause hazards in the measurement
environment, equipotential bonding must be attended according to the
regulations concerning potentially explosive atmospheres. Equipotential
bonding is done by connecting all conductive parts to the same potential e.g.
in a junction box. Equipotential bonding system must be grounded.
The instructions concerning the inspection and maintenance of Ex equipment
contained in the standards IEC/EN 60079-17 and IEC/EN 60079-19 should be
observed when executing service, inspection or repair procedures in
potentially explosive atmospheres.
The supply voltage of the device can be batteries / accumulators e.g. via
Labkotec Battery Box 10 or an ATEX-certified isolative voltage source
according to protection level ia with a output voltage of 11-17 V DC, 10 VA.
If the batteries / accumulators are charged with an external charger, they
must be disconnected from the device during charging.
See Technical specifications; Connection values and Appendix; System diagram.
2.5 Repair
The device may not be repaired or modified without the manufacturer’s
permission. If the device exhibits a fault, it must be delivered to the
manufacturer and replaced with a new device or one repaired by the
manufacturer.
2.6 Decommissioning and disposal
The device must be decommissioned and disposed of in compliance with local
laws and regulations.
DOC001599-EN-7
Installation and User Guide | idOil Solar
7/62
Product description
3.1 General
The idOil Solar is a solar-powered alarm and communication unit for monitoring
the levels of liquid hydrocarbon, sludge, or high levels in oil and sand
separators, in locations where mains power is unavailable.
This user manual includes installation and operating instructions for the
following idOil Solar versions:
idOil Solar 3G idOil Solar 3G with a Beacon idOil Solar Beacon
Typical applications for the above mentioned idOil Solar versions are illustrated in the following figure.
idOil Solar Oil Alarm for oil separators:
1. idOil Solar Control Unit
2. idOil-OIL / idOil-OIL-S sensor
3. Cable connector
4. Sensor mounting supplies
idOil Solar Sludge Alarm for sand separators:
idOil Solar Oil/Sludge Alarm for combined oil and sludge alarm:
idOil Solar Hi Level/Oil Alarm for combined high level and oil alarm:
idOil Solar Hi Level/Oil/Sludge Alarm for combined high level, oil and sludge alarm:
1. idOil Solar Control Unit
1. idOil Solar Control Unit
1. idOil Solar Control Unit
1. idOil Solar Control Unit
2. idOil-SLU sensor
3. Cable connector
4. Sensor mounting supplies
2. idOil-OIL / idOil-OIL-S sensor
3. idOil-SLU sensor
4. Cable connector
2. idOil-LIQ sensor
3. idOil-OIL / idOil-OIL-S sensor
4. Cable connector
2. idOil-OIL / idOil-OIL-S sensor
3. idOil-SLU sensor
4. idOil-LIQ sensor
5. Sensor mounting supplies
5. Sensor mounting supplies
5. Cable connector
6. Sensor mounting supplies
Figure 1. Application examples
DOC001599-EN-7
Installation and User Guide | idOil Solar
8/62
3.2 Device operation
The idOil Solar remains deactivated most of the time, which means that it
consumes very little power. The device initiates at predetermined measurement
intervals, in order to perform the sensor measurements. When equipped with a
3G modem, the device also starts listening at predeterminined intervals, to
receive any possible setting commands and simultaneously reports measurement
values.
In case of an alarm, idOil Solar will either initiate a flashing beacon, or
sends a text message (SMS) to pre-set phone numbers, or both. All alarms are
also visible locally, in the idOil Solar Control Unit, during the short wake-
up period.
The system’s power consumption depends on the pre-set measurement and
transmission intervals, as well as the number of alarms.
More information about the device operation is available in the Operation
chapter.
3.3 System components
The idOil Solar Control unit consists of a lockable IP65 polycarbonate
housing, containing a solar panel, idOil-30 Battery Control Unit with an in-
built charge controller, a lead acid battery (12 V / 7 Ah) and a main switch.
Any combination of fail-safe idOil-sensors, namely the idOil-OIL / idOil-OIL-S
oil sensor, idOil-SLU sludge sensor and idOil-LIQ high liquid level sensor,
can be connected to the system. The standard sensor cable length of a sensor
is 5 meters and extendable to at least 500 meters.
Each alarm unit and sensor combination can be equipped with a 3G communication
module, a flashing Xenon beacon or both.
1. Solar panel 2. Control unit idOil-30 Battery or
Control unit idOil-30 Battery 3G 3. Main switch 4. Battery 12 V / 7 Ah 5.
Flashing beacon (option)
Figure 2. System components – idOil Solar Control unit DOC001599-EN-7
Installation and User Guide | idOil Solar
9/62
3.3.1 Solar panel and battery
The solar panel charges the lead acid battery which powers the idOil-30 alarm
unit. Charging of battery is controlled by an idOil-30 built-in solar panel
charge controller. In normal use (under factory settings) there is no need to
recharge or replace the battery during its natural life time, due to the
sophisticated low-power function of the system. Battery life is normally about
5 years.
The idOil Solar will function for at least 6 months without any sunlight. When
the idOil Solar is equipped with a xenon beacon, the operational time will be
much less in case of an alarm (see Xenon beacon below).
Please note that the battery life, and operational time of the idOil Solar
depends on many things, such as the amount of solar energy per day and
previous days, temperature, battery age and the idOil Solar system settings.
Operational times presented in this document are best estimates in particular
cases.
3.3.2 idOil-30 Battery Control Unit
The idOil Solar operations are controlled by the idOil-30 Battery or idOil-30
Battery 3G control unit. The idOil-30 takes care of the low-power system
functions, measures sensor, and controls the flashing beacon and 3G
communication functions. The idOil-30 Battery includes a built-in solar panel
charge controller, which takes care of the solar panel and battery charging.
The idOil-30 is an Ex-barrier and power supply unit for the sensors in oil and
sand separators.
The idOil-30 Battery 3G version includes a built-in 3G modem and an external
3G antenna. A separate external antenna is also an option, if signal quality
is a problem. The user is able to set and modify the settings of the device
via text messages (SMS).
The idOil-30 operational settings are pre-set at the factory. The factory
settings can be changed via the in-built browser user interface. The browser
user interface is accessible via local WLAN connection between the control
unit and a smartphone, tablet or laptop. For more information, see idOil-30
installation and operating instructions DOC001699.
The display, test button and interfaces of the idOil-30 control unit are
described in the following figure.
DOC001599-EN-7
Installation and User Guide | idOil Solar
10/62
1. Local display 2. Test and reset button 3. Lead-through for supply voltage
4. Lead-throughs for relays (2 pcs) 5. Lead-throughs for sensors (3
pcs, blue) 6. 3G antenna (only in 3G version)
Figure 3. idOil-30 Battery – features
3.3.3 idOil-OIL / idOil-OIL-S Oil Sensor
The idOil-OIL / idOil-OIL-S oil sensor is installed into the light liquid
storage chamber and gives an alarm when the chamber is filled to a pre-
determined level. The sensor is normally fully immersed in water. Insert the
sensor into the separator using the access point provided by the separator
manufacturer. The sensor gives an alarm, at the earliest when the upper
electrode is in oil, and at the latest when the sensor is totally immersed in
a nonconductive liquid . In other words, it is totally separated from the
water. The sensor can be mounted suspended by a cable from the ceiling of the
separator. Please check the correct installation depth from the instructions
of the oil separator as well. The function is based on the measurement of the
electrical conductivity of the surrounding liquid water conducts electricity
more efficiently than oil. idOil-OIL oil sensor is for class IIA explosive
liquids and idOilOIL-S oil sensor is for class IIB explosive liquids. The
idOil-OIL sensor can be installed in a zone 0, 1 or 2 potentially explosive
(Ex) area, e.g. oil separator.
DOC001599-EN-7
Installation and User Guide | idOil Solar
11/62
3.3.4 idOil-SLU Sludge Sensor
The idOil-SLU sensor is installed in the separator or tank and it gives an
alarm when sludge reaches the sensor. The sensor is normally immersed in
water.
The idOIL-SLU sensor gives an alarm when there is enough sand or sludge
accumulated between the two heads of the sensor. When the sludge layer on the
bottom of the separator or settling tank is pretty solid, the correct
installation depth can be adjusted, based on the current level. In the event
that the level is not clear, a trest period of a couple of days may be useful.
The sensor can be mounted suspended from the ceiling of the separator by
cable. Please refer to the oil separator instructions for correct installation
depth.
The principle of measurement is ultrasonic. When sludge, sand or other solid
particles accumulate between the two sensor heads, the signal strength
weakens, an alarm is given. idOIL-SLU sensor can be installed in zone 0, 1, or
2 potentially explosive atmospheres.
3.3.5 idOil-LIQ High Liquid Level Sensor
The idOil-LIQ sensor is installed above the separator outlet’s upper level. It
monitors the total level of the separator, regardless of the existence of the
oil layer or sludge in the separator.
The sensor can be mounted suspended from the ceiling of the separator by the
cable. Please check the correct installation depth from the oil separator
instructions.
The principle of measurement is ultrasonic. The sensor is normally mounted in
the air.
idOIL-LIQ sensor can be installed in a zone 0, 1 or 2 potentially explosive
atmosphere.
3.3.6 Flashing Beacon
The idOil Solar can be equipped with a flashing beacon for visual alarms. In
case of alarm, a highly visible signal flashes once every 10 seconds. The
beacon is mounted on the top of the idOil Solar enclosure. The beacon is IP67
rated. In case of an alarm, the idOil Solar can operate the flashing the
beacon for about 10 days with no sun-light, before the battery becomes
discharged. In practise, there is always some solar power available, so the
idOil Solar may function much longer with no interruption.
DOC001599-EN-7
Installation and User Guide | idOil Solar
12/62
3.3.7 Main Power Switch
The main power switch is located inside of the idOil Solar enclosure (see
figure System components). Main switch connects and disconnects both battery
terminals and the solar panel of the system.
The main power switch must be in ON position during normal low-power
operation. The switch is in OFF position during delivery.
DOC001599-EN-7
Installation and User Guide | idOil Solar
4 Installation
13/62
4.1 Installing idOil Solar Control Unit
idOil Solar control unit can be wall mounted or installed on a pedestal. The
enclosure has mounting holes at each of the corners beneath the mounting holes
of the front cover.
For pedestal installation, idOil Solar is equipped with a connector flange
(see Appendix Connector Flange).
Orientate idOil Solar as accurately as possible towards south and direct
sunlight. Check the best possible installation angle (e.g. 68°) at your site.
Pedestals or other mounting equipment are not delivered with the device.
All wiring, except sensor cables, of idOil Solar is done already at the
factory.
The control unit must be installed in a safe (non-Ex) space.
4.2 General installation instructions for sensors
idOil sensors can be installed in zone 0 explosive atmospheres. Do not remove
the sensor markings from the cables or sensor frames. Read Section General
safety instructions before installation.
Check the correct installation depth of the sensor in the instructions of the
separator in question.
For example, sensors can be installed suspended from their cable (see next
figure). Leave a sufficient length of the sensor or extension cable coiled
inside the service well, so that you can easily lift the sensor out for
inspection and cleaning.
1
Suspension hook
2 Cable tie
Figure 4. Sensor suspension example
Figure 5. Sensor mounting supplies LMS-SAS5
4.2.1 Installing the idOil-LIQ high liquid level sensor
The sensor is normally in air, and it issues an alarm when the sensing element
is submerged in liquid. The sensor is installed at a suitable height above the
standard liquid level (L) so that the overflow alarm is activated once the
liquid level reaches the sensing element.
Overflow is possible in the following cases, for example:
if the filter is dirty if the automatic closure device is blocked or if some other situation causes blockage in the discharge pipe
DOC001599-EN-7
Installation and User Guide | idOil Solar
14/62
1 idOil-LIQ high liquid level sensor
A Air
B Oil
C Water
L Standard liquid level
S Sensor switching point
X
Liquid level)
alarm
limit
(maximum
surface
Figure 6. Installing the idOil-LIQ high liquid limit sensor
4.2.2 Installing the idOil-OIL / idOil-OIL-S sensor
The sensor must be submerged at the desired installation depth when the liquid
is at the separator’s standard liquid level (L).
The exact installation depth depends on the following:
separator type separator shape volume and height of the separator’s oil compartment
The sensor must always be immersed in liquid. The alarm is activated when the
lower surface of the oil layer reaches the alarm switching point (S), i.e.
when the sensor’s measuring electrode is covered in oil.
The sensor activates the alarm when it is in contact with air. For this
reason, the separator must always be filled with water after draining.
1 idOil-OIL / idOil-OIL-S oil sensor
A Air B Oil C Water L Standard liquid level S Alarm switching point X Maximum
allowed oil layer thickness
Figure 7. Installing the idOil-OIL / idOil-OIL-S sensor
4.2.3 Installing the idOil-SLU sludge sensor
The sensor issues an alarm on sludge, sand or other solids accumulated at the
bottom of the separator.
The sensor’s exact installation depth depends on the following:
separator type separator shape maximum allowed sludge layer thickness
DOC001599-EN-7
Installation and User Guide | idOil Solar
15/62
The sensor must always be immersed in liquid. The alarm is activated when the
sludge layer reaches the alarm switching point (S), which is located inside
the sensor gap (T).
The sensor activates the alarm when it is in contact with air. For this
reason, the separator must always be filled with water after draining.
1 idOil-SLU sludge sensor
A Air
B Oil
C Water
D Sludge
L Standard liquid level
Figure 8. Installing the idOil-SLU sludge S Alarm switching point
sensor
X Maximum allowed sludge layer height
T Sensor gap
DOC001599-EN-7
Installation and User Guide | idOil Solar
5 Connections
16/62
Read Section General safety instructions before installation. Read Section
Installation and commissioning before installation.
Make the connections when the device is de-energised. The legends for the
connection diagrams can be found in the section following the diagrams.
5.1 Connection diagrams
5.1.1 Connection with a single-sensor cable connector
Figure 9. Connection with a single-sensor cable connector DOC001599-EN-7
Installation and User Guide | idOil Solar 5.1.2 Connection with a two-sensor cable connector
17/62
Figure 10. Connection with a two-sensor cable connector 5.1.3 Connection with a three-sensor cable connector
Figure 11. Connection with a three-sensor cable connector DOC001599-EN-7
Installation and User Guide | idOil Solar
18/62
5.2 Explanations of connection diagrams
1 Supply voltage 1117 V DC e.g. via Labkotec Battery Box 10
– = negative supply voltage + = positive supply voltage Max. supply cable 2.5
mm2 (-, +) AWG 13.
2 Sensor connectors 9 = sensor 1, connection 1 10 = sensor 1, connection 2 11
= sensor 2, connection 1 12 = sensor 2, connection 2 13 = sensor 3, connection
1 14 = sensor 3, connection 2 The sensor connection is a polarity-free digital
bus, which means that it does not matter which sensor terminal the wires are
connected to.
3 Relay outputs RELAY 1 3 = Relay common contact 4 = Contact that opens in an
alarm situation 5 = Contact that closes in an alarm situation RELAY 2 6 =
Relay common contact 7 = Contact that opens in an alarm situation 8 = Contact
that closes in an alarm situation The maximum values presented in the
technical specifications must be taken into account.
4 Cable connector: LCJ1-1 for a single sensor LCJ1-2 for two sensors LCJ1-3
for three sensors
5 Sensors 6 Extension cable, e.g. protected, twisted-pair 2 x 0.5 mm2, maximum
resistance 68
Ohm. Extra wires and shield must be cut and isolated carefully. 7 Protection
plate The connectors for the external connections are separated with separator
walls on the protection plate. The separator walls must not be removed. The
protection plate covering the connectors must be reinstalled after connecting
the cables.
DOC001599-EN-7
Installation and User Guide | idOil Solar
6 Commissioning
19/62
1 Display
2 Reset and test button
3 Type plate with the serial number
Figure 12. User interface description
Most of the idOil Solar parameters are already initialized at the factory.
Factory settings are described in APPENDIX; Factory settings for idOil Solar.
idOil Solar must be activated in order to commission the system. This is done
by pushing the Test and reset button of idOil-30 Control Unit for 10 seconds.
Power switch must be ON.
6.1 Simple commissioning
Ensure that the sensors have been installed and connected in the control unit
in accordance with the instructions in the previous paragraphs.
Connect power to the control unit. A message is shown in the control unit display: NO SENSORS.
Figure 13. Initial start-up
DOC001599-EN-7
Installation and User Guide | idOil Solar
20/62
Open the cover of the control unit.
Briefly press the sensor identification button (1).
The control unit display shows the message “Detecting sensors, 0 sensor(s)
found” and three dots begin cycling at the bottom of the display.
Depending on how many sensors are connected to the control unit, the display
may show the following message, for example: “Detecting sensors, 3 sensor(s)
found”.
Once all sensors have been identified, the display shows the message: SYSTEM
OK.
The idOil separator alarm system is now operational at factory settings.
Figure 14. Sensor identification button. Figure 15. Sensor identification. Figure 16. Three sensors found. Figure 17. All sensors found.
If the control unit does not identify all connected sensors. Check the sensor connections. After the check, press the sensor identification button again.
The control unit will look for the sensors for approx. 2 minutes, unless it has already found three sensors.
The sensor identification can be stopped by pressing the sensor identification button for 5 seconds.
DOC001599-EN-7
Installation and User Guide | idOil Solar
SIM card installation (idOil-30 3G model only, option).
Ensure that the device is de-energised.
Open the cover of the control unit and ensure that the connection protection
plate is in place!
Install Mini-SIM card to SIM holder.
Close the cover and connect power to the control unit.
21/62
When the control unit is searching network, there is signal stength bar with X symbol in the upper right corner of the local display.
Figure 18. SIM card installation
When the control unit is found the network, the X symbol disappears and the signal strength bar is left in the upper corner of the local display.
Figure 19 . Device is searching network Figure 20 . Device is connected in network
6.2 Commissioning through the browser-based user interface
The commissioning process can also be performed through the control unit’s
built-in browser-based user interface. For this, you must establish a local
WLAN connection between the idOil control unit and a terminal device, such as
a smartphone, PC or tablet.
More details on using the browser-based interface is provided in the section
Using the browser-based interface.
DOC001599-EN-7
Installation and User Guide | idOil Solar
22/62
6.2.1 Establishing a WLAN connection
Connect power to the idOil control unit. The display presents the message shown in the figure: NO SENSORS.
Press the reset button briefly.
A symbol indicating a WLAN network connection is shown in the upper left
corner of the display.
If the device power is already on, press the reset button twice; the first
push activates the backlight and the second press activates the WLAN
connection.
Figure 21. WLAN network on
Establish a WLAN connection between the idOil control unit and terminal device as follows:
1. Use the network settings of the terminal device to find the WLAN network
provided by the idOil device.
2. Enter the WLAN network password. The password is five zeroes followed by
the eight final characters of the device’s serial number. The serial number
can be found in the idOil device’s type plate. If the serial number is
8540564_1112118J, for example, the WLAN password is 000001112118J.
3. Open the web browser of your terminal device and enter the IP address:
192.168.0.1.
A connection has now been formed between the terminal device and the idOil control unit. The following sections detail the measures required in connection to initial use.
DOC001599-EN-7
Installation and User Guide | idOil Solar 6.2.2 System settings
The System settings view shown in the figure is opened in the browser.
23/62
Figure 22. System settings Do the following: 1. Select the desired language as
the active language. The default is English. 2. In the Set system date and
time fields, enter the
Date: year-month-day Time: hours-minutes 3. Select the Time zone. 4. If
necessary, activate the Automatic daylight saving time. 5. Finish by pressing
the Save button.
DOC001599-EN-7
Installation and User Guide | idOil Solar
24/62
6.2.3 Sensor naming and identification
Once the system settings have been set, the control unit switches to sensor
identification mode and requests a password as shown in the figure.
Figure 23. Sensor identification; enter password Enter 1234 in the password
field and press the Login button. If no sensors have been identified before,
the view shown below is displayed.
Figure 24. Sensor identification; no sensors found. Press the Detect sensors
button. The control unit begins to detect connected sensors. After detection,
the message shown in the figure is displayed. In the example, three sensors
are connected.
DOC001599-EN-7
Installation and User Guide | idOil Solar
25/62
Figure 25. Sensor identifications; sensors found If necessary, enter
identifiers for the sensors in the Description field and press the Save
button. If the control unit does not identify all connected sensors. Check the
sensor connections. Once you have conducted the check, press the Detect
sensors button again. The control unit will look for the sensors for approx. 2
minutes, unless it has already found three sensors. After the search, the
device shows the number of sensors found in the browser view and the System OK
message in the control unit display. The sensor detection can be interrupted
by pressing the Stop detection button.
DOC001599-EN-7
Installation and User Guide | idOil Solar
26/62
Figure 26. Sensor identification, stop detection Once all connected sensors
have been identified and individual descriptions have been provided for them:
Press the home screen button in the upper left corner: The idOil separator
alarm system is now operational at factory settings.
DOC001599-EN-7
Installation and User Guide | idOil Solar
Operation
27/62
After installation and commissioning, the idOil separator alarm system functions entirely independently and does not require constant monitoring.
The idOil Solar is fully deactivated for most of the time, which means that it
consumes very little power. The device only starts at set measurement
intervals to perform the sensor measurements. Whe nequipped with 3G modem is
starts also at listening intervals to receive any possible setting commands
and at reporting intervals to send measurement values. The power consumption
depends on the set measurement and transmission intervals as well as number of
alarms. More information about the low-power mode settings is available in
chapter Commissioning.
All operations are controlled by the idOil-30 Control unit, which is installed
inside the idOil Solar enclosure (see System Components).
The user can activate the device at any time by pressing the reset/test button
briefly. This activates the device for 30 seconds, after which it returns to
low power mode. The device’s WLAN network is activated when the reset/test
button is pressed a second time. In this case, the device stays activated for
as long as an external terminal device is connected to it’s WLAN network. The
device returns to low power mode 5 minutes after the end of any active WLAN
connection by an external terminal device.
The following chapters describe operation of idOil Solar system through local
display, browser-based user interface and text messages.
7.1 Local display and alarms
Local display
The four-row local display in the front panel is normally off. You can
activate the display by pressing the reset button once, at which point the
display shows the system status as well as possible alarms and faults. In the
event of an alarm, the type of the sensor that activated the alarm is shown
(high liquid level, oil or sludge). In addition to this, the display can be
used to show the customer information specified in the context of
commissioning; company and telephone number (not a factor setting).
Alarms
In alarm and fault situations:
The device measures sensor status only at the set measurement intervals (e.g. 10 min).
After the alarm delay (10 s):
The buzzer sounds an alarm and the display’s backlight flashes for 10 s, after
which the device enters power saving mode. The relay states are not changed.
In a level alarm the sensor in the separator has detected that the liquid
level being monitored has reached the alarm limit (high liquid level, oil or
sludge).
In a fault alarm the control unit has detected a fault in the sensor circuit.
The monitoring covers the communication between the control unit and sensor as
well as short circuits and breaks.
DOC001599-EN-7
Installation and User Guide | idOil Solar
28/62
Resetting an alarm
An alarm can be reset by pressing the test button in the cover.
Resetting an alarm deactivates the buzzer. However, the buzzer is always
reactivated for 10 s every 24 hours until the cause for the alarm is
eliminated. Resetting an alarm deactivates the buzzer. However, the buzzer is
always reactivated every 24 hours (factory setting) until the cause for the
alarm is eliminated.
The relays do not change their state when an alarm is reset with the reset
button.
7.3 Using the browser-based user interface
The following sections describe the use of the idOil browser-based user
interface.
The process of establishing a connection to the browser-based interface is
described in the section Commissioning through the browser-based interface.
7.3.1 Home screen The browser-based interface always starts in the home screen
shown in the figure below. You can also access the home screen by pressing the
icon in the upper left corner.
Figure 27. Home screen The items listed in the following table are shown in
the home screen. The menus are described in more detail in the sections below.
DOC001599-EN-7
Installation and User Guide | idOil Solar
idOil 2017-01-04 16:45
Menu Settings
Type name of the control unit
Date and time of the device’s internal clock
Home screen button; by clicking this icon, you can return to the home screen
Selection of menu options Settings menu. Requires logging in with the
maintenance user password. The idOil device features two user levels:
Basic user:
The upper right corner of the home screen top bar does not show this symbol.
No rights to configure the device, except time and language settings.
Maintenance user:
The lock system is shown in the upper right corner of the home screen top bar.
The user has logged in with the maintenance user password. The right to
configure control unit settings in the Settings menu.
Status view
The status of the sensors connected to the device is shown under the Status
view heading:
Green means no alarm. Red means an alarm or fault status in the sensor. The
cause of the alarm or fault and the time of the alarm is shown below the
sensor.
Inspection Customer data
Below the Inspection menu, the device shows either the time of the next
scheduled inspection or the latest inspection alarm if the scheduled
inspection date is in the past and the alarm has not been reset. See Settings.
This section shows the customer and contact information set in the device.
7.3.2 Menu list The Menu list features the functions shown in the figure below.
Basic users can access the Menu options.
29/62
DOC001599-EN-7
Installation and User Guide | idOil Solar
30/62
Figure 28. Menu list 7.3.2.1 Alarm log
The alarm log records the times of the alarm and fault situations, the reset
times, and the times at which the alarms and faults are eliminated. The
following events are recorded in the alarm log:
Sensor alarm situation. Note! Alarms caused during maintenance are recorded in
the inspection log. Sensor fault Sensor bus short-circuit Test alarm (reset
button has been pressed for 3 s) Note! Alarms caused during maintenance are
recorded in the inspection log. Power off/on (start and stop time of a power
outage) The buttons at the bottom of the alarm log perform the following
functions: Load more items: Shows previous alarms if all alarms and faults do
not fit in the browser window at the same time. Update: The alarm log view
returns to the initial view which shows the latest alarms. Save report: Saves
the alarm log in the .csv format.
DOC001599-EN-7
Installation and User Guide | idOil Solar
31/62
Figure 29. Alarm log 7.3.2.2 Inspection
This function adds an inspection measure in the device’s inspection log.
Recording inspection measures resets the inspection counter.
Press the Start inspection button to activate the inspection form. In the
Inspection notes field, enter the inspection measures conducted and, in the
Inspector name field, enter your name. End the inspection measure with the
Inspection completed button. The device will switch to the Inspection log
view.
DOC001599-EN-7
Installation and User Guide | idOil Solar
32/62
Figure 30. Inspection
The inspection can also be conducted as a quick operation without using the
browser user interface. When the inspection alarm is active, the inspection
can be conducted with the test operation (see Test function). Press the
test/reset button in the front panel for 3 seconds and release the button. The
inspection interval counter and the inspection alarm is now reset.
7.3.2.3 Inspection log
The Inspection log view shows the latest inspection note first. Alarms during
inspection are shown in the inspection log. These alarms are not shown in the
alarm log.
The latest inspection note can be edited but this will not change the time
stamp. Old inspection notes can no longer be edited.
Press the Save button after any possible changes.
The buttons at the bottom of the inspection log perform the following
functions:
Load more items: Shows prior inspection measures if it is not possible to fit
all of them in the browser window at the same time. Update: The Inspection log
view returns to the initial view which shows the latest inspection measures.
Save report: Saves the inspection log in the .csv format.
DOC001599-EN-7
Installation and User Guide | idOil Solar
33/62
Figure 31. Inspection log 7.3.2.4 Language
You can select one of the supported languages in the Language menu. Select the
desired language and press the Select button.
This will change the language of the browser interface and local display to
the selected language.
DOC001599-EN-7
Installation and User Guide | idOil Solar
34/62
Figure 32. Language selection
7.3.2.5 Date and time
The control unit’s date, time, time zone and automatic daylight saving setting
can be set and updated in this view.
Make the necessary changes and press the Save button.
The date and time must be set (required information) when the first WLAN
connection to the control unit is established.
Figure 33. Date and time 7.3.3 Settings menu
The functions in the Settings menu can be used to change the control unit
settings. The settings can be accessed with the maintenance user’s password.
Press the Settings menu in the home screen, at which point the device requests
a password. The maintenance user password is 1234.
DOC001599-EN-7
Installation and User Guide | idOil Solar
35/62
Figure 34. Password prompt Enter the password and press the Login button.
The Settings menu features the functions shown in the figure below. The
functions are described in more detail in the following paragraphs.
Figure 35. Settings menu
7.3.3.1 Customer data
In the Customer data menu, you can enter the following information in the
device:
Company: The name of the device owner, supplier or maintenance company, for
example. The name is shown in the home screen and the control unit display.
The display shows the first 16 characters. Contact name: The name of the
contact person for the above company, for example. The name is shown in the
home screen but not the control unit display. Phone number: The contact
person’s phone number. The number is shown in the home screen and the control
unit display. Site name: A unique name can be entered for the device. The name
is shown in the home screen, in the Status viewbar and the loaded reports, but
not the control unit display.
DOC001599-EN-7
Installation and User Guide | idOil Solar
36/62
Figure 36. Customer data
7.3.3.2 Inspection settings
In the Inspection settings menu, you can set the inspection period counter.
You can select between:
never (factory setting, inspection period not used) 1 month 3 months 6 months
12 months
Select the desired inspection period and press the Save button.
The selection (with the exception of “never”) activates the inspection period
counter, which will activate the inspection alarm after the selected interval.
The time of the maintenance is shown in the home screen (year-month-day) and
the control unit display (year-month).
The inspection counter can only be reset once the inspection alarm has been
activated. In other words, an inspection cannot be performed before the
activation of the alarm (this does not reset the counter).
Figure 37. Inspection settings
DOC001599-EN-7
Installation and User Guide | idOil Solar
37/62
7.3.3.3 Alarm settings
In the Alarm settings menu, you can change the following alarm settings:
Alarm buzzer: Off/On. If Off is selected, the buzzer will not sound upon an
alarm. Alarm repeat (24 h): Off/On. If On is selected, the alarm will be
repeated 24 hours after a reset, if the cause of the alarm has not been
eliminated. Alarm delay for sensors. Delay between sensor detection and the
activation of the alarm buzzer and relay. You can use seconds, minutes or
hours for the setting. Alarm reset button: Disabled/Enabled. If Disabled is
selected, the alarm cannot be reset by pressing the reset button in the front
panel of the control unit (i.e. the buzzer will keep sounding the alarm).
Figure 38. Alarm settings 7.3.3.4 Relay settings
The following functions related to relays 1 and 2 can be set in the Relay
settings menu: Sensors connected to relays: Off/On. Relay action in case of
alarm and failure: Off/On. Relay action in case of an inspection warning:
Off/On. Relay return when alarm is reset by pressing the reset button: No/Yes.
DOC001599-EN-7
Installation and User Guide | idOil Solar
38/62
Figure 39. Relay settings
DOC001599-EN-7
Installation and User Guide | idOil Solar
39/62
7.3.3.5 Software update
The software of the control unit can be updated through the user interface.
The Software update menu shows the current software version and the available
language options.
Figure 40. Software update
Upload the new software as follows: Press the Upload new software package
button.
Select the software file to be uploaded (format: “.pkg”) from the terminal
device memory.
The software will now be uploaded to the control unit. The uploading process
may take several minutes.
Figure 41. Software upload
Once the software has been uploaded into the control unit’s memory, the
display will show the current software version and the new version to be
updated (see next figure).
DOC001599-EN-7
Installation and User Guide | idOil Solar
40/62
Figure 42. Software uploaded to the control unit Press the Update button. The
software update begins and the message in the figure below is shown in the
display. The various phases of the software update are presented in the
control unit display.
Figure 43. Software update started Once the programming has been completed,
the control unit reboots. The WLAN connection to the device is lost during a
software update.
Establish the WLAN connection again according to the instructions in the
Commissioning through the browser-based interface section. 7.3.3.6 Restoring
factory settings In the Factory settings menu you can restore the control
unit’s original factory settings. The factory settings of the idOil device are
described in the section Commissioning Restoring the factory settings clears
the alarm and maintenance log. The sensors connected to the control unit must
also be identified again.
DOC001599-EN-7
Installation and User Guide | idOil Solar
41/62
You can restore the factory settings as follows:
Check the Restore factory settings box and press the Restore settings button
(see the next figure).
Figure 44. Restoring factory settings
Confirm the restoration of the factory settings by pressing Yes, I want to
clear all data button.
Figure 45. Factory settings – confirm restoration After this, the system shows
the following message: “Restoring factory settings. Please reload the web page
in a few moments. If the WLAN connection is lost, reconnect the device.”
If necessary, establish the WLAN connection in accordance with section
Establishing a WLAN connection .
Configure the system settings and perform sensor identification. 7.3.3.7 WLAN
settings
If the WLAN connection is poor, several devices may be using the same WLAN
channel. You can change the WLAN channel by using the WLAN settings menu to
select another
channel and pressing the Save button.
DOC001599-EN-7
Installation and User Guide | idOil Solar
42/62
Figure 46. WLAN settings Establish the WLAN connection again according to the
instructions in the Establishing a WLAN connection section.
7.3.3.8 Low power mode settings
The following settings can be set in the Low power mode settings menu:
Beacon light adjustment (relay state change setting):
With the beacon light adjustment settings, the relay can be set to change its
state back and forth during the alarm event. This function can be utilized
e.g. when an external beacon light is needed to show the alarm.
Example: Repeat: 5 s Duration: 400 ms The beacon light will flash every 5
seconds and the flash duration is 400 ms.
Repeat: Sets the interval for the relay to change its state (de-energised or
energised) in seconds. You can choose between 2 s, 5 s, 10 s, 30 s and 60 s.
Duration: Set the length of time the relay remains de-energised. You can
choose between 200 ms, 400 ms, 600 ms, 800 ms and 1,000 ms. Relay 1 and Relay
2: Off/On. Activation of the relay state change.
Once you have made the desired changes, press the Save button.
Measure interval:
Repeat: Sets the measurement interval for the idOil device in minutes or
hours. You can choose between 10 min, 30 min, 60 min, 2 h, 3 h, 4 h, 6 h, 8 h,
10 h, 12 h or 24 h. Start delay: The delay for performing the measurement when
the measurement repeat interval is activated. You can choose between 1 s, 2 s,
3 s, 4 s or 5 s.
Once you have made the desired changes, press the Save button.
SMS message receipt interval:
Repeat: The interval at which the idOil device wakes up to detect whether or
not settings messages have been received. You can choose between 12 h, 24 h,
36 h and 48 h. The time is counted from the connection of voltage to the idOil
device.
Once you have made the desired changes, press the Save button.
Backlight blinking during alarm:
DOC001599-EN-7
Installation and User Guide | idOil Solar
43/62
Off/On: The flashing function of the idOil device’s display backlight can be
deactivated to save power.
Battery voltage monitoring:
Battery voltage level: Battery voltage value in volts Monitoring: Off/On.
Battery low voltage alarm: The voltage limit below which the idOil device
triggers a battery voltage alarm. The lowest voltage than can be set is 10.5
V.
Once you have made the desired changes, press the Save button.
Figure 47. Low power mode settings
DOC001599-EN-7
Installation and User Guide | idOil Solar
44/62
7.3.3.9 3G settings (idOil-30 3G model only, option)
The 3G settings can be found in the M2M settings menu, if the idOil device
features a 3G module.
The following settings can be set in the M2M settings menu:
Receiver phone number (max. 5 phone numbers):
Press the Add button.
Enter the phone number. Press the Save button.
SMS communication centre number: The idOil device detects the SMS
communication centre number automatically. If the operator is using multiple
communication centre numbers, provide another number and press the Save
button.
PIN code: If the PIN code prompt for the SIM card is enabled, enter the PIN
code and press the Save button. The idOil device will remember the PIN code
after this.
SMS reporting: Enable reporting: No/Yes Frequency: this sets the interval at
which the idOil device sends a situation report to the set recipient phone
numbers. Sending time: this sets the time at which the situation report should
be sent.
LabkoNet Enable LabkoNet service: Off/On
To activate the LabkoNet service, please contact the Labkotec Oy customer service (info@labkotec.fi).
DOC001599-EN-7
Installation and User Guide | idOil Solar
45/62
Figure 48. 3G settings
7.4 Operating idOil Solar with mobile phone
This chapter is relevant to idOil Solar versions with 3G functionality only.
After commissioning the idOil Solar system and installing a SIM card to 3G
modem, the user is able to send text messages to the system.
7.4.1 Setting telephone numbers and telephone number queries (TEL)
A total maximum of five numbers can be set 15 numbers at a time. The number
is always saved in the first free memory slot.
The format of the telephone number setting command is: TEL
Field legend TEL
Telephone number setting command
End user telephone numbers in international format delineated with spaces.
The device responds with a message including the name of the device (if set), the set telephone numbers and the corresponding memory slots in the device memory.
DOC001599-EN-7
Installation and User Guide | idOil Solar
46/62
TEL
is entered, the response is: TEL 1: +35840111111 2: +35840222222 3:
+35840333333 4: +35840444444
7.4.2 Name of the device or location (NAME)
This setting can also be entered via the idOil unit’s browser user interface.
It is a good idea to set a unique name for the device or location so that
alarm messages, for example, show which device the message is coming from.
The format of the setting command is: NAME <name of the device/location>
Field legend NAME <name of the device/location>
Name setting command
Name freely selected by the user up to 60 characters. The name can also
contain spaces.
Example: Send the following message to the idOil device: NAME Pirkkala
Myllyhaantie
The unit responds: NAME Pirkkala Myllyhaantie
DOC001599-EN-7
Installation and User Guide | idOil Solar
47/62
7.4.3 Time (CLOCK)
The time setting is needed if you wish to save log information with actual
time stamps or if you want the device to send timed messages to the end user
or the LabkoNet server.
This setting can also be entered via the idOil unit’s browser user interface.
The format of the time setting command is: CLOCK
Field legend CLOCK
Time setting command and query
Year (yyyy), month (mm) and date (dd) separated with a hyphen.
Hours (hh) and minutes (mm) separated with a colon.
Example
Do the following to set the time.
Send the following message to the idOil device: CLOCK 2018-10-23 15:30
The device responds as follows: CLOCK
In addition to the time, the response includes a possible name set for the
device in question.
7.4.4 Timed message interval (TXD)
The idOil unit can be timed to send information on system status and possible
alarms to the recipients’ phone numbers. The user can define interval in days
and the specific time of the message. The timed alarm information message is
described in the section “Alarm status query”.
This setting can also be entered via the idOil unit’s browser user interface.
The command format for setting the timed message interval is as follows: TXD
Field legend TXD
Timed message interval command.
The timed message interval in days.
The time of the message hours (hh) and minutes (mm) separated with a
colon.
The factory default for the interval and time is 0 00:00. When the interval is set to 0, the timed message is not in use.
Example 1
DOC001599-EN-7
Installation and User Guide | idOil Solar
48/62
Send the following message to the idOil device: TXD 1 12:00
Device response: TXD
The device sends a timed message every day at 12:00. Example 2 Switching off
the timed message
Send the following message to the idOil device: TXD 0 00:00
Device response: TXD
7.4.5 Measurement interval (MI)
An interval can be set for the device, according to which it will wake up from power saving mode, perform sensor measurements and, if necessary, activate the 3G modem to forward the alarm data. After this, the device returns to power saving mode.
The factory default for the measurement intervals is 10 (minutes). This setting can also be entered via the idOil unit’s browser user interface.
The format of the measurement interval setting command is as follows: MI
Field legend MI
Command
Measurement interval in minutes. Permitted values:
10, 30, 60, 120, 180, 240, 360, 480, 600, 720, 1440
Example:
If Pirkkala Myllyhaantie has been set as the device name and the command MI 60
is sent, the response is: MI Pirkkala Myllyhaantie 60
With this setting, the device wakes up to perform sensor measurements every 60
minutes and sends alarm data to the set telephone numbers, if necessary.
DOC001599-EN-7
Installation and User Guide | idOil Solar
49/62
7.4.6 Listening interval (LI)
A listening interval can be set for the device, according to which it will
wake up from power saving mode, activate the 3G modem and read any possible
setting messages and queries that have been sent to it. The device performs
any possible setting commands and responds to any possible queries. After
this, the device returns to power saving mode.
The factory default for the listening interval is 12 hours. The listening
takes plays every 12 hours from device activation.
This setting can also be entered via the idOil unit’s browser user interface.
The format of the listening interval setting is as follows: LI
Field legend LI
Command
Listening interval in hours. Permitted values 12, 24, 36, 48.
Example: If Pirkkala Myllyhaantie has been set as the device name and the
command
LI 24 is sent, the response is:
LI Pirkkala Myllyhaantie 24
7.4.7 Operating voltage alarm limit setting (VLIM)
The idOil-30 Battery 3G unit monitors the level of its operating voltage. The
device sends an alarm when the voltage drops below the alarm limit setting
specified for the operating voltage.
The factory default for the alarm limit is 11.4 V. This setting can also be entered via the idOil unit’s browser user interface.
The setting command for the operating voltage alarm limit is formatted as follows: VLIM <xx.x>
Field legend
VLIM
Setting command for the operating voltage alarm limit
The desired voltage in volts with one decimal. The integer and decimal are separated with a point. Permitted values: 0 (setting off), 10.599.9
A 0.2 V hysteresis has been set for alarm removal. In other words, the alarm removal limit is 0.2 V higher than the setpoint. The hysteresis value cannot be changed.
Example: If the device name has been set as Pirkkala Myllyhaantie and the command is:
DOC001599-EN-7
Installation and User Guide | idOil Solar
50/62
VLIM 11.8 The response is:
VLIM Pirkkala Myllyhaantie 11.8 V
7.4.8 Alarm information query (M)
To request alarm information from the device,
send the following message to the idOil device:
M
The device responds as described below by sending the device name, sensor
names and alarm or fault information. The information of each sensor input is
on a separate row of the message.
STATUS
The field legends are listed in the following tables.
Field legend STATUS
Heading of command M
If a name has been set for the device, it is indicated at the beginning of the
message.
The possible descriptive name set by the user for the sensor input and the
character “/”.
Alarm text (standard, cannot be changed, depends on the type of sensor
connected to the input): Oil level alarm Sludge level alarm High liquid alarm
Alarm time.
Alarm text regarding the fault (standard, cannot be changed, depends on the
type of sensor connected to the input): Oil level fault Sludge level fault
High liquid fault
Alarm time.
DOC001599-EN-7
Installation and User Guide | idOil Solar
51/62
Example 2: If there are no alarms active in the device, it responds with a
SYSTEM OK message:
STATUS Pirkkala Myllyhaantie SYSTEM OK 2018-05-31 13:05 7.4.9 Test idOil Solar
functions with the sensors idOil Solar status can be asked by sending the
measurement query: M to idOil Solar. (Example is from idOil Solar Oil Alarm)
When sensor is connected and totally immersed in water, idOil Solar should
reply: “STATUS Airport ABC System OK” When sensor is connected and it is
either immersed in oil or in air, idOil Solar should reply: “STATUS Airport
ABC Oil level alarm 2018-07-13 15:20” When sensor is not connected, idOil
Solar should reply: “STATUS Airport ABC Oil level Fault 2018-07-13 15:23”
DOC001599-EN-7
Installation and User Guide | idOil Solar
8 Maintenance
52/62
The operation of the separator system and alarm device must be checked at
least every 6 months by experienced personnel.
The following is recommended in conjunction with the inspection:
functional check of the idOil alarm device with the test function and sensor (see Section Functional test) sensor cleaning (see Section Maintenance measures)
The idOil control unit and sensors do not have wearing or replaceable parts.
The device does not include replaceable fuses.
8.1 Functional test
8.1.1 Test function
The test function creates a test alarm, which is used to ensure the
appropriate functioning of the idOil device and any other possible devices or
systems controlled by its relays in an alarm situation.
Activating the test function:
Press the reset/test button continuously for 3 seconds.
8.1.2 Functional test with sensors
The operation of the idOil device and sensors can be checked comprehensively
by simply simulating an actual alarm situation.
The idOil device can be set to test mode by pressing the reset/test button
once to activate display and after that again continuously for 10 seconds and
release it. The display shows the message Test mode and the device enters the
continuous measurement mode. The device returns to normal mode automatically
in 15 minutes. Alternatively, you can press the reset/test button continuously
for 10 seconds and release it.
To exit the continuous measurement mode, press the reset/test button for 10
seconds to ensure lower power consumption.
Depending on the sensor type, the functional test can be conducted as follows:
1. idOil-LIQ (high liquid level): Immerse the sensor in oil or water.
2. idOil-OIL / idOil-OIL-S (oil): Immerse the sensor in oil. If this is not
possible, lift the sensor into the air.
3. idOil-SLU (sludge): Immerse the sensor in sand or sludge. If this is not
possible, lift the sensor into the air.
The alarm will be activated after the delay (factory setting: 10 s).
DOC001599-EN-7
Installation and User Guide | idOil Solar
53/62
8.2 Maintenance measures
The sensors must be cleaned in conjunction with maintenance inspections. You
can clean the sensors with washing up liquid and a washing up brush, for
example.
Do not use corrosive substances to clean the sensors.
8.3 Troubleshooting
Adhere to the electrical safety regulations!
PROBLEM: Explanation: Action:
The display is dark after the reset/test button has been pressed.
The voltage received by the device is too low, or the fuse has blown.
1. First check that the voltage has not been cut by the mains switch.
2. Measure the voltage from connectors + and -. It should be 11 17 V DC.
EXPLOSION HAZARD! Observe the installation and maintenance instructions for
explosive atmospheres!
The measuring device must be Exi classified if the sensor is in an explosive
area.
PROBLEM:
Fault alarm on (the backlight of the display is flashing)
Explanation:
The sensor cable is short-circuited, cut or disconnected from the connector. The sensor could also be damaged.
Action:
1. Measure voltage separately from that sensor’s sensor connectors. The voltage should be 9.011.5 V.
2. If the voltage is correct, measure the current received by the sensor. It should settle between 6.08.0 mA within 10 seconds.
3. Reconnect the disconnected wire after the measurement.
The sensor cable wires are not numbered because the voltage polarity (+ or -) makes no difference.
If problems occur, contact Labkotec Oy’s service department.
DOC001599-EN-7
Installation and User Guide | idOil Solar
9 Technical and safety data
54/62
TECHNICAL SPECIFICATIONS idOil Solar alarm unit
Dimensions
200 mm x 400 mm x 132 mm (w x h x d)
Enclosure
Material: polycarbonate IP rating: IP43 with two ventilation devices
Weight
8,0 kg
Operating environment
Temperature: -30ºC…+60ºC Max. elevation above sea level 3,000 m Relative humidity RH 100% Suitable for outdoor use
Battery
12 VDC, 7 Ah lead-acid battery
Power consumption
Max. 10 VA Typical 13,5 mVA (on low-power mode)
Alarm indication
GSM text message AND/OR Xenon beacon AND/OR Potential free relay output (bistabe latching relay)
Alarm and Communication Unit
idOil-30 Battery or idOil-30 Battery 3G (See chapter 3. System components)
Sensors
idOil-OIL/idOil-OIL-S and/or idOil-SLU and/or idOil-LIQ (See chapter 3. System components)
ATEX IECEx UKEX
EESF 21 ATEX 024X IECEx EESF 21.0017X CML 21UKEX21351X
Ex classification Special terms (X)
idOil-30 Battery / idOil-30 Battery 3G II (1) G [Ex ia Ga] IIB
Ta = -30 °C…+60 °C
Exi connection values
Um = 30 V DC, Uo = 14.5 V, Io = 78 mA, Po = 367 mW, R = 243
Manufacturing year:
xxxxxxx x xxx xx YY x
where YY = manufacturing year
Please see the serial number on the type (e.g. 18 = 2018)
plate.
DOC001599-EN-7
Installation and User Guide | idOil Solar
10 Appendices
55/62
10.1 Factory settings for idOil Solar
Every idOil Solar alarm unit has the following settings pre-defined in the
factory.
The Low power settings of idOil Solar can be changed from idOil-30 Control
Unit’s settings either through the web user interface or by text messages:
Beacon light adjustment: Repeat time (factory setting 10 s) Duration (factory
setting 600 ms) Beacon connected to relay 1 or relay 2 (factory setting off)
Measuring interval: Repeat (factory setting 10 min) Start delay (factory
setting 5 s)
Display Backlight blinking during alarm (factory setting ON) Battery voltage
monitoring:
current battery voltage level Monitoring (factory setting ON) Battery low
voltage alarm (factory setting 11,4 V)
Most of the factory settings can also be set by text messages.
Command parameters
and Explanation
DI 1: 1: Oil level sensor. 2: High liguid sensor. 3: Sludge level sensor.
Command sets probe names as follows: Probe nbr 1 is identified as “Oil level sensor”. Probe nbr 2 is identified as “High liquid sensor”. Probe nbr 3 is identified as “Sludge level sensor” .
VLIM 11.4
Alarm level (in Volts) for minimum battery voltage.
MI 10
Measuring interval
LI 12
idOil Solar wakes up every 10 minutes for 20 seconds from low-power mode to
check the status of probes.
Listening interval (hours)
idOil Solar wakes up from normal (low-power) mode every 12 hours (starting from the time idOil is put to low-power mode) for 2 minutes to check if users have given new SMS commands, and to answer them.
More information about the format of each command and parameter can be found from the following documents:
idOil-30 Battery, Installation and Operating Instructions (DOC001699). idOil-30 Battery 3G, SMS-messages – Commissioning and use (DOC001696).
DOC001599-EN-7
Installation and User Guide | idOil Solar
10.2 Connector Flange for idOil Solar
56/62
1. M6 x 8 mm locking screw
2. Connector flange
3. Mounting pipe
Drill a 5 – 6 mm hole throught the mounting pipe (3) to ensure the idOil Solar
is in its correct position.
Position the connector flange locking screw in line with the drilled hole.
Adjust the locking screw until flush with the outer surface of the connector
flange.
DOC001599-EN-7
Installation and User Guide | idOil Solar
10.3 idOil Solar Wiring Diagram
57/62
DOC001599-EN-7
Installation and User Guide | idOil Solar
10.4 idOil Solar System Diagram
58/62
DOC001599-EN-7
Installation and User Guide | idOil Solar
59/62
DOC001599-EN-7
Installation and User Guide | idOil Solar
60/62
DOC001599-EN-7
Installation and User Guide | idOil Solar
10.5 idOil Solar EU Declaration of Conformity
61/62
DOC001599-EN-7
Installation and User Guide | idOil Solar
10.6 idOil Solar UK Declaration of Conformity
62/62
DOC001599-EN-7